Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC01, PPC01

Similar documents
Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC01, PPC01

Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC71, PPC71

Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC01, PPC01

Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC01, PPC01

Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multi-function Types DPB01, PPB01

1-Phase True RMS AC/DC Over and Under Current Types DIC01, PIC01

Monitoring Relays 3-Phase Active power Types DWB02, PWB02

Monitoring Relays 3-Phase Active power direction Types DWB03, PWB03

Monitoring Relays 3-Phase Load Guard Types DWB01, PWB01

Monitoring Relays 1-Phase True RMS AC/DC Over and Under Current Types DIC01, PIC01

Monitoring Relays 1-Phase True RMS AC/DC Over and Under Current Types DIC01, PIC01


V2UM230V10 Art.Nr.: V2UM230V10P Art.Nr.: Control elements. Tripping delay. Function selector. Status indication 230 V AC/DC

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks.

CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks.

EMD-FL-3V-400. Electronic monitoring relay for voltage monitoring in three-phase networks. INTERFACE Data sheet _en_03. 1 Description.

VEO. V2PF480Y/277VS01 Art.Nr.: B TECHNICAL DATA

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

Energy Management Energy Meter Type EM110

08/07/2015

Energy Management Energy Meter with plug-in Output Modules Type EM4-DIN

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.23

05/09/2012

Zelio Control Measurement Relays

Three-phase monitoring relay CM-PFS

Electronic timer CT-SDS.22

ABB NEW. Three-phase monitoring relays. CM-PVS.31 and CM-PVS.41 Data sheet. Features J. Approvals. Marks. Order data. Order data - Accessories

Three-phase monitoring relays

Moeller Electric Corporation

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.23 and CM-MPS.43

Type Nominal voltage (V) Code HSV V

Multifunctional three-phase monitoring relays CM-MPN CM-MPN.52, CM-MPN.62 and CM-MPN.72

Electronic timer CT-TGD.22

Energy Management Three-phase energy meter with output modules Type EM4-DIN

Electronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet

Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages

Measuring and monitoring relays CM-SRS.1 Current monitoring relays, single-phase AC/DC

02/11/2015

38 Series - Relay interface modules A

Electronic timer CT-SDD.22

38 Series - Relay interface modules A. Features /

38 Series - Relay interface modules A

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages

V2IM10AL10 Art.Nr.: V2IM10AL10P Art.Nr.: Control element. Tripping delay. Function selector. Status indication 24...

Energy Management Energy Meter Type EM110

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

48 Series - Relay interface modules A. Features

Three-phase monitoring relays CM-PVS CM-PVS.31, CM-PVS.41 and CM-PVS.81

Type CP-S, CP-C & CP-A Switch mode

Three-phase monitoring relays CM-PVS.81

22/10/2012

Electronic timer CT-YDE Star-delta change-over with 1 c/o (SPDT) contact

Electronic measuring and monitoring relays CM-range

Three-phase monitoring relay

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

27/04/2015

Current monitoring relays CM-SRS.1 For single-phase AC/DC currents

Electronic timer CT-MFS.21

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

08/07/2015

Current monitoring relays CM-SRS.M1 For single-phase AC/DC currents

RE22R2MMU Multifunction Timer Relay - 24VDC/ V AC - 2 C/O

Energy Management Power Analyzer with plug-in Output Modules Type W M22-DIN

Three-phase monitoring relay CM-PVE

Current monitoring relays CM-SRS.2 For single-phase AC/DC currents

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

RE17RCMU off-delay timing relay - 1 s..100 h V AC - 1 OC

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

48 SERIES. Relay interface modules 8 A CO forcibly guided contacts relay interface modules,15.8 mm wide Type 48.12

Conductive Sensors 2 to 4-point level controller Type CL with potentiometer

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents

Electronic timers CT-S range Selection and ordering details

Three-phase monitoring relay

s s s 3-60 s min min 3-60 min h h 3-60 h V AC, 50/60 Hz

Relay interface modules A

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

Electronic timer CT-ERS ON-delayed with 2 c/o contacts Data sheet

Electronic timer CT-SDE

Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Three-phase monitoring relays CM-PFE and CM-PFE.2

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

Electronic timer CT-EBE Flasher starting with OFF, 1 c/o (SPDT) contact

Liquid level monitoring relay CM-ENS.2x

02/11/2015

Model Number Structure. Ordering Information. Solid-state Power OFF-delay Timer H3DE-H. Model Number Legend. List of Models

Electronic timer CT-AWS Impulse-OFF with 1 c/o contact Data sheet

Electronic timer CT-WBS.22 Impulse generating and flashing with 2 c/o (SPDT) contacts

