AGN 022 Conditions for Parallel Operation

Similar documents
AGN 005 Fault Currents and Short Circuit Decrement Curves

AGN 034 Alternator Reactance

Application Guidance Notes: Technical Information from Cummins Generator Technologies

WDG 12 - Technical Data Sheet

AGN 124 AVR Power Supplies

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet

AGN 124 AVR Power Supplies

WDG 07 - Technical Data Sheet

WDG 71 - Technical Data Sheet

WDG 61 - Technical Data Sheet

WDG 51 - Technical Data Sheet

WDG 83 - Technical Data Sheet

AGN 165 Parallel Operation with Mains Grid Systems

PI734F - Winding 07. Technical Data Sheet APPROVED DOCUMENT

PI734F - Winding 28. Technical Data Sheet APPROVED DOCUMENT

AGN 026 Harmonic Voltage Distortion

WDG 13 - Technical Data Sheet

PI734E - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI734C - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI734B - Winding 312. Technical Data Sheet APPROVED DOCUMENT

AGN 008 Vibration DESCRIPTION. Cummins Generator Technologies manufacture ac generators (alternators) to ensure compliance with BS 5000, Part 3.

Sizing Generators for Leading Power Factor

PM734D - Winding 312. Technical Data Sheet APPROVED DOCUMENT. Generator Solutions AS

PM734F - Winding 312. Technical Data Sheet APPROVED DOCUMENT

Generator Advanced Concepts

AGN Japanese National Electrical Distribution System

TABLE OF CONTENT

Connection of Embedded Generating Plant up to 5MW

PI734C - Technical Data Sheet

PI734A - Technical Data Sheet

SPECIFICATION, CONTROLS AND ACCESSORIES

PM734B - Technical Data Sheet. Generator Solutions AS

HARMONICS CAUSES AND EFFECTS

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Application Guidance Notes: Technical Information from Cummins Generator Technologies

AGN Winding and Bearing Temperature Sensors

Generator Operation with Speed and Voltage Regulation

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

AS440 AUTOMATIC VOLTAGE REGULATOR (AVR)

A Practical Guide to Free Energy Devices

SYNCHRONISING AND VOLTAGE SELECTION

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

QUESTIONNAIRE for Wind Farm Power Stations only

S0L1-J1 - Technical Data Sheet

PI144H - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

Power Factor. Power Factor Correction.

Thyristorised Automatic Power Factor

TOSHIBA International Corp

Power Quality. Case Study. Conrad Bottu Laborelec January 2008

Rotek AS440 compatible VOLTAGE REGULATOR (AVR)

CONTENTS. 1. Introduction Generating Stations 9 40

Objective: Study of self-excitation characteristics of an induction machine.

Protection of Electrical Networks. Christophe Prévé

S4L1D-G41 Wdg Technical Data Sheet

S4L1S-D4 Wdg.17 - Technical Data Sheet

VOLTAGE REGULATOR R 449. Installation and maintenance. This manual must be sent to the end user R 449 X2 Z1 X1 Z2 E+ E- (12V - 10A)

GENERATOR INTERCONNECTION APPLICATION Category 3 For All Projects with Aggregate Generator Output of More Than 150 kw but Less Than or Equal to 550 kw

CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY

Alternator winding pitch and power system design

GX 340 SERIES (AUTOMATIC VOLTAGE REGULATOR)

AGN Rubber Tyred Gantry (RTG) Cranes

GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 150 KW BUT LESS THAN OR EQUAL TO 550 KW

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

SYNCHRONOUS MACHINES

FUJI Inverter. Standard Specifications

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application

AGN 015 Testing Winding Insulation Systems

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

EE171. H.H. Sheikh Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E

SPECIFICATION, CONTROLS AND ACCESSORIES

Table of Contents. Introduction... 1

Time constants ( s ) Resistance. Other data - Class H /6600 V kva. Efficiencies ( % )(3 phase - Classe H V kva)

