Catalogue 1SFC en, Edition 3 November 2003 Supersedes Catalogue 1SFC en, Edition 2 November Arc Guard System TVOC

Similar documents
20 - Arc Guard Systems

Spec Tech Industrial 203 Vest Ave. Valley Park, MO Phone: 888 SPECTECH. Arc Guard Systems Arc monitor Current sensing unit Accessories

Phase and neutral overcurrent protection

Transformer differential protection

CAMTO. Arc detecting relay. system. January Revised August D D1200

N. TEST TEST DESCRIPTION

Overcurrent Protection / 7SJ45

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

Harmonic restraint earth fault or single-phase overcurrent protection

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

Stabilized Differential Relay SPAD 346. Product Guide

I -limiter The world s fastest switching device

N. TEST TEST DESCRIPTION

Electronic Circuit Breaker with reset input ESS20-1..

Electronic Circuit Breaker ESS1 for System SVS1

Solid-State Soft Starters

in one housing (3). The light beam is reflected by a reflector (4). The objects are detected by interruption of the light beam.

SINEAX B 811 Power Pack with additional Functions

W 23-2: Focussing on what is essential and economic

Miniature circuit-breakers S 280 UC series. System pro M. Technical data

DEIF A/S. Insulation monitor. Type SIM-Q

Photoelectric switches WLL 170(T), fibre-optic cables LL 3: flexible solutions with fibre-optic cable systems

11/0 IZM circuit-breakers, IN switch-disconnectors

Time over/underfrequency relay with protection assemblies

Power supply CP-D 24/4.2 Primary switch mode power supply

Current and voltage measuring relays RXIK 1, RXEEB 1 and RXIB 24

PHOENIX CONTACT - 09/2009

Electronic timer CT-MFS.21

Electronic timer CT-AWS Impulse-OFF with 1 c/o contact Data sheet

TM1600. Circuit Breaker Analyzer System

Siemens AG Allows easy and consistent configuration with one series of overload relays (for small to large loads)

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

Electronic Circuit Breaker ESS1 for System SVS1

Modeion OTHER ACCESSORIES OF MOULDED CASE CIRCUIT BREAKERS

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

Low Voltage Products & Systems. ABB Arc Guard System TM TVOC

V2IM10AL10 Art.Nr.: V2IM10AL10P Art.Nr.: Control element. Tripping delay. Function selector. Status indication 24...

Installation / Monitoring Technique

Electronic Circuit Breaker ESS20-0..

Original operating instructions Fail-safe inductive sensor GM504S / / 2010

SPAD 346 C Stabilized differential relay

SIMEAS-T. Operating Instructions Transducer without auxiliary power. 7KG6111 and 7KG6101. Operating Instructions

Electronic timer CT-ERS ON-delayed with 2 c/o contacts Data sheet

Wireless multizone receiver RDE-MZ6

Measuring and monitoring relays CM-SRS.1 Current monitoring relays, single-phase AC/DC

Datasheet - PROTECT-IE-02

Advanced Test Equipment Rentals ATEC (2832)

Distribution/Substation Transformer

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

Catalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009

Operating instructions Fail-safe delay timer AZS About this document. Content

Type CP-S, CP-C & CP-A Switch mode

Original operating instructions Fail-safe inductive sensor GG507S / / 2013

Power supply CP-D 24/1.3

SINEAX I 503 / SINEAX U 504 Transducer for AC current or AC voltage

Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact

Contrast scanners detect the little differences

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300

Electronic timer CT-TGD.22

Online data sheet WS/WE260-R270 W260 PRODUCT PORTFOLIO

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC

Smart Power Relay E I...

Current monitoring relays CM-SRS.M1 For single-phase AC/DC currents

21 VA (l max 20 5 ms) Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque Inhibiting torque

Three-phase monitoring relays

PREMIER INSTALLATION AND OPERATING INSTRUCTIONS

Online data sheet WL260-S270 W260 PRODUCT PORTFOLIO

Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL

Switching power supplies CP range, Linear power supplies CP-L range. Content

TORKEL 900-series Battery Load Unit

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

)HDWXUHV Voltage restraint overcurrent stage with five different inverse or definite time characteristics

