RESULTS OF EXPERIMENTAL HIGH CURRENT IMPULSE 4/10 s OF METAL OXIDE VARISTORS ZINC IN THE HIGH VOLTAGE 220KV SURGE ARRESTER

Similar documents
Table 1: Results with standard impluse current 8/20 s applied to check for the residual voltage of V-MOV-ZnO

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

A SIMPLIFIED LIGHTNING MODEL FOR METAL OXIDE SURGE ARRESTER. K. P. Mardira and T. K. Saha s: and

7P Series - Surge Protection Device (SPD) Features 7P P P

Tab 8 Surge Arresters

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Electric Stresses on Surge Arrester Insulation under Standard and

Modeling insulation in high-voltage substations

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

High voltage engineering

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Transformers connected via a cable Overvoltage protection

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

In-Service Testing and Diagnosis of Gapless Metal Oxide Surge Arresters According to IEC

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

ABSTRACT 1 INTRODUCTION

Lightning performance of a HV/MV substation

MEDIUM VOLTAGE PRODUCT. PARAMETERS GUIDE How to specify the indoor instrument transformers correctly

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

Type DMX-N Surge Arresters Maximum System Voltage 2 to 36 kv

New Modeling of Metal Oxide Surge Arresters

International Journal of Advance Engineering and Research Development. Analysis of Surge Arrester using FEM

Testing 320 kv HVDC XLPE Cable System

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage

KEYWORDS: Impulse generator, Pspice software, spark gap, Power transformer, Hardware.

VariSTAR Type AZU heavy-duty distribution-class under-oil MOV surge arrester

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

Selection Guide for Low Voltage Surge Protector

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

ABSTRACTS of SESSION 6

Energy Division. Bowthorpe LV/MV Surge Arresters

Spark Gap Surge Protectors For Lv Mains

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES

Protection of low power mains against pulse power of natural lightning using spark gap arresters. Abstract

University of Zagreb Faculty of Electrical Engineering and Computing

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

Comparison of metal oxide surge arrester models in overvoltage studies

George Karady (ASU), A. Huang (NCSU), M. Steurer (FSU)

DC VACUUM CIRCUIT BREAKER

Power Engineering II. High Voltage Testing

Towards an Accurate Modeling of Frequency-dependent Wind Farm Components under Transient Conditions

INTERNATIONAL STANDARD

A New Modified Shifted Current Technique To Diagnose The Surge Arrester Condition

SURGE ARRESTERS AND TESTING. Keith Hill Doble Engineering Company

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

Abstract. 1 Introduction

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

EXPERIMENTAL ISSUES OF OVERVOLTAGE COORDINATION

شركة الوقت للكهرباء والمقاوالت ذ.م.م.

Precautions to be considered for use of surge arresters tested according to Class 1 of IEC

Protection against unacceptable voltages in railway systems

ISOLATING TRANSFORMERS FOR TLC PLANTS

Hazard of Induced Overvoltage to Power Distribution Lines Jiang Jun, Zhao Rui, Chen Jingyang, Tian Hua, Han Lin

Analysis of Major Changes to Arrester Standards IEC STEVE BREWER

Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids

Laboratory no. 3 FLUORESCENT LAMPS FITTINGS

The study of ferroresonance effects in electric power equipment

standard impulse voltage is represented by a double exponential wave [1-2] given by --- (1) Where α and β are constants in microseconds.

PRODUCT PORTFOLIO TEST AND MEASURING SYSTEMS

The Testing Of High Voltage Silicon Carbide Lightning Arresters

Effect of Shielded Distribution Cable on Very Fast Transients

Insulation Test System

TT 0710/03. TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: LB.W.3SA.3.1

TECHNICAL SPECIFICATION

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

EE 1402 HIGH VOLTAGE ENGINEERING

I. INTRODUCTION II. MULTICHAMBER SYSTEM (MCS) A. MCS Principle

Effects of ZnO varistor degradation on the overvoltage protection mechanism of electronic boards

Integrated Electro-optic Sensor based Transient Voltage Measuring System and its Applications

MEDIUM & HIGH VOLTAGE

TECHNICAL REPORT. Insulation co-ordination

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

Degradation Characteristics on MOV of Surge Arrester used for 6.6kV Power Distribution Line

Thermal Behavior of Metal Oxide Surge Arrester Block

Harmonic Components Analysis of Leakage Current for Standard and Anti-Fog Suspension Insulators under Humidity Conditions

Introduction EMC. Filter parameters. Definition of EMC / EMI. X-Capacitor. Sources of EMI. Coupling mechanism. Y-Capacitor.

