Introduction to Harmonics and Power Quality

Similar documents
Fundamentals of Power Quality

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron

Power Quality Basics. Presented by. Scott Peele PE

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

Motors and drives. Module B- Introduction to input measurements

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008

UNDERSTANDING POWER QUALITY

POWER QUALITY AND SAFETY

An Introduction to Power Quality

UNIT-4 POWER QUALITY MONITORING

There s Gold in Those Waveforms Richard P. Bingham, Dranetz-BMI

Power Quality Analysers

PowerMonitor 5000 Family Advanced Metering Functionality

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --

Roadmap For Power Quality Standards Development

1C.6.1 Voltage Disturbances

Power Quality Monitoring and Power Metering Tutorial

Fatima Michael College of Engineering & Technology

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Power Quality in Metering

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

PQ Audit - The right choice to ensure power system performance. Mr Lalit Kumar Wasan Tata Power- DDL

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

T-68 Protecting Your Equipment through Power Quality Solutions

POWER QUALITY STUDY PERFORMED AT THE DIRECTION OF ANYBODY ANYWHERE USA FOR BIG POWER USER ANYWHERE 25 EAST POWER STREET ANYWHERE, USA

Power Quality Symptoms What Is Normal? Power Quality Approach. Other Power Quality Solutions

Understanding Harmonics

Guide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics

PQ Monitoring Standards

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 9

ECET Modern Power

22.0 Harmonics in Industrial Power Systems

The seven types of power problems

EFFICIENT POWER QUALITY: AN APPROACH TO ENERGY CONSERVATION

Research Article Challenges and Trends in Analyses of Electric Power Quality Measurement Data

Managing Power Quality Issues

Protection from Voltage Sags and Swells by Using FACTS Controller

McGill Power Sales & Engineering, INC.

Power Quality Overview

1C.4.1 Harmonic Distortion

Unit V. Power Quality Monitoring

Reliability and Power Quality Indices for Premium Power Contracts

DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS

Electric Power Quality-Issues, Effects And Mitigation

A Guide to Power Quality Testing

Reliable Power Meters Multipoint Power Recorder

1. Introduction to Power Quality

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

Electromagnetic Harmonic Filters Technical Guide

Design and Development of Protective Circuit against Voltage Disturbances

Coupling modes. Véronique Beauvois, Ir Copyright 2015 Véronique Beauvois, ULg

Power Analysis Summary

A critical review-power quality concerns

POWER QUALITY MONITORING - PLANT INVESTIGATIONS

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

Electric Power Quality: Voltage Sags Momentary Interruptions

Industrial Electrician Level 3

Technical Brief: Flow Direction of Harmonics and High- order Harmonics

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.

Outline. Power Quality in Electrical Systems. Alexander Kusko, Sc.D., P.E. Marc T. Thompson, Ph.D.

Effective Harmonic Mitigation with Active Filters

SIMPLE RULES FOR SOLVING POWER QUALITY MYSTERIES

Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy

Emicon Engineering Consultants L.L.C.

Amelioration of Power Quality in Isolated Power Systems

Webinar: An Effective Arc Flash Safety Program

Power Quality Study of Electrical Installation in Academic Institute Case Study

How adjustable speed drives affect power distribution

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Thyristorised Automatic Power Factor

Generator Advanced Concepts

Analysis of Harmonic Distortion in Non-linear Loads

Catastrophic Relay Misoperations and Successful Relay Operation

Bruce L. Graves /01/$ IEEE. IEEE Industry Applications Magazine PhotoDisc, Inc.

ECE 528 Understanding Power Quality

QUESTION BANK PART - A

Overvoltage and undervoltage. Dr Audih 1

Power Quality Notes 2-2 (AK)

Harmonic Filters for Single Phase Equipment

CHAPTER 1 INTRODUCTION

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

IDEAL Test and Measurement THE BASICS OF POWER QUALITY

Power Quality Improvement using Hysteresis Voltage Control of DVR

EE 2028 POWER QUALITY

Power quality as a reliability problem for electronic equipment

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

HARMONICS CAUSES AND EFFECTS

CHAPTER 3 ELECTRIC POWER QUALITY

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

Construction Electrician Apprenticeship Program E-4. Learning guide E-4

Guidebook for Power Quality Measurement

Chapter 1. Introduction. 1.1 General

Understanding Power Quality

STUDY OF UNIFIED POWER QUALITY CONDITIONER FOR POWER QUALITY IMPROVEMENT RAJIV KUMAR SINKU

The power to work. Power conditioning products. Harmonic correction unit Sag ride-through power conditioner