Current monitoring relays CM-SRS.2 For single-phase AC/DC currents

12/2 Product overview. 12/3 7KT1 14, 7KT1 53 E-counters. 12/9 7KT1 11, 7KT1 12 digital measuring devices. 12/11 7KT1 0 analog measuring devices

ODEN AT Primary Current Injection Test System

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays


RARIC Shaft current protection

SIRIUS/SIKOSTART Soft Starters For Standard Applications

SPAJ 110 C. Earth-fault relay SPAJ 110 C. User s manual and Technical description. U aux V ~ V f n. n ( I o>> SPCJ 1C8

ABB NEW. Three-phase monitoring relays. CM-PVS.31 and CM-PVS.41 Data sheet. Features J. Approvals. Marks. Order data. Order data - Accessories

W 250: Compact photoelectric switch series for a broad range of applications

MVCT. Megger VT & CT Analyzer. MVCT Megger VT & CT Analyzer

XI1-I Time overcurrent relay. (Januar 2007) Manual XI1-I (Revision New)

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents

SPAE 010, 011 High Impedance Protection Relay

Electronic Circuit Protector ESX10-T

WLL 170 Photoelectric switches with fibre-optic cable, red light, manual sensitivity adjustment -- DC. Dimensional drawing R1.6 2-R

EMD-FL-3V-400. Electronic monitoring relay for voltage monitoring in three-phase networks. INTERFACE Data sheet _en_03. 1 Description.

Time relay RXKA 1. (xx jpg) RXKA 1

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages

DEIF A/S. Insulation monitor. Type SIM-Q/SIM-Q LF

V2UM230V10 Art.Nr.: V2UM230V10P Art.Nr.: Control elements. Tripping delay. Function selector. Status indication 230 V AC/DC

Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages

Electronic timer CT-MXS.22 Multifunctional with 2 c/o (SPDT) contacts

Content. Monitoring relay pluggable. 1-phase current monitoring relay phase direct-current voltage monitoring relay... 5.

Transcription:

Catalogue 1SFC 266006-en, Edition 3 November 2003 Supersedes Catalogue 1SFC 266006-en, Edition 2 November 2000 Arc Guard System TVOC

System units The two units of the are used as below: Approvals 1. with detectors Operates alone. F11 A1 Q1 2. and Operates only together. F21 T1 F11 A1 Q1 A1 Switchgear F11 F21 T1 Current transformer Q1 Circuit-breaker Dimensions in mm. The design, data and dimensions are subject to modification without notice. 2 Low Voltage Products

Contents Ordering particulars... 4 Description... 6 Technical data... 8 Dimensions... 9 Diagrams... 10 Application diagrams... 11 Low Voltage Products 3 1SFC 266006-en, Ed. 3 November 2000

Ordering particulars Order Code Weight kg For power supply voltage 60 220 V, DC or 60 240 V, 50 60 Hz 1SFA 663 001 R1001 1.68 24 48 V, DC 1SFA 663 001 R1002 1.68 - simplified version CRL97 665-09 CRL97 665-10 For power supply voltage 60 220 V, DC or 60 240 V, 50 60 Hz 1SFA 663 001 R1003 1.68 24 48 V, DC 1SFA 663 001 R1004 1.68 Detectors 1) with optical cable of plastic fibre Cable length 1 m 1SFA 663 003 R1010 0.02 2 m 1SFA 663 003 R1020 0.02 4 m 1SFA 663 003 R1040 0.04 6 m 1SFA 663 003 R1060 0.06 8 m 1SFA 663 003 R1080 0.08 10 m 1SFA 663 003 R1100 0.10 15 m 1SFA 663 003 R1150 0.15 20 m 1SFA 663 003 R1200 0.20 25 m 1SFA 663 003 R1250 0.20 30 m 1SFA 663 003 R1300 0.30 Other lengths On request The unit can be connected to either of these supply voltages: New 24, 48, 60, 110, 125, 220 V DC or 110 127 or 230 V AC. 1SFA 663 002-A 1.5 Optical cable of plastic fibre 1) For connection between units: to to to The cables are provided with plug-in connectors. Cable length 0.5 m 1SFA 663 004 R1005 0.01 1 m 1SFA 663 004 R1010 0.01 2 m 1SFA 663 004 R1020 0.02 4 m 1SFA 663 004 R1040 0.04 6 m 1SFA 663 004 R1060 0.06 8 m 1SFA 663 004 R1080 0.08 10 m 1SFA 663 004 R1100 0.10 15 m 1SFA 663 004 R1150 0.15 20 m 1SFA 663 004 R1200 0.20 25 m 1SFA 663 004 R1250 0.25 30 m 1SFA 663 004 R1300 0.30 1) Also suitable for 1SFA 663 001-A -B, SK 663 121-A -G and SK 663 122-A -G. Description page 6 Technical data page 8 Dimensions page 9 Diagrams page 10 4 Low Voltage Products