Electronic timer CT-MBS.22 Multifunctional with 2 c/o (SPDT) contacts

DIN 22.5/17.5 Size Lineup of A Wide Range of Measuring and Monitoring Relays. Model Number Structure

PART NUMBERING SYSTEM

2 Pole CO, 8 A Plug-in 2 CO (DPDT) 1 CO (SPDT) 8/15 16/25* 250/ /400 2,000 4, /0.5/ /0.5/ (5/5) 300 (10/5)

Multi-function (MI, ME, M2, M1) 2 NO (2 SPST-NO) 12 / / 400 3,000 1, / 0.3 / (5 / 5) AgNi

Electronic relays. Monitoring. Monitoring

Electronic timer CT-MVS.12 Multifunctional with 1 c/o (SPDT) contact

Energy Management Energy Meter GM3D

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

Transcription:

Monitoring Relays True RMS 3-Phase, 3-Phase+N, Multifunction Types DPC01 Product Description 3-phase or 3-phase+neutral line voltage monitoring relay for phase sequence, phase loss, asymmetry, over and under voltage (separately adjustable set points) with Type Selection PPC01 built-in time delay function. Supply ranges from 100 to 690 VAC covered by three multivoltage relays (ranges over 415 VAC only on the DIN-rail housing). TRMS 3-phase over and under voltage, phase sequence, phase loss and asymmetry monitoring relay Detect when all 3 phases are present and have the correct sequence Detect if all the 3-phase-phase or phase-neutral voltages are within the set limits Detect if asymmetry is below set value Separately adjustable setpoints Separately adjustable delay functions (0.1 to 30 s) Output: 2 x 8 A relay SPDT NE For mounting on DIN-rail in accordance with DIN/EN 50 022 (DPC01) or plug-in module (PPC01) 45 mm Euronorm housing (DPC01) or 36 mm plug-in module (PPC01) LED indication for relays, alarm and power supply ON Ordering key Housing Function Type Item number Output Power Supply DPC 01 D M48 Mounting Output Frequency 100 to 115 VAC 208 to 240 VAC 380 to 415 VAC DIN-rail 2 x SPDT 50-60 Hz DPC 01 D M23 DIN-rail 2 x SPDT 50-400 Hz DPC 01 D M11 400HZ DPC 01 D M23 400HZ DPC 01 D M48 400HZ Plug-in 2 x SPDT 50-60 Hz PPC 01 D M23 PPC 01 D M48 Mounting Output Frequency 440 to 480 VAC 380 to 480 VAC 600 to 690 VAC DIN-rail 2 x SPDT 50-60 Hz DPC 01 D M48 DPC 01 D M69 DIN-rail 2 x SPDT 50-400 Hz DPC 01 D M49 400HZ DPC 01 D M69 400HZ Input Specifications Input L1, L2, L3, N DPC01: Terminals L1, L2, L3, N PPC01: Terminals 5, 6, 7, 11 Measure on own supply Note: Connect the neutral only if it is intrinsically at the star centre Measuring ranges M11 85 to 132 VAC M23 177 to 275 VAC M48 DPC023 to 550 VAC DPC01 400HZ 323 to 475 VAC PPC023 to 475 VAC M49 DPC075 to 550 VAC M69 DPC01 510 to 793 VAC Ranges Upper level +2 to +22% Lower level -22 to -2% Asymmetry 2 to 22% Tolerance 2 to 22% Input Specifications (cont.) Note: The input voltage must not exceed the maximum rated voltage or drop below the minimum rated voltage reported above. Output Specifications Output 2 x SPDT relays N.E. Rated insulation voltage 250 VAC Contact ratings (AgSnO 2) µ Resistive loads AC 1 8 A @ 250 VAC DC 12 5 A @ 24 VDC Small inductive loads AC 15 2.5 A @ 250 VAC DC 13 2.5 A @ 24 VDC Mechanical life 30 x 10 6 operations Electrical life 10 5 operations (at 8 A, 250 V, cos ϕ = 1) Operating frequency 7200 operations/h Dielectric strength Dielectric voltage 2 kvac (rms) Rated impulse withstand volt. 4 kv (1.2/50 µs) Specifications are subject to change without notice (18.07.06) 1