Power Quality Overview

Transcription:

NWEMS Introduction to Harmonics and Power Quality August 20 24, 2018 Seattle, WA Track B Anaisha Jaykumar (SEL) Class Content» Definition of power quality (PQ)» Impact of PQ problems» Sources of poor PQ» Troubleshooting» Case studies 2 1

PQ Refers to Voltage and Current Characteristics Poor PQ refers to changes in electric power supply that can cause equipment to fail, misoperate, or degrade Noisy transformers Overheating Blown fuses 3 Amplitude and Frequency Characteristics of a Waveform 1. Amplitude 2. Frequency = 1 Hz T 4 2

Wave Shape Characteristics of a Waveform 3. Waveform distortion 5 Duration of Poor PQ Is An Important Characteristic Transient (<1 cycle) Short term (0.5 cycle up to 1 minute) Long term (>1 minute) 6 3

Several Factors Affect PQ Nonlinear loads Large load changes Faults 7 Nonlinear Loads Distort Waveforms Incandescent Bulb With Dimmer Current 0.15 A peak 0.07 A rms Voltage 169 V peak 120 V rms 8 4

LED Lights Provide Energy Efficiency But Distort Waveforms Current (A) 0.60 0.40 0.20 0.00 0.20 0.40 0.60 LED light 0.11 A peak 0.04 A rms Incandescent bulb with dimmer 0.60 A peak 0.44 A rms Time 9 What Is the Cost of Poor PQ? Equipment Failure, Misoperation, and Degradation Manufacturing facilities have costs ranging from $10,000 to millions of dollars associated with a single interruption to the process. Mark McGranaghan and Bill Roettger Economic Evaluation of Power Quality 10 5

EPRI 2001 Study of Typical PQ Phenomena Line noise Outages Spikes, transients 10% 5% 5% Harmonics Frequency variations 5% 5% 46% Voltage sags Overvoltage 7% Undervoltage 7% 10% 11 Voltage swells Voltage Sag, Swell, and Interruption (VSSI) 12 6

VSSI Are Described by Depth and Duration Voltage (V) 200 100 0 85 V sag peak 60 V rms 100 ~3 cycles 13 200 Sag event waveform Analyze Sag Event Using Waveform or RMS Plots 100% 50% 50 ms 1,000 ms V A rms V B rms V C rms 0% Time stamps 14 7

Overvoltage and Undervoltage Are Long Term Phenomena PQ Phenomena Amplitude Range Duration Sag 10 90% 0.5 cycles up to 1 minute Undervoltage 80 90% >1 minute Swell 110% 0.5 cycles up to 1 minute Overvoltage 110 120% >1 minute 15 Lightning Strikes Cause Voltage Sags Lightning strikes power pole Insulators flash over and fault current flows Flashover Instantaneous voltage drop occurs Protective relays operate Circuit breakers open 16 8

Power System Faults Can Cause Voltage Sags Voltage Profile of a Three Phase Fault 17 Effect of voltage disturbance is more at the fault point of fault and less away from it Motor Operation Can Cause Voltage Sags Motor Mechanical load 18 9

University Uses Voltage Sag Data to Continue Operations and Buy Planning Time 700 hp pump 19 Optimized Motor Shutdown Reduces Sag and Eliminates Problems Startup Shutdown Before After Startup Shutdown Current Voltage 20 10

Voltage Events Damage Motors and Sensitive Processing Equipment $1,300 $1,300 $65,000 21 VSSI Data Reveal Stuck Load Tap Changer 41 minutes Time stamps 22 11