Ordering particulars Mounting bracket set Order Code Weight kg For mounting of detectors. Detectors are secured to the bracket by means of cable straps. 1 set including 5 pcs of bracket and 10 pcs of cable strap 1SFA 663 006 R1010 0.25 Mounting kit 600 mm 1SFA 663 006 R1001 0.35 800 and 1000 mm 1SFA 663 006 R1002 0.60 Installation and Maintenance Instruction English Swedish German Spanish Finnish English (for the simplified version) Swedish (for the simplified version) Information label 1SFA 663 007 R1001 1SFA 663 007 R1002 1SFA 663 007 R1003 1SFA 663 007 R1004 1SFA 663 007 R1005 1SFA 663 007 R1011 1SFA 663 007 R1012 Label to apply to the front of the switchgear cubicle. Text: This equipment is protected by Arc Monitor type TVOC 1 set including 10 pcs 1SFA 663 005 R1001 0.02 Flush mounting set Consisting of mounting bracket, gasket and screws. 1SFA 663 006 R1015 0.53 Drilling plan 210 18.5 51.5 D=6 (4x) 173 70 173 Description page 6 Technical data page 8 Dimensions page 9 Diagrams page 10 Low Voltage Products 5

Description 1. CRL97 665-08 2. Example showing the position of detectors in: 1. Horizontal and vertical busbar system 2. Circuit-breaker cubicle CRL97 665-07 Arc faults Most short circuit faults in LV and MV switchgears are accompanied by an electric arc. An arc fault always leads to considerable damage to equipment and personnel unless it is distinguished very fast. The fault should be disconnected as fast as possible and in less than 0.1 s to avoid serious damages and give involved person a fair chance to survive the accident without severe damages. This is a demand found in the electrical safety rules in all CE countries, ref. IEC364-4-42. The is an aid to quickly detect an arc fault and trip the incoming circuit-breaker. The main advantage with the Arc Guard System is that it can trip instantaneously, i.e. override other tripping functions. Function The is used for high-speed tripping of the main circuit-breaker in the event of an arc fault. with detectors The unit reacts to short-circuit arcs and immediately transmits a tripping signal. A maximum of nine detectors can be connected to each unit. (Max. four detectors for the simplified version). Normally only one detector is required in each compartment The can be located anywhere in the switchgear. For practical reasons, the length of the optical fibre cables should be kept to a minimum. Should an arc occur, the detector concerned transmits the light to the and a solid state contact in it operates within a millisecond. This contact is connected in series with the shunt release of the circuitbreaker. Even if the over-current release of the circuit-breaker is delayed to provide selectivity, this does not influence the operation of the Arc Monitor. In addition to the light produced by arcs, the is also sensitive to other sources of intense light such as photo flashes, sunlight directly on the detector, intense lamp light close to a detector or normal arc light from such large items as circuit-breakers. By combining the with a, a current logic condition is introduced that prevents circuit-breaker tripping by none relevante light sources. EMC feature The switchgear and controlgear equipment in which the Arc Guard System is intended to be placed generally represents a severe environment in terms of electromagnetic interference. High currents in busbars and cables, switching of inductive loads, arcs from switching equipment etc. generate electromagnetic fields of considerable strength. Electrical wires act as antennas and pick up electrical interference voltage. By using optical fibres the installation is not sensitive to electromagnetic interference. The basic EMC publications IEC 1000 define different electrical environment classes and corresponding test levels. A switchgear is generally regarded as a more severe electrical environment than a typical industrial electrical installation. The is tested acc. to the test level for servere industrial environment or switchgears with mixed signal and power cables. The Arc Guard System is tested according to following standards: IEC 1000-4-2, level 3 IEC 1000-4-3, level 3 IEC 1000-4-4, level 4 and corresponding part of SS 436 15 03, PL4 IEC 1000-4-5, level 4/3 IEC 1000-4-6, level 3 IEC 1000-4-11 IEC 1000-4-12, level 4/3 The Arc Guard System fulfils the requirements for CE-marking acc. to: The EMC-directive 89/336/EEC, tested according to EN 50081-1 and EN 50082-2. The Low Voltage Directive 73/23/EEC. The Arc Guard System is UL-listed. System security The Arc Guard System is a product to ensure highest possible safety level and is expected to operate with absolute dependability. The system is provided with testing functions and it should be checked at regular intervals. The test procedure is described in the instruction manual. Description of the Arc Guard System The two units of the, the and the are each built into a light-alloy enclosure provided with a hinged door. Communication between the units and between s and detectors is via optical fibre cables. The simplified version of the Arc Guard System is specially suited for substations. Note: The simplified version of the Arc Guard System can not be used with the. 6 Low Voltage Products