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

UNIT-III STATOR SIDE CONTROLLED INDUCTION MOTOR DRIVE

Connection Impact Assessment Application

THE STUDY OF THE SYNCHRONOUS MOTOR

Upgrading from Stepper to Servo

SPECIFICATION, CONTROLS AND ACCESSORIES

DISCUSSION OF FUNDAMENTALS

Upgrading Your Electrical Distribution System To Resistance Grounding

Contents. About the Authors. Abbreviations and Symbols

Pulse Width Modulated Motor Drive Fault Detection Using Electrical Signature Analysis

WHITE PAPER. Medium Voltage On-Site Generation Overview. BY MIKE KIRCHNER Technical Support Manager at Generac Power Systems

Type of loads Active load torque: - Passive load torque :-

PART 2 - ACTUATORS. 6.0 Stepper Motors. 6.1 Principle of Operation

440 (12) 416 (12) 416 (12) 440 (12)

Paralleling Dissimilar Generators: Part 2 Compatible Alternators

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

PART 1 OWNER/APPLICANT INFORMATION

TAL 044 Low Voltage Alternator - 4 pole

Impact Assessment Generator Form

Spec Information. Reactances Per Unit Ohms

IEEE sion/1547revision_index.html

VARIABLE FREQUENCY DRIVE

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

Transcription:

Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 022 Conditions for Parallel Operation SYNCHRONISATION The parallel operation of Generating Sets is common, to share the load requirements between generators or between Generating Sets and the utility supply (Mains Grid System). Generating Sets must be synchronised with each other for parallel operation and specific requirements must be met to ensure a smooth synchronisation process. It is imperative that, at the instant of closing the synchronising Circuit Breaker, the transient current surge experienced by the in-going Generating Set does not exceed 50% of that generators rated current. Achieving this critical requirement will limit the forced levels of synchronising alignment torques experienced throughout the Generating Set equipment component parts. For example; the mechanical drive line, the stator winding assembly and the rotating diode assembly s component parts. Poor synchronisation will impact the in-service life of the equipment package. Synchronisation with transient current surge <50% of rated current is possible if the guidance and synchronisation window are followed. For a parallel running network consisting of less than five units, but accepting that each unit may have a different kva rating, then the following well established practice should be conducted. The Generating Sets that are to be synchronised must be appropriately set during commissioning and this should involve the No-Load voltage levels of the generators to be set within 1V of each other by use of one calibrated true rms meter. Each Generating Set should be operated at rated load and the level of quadrature droop set to the same level, typically 3% for 0.8pf. The same care and close tolerance levels should be AGN 022 ISSUE B/1/6

adopted for setting the engine No-Load speed and also the same level of On-Load speed droop. Remember; the engine power provides the kwe, the excitation level provides the kvar, they combine to ensure the paralleled Generating Sets will equally share the supplied kva and so operate at the same power factor. The Required Synchronising Window It is essential that the phase sequence of the incoming Generating Set matches that of the Point of Common Coupling (PCC) bus bar and also that all of the following conditions are met before the Circuit Breaker of the incoming Generating Set is closed on to that bus bar. The frequency must match within 0.1 Hz The rate of change of frequency must be within 0.1 Hz / second This rate of change of frequency is very significant, as an unstable and erratic engine speed (e.g. a cold gas engine), produces a circumferential rotational speed, which accelerates and decelerates in a fast oscillatory manner. Such an unstable running condition may satisfy a Rate of change of frequency monitor considering an average condition and so, may allow synchronisation to take place under a momentary situation where, in fact, the Generating Set s rotor is grossly miss-positioned. This will result in a compensating, very high alignment torque, which can damage mechanical components within the generator or the engine to generator drive/ coupling system. The voltages must match within 0.5% For the Circuit Breaker closing angle, refer to the following guidance: If the Generating Set is to be synchronised regularly daily then setting to close limits will result in lowest possible stress and therefore, resulting in Generating Set longevity. The Circuit Breaker closing angle must be < 5deg. If the Generating Set is infrequently synchronised put in synchronism and remains operational for many weeks before being again synchronised then the Circuit Breaker closing angle must be <10deg. The actual point of synchronising Circuit Breaker closure should result in a minimal current surge from the forced alignment of the two connected systems. This minimal current is advised as being no more than 50% of the Generating Set s rated output current. To achieve minimal current the synchronising equipment s control system must incorporate a rate of change of frequency monitoring capability. This enables a predictive function with regard to ensuring the moment of closure occurs within the closing angle window and the angle is dynamically decreasing towards the optimum zero degrees - rather than an increasing angle. AGN 022 ISSUE B/2/6