Supply Specifications Power supply Overvoltage cat. III Rated operational voltage (IEC 60664, IEC 60038) through terminals: L1, L2, L3, N (DPC01) 5, 6, 7, 11 (PPC01) M11 - Delta : 100 to 115VAC ±15%; 45 to 65Hz M23 - Delta : 208 to 240VAC ±15%; 45 to 65Hz DPC01 M48 - Delta : 380 to 480VAC ±15%;45 to 65Hz DPC01 M48 - Star : 220 to 277VAC ±15%;45 to 65Hz PPC01 M48 - Delta : 380 to 415VAC ±15%;45 to 65Hz PPC01 M48 - Star : 220 to 240VAC ±15%;45 to 65Hz M48 400HZ - Delta : 380 to 415VAC ±15%;45 to 440Hz M48 400 HZ- Star : 220 to 240VAC ±15%;45 to 440Hz M49 400HZ - Delta : 440 to 480VAC ±15%;45 to 440Hz M49 400 HZ- Star : 254 to 277VAC ±15%;45 to 440Hz M69 - Delta : 600 to 690VAC ±15%;45 to 65Hz M69 - Star : 347 to 400VAC ±15%;45 to 65Hz M69 400HZ- Delta : 600 to 690VAC ±15%;45 to 440Hz M69 400HZ- Star : 347 to 400VAC ±15%;45 to 440Hz Rated operational power M11 8 VA @ 115 VAC, 50 Hz M23 9 VA @ 230 VAC, 50 Hz M48 13 VA @ 400 VAC, 50 Hz M69 21 VA @ 600 VAC, 50 Hz Supplied by L2 and L3 for the DIN-rail versions and by L1 and L2 for the Plug-in versions General Specifications Power ON delay Accuracy Temperature drift Delay ON alarm Repeatability 1 s ± 0.5 s or 6 s ± 0.5 s (15 min warm-up time) ± 1000 ppm/ C ± 10% on set value ± 50 ms ± 0.5% on full-scale General Specifications (cont.) Reaction time Incorrect phase sequence or total phase loss level < 200 ms (input signal variation from -20% to +20% or from +20% to -20% of set value) Asymmetry level Alarm ON delay: < 200 ms (delay < 0.1 s) Alarm OFF delay: < 200 ms (delay < 0.1 s) Indication for Power supply ON LED, green Alarm ON LED, red (flashing 2 Hz during delay time) Output relays ON 2 x LED, yellow Environment (EN 60529) Degree of protection IP 20 Pollution degree 3 (DPC01), 2 (PPC01) Operating temperature @ Max. voltage, 50 Hz -20 to +60 C, R.H. < 95% @ Max. voltage, 50 Hz -20 to +60 C, R.H. < 95% Storage temperature -30 to +80 C, R.H. < 95% Housing Dimensions DPC01 45 x 80 x 99.5 mm PPC06 x 80 x 94 mm Weight Approx. 220 g Screw terminals (DPC01) Tightening torque Max. 0.5 Nm acc. to IEC 60947 Approvals UL, CSA GL (DPC01 only, except 400Hz, M11) CE Marking es EMC Electromagnetic Compatibility Immunity According to EN 61000-6-2 Emissions According to EN 61000-6-3 Mode of Operation Asymmetry definition. Asymmetry is an indicator of the mains quality and it is defined as the absolute value of the maximum deviation among the mains voltages, divided by the nominal voltage of the 3-phase system. The definition changes according to the voltage reference: 1) in case of measuring phase-phase voltages: max V PH-PH x 100 V NOM 2) in case of measuring phase-neutral voltages: max V PH-N V NOM x 100 Tolerance definition. Tolerance is another indicator of the mains quality and it is definied as the absolute value of the maximum deviation of the mains voltages from the nominal voltage, divided by the nominal voltage of the 3-phase system. The definition changes according to the voltage reference: 1) in case of measuring phase-phase voltages: max V NOM - V PH-PH V NOM x 100 2) in case of measuring phase-neutral voltages: max V NOM - V PH-N V NOM x 100 Example: phase-neutral monitoring L1 N V L2-N V L3-N L3 L2 L3 L2 L3 L2 PH-N = V -V L3-N V L1 N N L2-N max V NOM -V PH-N = V NOM -V L3-N L1 L1 V V L2-L1 = V L1-N = V =V L1 NOM L2-N L3-N PH-N = 0 AS = 0 Example: phase-phase monitoring max V NOM -V = V -V = V -V = V -V L3 L3 V L3-L2 L2 L3 PH-PH VL3-L2-V L2-L1 PH-PN = 0 AS = 0 = V L1-L3 = V = V L1 NOM L2-L1 L3-L2 PH-N NOM L1-N NOM L2-N NOM L3-N L1 V L1-L2 V L2-L1 V L2-L1 V L1-L3 V L3-L2 V L3-L2 L2 L2 max V NOM-VPH-PH V NOM-V L2-L1 max V NOM -V PH-N = V NOM -V L1-L3 = V NOM -V L2-L1 = V NOM -V L3-L2 2 Specifications are subject to change without notice (18.07.06)