Description Combinations F11 A1 Q1 Arc Guard System with F11 F21 A1 T1 A1 F11 F21 T1 Q1 Switchgear Current transformer Circuit-breaker Arc Guard System with and Available for AC and DC supply. The two output stages are triacs triggered via a pulse transformer. In this way, the output stages are galvanically separated from each other and from other circuits. The has two separate relay outputs. Each relay has one change-over contact function. Relay K1 is used for EXTERNAL TRIP indication and relay K2 is used for POWER ON indication. A switch is included for selection of automatic relay resetting (after approx. 200 ms) or manual resetting of relay K1. A digital display, visible through the window in the door, shows which detector has caused tripping. The display and relay are reset by the pushbutton in the door. The can trip again even if it is not reset. Terminals for connection of power supply voltage, circuit-breaker trip circuits and signal circuits. Optical plug-in connectors are provided for the detectors and for the communication cables to other units. (Not for the simplified version) The power consumption of the unit is approx. 6 W. Energy is stored in the unit for operation up to 0.2 s if the supply voltage would fail, this is sufficient to activate the output even if voltage disappears in conjunction with a short circuit fault. Current sensing unit For AC and DC Terminals for connection of external current transformers. The function of the current sensing unit is to block the tripping of the arc monitor at a load current below a certain adjustable value. The unit incorporates a selector switch and a potentiometer for testing purpose. Power consumption is approx. 11 W. Optical signal transmission If several s are needed, they can be connected in series using optical cables. LEDs indicate when the load current exceeds approx. 70% and100% of the set value. Connection of current transformers The unit is to be connected to current transformers with a rated secondary current of 1, 2 or 5 A. Note that current transformers for relay protection are to prefer since these do not saturate as quickly as ordinary current transformers. The transformers selected should not saturate before at least 2 times the set over current level. The current sensing unit can be either 1, 2 or 3-phase connected, however, three-phase is to prefer for safety reasons. The burden of the unit is only 0,7 VA so current transformers for other purposes can often be used. Detectors and Optical cables General The used optical plastic fibre cables are prefabricated and can not be cut or joint and they must be run in smooth curves during the installation. Both Detector cables and Optical cables are available in certain standard lengths, see the ordering table. Other lengths can be quoted on request. Maximum length, see ordering table. The plastic fibre is made of polymethylene acrylate (PMMA) with a jacket of PVC. Detectors Each detector consists of an optical cable and a lens that are calibrated together to get the same sensitivety independent of cable length. The detector has a plug-in connector that fits to the arc monitor. The lens collects light from all directions, with exception of a small shaded area behind the detector. See polar diagram below. Practical experiments have shown that arc light reflected between metallic surfaces may be sufficient to cause tripping. A maximum of nine detectors can be connected to 1SFA 663 001 R1001 and 1SFA 663 001 R1002. To the simplified version 1SFA 663 001 R1003 four detectors can be connected If more detectors are required, several units can be connected in parallel. Detection area Polar diagram of detector in three dimensions Tripping of several breakers For tripping of several breakers an intermediate relay is often required. In order not to delay the tripping function a relay of fast acting type (4 ms) is recommended. For DC trip circuits ABB s relay of type RXMS (Order Code. RK 216 263-...) is suitable. Where a greater load capacity is required this relay can be connected in parallel with a relay of type RXMH (Order Code RK 223 067-...). In DC trip circuits it is necessary to add an external break contact in series to reset the triacs after tripping. An impulse relay with an indication flag can be used to indicate a tripped even after loss of auxiliary voltage. A suitable impulse relay of type E251, E252, E254, E255 or E256 can be choosen from our system ProM assortment. Low Voltage Products 7