Voltage Unbalance Damages Motors» Causes temperature rise» Reduces life expectancy Photo courtesy of Electrical Apparatus Service Association 23 Unbalance Occurs When V A + V B + V C 0 V V B V C 120 120 V A 120 Magnitude (pu) 1.0 0.5 0 0.5 Unbalanced Balanced Three Phase Waveforms A Phase B Phase C Phase Unbalance 1.0 0 0.5 1.0 1.5 2.0 2.5 3.0 Cycles 24 12

Typical Voltage Unbalance Levels in U.S. Three Phase Power Delivered to Industrial Plants <1% Operates normally 1 3% Causes overheating and premature aging >3% Can cause significant damage 66% 32% 2% 25 Facilities Operator Uses Data to Balance Loads 26 13

Unbalanced Magnitude Phasor 150 100 Magnitude (V) 50 0 50 100 150 0 0.33 0.67 1 1.33 1.67 2 Time (t) A Phase B Phase C Phase V 0 27 Common Causes of Unbalance» Faulty distribution equipment» Random phase loading (arc furnaces)» Unbalanced distribution feeders 28 14

Harmonics Occur as Multiples of 60 Hz 29Voltage (pu) Fundamental: 60 Hz Third harmonic: 60 x 3 = 180 Hz Harmonics Occur as Multiples of 60 Hz 30Voltage (pu) Fundamental: 60 Hz Fifth harmonic: 60 x 5 = 300 Hz 15

Low Harmonics Are More Common in Power System Third order Fifth order 31 Fiftieth order Harmonics Cause Humming in Transformers 32 16

Harmonics Described as Percent of Fundamental Frequency Harmonic Order Frequency (Hz) RMS Value Fundamental (1) 60 120 3rd 180 6 4th 240 4 5th 300 3 2 2 2 Sum of squares of harmonics 100 6 4 4 100 THD 6.9% Amplitude of fundamental 120 33 Total Harmonic Distortion (THD) Is High Under Low Load Conditions Although Impact Can Be Low LED light Current THD: 45% 0.04 A rms Incandescent bulb with dimmer Current THD: 20% 0.44 A rms 34 17

Harmonic Trending Pinpoints Cause of Lighting Ballast Failures Image 2016 Google 35 Electronic Ballasts Cause Fifth Harmonic Disturbance Current harmonics (%) 14 13 12 11 10 98 7 6 5 4 3 2 5:30 a.m. 5:30 a.m. 5:30 a.m. Day 1 Day 2 Day 3 36 18

Adjustable Speed Drives Cause Harmonics Current (amperes) 6 pole adjustable speed drive creates fifth and seventh harmonics 37 Identify Sources of Harmonics» Nonlinear loads» HVdc interties» Saturated transformers» Arcing devices» Renewable energy generation» Electronic ballast fluorescent lights 38 19

Turning on Water Results in Voltage Variation That Affects Lights Variable-frequency drive (VFD) for constant water pressure 39 VFD Not Running 512 Samples Per Cycle 40 20

VFD Running 512 Samples Per Cycle 41 Reduce Harmonic Disturbances» Isolate voltage sources for sensitive devices from harmonic generating devices» Use K rated transformer or derate transformer» Install filters between drive and power system 42 21

Flicker Affects Human Eye Brain Response Amplitude modulation of voltage when signal carries another signal Voltage (V) 43 Nonlinear Loads Cause Unwanted Zero Crossings That Affect Digital Clocks 44 22

PQ Problems May Affect Metering Accuracy ANSI C12.20 2015, Accuracy Class 0.1 Adds New Tests Test 39: 90 degree phase fired waveform Test 40: quadriform waveform Test 41: peaked waveform Current Voltage Test 42: pulse waveform Test 43: multiple zero crossing Test 44: multiple zero crossing Current 45 Voltage Phase angle Phase angle Phase angle Summary» PQ issues are changes in electric power supply that can cause equipment to fail, misoperate, or degrade» Common PQ phenomena are VSSI, harmonics, voltage unbalance, and transients» PQ characteristics can be described by amplitude, duration, frequency, and wave shape 46 23

Troubleshooting Summary» Look for patterns in disturbances by noting time of day, duration, and how often events occur» Correlate PQ events with load changes, switching capacitor banks, and so on» Remember that PQ events are typically worse near the source of the problem» Note that a high neutral current can indicate third harmonics 47 NWEMS Questions? 24