The use of old technology synchronisers, which incorporate phase locking technology and so has no predictive capability should be avoided. In fact, where unstable gas engines are used, such low technology synchronisers should never be used. During commissioning, the time delay between synchroniser issuing the command to close the synchronising Circuit Breaker and the time for this instruction to be followed must be identified. Typically it can vary from 40 to 100ms and the predictive part of the synchroniser package must be set to take this closing time into account. A variety of proprietary equipment packages are available for synchronising a Generating Set by automatically considering the above parameters and issuing control signal commands to control systems of both the engine and alternator to achieve ideal alignment and so, perfect synchronising with minimal imposed stress to any of the Generating Set components. Mis-Synchronisation of Generating Sets Failure to create and maintain the above four listed conditions at moment of closing the synchronising Circuit Breaker will generate excessive mechanical and electrical stresses, which may not be immediately apparent, but nevertheless will become additive and eventually result in equipment damage. At the instant paralleling occurs; if any one or more of the above conditions has not been matched there will be an immediate transfer of power / energy between the two systems that have just been paralleled, or forced together, in an attempt to create total system equilibrium. When achieving this system equilibrium, a correction to the phase angle alignment between the two systems is required and therefore an immediate change to the relative physical position of the alternator s rotor / stator alignment is required. As a rotor is instantly forced into the correct relative alignment (like electrical gear teeth being forced into mesh), this means that the engine crankshaft via the coupling is also rapidly forced into a new rotational correct alignment position. Such rapid acceleration / deceleration forces stress on the whole mechanical drive train, with obvious resulting torque reactions present within the alternator stator windings, core pack, frame and feet, to the Generating Set s bedplate, flywheel housing and engine block and feet. Under the forces that mis-synchronisation imposes onto a system the alternator stator and rotor will be subjected to transient voltage and current levels several times the normal rated designed conditions. As a consequence of the transient stator / rotor mutual inductance conditions, there will be the generation of high voltage spikes in the rotor winding, which could cause a breakdown to the P-N junction of one or all of the rotating diodes. To prevent the diodes from being damaged, the rotating diode assembly incorporates a Surge Suppressor [VDR], which often becomes sacrificial in its endeavours to limit the level of the transient voltage and so safeguard the diodes. Any occurrence of mis-synchronisation always subjects Generating Set components to high stress levels and must therefore be avoided. For reasons of safety and damage assessment, any occurrence of miss-paralleling should be investigated to ensure it will not re-occur and AGN 022 ISSUE B/3/6

then any signs of components having suffered from mechanical or electrical stress damage must be observed. Inspection of mechanical components becomes a visual inspection for component stress or assembly relative movement, whilst the electrical components should be visually inspected, insulation values measured, and rotating diode assembly checked. Then run the Generating Set under progressively increased load up to rated, whilst monitoring the alternator s excitation voltage, comparing these newly measured values with those recorded in the plant maintenance manual, established for normal site duties during commissioning. Alternatively, refer to the alternator manufacturer s design data, published in the Technical Data Sheet. DEAD FIELD PARALLELING FOR GENERATING SETS OPERATING IN PARALLEL Standard synchronisation technique usually follows the procedure where the first Generating Set is energised to the Point of Common Coupling (PCC) bus bar, followed by the synchronisation of the subsequent Generating Sets to the PCC. There is also another established practice, however; to parallel Generating Sets by using a simultaneous build-up of their excitation and so achieve dead field paralleling of several Generating Sets onto a common dead bus-bar. This practice is common place for appropriately designed systems used as mains failure units at hospitals on mainland Europe, where the expectation is that a stand-by system must be in readiness to accept load in the shortest possible time and often on more than 8 seconds is specified. For AvK and STAMFORD alternators with digital AVRs, excitation build-up can be achieved in programming the AVR setup. For STAMFORD alternators with analogue AVRs, the control system for such equipment incorporates an isolated switching contact (rated at 10A; 240V) for each alternator AVR s K1 - K2 connections. The K1 - K2 inter-connection is kept open circuit while the Generating Sets are all simultaneously started and run up to rated speed. Once at speed, an output contactor for each Generating Set is closed, such to connect each running Generating Set onto the common dead bus-bar. When all the output contactors have closed, indicating all Generating Sets have started and are running at required rated speed, the K1 - K2 contacts for all the AVRs are simultaneously closed. This causes all the alternators to simultaneously excite and therefore, a (generally) simultaneous build up to their pre-set working No-Load voltage, thereby forcing the necessary AGN 022 ISSUE B/4/6