Selection of MO surge arresters Overvoltage protection

Shunt Reactor Switching

Industrial Controls. Catalog IC SIRIUS. Answers for industry.

PANIMALAR ENGINEERING COLLEGE Department of Electrical and Electronics Engineering

Solid State Modulator for Plasma Channel Drilling

MFAC. Grid Solutions. High Impedance Differential Relay. MFAC Types. Key Benefits. Application. Description. Imagination at work

2007 DEHN + SÖHNE / protected by ISO EXFS / 5392

Tab 2 Voltage Stresses Switching Transients

Arrester 2050 JONATHAN WOODWORTH

VBS TBS KTS BSS LFS UFS

Insulation Co-ordination For HVDC Station

High-Voltage Test Techniques

Method for Static and Dynamic Resistance Measurements of HV Circuit Breaker

Appendix B to Working on Exposed Energized Parts

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

IEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4

APPLICATION GUIDELINES. Overvoltage protection Metal-oxide surge arresters in medium-voltage systems

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM

Transcription:

RESULTS OF EXPERIMENTAL HIGH CURRENT IMPULSE 4/10 s OF METAL OXIDE VARISTORS ZINC IN THE HIGH VOLTAGE 220KV SURGE ARRESTER PhD. Nguyen Huu Kien National Key Laboratory for High Voltage Techniques - Institute of Energy ABSTRACT This paper presents the results of experimental researching the technical characteristics of metal oxides varistors zinc (V-ZnO) in the 220 kv surge arrester at the National Key Laboratory for High Voltage Techniques - Institute of Energy (HVLAB). The results of experimental researching the peak value of discharge current having a 4/10 s impulse shape which is used to test the stability of the arrester on direct lightning strokes. The voltagecurrent linear characteristics of metal oxides varistor zinc V-ZnO at current on resistor plate of surge arrester. When voltage apply to the V-ZnO larger U peak, a small increasement of voltage will make the current through the V-ZnO increase quickly. This feature is used to discharge the lightning when the over-voltage current appeare. U peak is based reference limits to design the core of V-ZnO. From the results of this test allow to assess some category of the V-ZnO quality arrcording to IEC 60099-4, to install surge arrester into the grid with high efficiency. Key words: Metal oxides varistor zinc; V-ZnO; V-SiC; Surge arrester. I. INTRODUCTION The surge arrester (SA) is one of the critical lightning protection device for substations, its quantity and installation location is selected from the specific protection requirement. [1]. Since the 1970s, a new type of SA which nonlinear resistor were made from zinc oxide ZnO (V-ZnO) has been appeared. They have been used instead of classical SA with gap which nonlinear resistors were made from Cacbuasilis SiC (V-SiC). Cause the value of V-ZnO s nonlinear parameter was only 1/10 of the V- SiC, the basic structure of lightning has been changed. Analyze the characteristics volt - ampere we will see: U = k. i When setting the in different value, the nonlinear parameter of V-SiC vary in the range from 0.18 to 0.24 (average is 0.2) and the nonlinear parameter of V-ZnO is 0.02 (smaller 10 times than the V-SiC). Figure 1: The nonlinear parameter of SA We can also see : with a current zone I > 1kA, the residual voltage of SA when using V-ZnO is very small compared to the V-SiC. Thus, with the using non-linear resistors V-ZnO will have a higher level of safety and could lower the level of pulse insulation around electrical equipment. This will bring economic efficiencies for the industrial of power equipment manufacturing. [2]. In zone I the working zone (I leakage ) the leakage current through the nonlinear resistor V-ZnO is much smaller than the leakage current through the nonlinear resistor V-SiC, and it s small enough to be able to connect directly to the power grid without isolating with the discharge gap as in the classic lightning (Figure 2). The non- gap discharge not only simplifies the structure of protection

