RWD44U Controller. Installation and Commissioning Guide Document No October 5, Function. Application

Similar documents
RWD68U Controller. Installation and Commissioning Guide Document No October 1, Function. Application

Technical Instructions Document No EA GQD October 25, OpenAir GQD Series

R7420B. MicroniK 100 HONEYWELL TEMPERATURE CONTROLLER PRODUCT DATA GENERAL FEATURES

ELECTRONIC THERMOSTAT: T920

Technical Instructions Document No EA GQD June 23, OpenAir

TLC3-BCR-U Series Thermostat

Analogue temperature controllers

TBX-68S Isothermal Terminal Block

ECB-103 BACnet B-ASC 10-Point Programmable Controllers

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

Series Valve Temperature Controller. Instruction Sheet

SRC-110 Series Zone Controllers with Modbus RTU

Microprocessor Based Multistage Temperature Controller & Two Channel 365 Day Time Switch. Made in Australia 100% Australian Owned Company

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

April 1994 UCM-420A. Setpoint Controller. Operating and Installation Instructions

Intelligent Compact Controller

ELECTRONIC THERMOSTAT: T951

CHAPTER KEYPAD OPERATION AND QUICKSTART. In This Chapter... The GS2 Digital Keypad GS2 Quickstart...3 6

Variable Speed Brushed DC Motor Drive

R7426A. MicroniK 200 TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK

QPM Series Indoor Air Quality Duct Sensors

OVEN INDUSTRIES, INC. Model 5C7-362

Interface EKC 366 REFRIGERATION AND AIR CONDITIONING. Manual

A Few Applications For Signal Conditioners

TAC ATV38, IP55. Variable Speed Drives for Asynchronous Motors. 3-phase. 380/460 V, Hz

Electronic Controls For general purpose and multi stages controls. Features and Benefits

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)

TC 204 Heating Controller

REE series digital interpolators

MFJ ENTERPRISES, INC.

MFJ ENTERPRISES, INC.

DP2500 DP0100 DP0250 Differential Pressure Transmitter

TEC Controller Constant Volume with Hot Water Reheat, Application Application Note Building Technologies

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

The GS1 Digital Keypad LED Display Function Keys Displaying the Status of the GS1 AC Drive Programming the GS1 AC Drive...

DP2500 DP0100 DP0250 Differential Pressure Transmitter

BT300 VFD FS8 and FS9 Bypass Option EMC Filter Package. Product Description. Expected Installation Time. Prerequisites. Warning/Caution Notations

Use of the application program. Contents. instabus EIB Application program description. September S2 Room temperature controller

Variable Refrigerant Flow (VRF) System Simple Touch Remote Control SAFETY WARNING

PROCESS & TEMPERATURE CONTROLLERS

AMERITRON SDC-102 Screwdriver Antenna Controller

Room Temperature Controllers. for heating and cooling systems

Installation Guide. ECL Comfort 310, application A Table of Contents

6.6 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0)

Room Temperature Controllers. for heating and cooling systems

USER MANUAL. EPP Intelligent Positioner Control Unit 1/22.

TC LV-Series Temperature Controllers V1.01

APPENDIX APPENDIX A 1

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

Honeywell. W7620 Zone Controller Water Source Heat Pump A. GENERAL RESIDENTIAL AND BUILDING CONTROL GUIDE SPECIFICATION FOR THE ENGINEER

B850 Boiler House Energy Monitor

Digital amplifier for proportional valves PEM XD

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS

Manual BC20 Control Service Guide

CONNECTIONS. TABLE 1: Wiring Configuration Based on Motor Amps. FIGURE 1: Typical Wiring Diagram

P5201 Universal Programmable Transmitters with Galvanic Isolation

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

Operating instructions Electronic level sensor LK / / 2008

Electronic amplifier for the control of proportional valves without position control Model VT 3006, Series 3X H/A 4240/94 VT X

Electronic Air / Fuel Ratio Control System

TAC 2112 Manual (GB),

Installation, Operation and Maintenance Instructions

F2A3X Frequency to Analog Converter Module

Series R48 Single Zone Load Sequenced Economizer System: Installation & Troubleshooting

This Errata Sheet contains corrections or changes made after the publication of this manual.