gentle adjustment in phase angle relationship and so self-synchronisation and so parallel running of all the Generating Sets. Once the bus-bar voltage is detected, the output Circuit Breaker can be closed, thereby connecting all loads to the Generating Sets. Note; The above synchronising procedure has been tried as a method of paralleling Generating Sets with live bus-bar (Mains Grid System). The tests were unsuccessful, because they resulted in failure of components associated with rotating diode and protection suppression devices. CIRCULATING CURRENTS IN PARALLEL OPERATION The pre-requisite for parallel operation is to have the same AVR set voltage level on all alternators. Generating Sets working in parallel with different AVR set voltage levels will cause circulating currents to flow. Parallel operation of alternators with dissimilar winding pitches can result in circulating currents. All STAMFORD alternators and some AvK alternators are wound with a 2/3 rd winding pitch with minimal triplen harmonics. There is no basic reason why any system consisting of these types of alternators cannot have their star points interconnected and in turn, the Neutral link continued to the distribution network s Neutral (star point) connection at the Point of Common Coupling (PCC). Refer AGN 045 Alternators for Parallel Operation, for information on dissimilar winding pitches. If during commissioning, it is found that apparently unexplained neutral currents are flowing, then this may well be a product of the characteristics of the connected load that is being supported on this local network. Alternatively, it may be a function of unbalanced voltages across the Mains Grid System - supply network to which the Generating Set is paralleled. In the real world, some circulating neutral current is inevitably present. So, if some neutral current is present is it harmful? The simple answer is no. The answer is no, providing it does not cause the alternator s designed rated output current to be exceeded through any part of its windings. Obviously, it can be reasoned that the unwanted neutral, or circulating current, is adding to the overall operating temperature of the alternator, which in turn is having a thermal degradation effect on the insulation systems life, but the thermal degradation can usually be reasoned to be minimal if the rated line current is not being exceeded. It should be cautioned that neutral current can be caused by unbalanced loading of the three phases of the alternator, which will cause additional electrical and thermal stresses on the damper windings on the rotor. The situation regarding Generating Set s being REFERENCED to EARTH and this by Neutralising the Generating Set s star point to other Generating Set star points, is a decision that will need to be based on the specific expectations for individual installations and will be specific to: the on-site Electrical Protection Equipment and the characteristics of the local site load. Here the single phase content must be understood and of course, the intended role of the generating plant. When operating in parallel with the Mains Grid System supply network AGN 022 ISSUE B/5/6

the local host REC will advise the required situation based on their protection system employed for that section of their network. Generating Sets operating in Island Mode When the Generating Sets are operating as an islanded unit, then most definitely the system will have to be referenced and the method used, dependent upon the protection system employed for this duty. The following additional consideration must be taken in to account for small islanded systems of up to 5 paralleled Generating Sets: Expect some circulating currents (kvar) to occur if two parallel Generating Sets are running under a No-Load condition, as synchronous alignment effort is dynamically present until a level of connected load is applied. Circulating current (kw) will occur if the engine speed governing characteristics are not very similar. Once the Generating sets are connected to a common load, however; this will reduce. Application Guidance Notes are for information purposes only. Cummins Generator Technologies reserves the right to change the contents of Application Guidance Notes without notice and shall not be held responsible for any subsequent claims in relation to the content. AGN 022 ISSUE B/6/6