Harmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez

Similar documents
Understanding Input Harmonics and Techniques to Mitigate Them

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives

CHAPTER 4 HARMONICS AND POWER FACTOR

Reliable power onboard and offshore

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

Harmonics Reduction using 4-Leg Shunt Active Power Filters

VARIABLE FREQUENCY DRIVE

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

7/15/2002 PP.AFD.08 1 of 28

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

NJWA - Harmonics and Drives Proper System Design

Voltage and Current Waveforms Enhancement using Harmonic Filters

Literature Review for Shunt Active Power Filters

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

SHUNT ACTIVE POWER FILTER

Harmonic Distortion and Variable Frequency Drives

Power Quality improvement of a three phase four wire system using UPQC

Open-Delta Systems Affect Variable Frequency Drives

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

APPLICATION GUIDE. Harmonics in HVAC applications

Drives 101 Lesson 5. Power Input Terminology for a VFD

Economical Solutions to Meet Harmonic Distortion Limits[4]

Harmonic Solutions. Clean Power Drive Solution to Harmonic Distortion

Analysis of Harmonic Distortion in Non-linear Loads

Harmonic Requirements

Effective Harmonic Mitigation with Active Filters

22.0 Harmonics in Industrial Power Systems

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Nonconventional Technologies Review no. 4/2009

The increase in the application

VFDs and Harmonics in HVAC Applications

MIRUS International Inc.

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Reactive power compensation for linear and non linear loads by using active and passive filter for smart grid applications.

High Voltage DC Transmission 2

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Understanding Harmonics

Power Quality Analysis in Power System with Non Linear Load

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 4 MODIFIED H- BRIDGE MULTILEVEL INVERTER USING MPD-SPWM TECHNIQUE

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

Harmonics White Paper

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF)

Mitigation of Harmonics Produced by Nonlinear Loads in Industrial Power System

Emicon Engineering Consultants L.L.C.

A Subsidiary of Regal-Beloit Corporation. AC Inverter Terminology

Harmonic Filters for Single Phase Equipment

Analysis of Advanced Techniques to Eliminate Harmonics in AC Drives

Study of Power Factor Correction in Single Phase AC-DC Converter

OPTIMAL DESIGN OF A SINGLE TUNED PASSIVE FILTER TO MITIGATE HARMONICS IN POWER FREQUENCY

Power Quality Analysis: A Study on Off-Line UPS Based System

shunt (parallel series

Harmonic control devices. ECE 528 Understanding Power Quality

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller

Reducing Total Harmonic Distortion with Variable Frequency Drives

Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation

Peteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS. ABB Group December 14, 2011 Slide 1

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

IMPORTANCE OF VSC IN HVDC

How adjustable speed drives affect power distribution

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution

Frequently Asked Questions (FAQs) MV1000 Drive

Performance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System

Harmonic Reduction and Power Factor improvement in three phase three wire system by using Passive Filters

AC Drives and Soft Starter Application Guide

Harmonic control devices

Harmonic Filters and Reactors

Technical Paper. Harmonic Distortion in Data Centers

Svpwm Technique to Eliminate Harmonics and Power Factor Improvement Using Hybrid Power Filter and By Using Dsp Tms 320lf2407

Hybrid Active Power Filters for Reactive Power Compensation with Adaptive DC-Link Voltage Control

DESIGN AND ANALYSIS OF ELIMINATION OF HARMONICS USING WIND ENERGY CONVERSION SYSTEMS

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Harmonic Mitigation in Variable Frequency Drives: 6-Pulse Drive with MTE Matrix AP Harmonic Filter vs. 18-Pulse Drive

The unified power quality conditioner: the integration of series and shunt-active filters

Study and analysis of THD and content of Harmonics in Three Phase PWM Inverter with Filters.

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

Liebert AF2 Next Generation Active Harmonic Filter. Power Protection for Business-Critical Continuity TM

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

Introduction to Rectifiers and their Performance Parameters

Application of Tuned Passive Filter for Industrial Six-Pulse Rectifier with R-L Load Viralkumar A. Rana 1 Keyur Rana 2 Atul Talati 3

16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER,

Outcomes of Harmonics & Its Reduction Techniques: A Comprehensive Review

Alternators Reactance for Nonlinear Loads

Mitigation of Harmonics and Interharmonics in VSI-Fed Adjustable Speed Drives

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

Harmonic Filtering in Variable Speed Drives

Transcription:

Harmonic Power A VFDs.com Whitepaper Written by Ernesto Jimenez

Table of Contents 1. Need for Clean Electricity 2. What Are Harmonics? 3. Lower Order Harmonics 4. Causes of Harmonics 5. Effects of Harmonics 6. Problems Associated with Harmonics 7. Regulations 8. Total Demand Distortion 9. Harmonics Purging Techniques a. Line Reactors or DC Link Chokes b. Hybrid Harmonic Filter c. Multi-pulse Converter Systems d. Active Harmonic Filter 10. Harmonic Filters Comparison Table 11. Cost Comparison of Harmonic Filters 12. References

Why Mitigating Harmonic Distortion Is Important in Any Electrical System key words: harmonics, passive filter, harmonic filter, non-linear load, electrical noise Need for Clean Electricity Electricity users expect and require clean power: power free from distortion, noise and glitches. Utility service providers attempt to maintain and provide clean power to their customers by using electrical devices that improve power quality. Unfortunately, many electrical devices utilized by consumers that are connected to the network create electrical pollution that is fed back into the network. Pollution (or noise) in an electrical system is called harmonics. Harmonics can overheat equipment, create mechanical and electrical oscillation in alternators & prime movers (engines), degrade insulation, interrupt communications and cause failure in control systems, trip fuses unpredictably, and bring premature equipment failure. What are harmonics? In AC power supply, the current and voltage are supplied in a sinusoidal waveform. This sinusoidal wave cycles many times per second. This is defined as the wave s frequency (in units of Hertz (Hz) or cycles per second). The frequency at which current and voltage are supplied is referred to as the fundamental frequency. Harmonics are frequencies that are integer multiples of the fundamental frequency and are considered noise. When harmonics are present in an electrical signal, they superimpose with the fundamental frequency and distort the wave, as shown in Figure 1. Figure 1 Harmonics superimpose with the fundamental frequency and produce a resultant wave that is distorted from the original sinusoidal wave. Lower Order Harmonics

Harmonics follow an inverse law in the sense that the higher the harmonic order of a particular harmonic frequency, the lower is its amplitude. The most troublesome harmonics are, thus, the lower order harmonic frequencies (i.e. 3rd, 5th, 7th, 9th and 11th). Figure 2 shows the effect of having the 3rd harmonic in the electrical signal. In power systems the utilities are most concerned with the lower order harmonics. Figure 2 The 3rd Harmonic is ⅓ of the amplitude of the fundamental waveform, yet, significantly affects the resultant waveform. Causes of Harmonics Industrial, commercial and residential users use devices with electronic switching, and these devices draw non-linear current; they switch the current on for only a fraction of the time the sinusoidal voltage is supplied. The National Electrical Code (NEC) defines nonlinear loads as a load where the wave shape of the steady-state current does not follow the wave shape of the applied voltage [1]. In Figure 3, on the left, current is drawn proportional to voltage, producing a current waveform that behaves linearly with the voltage waveform and a linear load demand. The right side shows current being drawn only when voltage exceeds a minimum value, for a

fraction of the time voltage is available, resulting in a current waveform that does not behave linearly with voltage and a load demand that is non-linear. Figure 3 Linear load: when current is drawn proportionally to the voltage, producing a steady rise in load. Non-linear load: when current is drawn after voltage exceeds a minimum value, producing a sudden rise in load. source Variable frequency drives are one of many electronic devices producing harmonics in an electrical network. Devices that draw non-linear loads, the loads that create harmonic pollution, include [3, 5, 6, 8]: Silicon-controlled rectifiers (SCRs) Power transistors Microprocessor controls Converters Welding equipment Variable frequency drives Periodic switching of voltage and currents, such as SMPS, Uninterrupted Power Systems (UPS), CFL Fluorescent, LED and HID lighting Harmonics create electrical stress in the equipment they power, damaging the equipment, as will be discussed. Service providers are not able to directly control the magnitude of harmonics released into the network by consumers, thus, this pollution spreads throughout the network and is fed into other consumer devices connected to the network. Effects of Harmonics Power quality is a point of common interest for both the users as well as the utility. Utility providers care about harmonics because harmonics in the system can cause damage to power service equipment. Likewise, users expect clean power supply that will not damage their electronic devices. Only the power from fundamental component is useful power; all other components result in losses (heat). Harmonics affect electrical system components including the transformers, insulators, switch-gears, neutral conductors, lines and cables, rotating machines, fuses, etc. These problems can manifest as overheating, mechanical &/or electrical