PID500 FULL FEATURED PID TEMPERATURE CONTROLLERS

3400HD Series TECHNICAL MANUAL X-3400HD DTI-3400HD D-3400HD. 3400HD Unwind (using 3400ce Circuit Board) Montalvo. Unwind Tension Controllers

FCU-503 FAN COIL CONTROLLER WITH RDU-TOUCH INTERFACE

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W

RCMS460 and RCMS490 Series

DSCL, DSCP, SCTP. Industrial Loop Isolators and Transmitters DSCL, DSCP, SCTP. Industrial Loop Isolators and Transmitters

ecotrans Lf 01/02 Transmitter / Switching Device for Conductivity Type B Operating Instructions 02.07/

Multi-point Temperature Controller

Functional Safety Application Guide

Fuse, external A 6A, medium time lag. Power consumption W min 20 - max 60 (see paragraph 5.2) Output current A maximum 4.5 (see paragraph 5.

400,440Vac Vdc V, A, W, VA, var, Hz, V, Avg. A cos phi, sin phi and phi measurement kwh, kvarh (via Pulse Output)

Room Temperature Controllers. for heating and cooling systems

SmartZone-2 & SmartZone-4

NX Series Inverters. HVAC Pocket Programming Guide

Self-learning Room Temperature Controller Receiver

VSD Series II Variable Speed Micro Drives (VSM II) FS1 FS5

INSTRUCTION SHEET. Eaton Logic Controller ELCM TC Temperature Modules. [Applicable Temperature modules] ELCM-TC04ANNN MTN1

ECP-400 Series. ECP-400 Series. 24-Point Free Programmable Controller. Applications. Features

Micro-controller X Model: PXE4. Operation Manual. INP-TN5A1887a-E

TA-Slider 160 KNX R24 Protocol Implementation

Valve Island with Electronic I/O

ALPTEC POWER FACTOR CONTROLLER

KNX manual High-performance switch actuators RM 4 H FIX1 RM 8 H FIX2

Fan Coil Actuator FCA 2

EY-EM 527: Remote I/O module, ecolink527

LabCon User Manual. Multi-Purpose Temperature Controller Temp High SP

DPF-MAC Auto power factor controller

Troubleshooting Guide for Aquatrac Smart AS and Flex

F4-08RTD 8-Channel RTD Input

ControlMaster CM10, CM30, CM50 Universal process controllers, 1 /8, 1 /4 and 1 /2 DIN

Model No. DFC Support DIGITAL ENHANCED GAS FIRED MODULATING CONTROL

Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual

The appliance is fitted with a 3-digit display in order to show the room temperature and the 2 + and - key parameters for the programming functions.

Modbus communication module for TCX2: AEX-MOD

Transcription:

RWD44U Controller Installation and Commissioning Guide Document No. 129-408 Function RWD44U controllers are intended for HVAC and Refrigeration systems including Heat Pumps. They are suitable for 1-, 2-, and 3-stage compressors. Input X1 detects the room or space temperature and compares it with the setpoints. Depending on the deviation, the controller acts accordingly with its outputs to achieve the desired setpoints. Function Summary Controller Stand-alone controller with four two-position (On/Off) outputs. Universal input (X1) for the main temperature sensor. Universal input (X2) for the following auxiliary functions: On/Off (Standby) Remote setting unit Alarm Filter alarm Setpoint reset Sensor averaging Winter/Summer setpoint changeover Sensor select Application Digital input (D1) for the following digital functions: Day/night changeover setpoint On/Off (Standby) Alarm Filter alarm The RWD44U controller is intended for either DIN rail mounting in a switchboard or screw mounting with a protective enclosure. Desired output configuration and auxiliary function must be entered for initial setup. See Initial Program Settings (New Controller). The RWD44U has standard pre-configured applications. There are three main configuration loops with combinations of ten auxiliary functions. See Table 1. Item Number 129-408, Rev. BA

