Presents. Harmonics Years

Similar documents
Harmonics I Harmonics White Paper. Power Protection Products, Inc. by Dan Maxcy l 2018 Update

Power Factor & Harmonics

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

7/15/2002 PP.AFD.08 1 of 28

Power Quality. Answering Today s Power Challenges. Why Your Existing Transformer May Be Inadequate. How Harmonics Affect Transformers

2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution

22.0 Harmonics in Industrial Power Systems

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation

Load Isolation Transformers

Harmonic mitigating transformers. Energy savings through harmonic mitigation

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --

Economical Solutions to Meet Harmonic Distortion Limits[4]

Effects of Harmonic Distortion I

Harmonic control devices. ECE 528 Understanding Power Quality

Harmonics, its Mitigation & Result of Case study of Spinning Mill

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM

Harmonic Mitigating Transformer - Technical Guide

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Guide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics

Thyristorised Automatic Power Factor

Harmonic mitigating transformers. Energy savings through harmonic mitigation

Understanding Harmonic Suppression Systems

Electromagnetic Harmonic Filters Technical Guide

Low Pass Harmonic Filters

Single-Phase Transformation Review

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

General Description & Features Selection Charts Definition of Terms... 42

Harmonic Filters for Single Phase Equipment

Bruce L. Graves /01/$ IEEE. IEEE Industry Applications Magazine PhotoDisc, Inc.

ULTRA-K Series 600K - he

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

Preface...x Chapter 1 Electrical Fundamentals

Dry Type Distribution Transformers NON-LINEAR TRANSFORMER PRESENTATION

Understanding Harmonics

Non-Linear Load Transformers

Tech Byte 16: The Truths About Transformers Part 2

Active Harmonic Filter

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

Harmonic control devices

SWF DV/DT Solutions Sinewave Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

ECET Modern Power

ASSOCIATION OF ENERGY ENGINEERS NORTHERN OHIO CHAPTER APRIL 21, 2005

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Tuningintobetter power quality

An Introduction to Power Quality

Effective Harmonic Mitigation with Active Filters

How adjustable speed drives affect power distribution

Emicon Engineering Consultants L.L.C.

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008

THE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY

HARMONIC MITIGATIONCASE STUDY

Power Quality Solutions

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Review of Electrical Noise on 120/240 volt Power Systems. Dec 12,

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant

Frequently Asked Questions (FAQs) MV1000 Drive

New power tools provide quality and efficiency By

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

1C.4.1 Harmonic Distortion

Glossary 78 LIFETIME LIMITED WARRANTY. GREENLEE Phone: (International)

Alternators Reactance for Nonlinear Loads

ABB n.v. Power Quality Products, October 2014

TOSHIBA International Corp

Drives 101 Lesson 5. Power Input Terminology for a VFD

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

Generator Advanced Concepts

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012

Power Factor. Power Factor Correction.

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

Technical Paper. Harmonic Distortion in Data Centers

+ 24V 3.3K - 1.5M. figure 01

Harmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Do You Have a Harmonic Problem?

Fundamentals of Power Quality

CHAPTER 4 HARMONICS AND POWER FACTOR

Alternative Designs to Support Electronic Loads in Extensive UPS Distribution Systems

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

Do Capacitor Switching Transients Still Cause Problems?

Harmonic Analysis and Its Mitigation Using Different Passive Filters

TECHNICAL BULLETIN 004a Ferroresonance

PRODUCT FEATURES TYPICAL APPLICATIONS

Harmonic Filters and Reactors

A. Harmonics. non-linear loads. are. required)

Grounding for Power Quality

Fluke 40/41 Power Harmonics Analysers

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

Clamp Meter ABCs. Application Note. The transformer action

Alternator winding pitch and power system design

SHARDA Make Harmonics Filter

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

Fluke Clamp Meters Solutions for every need

Transcription:

Presents Harmonics

What is a Harmonic? A harmonic is the term used for current flow on your facilities power system at frequencies other than 60Hertz.

Harmonic Problems Include:

Harmonic Problems Over heating and failure of: Transformers Computers Motors Lights & Ballast's Switchgear etc... Motor Control Centers

Harmonic Problems Electrical and Electronic damage. Control System errors due to Electrical noise caused by harmonics. Blown Fuses for no APPARENT reason. Nuisance tripping of Circuit Breakers.

What exactly is a Harmonic?

Linear use of power 680V Volts 0V 680V 200A 0A Amps 200A

Equipment: Power in a Linear fashion

Non-Linear use of power 680V Volts 0V 680V 200A 0A Amps 200A

Equipment: Power in a NON-linear fashion Computers Modern Lights and Ballast's Copiers & Other Office Equipment Variable Frequency Drives All equipment that uses an AC to DC power supply

Typical Non-Linear frequencies that cause problems: 3 x 60 = 180HZ 5 x 60 = 300HZ 7 x 60 = 420HZ 11 x 60 = 660HZ 13 x 60 = 780HZ

Why does Non-Linear current flow cause problems in my facility?

