Modeling of Statcom. P.M. Sarma and Dr. S.V. Jaya Ram Kumar. Department of Electrical & Electronics Engineering GRIET, Hyderabad, India

Similar documents
D-STATCOM FOR VOLTAGE SAG, VOLTAGE SWELL MITIGATION USING MATLAB SIMULINK

Investigation of D-Statcom Operation in Electric Distribution System

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Voltage Improvement Using SHUNT FACTs Devices: STATCOM

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

DIGITAL SIMULATION OF MULTILEVEL INVERTER BASED STATCOM

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

Power Quality enhancement of a distribution line with DSTATCOM

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

2020 P a g e. Figure.2: Line diagram of series active power filter.

Enhancement of Power Quality with Multifunctional D-STATCOM Operated under Stiff Source for Induction Motor Applications

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition

Application of Distribution Static Synchronous Compensator in Electrical Distribution System

Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control

UNIFIED POWER QUALITY CONDITIONER IN DISTRIBUTION SYSTEM FOR ENHANCING POWER QUALITY

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR

Power-Quality Improvement with a Voltage-Controlled DSTATCOM

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality

Power Control Scheme of D-Statcom

Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

Power flow improvement using Static Synchronous Series Compensator (SSSC)

Improvement of Power Quality Using a Hybrid Interline UPQC

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

Voltage Flicker Mitigation in Electric Arc Furnace using D-STATCOM

DESIGN A D STATCOM FOR VOLTAGE HARMONIC SUPPRESSION IN DISTRIBUTION SYSTEM

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

SIMULATION OF D-STATCOM IN POWER SYSTEM

Modified three phase Unified Power Quality Conditioner with capacitor midpoint topology

Power Quality Improvement By Using DSTATCOM Controller

Power Quality improvement of a three phase four wire system using UPQC

Key terms: Voltage, Phase Angle, FACTS, Multilevel Converter, Power Quality, STATCOM.

Chapter 2 Shunt Active Power Filter

Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller

Devineni Gireesh Kumar Assistant Professor, M Tech, Department of Electrical and Electronics

ISSN Vol.04,Issue.08, July-2016, Pages:

A New Control Scheme for Power Quality Improvement with STATCOM

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

PUBLICATIONS OF PROBLEMS & APPLICATION IN ENGINEERING RESEARCH - PAPER CSEA2012 ISSN: ; e-issn:

ISSN Volume.06, Issue.01, January-June, 2018, Pages:

Harmonic Reduction of Arc Furnaces Using D-Statcom

Volume I Issue VI 2012 September-2012 ISSN

Mitigation of Voltage Sag, Swell and Load Hamonics by the Combined Opertation of Series APF and Solar System

Analysis & Function of Unified Power Quality Conditioner for Power Quality Improvement of Distributed Network

Power Quality Compensation by using UPFC

Performance of DVR & Distribution STATCOM in Power Systems

UPQC (Unified Power Quality Conditioner)

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

Performance of DVR under various Fault conditions in Electrical Distribution System

Modeling and Simulation of STATCOM

Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation

STATCOM WITH POD CONTROLLER FOR REACTIVE POWER COMPENSATION Vijai Jairaj 1, Vishnu.J 2 and Sreenath.N.R 3

Literature Review for Shunt Active Power Filters

SHUNT ACTIVE POWER FILTER

Multi-Pulse Voltage Source Converter Statcom For Voltage Flicker Mitigation

CHAPTER 5 CONTROL SYSTEM DESIGN FOR UPFC

Level Shifted Pulse Width Modulation in Three Phase Multilevel Inverter for Power Quality Improvement

Improvement in Power Quality of Distribution System Using STATCOM

Power Quality Improvement using Active shunt Power filter using PI Controller

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

Application of Dynamic Voltage Restorer for Voltage Balancing with ASD Load Using DQO Transformation

Mitigating Voltage Sag Using Dynamic Voltage Restorer

Fig. 1 Schematic Diagram Showing Connections to the Active Filter With Non-Linear Load

A Review on Improvement of Power Quality using D-STATCOM

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.