Document Number 129-408 H = Heating C = Cooling Cr = Compressor RV = Reversing valve Eco = Economy RWD44U Controller Installation and Commissioning Guide Table 1. Application Numbers. Main Loop RV RV Auxiliary Loop #1 (2H & 2C) #2 (3 stage Cr + RV cool) # 3 (3 stage Cr + RV heat) #x0 (Standby) #10 #20 #30 #x1 (Remote #11 #21 #31 setpoint) #x2 (Alarm) #12 #22 #32 #x3 (Filter alarm) #13 #23 #33 #x4 (Setpoint reset) #14 #24 #34 #x5 (Avg. X1, X2) #15 #25 #35 #x6 (Win/Sum Digital) #16 #26 #36 #x7 (Win/Sum #17 #27 #37 Analog) #x8 (Sensor select) #18 #28 #38 #x9 (Active input) #19 #29 #39 Three-stage compressor applications are also used for one- and two-stage applications. Compressor stages are selected during commissioning. Example: Two-stage compressor with reversing valve on heating, and two averaging sensors: #35 Table 2. Input Configurations X1, X2, and D1. Applications 10 Through 39 D1 Options X1 X2 Filter Alarm Alarm Day/Night Standby #x0 (Standby) Main Standby #x1 (Remote setpoint) Main Remote setpoint #x2 (Alarm) Main Alarm #x3 (Filter alarm) Main Filter alarm #x4(setpoint reset) Main Setpoint reset #x5 (Avg. X1, X2) Main Main #x6 (Win/Sum Digital) Main Win/Sum #x7 (Win/Sum Analog) Main Win/Sum #x8 (Sensor select) Main Main #x9 (Active input) Main Standby Table 3. Output Configurations Q1, Q2, Q3, and Q4. Application Q1 Q2 Q3 Q4 Numbers 10 through 19 Heating Stage 2 (H2) Heating Stage 1 (H1) Cooling Stage 1 (C1) Cooling Stage 2 (C2) 20 through 29 30 through 39 Reversing Valve (RV) Compressor Stage 1 (Cr1) Compressor Stage 2 (Cr2) Compressor Stage 3 (Cr3) Application sheets for the listed applications are available online. Page 2 of 10 Siemens Industry, Inc.

RWD44U Controller Installation and Commissioning Guide Document Number 129-408 Display Explanation Symbol Description Setting Range Symbol Description Setting Range Main Screen + Adjustable setting screen TOOL PC communication port being used - #10 Application No 10 through 39 OUT RANGE The setting is out of range Day time operation Err Sensor error Night time operation Sec Seconds X1 Universal (Main) Input X1 Ni 1000 Ω: -58 F to 302 F (-50 C to 150 C) (unchangeable) Pt 1000 Ω: -4 F to 356 F (-20 C to 180 C) (unchangeable) 0 to 10 Vdc: -100 to 2400 X2 Universal (Auxiliary) Input Ni 1000 Ω: -58 F to 302 F (-50 C to 150 C) (unchangeable) Pt 1000 Ω: -4 F to 356 F (-20 C to 180 C) (unchangeable) 0 Vdc to 10 Vdc: -100 to 2400 Variable resistor: The resistance range should be within 0 Ω to 1000 Ω C Celsius scale Cooling F Fahrenheit scale Heating K Kelvin SP-h Setpoint on the heating side for temperature control Q Digital outputs SP-c Setpoint on the cooling side for temperature control R/V Reversing valve status = On Output status = Off Standby mode Output status = On "OFF" Controller = Off "ON" Controller = on standby PS 4 Differentials and Delays SD Switching Differential 0.1 K to 50 K TD Time Delay from heat cool TON Minimum switch on time 0 to 4,096 sec TD Time Delay for next for Q stage ON TOFF Minimum switch off time 0 to 4,096 sec for Q PS 3 - Auxiliary Control Loop Set-up Setpoint reset shift Setpoint reset shift (Start point, End point and (Start point, End point and Shift differential) Shift differential) SUM Summer changeover point Time delay from Winter Summer changeover point WIN Winter changeover point D1 Digital input function PS 2 - Unit, X1 and X2 Sensor Type and Sensing Range Definition Unit Define unit C or F ΔX1 Calibration offset for X1 (Ni and Pt sensor only) X1NI 1000 X1 is Ni 1000 Ω temperature sensor Ni 1000 Ω: -58 F to 302 F (-50 C to 150 C) (unchangeable) ΔX2 Calibration offset for X2 (Ni & Pt sensor only) X2NI 1000 X2 is Ni 1000 Ω temperature Ni 1000 Ω: -58 F to 302 F X1L Start point of the X1 sensor (-50 C to 150 C) (unchangeable) (for 0 Vdc to 10 Vdc only) X1Pt 1000 X1 is Pt 1000 Ω temperature Pt 1000 Ω: -4 F to 356 F X2L Start point of the X2 sensor (-20 C to 180 C) (unchangeable) (for 0 Vdc to 10 Vdc only) X2Pt 1000 X2 is Pt 1000 Ω temperature Pt 1000 Ω: -4 F to 356 F X1H Stop point of the X1 sensor (-20 C to 180 C) (unchangeable) (for 0 Vdc to 10 Vdc only) X2SP Remote setpoint 0 Vdc to 10 Vdc or 0 to 1000 Ω X2H Stop point of the X2 (for 0 Vdc to 10 Vdc only) X2Vr Variable Resistor 0 Ω to 1000 Ω 0 to 4,096 sec 0 to 4,096 sec -5 K to 5 K or -9 F to 9 F -5 K to 5 K or -9 F to 9 F -100 to 2400-100 to 2400-100 to 2400-100 to 2400 Siemens Industry, Inc. Page 3 of 10