Magnetic field produced around wire 200A 0A 200A Section of Wire

Combination of Linear & Non-Linear power 200A 0A 200A Section of Wire

Harmonic currents flow on your power system neutral Why?

Normal 3 Phase Balanced System (Linear Load) A Phase +60A B Phase C Phase Regular Lighting Motors 0A -60A

Normal 3 Phase Balanced System (Linear Load) A Phase B Phase Freeze Time C Phase +60A 0A -60A

Normal 3 Phase Balanced System (Linear Load) -60A +20A +40A =0Amps

Balanced Linear loads A Phase B Phase C Phase

01-Harmonics Video

Unbalanced Linear Loads

02-Harmonics Video

Harmonics occur when equipment uses current in a Non-Linear fashion. Equipment that commonly does this: Personal Computers Various Office Equipment Copiers, Printers etc Electronic and Magnetic Ballast's Modern Welders Variable Frequency Drives Any device that uses Switched-Mode Power Supplies

Harmonic 3 Phase Un-Balanced System B Phase Copier or other Office equipment Freeze Time +60A +70A 0A +20A -60A +20A +70A

Harmonic 3 Phase Un-Balanced System

These Harmonic current flows on the neutral may be 1.73 times larger than the supply current. IEEE 519 is the standard used to determine maximum Harmonic distortion levels. They are different between voltage and current.

Non linear loads A Phase B Phase C Phase

Non Linear Loads B Phase A Phase C Phase

03-Harmonics Video

A Phase 14.1 Amps B Phase 14.2 Amps C Phase 13.9 Amps Neutral 22.5 Amps

A Phase 100Amp B Phase 100Amp C Phase 100Amp Neutral? Amp 50 Amp 173 Amps

5 th, 7 th, 13 th Harmonics Harmonic Profile 100 80 60 40 20 0 5th 7th 13th -20-40 -60-80 High Harmonic Current -100

IEEE 519 - Current Maximum Harmonic Current Distortion ISC / IL TDD 1-20 5% 20-50 8% 50-100 12% 100-1000 15% 1000+ 20% ISC=Maximum short circuit current IL= Maximum demand load TDD= Total Demand Distortion

Current Harmonics Example: Typical Office Building 1200A 208Y/120 service 30K AIC The Maximum IEEE Harmonic distortion is: 30,000 AIC / 960 = 31 31 on the IEEE chart is 8%

IEEE 519-Voltage Maximum Harmonic Voltage Distortion Voltage TVD 69kV and below 5% TVD=Total Voltage Distortion

Harmonics: Low Harmonic Waveform

Highly Distorted Waveform

Since current flow induces voltage, you may see very large voltage spikes with large Harmonic systems. 180HZ 3rd Harmonic

Large ground currents can induce voltage into systems that are damaged by grounds that are not at zero potential.

Harmonic currents travel throughout your power system. Since they are not at 60HZ they can damage capacitors and transformers that are designed to operate only at 60HZ Harmonics can cause damage and unexpected shutdown of Computers, Variable Frequency Drives, UPS Systems and other electronic equipment.

Harmonic Problems- Transformers When harmonic currents flow through a transformer, the transformer will heat up more than one with 60Hz currents flowing through it. This is caused by eddy current loses in the core and coil windings of the transformer. What are eddy currents?

Harmonic Problems - Transformers When these magnetic lines of force cut through the wire they induce current flow. This current flow (internal to the wire) is called an eddy current. Eddy currents The higher frequency current (caused by harmonics) running through the transformer core and coils cause eddy currents to flow more readily in each of the core and coil winding conductors. These eddy currents cause excessive heat to build up in the transformer leading to damage and limiting the life of the transformer.

Harmonic Problems - Transformers This figure shows that the de-rating can reach 50% when the transformer supplies more than 70% of its load to single phase power supplies of electronic load equipment. Figure 8-5 shows an example of a de-rating curve (appearing in Zavadil et al. [B8]2 ) obtained by more accurate computations based on IEEE Std C57.110. Source: Based on Zavadil [B8]. Source-IEEE Std. 1100 Copyright IEEE. All rights reserved.

Harmonic Problems Variable Frequency Drives, Computers, UPS Systems DC bus Voltage = 150 Volts DC bus Voltage with Clean Voltage

Harmonic Problems Variable Frequency Drives, Computers, UPS Systems DC bus Voltage = 135 Volts (10%) low DC bus Voltage with Distorted Voltage 10% lower

Detecting a Harmonic System Problem Use a Harmonic analyzer test meter ON 15% OFF VOLT AMP WAVE HARM THD% MODE ALL HARMONIC ANALYZER Use a Power Monitoring System D PowerLogic Use a True RMS Volt-Ohm-Ammeter COMPARED 100 AMP TO: VOLT AMP An Averaging Volt-Ohm-Ammeter 90 AMP VOLT AMP WATT OHM WATT OHM DIGITAL MULTIMETER MULTIMETER

True RMS amp meter Averaging amp meter

Solving a Harmonic System Problem Size Equipment to withstand the large Harmonic Neutral currents by using: 1. Oversize (K-factor) Transformers. 2. Oversize Neutrals in Switchboards Panelboards,Busway, and all Neutral wiring. Install Harmonic Filter Banks that trap and eliminate Harmonics. Use Harmonic cancellation transformers.