Mode of Operation (cont.) Connected to the 3 phases (and neutral) DPC01 and PPC01 operate when all 3 phases are present at the same time and the phase sequence is correct. It can be decided whether to monitor upper and lower voltage level of each phase or their asymmetry and tolerance. level monitoring: if one or more phase-phase or phase-neutral voltage exceed the upper set level or drop below the lower set level, the red LED starts flashing 2 Hz and the respective Function/Range/Level/Time Setting Adjust the input range setting the DIP-switches 3 and 4. Select the desired function setting the DIP-switches 5 and 6 as shown below. To access the DIP-switches PPC0-phase monitoring relay DPC0-phase monitoring relay AL PPC01 AL DPC01 0.0s 0.0s DELA 1 DELA 2 0.0s 0.0s DELA 1 DELA 2 / / DPC0-phase monitoring relay output relay releases after the set time period. Asymmetry and tolerance monitoring: if one or more phase-phase or phase-neutral voltage exceed the set levels the red LED starts flashing 2 Hz and the respective output relay releases after the set time period. Note: For both functions, if the phase sequence is wrong or one phase is lost, both output relays release immediately. Only 200 ms open the plastic cover using a screwdriver as shown below. AL 0.0s 0.0s DELA 1 DELA 2 DPC01 400 HZ / delay occurs. The failure is indicated by the red LED flashing 5 Hz during the alarm condition. Example 1 (Mains monitoring - over and under phase-phase voltage) The relay monitors over and under voltage, phase loss and correct phase sequence. Example 2 (Motor monitoring - starting and operating load -asymmetry and tolerance of phase-neutral voltage) Centre knobs: Setting of upper ( ) and lower ( ) level or setting of asymmetry (AS) and tolerance ( ) on relative scale. Power-ON delay ON: 6 s ± 0.5 s OFF: 1 s ± 0.5 s Monitoring ON: Phase-Neutral voltages OFF: Phase-Phase voltages Measuring range Output ON: 2 x SPDT relays OFF: 1 x DPDT relay DPC01 and PPC01 ensure correct starting and operating conditions. They monitor the voltage level, phase sequence (correct direction of the motor rotation) and asymmetry. Frequent failures are fuse blowing and incorrect voltage level. In case of fuse blowing the motor regenerates a voltage in the interrupted phase. The relay detects the failure and reacts due to excessive imbalance among the phases. Lower knobs: Setting of delay on alarm times (DELA 1, DELA 2) on absolute scale: 0.1 to 30 s. SW3 ON ON OFF OFF SW4 ON OFF ON OFF M11 Ph-Ph 100 VAC 100 VAC 115 VAC 115 VAC M23 Ph-Ph 208 VAC 220 VAC 230 VAC 240 VAC M48 Ph-Ph 380 VAC 400 VAC 415 VAC 480 VAC DPC01 only M48 Ph-N 220 VAC 230 VAC 240 VAC 277 VAC DPC01 only M49 Ph-Ph 440 VAC 440 VAC 480 VAC 480 VAC M49 Ph-N 254 VAC 254 VAC 277 VAC 277 VAC DPC01DM69 600 VAC 600 VAC 690 VAC Ph-Ph Volt. 690 VAC DPC01DM69 347 VAC 347 VAC 400 VAC Ph-N Volt. 400 VAC Function ON: Asymmetry and tolerance monitoring OFF: Over and undervoltage monitoring Specifications are subject to change without notice (18.07.06) 3

Operation Diagrams Over and undervoltage monitoring (2 x SPDT relays) Upper Level L1 or L1-L2 L2 or L2-L3 Lower Level L3 or L1-L3 Relay 1(Upper) ON (15/16/18) Relay 2 (Lower) ON (25/26/28) DELA1 T DELA2 T DELA2 T Red LED ON Asymmetry and tolerance monitoring (2 x SPDT relays) Asymmetry (+) Balanced L2-L1 or VL2-L1-VL3-L2 L3-L2 or VL3-L2-VL1-L3 Asymmetry (-) L1-L3 or VL1-L3-VL2-L1 Relay 1 Asymmetry (15/16/18) ON DELA1 T DELA1 T DELA1 T Red LED ON Relay 2 Tolerance (25/26/28) ON DELA2 T DELA2 T L1 or L1-L2 Tolerance (+) Nominal voltage L2 or L2-L3 Tolerance (-) L3 or L1-L3 4 Specifications are subject to change without notice (18.07.06)

Operation Diagrams (cont.) Phase sequence, total phase loss Wiring Diagrams Ex.1 Ex.1 Ex.2 Ex.2 DPC01 PPC01 Specifications are subject to change without notice (18.07.06) 5

Dimensions DIN-rail Plug-in 45 99.5 36 94 90 80 83.5 63 80 63 28.5 28.5 6 Specifications are subject to change without notice (18.07.06)