oscillation in alternator & prime movers, insulation degradation, communication failure in control systems, unpredictable fuse tripping, premature equipment failure, etc. Effects on transformers Transformers are the most impacted service devices because they are connected directly to non-linear loads in commercial, industrial and residential settings. Effects on motors and other rotating machines Harmonic distortion increases motor losses and results in overheating of the motor. Effects on fuses As mentioned before, harmonics increase peak current, which can lead to unexpected melting of fuses in VFD capacitor banks, which may result in temporarily shutting down the process. Regulations Harmonics released into the network by a user can not be readily mitigated by the utility provider. Therefore, they require customers to mitigate their harmonic pollution and enforce limitations on the total harmonic distortion. Harmonic distortion limits are dependant on the region. In the US, utility companies utilize the limits set in IEEE Std. 519 for user system specifications. Most of the standards are made according to the regional requirements of the country; few are based on the global needs and requirements. European IEC 61800 specifications, on the other hand, are equipment (rather than system) based. Harmonics becomes an increasing issue when new harmonic-generating electronic devices are installed into a power system. This may result in unwanted and unexpected termination of power supply from the utility company until the Total Demand Distortion (TDD) falls under the limits specified by the utility provider. The point where utility providers interface with the consumer is called the point of common coupling (PCC), and is where harmonic distortion is measured [2]. Total Demand Distortion The table below shows the maximum limits on the I SC /I L ratio, which is a measure of the customer s effect on the electrical distribution system. A customer with a large load (I L ) running on a utility with a small short circuit capability (I SC ), thus, a small I SC /I L ratio, will be allowed less Total Demand Distortion (TDD) [2]. Location I SC /I L IEEE Allowed TDD <20 5.0 20<50 8.0 50<100 12.0 100<1000 15.0 >1000 20.0

Harmonics Purging Techniques There are several techniques to mitigate harmonics. These techniques can be classified into one of the following categories: 1. Line Reactor or DC Link Choke 2. Hybrid VFD filter 3. Multi-pulse converter system 4. Active Bridge Filter Below we ll discuss the advantages and disadvantages of each. Table 1 shows a summary of the benefits, drawbacks and functionality of the most common harmonic filters. Line Reactors or DC Link Chokes Line reactors are the most affordable option to mitigate harmonics in power lines. Due to their inline impedance, they also protect the equipment they precede in the current flow from voltage surges. Figure 4 shows a line reactor in a 3-phase power system connected to a variable frequency drive (VFD). Line reactors offer an impedance that is proportional to the load. A 3% reactor will get you 35% THID and 5% will get 30%. DC link chokes are a least costly option to line reactor. Figure 4 Line reactor is connected in series with the VFD and protects the VFD from voltage surges, in addition to mitigating harmonics. Hybrid harmonic filter Hybrid harmonic filters, in the context of this article, are designed specifically for VFDs and comprise of a series passive filter and a shunt passive filter, as shown in Figure 5.

Figure 5 The MDI harmonic filter: a hybrid (series passive & shunt passive) harmonic filter provides high THID mitigation (THID=4-15%) at a low cost. Multi-pulse Converter Systems Multi-phase converter systems utilize 6-pulse converters in series or parallel, and shift the voltages supplied to the diode bridges to cancel the lower order harmonics. Where multi-phase converter systems are used, only characteristic harmonics exist, all others cancel out as a result of the phase shift. Characteristic harmonics follow the formula: h = (n*p) ± 1, where h is harmonic order, n is an integer and p is the number of pulses. A 12-pulse converter, as shown in Figure 6, has the following characteristic harmonics: 11, 13, 23, 25, 35, 37,, etc. These systems will not completely eliminate non-characteristic harmonics if voltages are not precisely balanced. Parallel phase shifting used in low voltage drives (under 1000 V) is difficult to balance, whereas series phase shifting used in medium voltage drives (above 1000V) performs much better. Hybrid filters tend to have similar performance to 18-pulse, but at a lower cost. Hybrid filters are typically used more often for low voltage drives than 18-pulse converters.

Figure 6 A 12-pulse converter system eliminates lower-order harmonics by phase shifting the voltages applied to each converter, such that the non-characteristic harmonics cancel out when they combine. Figure 7 A 18-pulse converter system works similar to a 12-pulse converter system, but with a different voltage phase shift. The phase shift required follows the formula: phase shift = 360/(# of pulses). Active harmonic filter Active Power Filters (APF) are the best performing, but most expensive. They are rarely used, except in instances where harmonic mitigation requirements are extreme or a regenerative drive is required. Active Power Filters use power electronics to introduce current components to

remove harmonic distortions produced by the non-linear load. APF s detect the harmonic components in the line and then produce and inject an inverting signal of the detected wave in the system [7]. Active harmonic filters are mostly used for low-voltage networks due to the limitation posed by the required rating on power converter [4]. They permanently monitor the nonlinear load and dynamically provide precisely controlled current. This current has the same amplitude as the harmonic current, but is injected in the opposite phase-shift. Active harmonic filters also correct poor displacement power factor (DPF) by compensating the system s reactive current. higher sophisticated devices are equipped with Insulated Gate Bipolar Transistors (IGBT) and Digital Signal Processing (DSP) components.