Technical data Solid state contacts (K3, K4)(triacs)disconnectible terminals Largest load current: Continuously 0.7 A For 200 ms 30 A Smallest recommended load current (temperature 25 C) DC 45 ma at stated polarity AC 80 ma (temperature - 25 C) DC 80 ma at stated polarity Leakage current, I r at 220 V, AC 8 ma at DC 0.5 ma For other voltages AC I r = U x f x 0,0006 (ma) Peak withstand voltage 600 V Load voltage Max. 250 V Signal relay contacts (K1, K2) 1SFA 663 001... R1001, R1002 R1003, R1004 Thermal rated current, I th 5 A 5A Rated operational current, I e Utilisation category as per IEC 947-5-1: AC-15 U e=250 V 1.5 A 1.5 A DC-13 U e=48 V 1.0 A 1.0 A 110 V 0.3 A 0.3 A 220 V 0.15 A 0.15 A Minimum switching load 5 V DC, 10 ma 5 V DC, 10 ma Optical inputs Quantity For light detectors 9 4 From or another 1 - Optical outputs To another 1 - To Breaker Fault Unit 1 Not used - Indications: Operating voltage available Upon tripping Decimal point on digital display lit up. Relay K2 energized. Digital display lit up. The digit shows which detector was active (1...9). Relay K1 energized. Control devices/settings: External (on door) Pushbutton - Resetting button Manual resetting Internal (on p.c.b.) Change-over switch - Switching on and off of On/Off - Manual resetting of signal relay On/Off Trimming potentiometers - Sensitivity setting Normally not to be adjusted Supply voltage: See ordering table Permitted variation +/ 20 % at DC +/ 10 % at AC Internal fuse 0.8 A delayed (5 x 20 mm) Main fuse max 10 A fast Power consumption 6 W Permissible ambient temperature 25...+55 C Operating time: From detection to switched on approx. 1 ms (dependent on triac outputs light intensity) From detection to made relay contact < 10 ms Current condition from input to output < 0.3 ms (with 1 m optical cable) (not for the simplified version) Degree of protection IP 54 Start-up time for power on 50 ms at 60V AC/DC 15 ms at 220-240 V AC/DC 50 ms at 24 V DC 15 ms at 48 V DC Approvals See page 2 Rated current Selectable, for connection of external current transformers with secondary rated current 1, 2 or 5 A Load on the external 0.2 VA connected for 1 A current transformers 0.7 VA connected for 5 A The withstands a maximum of: Continuously 1 x rated current For 1 s 15 x rated current Optical outputs: To /Current Quantity: Sensing Unit 2 Optical inputs: From other Current Sensing Quantity: Unit 1 Indications: Signal to / Pre-warning Test position Control devices/settings: (on the p.c.b.) Change-over switch Test position Optical input is used or not Trimming potentiometers Setting of overcurrent level Simulation of overcurrent level in test position Supply voltage Permitted variation Power consumption Green LED lit up at load current < set overcurrent level Yellow LED lit up at load current < approx. 70% of set overcurrent level Red LED On/Off On/Off 0.5 3.5 x rated current See ordering table +/ 20 % at DC +/ 10 % at 110-127 V AC +10 % 15 % at 230 V AC 1 W at 24 V 11 W at 220 V Permissible ambient temperature 25...+ 55 C Operating times From overcurrent occurring to actuating optical outputs: At currents 2 x set overcurrent level 3-phase supply. < 2 ms 1-phase supply. < 8 ms Current conditions from optical input to optical outputs < 0.3 ms Degree of protection IP 54 8 Low Voltage Products

Dimension drawings Detector with optical cable A flange with 6 tapped holes (size 18.6 mm) 4 cable glands (sealing diameter 5.5-8.5 mm) and 2 plastic blank plugs are supplied. Detector and optical fibre cable Permissible ambient temperature Continuous -25...+70 C Short-time -25...+85 C Smallest bending radius of optical cable: after installation 45 mm upon handling 10 mm Terminals Terminal Cross section of connectible cables mm 2 13,14, 25...30 4 20...23 2.5 1...6 4 10...14 2.5 Mounting bracket Mounting kit Low Voltage Products 9