Document Number 129-408 RWD44U Controller Installation and Commissioning Guide Display Explanation, Continued PS 1 Application Number Selection: Standby mode AVERAGE Averaging sensor X1 and X2 REM Remote setting WIN/SUM AnG Winter/Summer changeover by analog ALARM Alarm indication WIN/SUM dig input Winter/Summer changeover by digital input FILTER Filter alarm indication X2 X1 Selecting X2 or X1 as the main sensor COMP Setpoint reset function Act Active sensor input Commissioning Guide Commissioning is implemented via push buttons on the controller. The push buttons have the following functions: Press SEL Button to enter the PS page OR edit and save the value when the page appears with the logo + Press + Button for viewing the next page OR to increase the value. Press Button for viewing the previous page OR to decrease the value. Changing a parameter: 1. Press the SEL λ button. 2. Press the + σ or τ button to increase or decrease the flashing parameter. 3. Press the SEL λ button to save the value (During PS mode, the values are saved only after exiting the PS mode). A 9-pin port is provided for optional commissioning via Siemens software tool. See Software Tool (Optional Programming). Initial Program Settings (New Controller) There are five levels of parameter setting (PS) modes: PS1 through PS4, and a setpoint mode. Each PS has a set of default parameters, which can be changed during commissioning. When powered the first time, the controller will proceed to PS1 with default application 10. See below for commissioning steps. PS 1 Application Settings Range/Type Default Enter application number 10 through 39 10 Select number of compressor stages 1-, 2- or 3-stage 2-stage Select reversing valve output On or Off during no demand On or Off Off After completing PS1, the user has the option to progress to setpoint mode (only for new RWD) by waiting for two seconds and default parameters will be accepted. If parameters PS2 through PS4 need to be adjusted, press the + button immediately to the next PS (see Commissioning Flowchart). PS 2 Input X1, and X Range/Type Default Select unit F or C F Select main sensor X1 Ni 1000, Pt 1000, 0 to 10V Ni 1000 Enter X1 sensor calibration offset (Ni or Pt only) 9 F (5 C) 0 F Enter X1 active sensor range (0 to 10 Vdc only) -100 to 2400 32 F to 122 F (0 C to 50 C) Select auxiliary sensor X2 Ni 1000, Pt 1000, 0 to 10 Vdc Ni 1000 Enter X2 sensor calibration offset (Ni or Pt only) ± 9 F (+5 C) 0 F (0 K) Enter X2 active sensor range (0 to 10 Vdc only) -100 to 2400 32 F to 122 F (0 C to 50 C) Page 4 of 10 Siemens Industry, Inc.