devices, miniaturization, but also eliminates the problem of arc extinguishing the power electric with continuous frequency. Besides, using the new lightning types (V-ZnO) with residual voltage lower than V- SiC type will allow us to study the changing in lightning protection scheme for substations and others high voltage equipments. Research the plan to change the quantity, placement in the diagram or shorten the front protection of the station. The changes menttioned above will not only bring economic efficiency of investment in equipment for the station lightning protection but also ensures the reliability of lightning protection for devices and also resolve the difficulties in setting up the node stations which have to improve the line on both side from the node point. As we know, the synthesis of anti wave transmission from line can not guarantee the absolute reliability for the equipment in the station. So the ultimate goal is to find a set of solutions ò lightning protection for the station with a minimum cost of investment in constructing and operating the protective equipment as well as the smallest damage due to lightning strike. To archive this, we have to know the specific over voltage levels on the device in the protection diagram to determine the reliability of the diagram and select proper SA. Atmospheric overvoltage caused by lightning creates a huge current, can reach hundreds of ka and make the electric devices in dangerous. To protect over voltage for electrical equipment, the surge arrester need to connect in parallel with electric devices. When overvoltage appears, the non-linear characteristics resistor of the surge arrester (Figure 2) fall down very quickly to small values, V-ZnO allows the current of overvoltage pass through (early discharge) and conduct lightning current to ground. Thus, electrical devices are protected and grid operation safely. [3]. Figure 2: Diagram of surge arrester (V- ZnO) protection in parallel with devices require to protect; V-SiC with air gap. II. TESTING FOR V-ZnO. The SA as other products of electrical engineering, from the research stage to the manufacturing stage before commissioning phases, must pass the quality control testing for the purpose of ensuring the specifications to safety protect for electrical equipment and keep out the problems during the grid operation. [2]; [4]. 1. Type tests These tests are to research in designing and creating new products. The test will calibrate a product to determine the characteristics and to demonstrate its compliance with manufacturing standards. These test do not need to do again in other products, unless the design proccess change its the characteristics. In that case, only the experiment involved need to test again. 2. Routine tests These test are to perform on each surge arrester, the SA element, the lightning protection materials, to ensure products meet the technical regulations required, including the following types of test: - Periodic test for batches of product: Check quality of V-ZnO or SA periodically or check the batches of products. - Factory finished SA tests: qualify surge arrester quality before using. - Test before installation: check the basic quality field of the SA, all the transporting storaging proccess the SA must meet the technical criteria for installation. 3. Acceptance tests

These tests are performed when the agreement between the manufacturer and the buyer at a kind of product was meet. Nonlinear resistor block (V-ZnO) is the core element of the SA, the quality test for it becomes very important. [4]. Within the scope of this article and the later article we will only mention the test before installing SA to the grid. III. SPECIMEN PREPARATION AND MEASUREMENT CIRCUIT. The specimen is non-linear resistor block (V-ZnO) which were obtained from 220kV SA of ABB manufacturer. The capacitors in the impulse current test set of HighVolt-IP 125/100Ssp (German) are arranged in a semicircle to keep a specified distance with the specimen. This design ensures the circuit have small inductance for short time impulse current. (Figure 3). - The minimum time between 2 pulses : 60s - Supply voltage: 400/220V, 50Hz, 3W + N - System power capacity : 30kVA ~ - Operating Conditions and Test: + Altitude : less than 100 meters from sea level. + Ambient temperature : +5 0 C to +40 0 C + Moisture : < 90 % IV. TEST RESULT AND ANALYSIS. The voltage-current linear characteristics of non-linear resister V-ZnO. (Figure 4) show the linear of V-ZnO at 1mA current. When voltage apply to the V-ZnO larger U peak, a small increasement of voltage will make the current through the V-ZnO increase quickly. [4]. Figure 3: Test high current impulse 4/10 s for V-ZnO resitor block at HVLAB 1. The system functions. Impulse current testing system IP125/100Ssp is designed to test the SA components arrcording to IEC 60099-4 with the line discharge level is 2 and 3. [5]. Types and characteristics of SA can be tested: - Operating voltage of SA : Up to 765kV - Voltage range of SA elements: 3 12kV - Line discharging level arrcording to IEC 60099-4: 2 and 3 - SA type : Metal Oxide Aresster 2. System technical specifications. - Loaded voltage: 10 kv - Nominal Pulse Energy : 125kJ - Pulse capacitance: 25μF (10 x 2,5 μf) Figure 4: Voltage-current linear of V-ZnO compare to V-SiC resistor. This feature is used to discharge the lightning when the over-voltage current appeare. U peak is based reference limits to design the core of V-ZnO. The designer often take the range value of (50 70)% U peak to design the nominal voltage of the V-ZnO. Before and during the test, HVLAB staff calibrated the IP-125/100Ssp test set by calibration specimen to accurate measurement result. [6]. Zone 1: The V-ZnO linear domain, V-ZnO leakage current is very small (I leakage = 10-7 10-6 A). When over-voltage occurs, the V- ZnO applied voltage increase suddenly, this non-linear resistor V-ZnO change to operate in Zone 2. Zone 2: Due to the nonlinear properties of V-ZnO in 2 slope area, when the voltage increase a small value, the current through