Diagrams (Order Code 1SFA 663 001 R1001, 1SFA 663 001 R1002) 1 9 Detector input 10 Input current signal from a Current Sensing Unit or another 11 Output current signal to another Arc Monitor 12 Not used D9 Display for activated detector Decimal point lights up during operation. F1 Fuse for supply voltage K1 Indication has tripped K2 Indication in operation K3,K4 Solid state trip contacts for circuitbreaker S1 Switch for: 1 Closed: Current signal used, Open: Current signal not used 2 Closed: Manual reset K1 (via S2) Open: Automatic reset K1 after 200 ms 3 and 4 Not used S2 Manual reset button for K1 and D9 Terminals 13,14 Power supply 20 23 Solid state trip contacts 25 30 Indication contacts, simplified version (Order Code 1SFA 663 001 R1003, 1SFA 663 001 R1004) 250 V AC/DC 30 A 200 ms 0.7 A cont. 1 Arc detectors 5 A 240 V AC general purpose 5 A 240 V AC general purpose U 0 /+ /- D9 Indication of activated detector Decimal point illuminated at operation F1 Fuse for power supply. 0.8 A T R... For adjustment of sensitivity S2 Reset button K1 Relay for trip indication K2 Relay for in service indication K3, K4 Solid state contacts (triacs) for tripping circuit-breakers 10 Low Voltage Products

Application diagrams A) Testing facilities: R29 Simulating a test current S1 1 = Test position 2 = Operation position V22 Red ON = S1 in test position OFF = S1 in operation position B) Setting facilities: R21 Overcurrent setting S2 1 = Input 9 not used 2 = Input 9 used V27 Yellow ON = Load current less than 70% of set overcurrent level OFF = Load current more than 70% of overcurrent level V29 Green ON = Load current less than set overcurrent level OFF = Load current more than set overcurrent level X) Current range bridge connections: 1A: 24 17, 25 20, 26 23 2A: 24 16, 25 19, 26 22 5A: 24 15, 25 18, 26 21 On delivery Power supply terminals 10 and 12 24 V DC 11 and 12 60 V DC 11 and 12 48 V DC Interconnection 11-13 13 and 12 110 V-125 V AC/DC 14 and 12 220 V DC, 230 V AC Terminals 1 6 Current transformer terminals 7 8 Output current signal to another or 9 Input current signal from another Arc Guard System with two separated circuit-breakers (Suitable for Order Code 1SFA 663 001 R1001, 1SFA 663 001 R1002) Several s The can be linked with several s by connecting the s in series. Parallel connection of Arc Monitors In installations with more than one. Current sensing function is transmitted to next via fibre cable (4). (4) A1 Switchgear or similar F11, F12 F21, F22 Q1,Q2 Circuit-breaker T1, T2 Current transformers (1), (7) Detector cables (optical fibre cable) (2), (8) Trip circuit for circuit-breaker (electric cable, separately powered) (3) Current signal to (optical fibre cable) (4) Current signal is transmitted to second via optical cable Low Voltage Products 11 1SFC 266006-en, Ed. 3 November 2000

Application diagrams Arc Guard System with current measuring in five incoming feeders (Suitable for Order Code 1SFA 663 001 R1001, 1SFA 663 001 R1002) A1, A2 Switchgear or similar F11 F15 F21 F25 K1, K2 Fast tripping relay T1 T5 Current transformers Q1 Q5 Circuit-breaker Q6 Bus coupler (1), (7) Detector cables (optical fibre) (2), (8) Trip circuit for circuit-breaker (electric cable, separately powered) (3) Current signal to (optical fibre cable) Prod. ABB Automation Technology Products AB/Control/XM Printed in Sweden Västerås 2003-11 ABB Automation Technology Products AB/Control SE-721 61 Västerås, Sweden Catalogue 1SFC 266006-en, Edition 3, November 2003 Supersedes Catalogue 1SFC 266006-en, Edition 2, November 2000 Telephone +46 21-32 07 00 Telefax +46 21-12 60 01