Compare Stability Management in Power System Using 48- Pulse Inverter, D-STATCOM and Space Vector Modulation Based STATCOM

IJCSIET--International Journal of Computer Science information and Engg., Technologies ISSN

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

Power Quality and the Need for Compensation

Voltage Flicker Compensation using STATCOM to Improve Power Quality

Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System

CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM

Vol. 1, Issue VI, July 2013 ISSN

Grid Interconnection of Wind Energy System at Distribution Level Using Intelligence Controller

A Power Control Scheme for UPQC for Power Quality Improvement

ISSN Vol.03,Issue.42 November-2014, Pages:

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

SPWM Switching Strategy for Compensation of Unbalanced and Non Linear Load Effects in Three Phase Four Wire System Using D-Statcom

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

Power Quality Improvement using Hysteresis Voltage Control of DVR

COMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N.

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Mitigation of Flicker Sources & Power Quality Improvement by Using Cascaded Multi-Level Converter Based DSTATCOM

Unit Vector Theory based Unified Power Quality Conditioner for Power Quality Improvement

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

Development of a Robust Constant Current Source For a Current Source Inverter

Modelling of Dynamic Voltage Restorer for Mitigation of Voltage Sag and Swell Using Phase Locked Loop

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Control of Shunt Active Power Filter for Improvement of Power Quality

Voltage Sags in Distribution Systems with Induction Motor Loads Fed by Power Converters and Voltage Mitigation using DVR and D-STATCOM

Transcription:

International Journal of Electrical Engineering. ISSN 974-2158 Volume 6, Number 1 (213), pp. 69-76 International Research Publication House http://www.irphouse.com Modeling of Statcom P.M. Sarma and Dr. S.V. Jaya Ram Kumar Department of Electrical & Electronics Engineering GRIET, Hyderabad, India Department of Electrical & Electronics Engineering JNTUH, Hyderabad, India Abstract Statcom is a power electronic device connected in shunt across the load to solve power quality problems, reduce fluctuations in bus voltage, reduce unbalance of three phase voltages and reduce flicker. Modeling of Statcom specifically to simulate for solving power quality problems presents various problems due to various types of control strategies. Modeling of statcom for hysteresis control strategy is presented. Index Terms Point of Common Connection, hysteresis control, modeling, Introduction Statcom is based on Voltage Source Inverter that can be connected to the grid. It can be controlled in such a way that it can supply a particular desired value of reactive power or it can supply an amount of reactive power that is needed to keep the bus voltage at the point of common connection (PCC) constant. The first application of supplying reactive power of required amount can be called constant reactive power mode. The later method is called constant voltage method. Both have their own area of applications The first method gives rise to improved power factor to the desired extent and also harmonics can be suppressed to a large extent. The second method guards against voltage sags or swells and also mitigates the flicker. These effects depend on the control strategy and also on the way feedback is taken. Statcom has a voltage source inverter which takes DC voltage from a capacitor which is maintained at a relatively constant voltage. The three phase inverted voltage is connected to the grid by means of a reactor in each phase. If the voltage output of the inverter is exactly equal to that of the bus

7 P.M. Sarma and Dr. S.V. Jaya Ram Kumar voltage, the voltage across the reactance is equal to zero. However when the voltage output of the inverter is greater than that of the bus the difference in the two voltages is dropped across the reactance. The current flow in the reactor lags by 9 with respect to the drop across the reactor this current flow from the inverter in to the system and causes reactive power to be injected in to the system. On the contrary if the inverted output voltage is less than that of the bus at PCC it draws reactive power from the system. The coupling between bus voltage and reactive power injection is well known to power system engineers. So the reactive power injection causes bus voltage to increase and reactive power drawal causes bus voltage to drop. This effect can be utilized by taking actual bus voltage as feedback and subtracting it from the voltage reference value and using the error as a guide to inject or draw reactive power which goes a long way in improving the bus voltage. The control strategy applied here determines whether the statcom will be effective in controlling voltage sags and swells or in mitigating flicker in the presence of highly non linear fluctuating loads like an arc furnace are present. Control strategies adapted in control of statcom The control strategies adopted are Phase angle control, Constant DC link voltage, Direct current control based on PQ theory. In the first method reactive power has to be measured based on the three phase voltages and phase currents. Actual value of reactive power so obtained is subtracted from the reactive power reference value. The error is fed to a PI controller giving rise to reference phase angle. Now the firing pulses are shifted so as to cause the inverted voltage to be shifted slightly in phase with respect to the system voltage at PCC. This causes active power to flow in to the DC link capacitor and charge it to a higher voltage and produce higher inverter voltage and hence the injection of reactive power to be increased. Now the actual reactive power equals the reference and no error will be produced causing no further shift in phase angle. Thus phase angle control is used to supply a desired value of reactive power to the system. In the constant DC link voltage method the capacitor voltage is kept constant by means of a control loop. Also reactive power is measured and compared with reference and the error is fed to a PI controller. V d is calculated from the three phase voltages which in turn is subtracted from V dref and fed to a PI controller. A fixed amplitude sine wave is produced which is modulated by the control signal obtained from reactive power error this modulated signal is used to control the sinusoidal pulse width modulation generator. This way the output voltage of the inverter is made to inject reactive power of required magnitude. In the third method the three phase voltages and the three phase currents are transformed to Alpha, Beta, Zero coordinates and the current references are calculated in the Alpha, Beta coordinates. These three reference currents are compared with the actual currents and the hysteresis current control method is