Install Harmonic Filter Banks that trap & eliminate Harmonics. The most popular filter is a series tuned L-C shunt filter. A phase B phase C phase Tuned L-C (Inductor-Capacitor) Filter (Trap) Tuned to the Harmonic level that is causing problems in the system.

Passive Harmonic Filter

Install Active Harmonic filters that repair the distorted voltage.

Example of Harmonic Correction

Use Harmonic Mitigating transformers.

Harmonic Mitigating Transformers Function N A B C N A B C Mitigation Standard and K rated Transformers Harmonic Mitigating Transformers

Non Linear load with Harmonic Mitigating transformer B Phase A Phase C Phase

04-Harmonics Video

Harmonic Mitigating Transformers Conventional Transformer Harmonic Mitigating Transformer

Harmonic Mitigating Transformers Harmonic Mitigating Transformer

5 th, 7 th, 13 th Harmonics Harmonic Profile 100 80 60 40 20 0-20 -40-60 -80 5th 7th 13th High Harmonic Current -100

5 th, 7 th, 13 th Harmonics 100 Harmonic Profile 80 60 40 20 0-20 -40-60 -80-100 5th 7th 13th High Harmonic Current GONE

Harmonic Mitigating Transformers Installation involving Harmonic Mitigating Transformers in a typical four-story office building 4th Floor Panel with regular transformer Total Harmonic Distortion 7.7% 3rd Floor Panel with regular transformer Total Harmonic Distortion 5.9% 2nd Floor Panel with regular transformer Total Harmonic Distortion 5.4% 1 st Floor Panel with regular transformer Total Harmonic Distortion 5.1% 480 Volt Main Switchgear Total Harmonic Distortion 2.8% Harmonic levels on each floor are above the IEEE 519 maximum allowed level of 5%. The 7.7% level on the forth floor resulted in a distorted voltage waveform.

Harmonic Mitigating Transformers After installation of only one Harmonic Mitigating Transformer on the 4th floor the following readings were logged: New Harmonic Mitigating Transformer 4th Floor Panel with new transformer Total Harmonic Distortion 3.2% 3rd Floor Panel with regular transformer Total Harmonic Distortion 4.8% 2nd Floor Panel with regular transformer Total Harmonic Distortion 4.3% 1 st Floor Panel with regular transformer Total Harmonic Distortion 4.0% 480 Volt Main Switchgear Total Harmonic Distortion 1.7% Total Harmonic Distortion on the 4th floor dropped from 7.7% to an acceptable IEEE519 level of 3.2%. This also had an effect on the rest of the building power lowering the Harmonic levels as shown.

Harmonic Mitigating Transformers Installation of Transformers that treat harmonics have many benefits, however the two largest benefits are: Elimination of harmonics that cause damage to or errors with your sensitive equipment. Energy savings from eliminating harmonics in your facility.

DOE 2016 Transformers The U.S. Department of Energy (DOE) adopted a new set of minimum efficiency standards for Dry-Type Transformers that are sold into the United States. This had a significant impact for distributors and end users. The new rule took effect on January 1st, 2016. The rule replaced the old minimum efficiency levels, which were known as the NEMA TP-1 or DOE 2010 efficiency levels. The new efficiency level is generally referred to as the DOE 2016 efficiency level.

Power Quality & Efficiency Matrix Delivers best voltage quality to connected equipment Improves voltage quality to connected equipment UL Listed to survive when feeding electronic equipment Not designed to feed load with load >10% current distortion (ANY mix of electronic equipment) K-Rated Old Standard Old TP-1 DOE 2016 Harmonic Canceling Energy Efficient EE/HMT (DOE2016) Better Power Quality Survival UL Issue Power Quality Efficiency

Energy savings with NON-LINEAR loads & Power Quality Cost Energy Savings Power Quality TP1 Manufacturing Stopped Jan, 1 2016 1 Unit 1 Unit None K-rated 2 Units 1.1 Units None DOE 2016 1.25 Units 0.99 Units None Harmonic Mitigating Energy Efficient DOE 2016 1.5-2 Units 0.75 Units Yes

Payback Calculator

Harmonics END Please fill out the evaluation form to receive attendance credit. An Email Address MUST be Provided to receive your attendance certificate. Thank you for attending PQU s Harmonics Seminar