, -Way, haracterized ontrol Valve Stainless Steel all and Stem pplication This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VV box re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. Suitable ctuators Non-Spring Spring TR, LR, NR TR, L ate created, 0/07/06 - Subject to change. elimo ircontrols (US), Inc. Technical ata 069 Service chilled, hot water, up to 60% glycol low haracteristic equal percentage ontrollable low Range 75 Size [mm] 0.5 [5] nd itting NPT female ends ody forged brass, nickel plated all stainless steel Stem stainless steel Stem Packing PM (lubricated) Seat Teflon PT Seat O-ring PM (lubricated) haracterized isc TZL ody Pressure Rating [psi] 600 Media Temperature Range 0 to 50 [-8 to 0 ] (Water) Max ifferential Pressure (Water) 50 psi (345 kpa) lose-off Pressure 00 psi v 3 Weight 0.7 lb [0.3 kg] Leakage 0% for to Servicing maintenance free low Pattern H LR, LRX H H H 9.4.38 5.58 5 [7].3 [33].8. [8] [39] [60] [4] [30] 800-543-9038 US 866-805-7089 N 03-79-8396 LTIN MRI / RIN
, -Way, haracterized ontrol Valve Stainless Steel all and Stem TR R N4, RX N4, NR N4, NRX N4 3.7 [95].38 [60] 5.9 [3] 4.6 [7].5 [3].36 [89].38 [60] 7.68 [95] 7.06 [79].44 [6] TR, TRX 6.59 [67].38 [60] 5.48 [39] 4.7 [0].53 [38] L ate created, 0/07/06 - Subject to change. elimo ircontrols (US), Inc. 7.9 [0].38 [60] 6.06 [54] 5.48 [39].8 [46] 800-543-9038 US 866-805-7089 N 03-79-8396 LTIN MRI / RIN
LRX4-MT Modulating, Non-Spring Return, 4 V, Multi-unction Technology ate created, 0/4/07 - Subject to change. elimo ircontrols (US), Inc. Technical ata 60 Power Supply 4 V ± 0%, 50/60 Hz, 4 V ± 0% Power onsumption Running.5 W Power onsumption Holding. W Transformer Sizing 5 V (class power source) lectrical onnection 8 G plenum rated cable with / conduit connector protected NM (IP54) 3ft [m] 0ft [3m] and 6ft [5m] Overload Protection electronic thoughout 0 to 90 rotation Operating Range to 0 V, 4 to 0 m w/ ZG-R0 (500 Ω, /4 W resistor), variable (V, floating point, on/off) Impedance 00 k Ω for to 0 V (0. m), 500 Ω for 4 to 0 m, 500 Ω for PWM and on/off eedback Output U to 0 V, 0.5 m max, V variable ngle of Rotation 90 irection of Rotation (Motor) reversible with built-in switch Position Indication integrated into handle Manual Override external push button Running Time (Motor) 50 sec (default), variable (35 to 50 sec) mbient Temperature Range - to [-30 to 50 ] Storage Temperature Range -40 to 76 [-40 to 80 ] Housing NM, IP4, UL enclosure type gency Listings culus acc. to UL60730-/--4, N/S 60730-:0, acc. to 004/08/ Noise Level (Motor) <35 d () Servicing maintenance free Quality Standard ISO 900 Rated Impulse Voltage 800V, Type action., ontrol Pollution egree 3. 800-543-9038 US 866-805-7089 N 03-79-8396 LTIN MRI / RIN
Wiring iagrams INSTLLTION NOTS Provide overload protection and disconnect as required. ctuators may be connected in parallel. Power consumption and input impedance must be observed. ctuators may also be powered by 4 V. Only connect common to negative (-) leg of control circuits. 500 Ω resistor (ZG-R0) converts the 4 to 0 m control signal to to 0 V. ontrol signal may be pulsed from either the Hot (Source) or ommon (Sink) 4 V line. or triac sink the ommon connection from the actuator must be connected to the Hot connection of the controller. Position feedback cannot be used with a triac sink controller; the actuator internal common reference is not compatible. IN4004 or IN4007 diode. (IN4007 supplied, elimo part number 4055). ctuators with plenum cable do not have numbers; use color codes instead. Meets culus requirements without the need of an electrical ground connection.! WRNING! LIV LTRIL OMPONNTS! uring installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. ailure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. LRX4-MT Modulating, Non-Spring Return, 4 V, Multi-unction Technology 4 V Transformer 3 8 Position ( ) eedback V (+) On/Off Position ( ) eedback V (+) lk () 4 V Transformer ( Only) loating Point ontrol Signal ( ) V / m (+) Ω 500 Ω /4 watt ommon 0 8 lk () ommon 4 V Transformer 3 5 8 V/m ontrol 7 lk () 4 V Transformer ( Only) Position eedback V PWM ontrol ( ) (+) ommon 8 8 lk () ommon ate created, 0/4/07 - Subject to change. elimo ircontrols (US), Inc. 800-543-9038 US 866-805-7089 N 03-79-8396 LTIN MRI / RIN
LRX4-MT Modulating, Non-Spring Return, 4 V, Multi-unction Technology 4 V Transformer ( Only) 5 8 ontrol Signal ( ) V / m (+) Ω 7 unctions Min 0% Mid 50% Max 00% Normal ontrol mode acc. to Override ontrol lk () a b c ommon + Hot ate created, 0/4/07 - Subject to change. elimo ircontrols (US), Inc. 800-543-9038 US 866-805-7089 N 03-79-8396 LTIN MRI / RIN