Modeling of Statcom 71 used to inject suitable values of current in to the system. This is known as direct current control method using PQ theory. MATHEMATICAL MODELING OF STATCOM The Mathematical modeling of statcom is based on the following equations, where e represents the voltage of the statcom and v represents the bus voltage at the point of common connection and 'i' represents the current drawn by the statcom. The difference in bus voltage and statcom voltage is dropped across the coupling inductor whose inductance is L and resistance is R. The reactive power injection is done through the linkage reactance which may be the actual reactance of a reactor connected between the PCC and the statcom or the leakage reactance of the coupling transformer used to step down the grid voltage to a suitable voltage. When the statcom voltage is less than the system voltage the statcom draws reactive power or else when the statcom voltage is higher it injects reactive power. The current through the statcom is decided by the difference in voltages which actually acts across the linkage reactance and produces a current and hence the reactive power is decided by the difference in voltage and reactance value. The above equations can be put in the standard form of Where X = and A= R L nsin( t ) ia ib ic Vdc R L nsin( t 12) ea and u= eb ec R L nsin( t 24) m sin( t ) msin( t 12) msin( t 24)

72 P.M. Sarma and Dr. S.V. Jaya Ram Kumar 1 L B= 1 L 1 L The difference in voltages is either in phase or exactly 18 out of phase with the bus voltage at PCC. But the current is at 9 lagging with respect to the voltage reference and hence the current either leads the bus voltage by 9 or lags by 9 either way the power drawn or injected in to the bus is reactive in nature. This is the basis of working of statcom. It can be further explained by the following diagrams. Fig.1. single phase equivalent circuit of statcom demonstrating drawal and injection of reactive power and corresponding vector diagrams. HYSTERESIS CURRENT CONTROL STRATEGY This method of current control is very suitable for the control of a Statcom. There are two control loops in this method. The two control loops are 1) DC link voltage control loop 2) Current control loop. The DC voltage signal is sampled at the rate of one sample per power cycle. The DC link capacitor voltage can be controlled to the required value by setting the reference value for the DC link voltage. The sampled DC link voltage is compared with the reference value and the error so obtained is fed to PI controller the output of which is multiplied with a sine wave of unit magnitude and is used as reference current. At this stage three sine waves with phase angles shifted by 12 degrees from each other are used for three phase statcom. Now the actual value of current is also obtained and from the reference current the hysteresis band is obtained by adding and subtracting 1% of the current reference value from it. The resulting reference current value with hysteresis band and the actual current are shown in the FIG.

Modeling of Statcom 73 This helps in maintaining the DC link voltage at the reference value and also to see to it that the value of current drawn by the statcom does not also exceed the rated current. The DC link voltage reference ultimately decides the statcom output voltage and hence the reactive power injected into the system. Fig.2.Simulink Diagram for implementing hysteresis current control strategy. Fig 3. Simulink Diagram for DC link voltage control and generation of current reference. STATCOM OPERATION The statcom can be operated in one of two modes: Reactive power control mode and the voltage control mode. In reactive power control mode the actual reactive power injected in to the system is measured by sampling the three phase currents and the two bus voltages at the point of common coupling. The actual value of reactive power is compared with the set value of reactive power. The set value of reactive power may in turn be derived from the required power factor value. The error in this reactive power injection is fed to a PI controller whose output can be treated as the reference value for the DC link voltage. This actually completes the closed loop and maintains the desired power factor as may be required. On the other hand if it is desired to maintain the system voltage constant at the point of common connection this voltage may be sampled at the rate of once per power cycle and can be compared with voltage reference which in turn is subtracted from the reference value and the corresponding error is obtained. This error is fed to a PI controller the output of which is treated as the reference value for the DC link voltage and thus completes the closed loop. This system acts in such a way as to inject only that much reactive power in to the system as may be required for keeping the bus voltage constant at the point of common connection constant. If the system is so