Table 1. Most Common Harmonic Filters DC Link Choke AC Line Reactor Hybrid Harmonic Filter (Passive shunt passive series) Multi-pulse converter systems Active Bridge Filters Bus-type Active Filter How it works Installed in a VFD before the VFD s DC bus capacitor to reduce the peak currents the capacitor draws in order to charge. An inductor in series with the power source. It functions the same as a DC Link Choke with the added advantage of protecting the drive from current spikes and voltage surges, and prevent harmonics from leaking into the power supply. A low pass filter specially designed to filter out harmonics characteristic of VFDs. offers very low impedance to the tuned frequency to divert it into the filter and away from power line. The impedances of the series inductors are proportional to frequency, thus, filter higher order harmonics. Combine 6-pulse converters in series or parallel and appropriately phase shift the voltages supplied to the diode bridges to combine and cancel out lower order harmonics. Use high computational capabilities to detect the harmonics in line and produce current into the line with offset harmonics to cancel with those already in the line. Works like the active bridge, but sits on the bus. Effectiven ess A 6% DC Link reactor mitigates current distortion by same amplitude as a 3% AC line reactor. The effective impedance is directly proportional to frequency. The effective impedance is directly proportional to frequency. Is tuned to completely mitigate harmonics characteristic of VFDs. Depends on the design and balance of the system. If fuly balanced: Harmonics that don t meet the following formula: h = (n*p) ± 1, where h is harmonic order, n is an integer and p is the number of pulses. A 12-pulse converter, for example, would not filter the following harmonics: 11, 13, 23, 25, 35, 37, The most effective filter for VFDs. Effectiveness depends on amplitude of current fed into the line by filter. Design involved Inductor inserted between converter and DC link capacitor. Inductor inserted immediately upstream of VFD. and DC link capacitor. The shunt passive component is installed between two series passive components. Should be installed directly upstream of VFD. Converters of lower pulse values, usually 6- pulse, are connected in series or in parallel. Active bridge replaces the diode bridge in a VFD. It is installed on the bus to filter out harmonics existing on bus. Percent THID Mitigation Reduces THID to 30-40%, depending upon the size of the reactor. Reduces THID to 30-40%, depending upon the size of the reactor Reduced to 4-15%, depending on the effectiveness of the filter. Reduced to 4-15%, depending on the effectiveness of the filter. Reduced to 2-10%, depending on load. Up to a 10:1 attenuation ratio, depending upon filter size and application. Load types non-regenerative non-regenerative non-regenerative non-regenerative Regenerative non-regenerative Benefits Most affordable countermeasure for mitigating harmonics from a VFD. All the benefits of DC Link reactor, plus benefits of surge protection for VFD. Lowest cost method of achieving current distortion levels under 12%. Reduce the possible harmonics in the system from odd integers to only characteristic harmonics : h = (n*p) ± 1, in a balanced network. Best performance of any filter type. One filter can filter harmonics from multiple loads. Drawback s Unlike line reactors, they don t protect the VFD converters from voltage spikes because they are connected downstream of the converters.cannot reduce distortion significantly below 30%. Cannot reduce distortion significantly below 30%. Can cause standby generator instability if not correctly applied. They are more expensive than line reactors. Very sensitive to voltage imbalance. Significantly higher cost than hybrid harmonic filter. It is the most expensive filtering technology. It is the most expensive filtering technology. Current carried Full load Full load Full load Full load Full load Harmonic current

Recommended Harmonic Filters In this article we have organized the drives from least to most expensive option. In low voltage drives (below 1000 V), the filters that are typically used are: (1) line reactors (2) hybrid filters (3) active bridges, depending upon performance requirements. For medium voltage, the most common are: (1) multi-pulse, (2) active bridge.

References [1] National Electrical Code, Article 100 [2] IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, ANSI/IEEE Std. 519-1992. [3] S.J.Chapman. Electric machinery fundamentals. McGraw-Hill Science/Engineering/Math, 2005. [4] B.R. Lin, B.R. Yang, and H.R. Tsai. Analysis and operation of hybrid active filter for harmonic elimination. Electric Power Systems Research, 62(3):191 200, 2002. [5] N. Mohan,T. Undeland and W. P. Robbins. Power Electronics Converters, Applications and Design Wiley, 2006. [6] H.Rashid. Power Electronics Circuits Devices and Applications. Prentice Hall Int. Ed.,1993. [7] Hadeed Ahmed Sher et. al. Harmonics Generation, Propagation and Purging Techniques in Non-Linear Loads. [8] W. Theodore et al. Electrical Machines, Drives And Power Systems 6/E. Pearson Education, 2007.