the V-ZnO increased rapidly and turn the ligtning current to the ground, prevent electrical devices from breakdown due to lightning. Relations between current and voltagesin the Zone 2 is represented by the equation: I = k.u Legend: - non-linear parameter, k - constant Zone 3: Area of V-ZnO saturation. In Figure 4 - Voltage of U peak corresponding with the value 10-3 A current through the V- ZnO. - Working voltage U c is the voltage which can matain long time on the 2 plole of V- ZnO, has the value about (50 60)%U peak (depend on the manufacturer's design). - Leakage current I leakage which is passing V- ZnO, correspond to the working voltage U c applied on the poth poles of V-ZnO. - nonlinear parameter in Zone 2 of non V- ZnO linear characteristics can be determined by the formula: lg I2 lg I1 lg U 2 lg U1 Table 1: Result of the test high current impulse 4/10 s for V-ZnO resitor block. increase quickly. This feature is used to discharge the lightning when the overvoltage current appeare. Before perform the 4/10μs high current impulse test, the officers had calibrated the standard value of 100 ka impulse current test for V-ZnO. High current impulse test of 4/10 impulse current perform checking residual voltage of the V-ZnO. The results of experimental researching the peak value of discharge current having a 4/10 s impulse shape which is used to test the stability of the arrester on direct lightning strokes. The voltage-current linear characteristics of V-ZnO at current on resistor plate of SA. When voltage apply to the V-ZnO larger U peak, a small increasement of voltage will make the current through the V-ZnO

When lightning current flows through V- ZnO to the ground, due to existing ground resistive and resistance of V-ZnO; On V- ZnO appears residual voltage (U res ). If the U res on V-ZnO is greater than the durability of electrical device insulation. The value of the high current impulse 4/10 s impluse current approximately 100kA more than. According to IEC 60099-4, the V-ZnO plate resistors which used to produce 220 kv SA must withstand the value 100 ka of standard current impulse when the the 4/10μs high current impulse perform. [7]. V. CONCLUSION Since the test results presented above, we can draw the following conclusions: - When the load voltage increased from U ch = (35 45)kV, the pulse current flowed

through the V-ZnO increased from I p = (99.26 102.8)kA and the samples did not crack during the test. This will support us to determine the insulating properties and the energy absorption capacity of the V-ZnO is completely achiseved the technical specifications of IEC60099-4 when perform the 4/10μs high current impulse test. - The 4/10μs high current impulse values recorded in Table 1, are the impulse current which was discharged through the V-ZnO after being V-ZnO absorbed a part of the energy exceeds the standard value of 100kA. This showed the ability of V-ZnO samples in protecting elcetrical device when the over voltage on the grid apears. REFERENCES 1. Trần Văn Tớp; Kỹ thuật điện cao áp - quá điện áp và bảo vệ chống quá điện áp; Nhà xuất bản Khoa học Kỹ thuật, 7, 2007. 2. Professor A.T Johns; J.R.Platts H M Ryan; High voltage engineering and testing; Peter Peregrinus Ltd on behalf of the IEE, London, UK 1994. 3. EM Bazelyna; Lightning Physics and Lightning Protection; IOP Publishing Ltd 2000. 4. International standard IEC 60099-4 Surge arresters Part 4; Metal-oxide surge arresters without gaps for A.C systems; 07 (2006). 5. Jinliang He; Development of Polymeric Surge ZnO Arresters for 500kV compact transmission line; IEEE Transactions on power delivery Vol.21 No.1 January, (2006). 6. C.L. Wadhwa; High Voltage Engineering - New Age International (P) Ltd., Publishers, 2007. 7. M.A.Ramirez; The failure analyses on ZnO varistors used in high tension devices; Journal of materials science 40, 5591-5596, (2005).