74 P.M. Sarma and Dr. S.V. Jaya Ram Kumar designed that it has sufficiently good bandwidth this mode can control the voltage flicker as may be caused by such loads as arc furnaces, heavy induction motor loads etc and also voltage sags and swells which are menacing power quality problems. A block diagram of the statcom implementing the hysteresis current control strategy is shown below Fig.4.Single phase implementation of the statcom using hysteresis current control strategy V Results The wave forms showing current reference along with a band showing the derived upper and lower limits are depicted in fig. 5.The actual current drawn by the statcom can be regulated precisely to fall within this band and it can be made as close to the required value as desired. Fig.5. Sinusoidal current wave form showing the allowable upper and lower bands The gate pulses generated are not of very high frequency as in the case of carrier based pulse width modulated method of generating gate pulses but of reasonably moderate frequency. The frequency is not constant either. Because of these features the switching losses are moderate as also the generation of higher order harmonics is also minimized. The nature of firing pulses is shown in fig.6.

Modeling of Statcom 75 Fig.6. Gate pulses generated in case of hysteresis current control strategy. The dynamics of voltage across dc link capacitor is important because the response of the system to changes in bus voltage or of reactive power requirement depends on this aspect. Response of the dc link voltage to step change in load is depicted in fig. 7 as shown below. Fig. 7 showing settling of dc link capacitor voltage after a disturbance has occurred. The wave form of the current drawn by the statcom is purely sinusoidal as may be seen from fig. 8 below. The glitches seen on the waveform are but inherent in the nature of this type of current control strategy. This could be reduced by keeping the upper and lower bands closer. But it can be seen that this leads to higher switching frequencies. It is important to keep this trade off in mind while deciding the range of these limits.

76 P.M. Sarma and Dr. S.V. Jaya Ram Kumar Fig. 8. Waveform of current drawn by the statcom. VI CONCLUSIONS It is shown that a statcom when applied properly in a power system can be used to improve power factor or mitigate power quality problems essentially of the nature of aperiodic voltage fluctuations. The method is simple and straight forward and can be easily implemented either in hardware or software. VII REFERENCES [1] S.Hadjeri etal Simulation of thee level 48 pulses STATCOM vol. 49, Number 2, 28, Acta Electrotechnica. [2] Pierre Giroux, Gilbert Sibelle, Hoang Lettuy Modeling and Simulation of a distribution sttatcom IECON 1, The 27 th Annual Conference of IEEE INDUSTRIAL Electronics Society, pp 99-994,.783-718- 9/1/$1 IEEE. [3] Bhattacharya Sourabh Application of Dstatcom using MATLAB / Simulation in using MATLAB / Simulation in Power Systems. Research Journal of Recent Sciences, vol. 1, (ISC 21), 43-433, (212 [4] M.Sajedi Hir etal Analysis and Simulation of a Dststcom for voltage quality improvement.australian Journal of Basic and Applied Sciences5(1):864-87.211, ISSN 1991-8178. [5] Saeed Mohammadi Impact of a dstatcom on Voltage Stability Indian Journal of Education Inf. & management., vol. 1, No.6, (Sep. 212) ISSN 2277-5374. [6] M.S.ElMoursi, A.M.Sharaf Voltage Stabilisation using a novel FACTS STATCOM scheme -783-/5/s2 25IEEE CECE/CCGEI, Saskatoon, may25, pp 537-54. [7] N.G.Hingorani, L.Gyugyi Understanding FACTS IEEE Press. [8] G.Sundar, S.RamaReddy, Digital Simulation of multilevel inverter based statcom Journal of Theoretical and applied Information Technology, pp 19-23