RWD44U Controller Installation and Commissioning Guide Document Number 129-408 PS 3 Digital and Auxiliary Functions Range/Type Default Select digital input D1 D/N, Filter Alarm, Alarm, on/off Depends on #x Aux. Function = Setpoint reset Setpoint reset start point, reverse acting Setpoint reset sensor range 72 F (22 C) Setpoint reset end point, reverse acting Setpoint reset sensor range 65 F (18 C) Setpoint reset shift Setpoint reset sensor range 8 F (4 K) Setpoint reset n start point, direct acting Setpoint reset sensor range 83 F (28 C) Setpoint reset end point, direct acting Setpoint reset sensor range 90 F (32 C) Setpoint reset shift Setpoint reset sensor range 8 F (4 K) Aux. function = WIN SUM analog Enter changeover setpoint for winter Sensor range 72 F (22 C) Enter changeover setpoint summer Sensor range 83 F (28 C) Enter changeover time delay, winter summer 00.01 to 23 hours 59 minutes 00.01 minute PS 4 Differentials and Time Delays Range/Type Default Enter switching differential (SD) for output stage 1, 2, and 3 Sensor range 2 F (1 K) Enter min On time for output stage 1, 2, and 3 0 to 4,096 s 0 s Enter min Off time for output stage 1, 2, and 3 0 to 4,096 s 60 s Enter time delay TD for next stage On 0 to 4,096 s 30 s Enter changeover time delay TD, heating cooling demand 0 to 4,096 s 120 s Setpoint Mode Range/Type Default Enter SP-h1 Sensor range 70 F (21 C) Enter SP-h2 Sensor range 68 F (20 C) Enter SP-h3 Sensor range 66 F (19 C) Enter SP-c1 Sensor range 74 F (23 C) Enter SP-c2 Sensor range 76 F (24 C) Enter SP-c3 Sensor range 77 F (25 C) If D1 is set for Day/Night Enter night SP-h1 Sensor range 64 F (18 C) Enter night SP-h2 Sensor range 62 F (17 C) Enter night SP-h3 Sensor range 60 F (16 C) Enter night SP-c1 Sensor range 79 F (26 C) Enter night SP-c2 Sensor range 80 F (27 C) Enter night SP-c3 Sensor range 82 F (28 C) For remote setpoint Heating stage 1 is the remote setpoint and the reference point. A SP is set between the stages. H3 H2 Remote Setpoint C1 C2 C2 Enter SP H2 Sensor range -2 F (-1 K) Enter SP H3 Sensor range -4 F (-2 K) Enter SP C1 Sensor range 4 F (2 K) Enter SP C2 Sensor range 6 F (3 K) Enter SP C3 Sensor range 8 F (4 K) After completing the setpoints, press + button for the main display. Siemens Industry, Inc. Page 5 of 10

Document Number 129-408 Main Display (Normal Operation) The controller is active during main display. The main display shows: 1. Whether Q... is On or Off ( = Off, ν = On). 2. X1 temperature in F or C. 3. Day/night settings ( = day, = night). 4. Reversing valve status ( = Off, R/V = On). RWD44U Controller Installation and Commissioning Guide Figure 1. Main Display. Other displays are available by pressing the + button. The various displays are listed below. 1. Setpoints 2. Digital input active or inactive 3. X2 sensor reading 4. Q output status 5. Application #xx Figure 2. Setpoint Display. Changing Setpoint in Main display Time out On entering any of the setpoint displays, the setpoint on display can be adjusted by pushing the SEL λ button. Increase value by pressing the + button, or decrease the value by pressing the button. When the required value is reached, press the SEL λ button to save the new value. For setpoint adjustment during normal operation the controller will exit the setting after 20 seconds, and return to the main screen. However, for setpoint adjustment in PS mode, there is no time limit. The controller remains in the PS mode until the user completes the entire process. Changing the heating setpoints to a lower value, set SP-h3 before setting SP-h2 and SP-h1. Changing the cooling setpoints to a higher value, set SP-c3 before setting SP-c2 and SP-c1. The controller will display an out range message if SP-h3 > SP-h2>SP-h1 and SP-c1>SP-c2>SP-c3. Page 6 of 10 Siemens Industry, Inc.

RWD44U Controller Installation and Commissioning Guide Document Number 129-408 Main Display to PS Mode Press both first. + buttons, and hold for five seconds to enter the PS mode. PS4 will appear Press the button to scroll down to the right PS for editing parameters. When changing from the main display to PS mode, the controller remains active unless a parameter has been changed. Ensure all outputs are disconnected before changing an application. Software Tool (Optional Commissioning) Commissioning Flowchart A software tool for the controller application selection and parameter adjustment is available. It is a user-friendly Windows 95 (or later) based software tool. The software tool has the following functions: Adjusting all available parameters. Uploading and downloading the program. Saving parameter settings. Viewing or providing a printout of the settings. Parameters can be hidden from displaying. Figure 3. Commissioning Flowchart. Siemens Industry, Inc. Page 7 of 10

Document Number 129-408 RWD44U Controller Installation and Commissioning Guide Wiring Terminals Screwed terminals for cables with min 2 16 or 1 14 AWG. Figure 4. Wiring Terminals. G, G0 SELV 24 Vac power supply D1 Digital input M Ground (G0) for signal inputs and universal inputs Q1 to Q4 Relay outputs: Max. rating 24 to 240 Vac Vac/5A res/5 FLA/30 LRA/ 1/2 HP X1 Signal input (main input: Siemens Ni 1000, Pt 1000 and 0 to 10 Vdc) X2 Signal input (aux input Siemens Ni 1000, Pt 1000, 0 to 10 Vdc, and remote setting unit) Tool Communication port for PC (9-pin plug) Wiring Diagrams C1 C2 H1 H2 X1 X2 S1 PC Cooling stage 1 Cooling stage 2 Heating stage 1 Heating stage 2 Room temperature sensor Auxiliary sensor or a digital input Switch or time clock Personal computer (optional, for set-up only) Figure 5. Applications 10 Through 19. CR1 CR2 CR3 RV X1 X2 S1 PC Compressor stage 1 Compressor stage 2 Compressor stage 3 Reversing valve relay Main temperature sensor Auxiliary sensor or a digital input Switch or time clock Personal computer (optional, for set-up only) Figure 6. Applications 20 Through 39. CAUTION: For a single compressor, CR2 and CF3 are not connected. For a dual compressor, CR3 is not connected. The TOOL signal ground is galvanically connected to G0 inside the controller. If the signal line of the computer is grounded to Earth, the G0 line after TOOL connection will be grounded as well. This will change the SELV to a PELV. Page 8 of 10 Siemens Industry, Inc.

RWD44U Controller Installation and Commissioning Guide Document Number 129-408 Installation Mounting Notes Figure 7. Mounting Options. The RWD44U can be mounted as follows: Observe all local installation and mounting regulations. A B C On a DIN rail (EN 50 022-35 7.5) at least 4.75 inches (120 mm) long for RWD44U. Wall-mounted with two screws. (Minimum length of the screws should be 2.75 inches (70 mm) (φ3.2 mm) Front-mounted using standard elements: One DIN rail 5.90 inches (150 mm) long for RWD44U Two hexagonal placeholders 1.96 inches (50 mm) Washers Screws (Ensure all terminations are tightened before final mounting to front panel.) D Inside the ARG62.21 (single RWD44U). WARNING: There must be a minimum of 0.31 inches (8 mm) distance from terminations to panel/enclosures to avoid electric shock. Electrical Installation Notes Standard cables can be used for the controller. However, when mounting in an environment greatly exposed to EMI, use only shielded cables. The RWD44U is designed for 24 Vac operating voltage. Low voltage must comply with the requirements for safety extra-low voltage (SELV) as per EN 60730. Use safety insulating transformers with double insulation as per EN 60742; they must be designed for 100% duty. When using several transformers in one system, the connection terminals G0 must be galvanically connected. Supplying voltages above 24 Vac to low voltage connections may damage or destroy the controller or any other connected devices. Additionally, connections to voltages exceeding 42 Vac endanger personal safety. Siemens Industry, Inc. Page 9 of 10

Document Number 129-408 RWD44U Controller Installation and Commissioning Guide Dimensions Figure 8. RWD44U Controller Dimensions in Inches (Millimeters). Figure 9. ARG62.21 Enclosure Dimensions in Inches (Millimeters). Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Windows is a registered trademark of Microsoft Corporation. Other product or company names mentioned herein may be the trademarks of their respective owners. 2007 Siemens Industry, Inc. Siemens Industry, Inc. Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089 + 1 847-215-1000 Your feedback is important to us. If you have comments about this document, please send them to SBT_technical.editor.us.sbt@siemens.com Document No. 129-408 Printed in the USA Page 10 of 10