EMD-FL-C-10. Current Monitoring Relay. Data Sheet. Functions. Structure 08/2004

Similar documents
EMD-FL-3V Phase Voltage Monitoring Relay INTERFACE. Data Sheet. Description

EMD-FL-3V-400. Electronic monitoring relay for voltage monitoring in three-phase networks. INTERFACE Data sheet _en_03. 1 Description.

V2IM10AL10 Art.Nr.: V2IM10AL10P Art.Nr.: Control element. Tripping delay. Function selector. Status indication 24...

V2UM230V10 Art.Nr.: V2UM230V10P Art.Nr.: Control elements. Tripping delay. Function selector. Status indication 230 V AC/DC

VEO. V2PF480Y/277VS01 Art.Nr.: B TECHNICAL DATA

Electronic relays. Monitoring. Monitoring

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

RAD-IN/OUT-8D. Digital extension modules for the bidirectional wireless system. INTERFACE Data sheet _en_05. 1 Description

27/04/2015

MINI-PS AC/24DC/1.3

Protection and safety SQZ3 phase and sequence relay

Measuring and monitoring relays CM-SRS.1 Current monitoring relays, single-phase AC/DC

QUINT-PS-24DC/24DC/10

650 PHOENIX CONTACT Courtesy of Power/mation Energy Lane, Saint Paul, MN

MINI MCR-SL-UI-f(-SP)

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

PHOENIX CONTACT - 09/2009


QUINT-PS AC/24DC/40

Current monitoring relays CM-SRS.1 For single-phase AC/DC currents

QUINT-PS/ 3AC/24DC/10

Current monitoring relays CM-SRS.2 For single-phase AC/DC currents

Electronic timer CT-TGD.22

IB IL 24 PWR IN/PS IB IL 24 PWR IN/PS-PAC

Control module CP-A CM

MINI-PS AC/2X15DC/1

Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact

MCR-SL-CUC Universal current transducer. Data sheet _en_05. 1 Description

PHOENIX CONTACT - 06/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Zelio Control Measurement Relays

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents

QUINT-PS/ 3AC/24DC/40

Moeller Electric Corporation

Electronic timer CT-EBE Flasher starting with OFF, 1 c/o (SPDT) contact

Control module CP-A CM

Current monitoring relays CM-SRS.M1 For single-phase AC/DC currents

PHOENIX CONTACT

CP-T range Product group picture

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages

ABB NEW. Three-phase monitoring relays. CM-PVS.31 and CM-PVS.41 Data sheet. Features J. Approvals. Marks. Order data. Order data - Accessories

CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC

QUINT-PS/ 1AC/24DC/20

Three-phase monitoring relays

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

Electronic timer CT-ERS ON-delayed with 2 c/o contacts Data sheet

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300

PHOENIX CONTACT - 03/2007

Three-phase monitoring relay CM-PVE

Time relays. Monitoring relays /

Power supply CP-T 24/20.0 Primary switch mode power supply

Power supply CP-T 24/10.0 Primary switch mode power supply

Power supply CP-T 24/40.0 Primary switch mode power supply

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

This data sheet is only valid in association with the IL SYS INST UM E user manual.

Electronic timer CT-SDD.22

Power supply CP-E 24/2.5

Electronic timer CT-AWS Impulse-OFF with 1 c/o contact Data sheet

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

Power supply CP-E 24/20.0

Electronic timer CT-SDE Star-delta change-over with 1 n/c + 1 n/o contact

IMPULSE SWITCH, REMOTE SWITCH

MCR-VAC-UI-0-DC. Voltage transducer for AC voltages. INTERFACE Data sheet _en_02. 1 Description

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks.

Content. Monitoring relay pluggable. 1-phase current monitoring relay phase direct-current voltage monitoring relay... 5.

CP-T range Benefits and advantages

MACX MCR-UI-UI-UP(-SP)(-NC)

Power supply CP-E 24/0.75

Power supply CP-T 48/20.0 Primary switch mode power supply

s s s 3-60 s min min 3-60 min h h 3-60 h V AC, 50/60 Hz

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Power supply CP-T 48/5.0 Primary switch mode power supply

Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages

Electronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC

Passive Current Transducers for Sinusoidal Alternate Currents From A/0...5 A MCR-SLP-1/5-UI-0(-SW)

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

STEP-UPS/24DC/24DC/3. Uninterruptible power supply. Data sheet. 1 Description. Features

PHOENIX CONTACT

Type CP-S, CP-C & CP-A Switch mode

Power supply CP-E 48/5.0 Primary switch mode power supply Data sheet

PSR-SCP- 24DC/ESD/5X1/1X2/300

Operating Manual MU2000K

Three-phase monitoring relays CM-PVS CM-PVS.31, CM-PVS.41 and CM-PVS.81

Power supply CP-E 24/2.5

Current monitor Type C 551

Power supply CP-E 12/10.0 Primary switch mode power supply Data sheet

Electronic timer CT-YDE Star-delta change-over with 1 c/o (SPDT) contact

Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts

RISH Ducer TV 808, 2 channels Isolating amplifier unipolar / bipolar

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

Safety relays - PSR-SCP- 24DC/ESD/4X1/

Type Nominal voltage (V) Code HSV V

Electronic timer CT-SDS.22

Insulation monitoring relay CM-IWS.1 For unearthed AC, DC and mixed AC/DC systems up to U n = 250 V AC and 300 V DC

MINI MCR-SL-UI-I-LP-NC

Switching power supplies CP range, Linear power supplies CP-L range. Content

Three-phase monitoring relay CM-PBE

Three-phase monitoring relay CM-PFS

Transcription:

Current Monitoring Relay Data Sheet 08/2004 Functions Structure Current monitoring of direct and alternating current in 1-phase networks with settable threshold values, starting override and response delay that can be set separately, fault memory and the following functions that can be selected with the rotary switch: OVER overcurrent monitoring UNDER undercurrent monitoring WIN monitoring of the range between the thresholds MIN and MAX Figure 1 Structure 1 LED: Supply U 2 LED: Threshold value MAX 3 LED: Threshold value MIN 4 LED: Output relay R 5 Potentiometer START starting override 6 Potentiometer MAX 7 Potentiometer MIN 8 Potentiometer DELAY response delay 9 Rotary switch function 10 Snap-on foot 102057_00_en 1

Technical Data Power Supply Supply voltage Connection terminal blocks (electrically isolated) Tolerance Nominal frequency 24 V 240 V AC/DC A1 - A2-15%... +10% AC / -20%... +25% DC 48 Hz... 400 Hz on request 16.6 Hz Nominal operational power 4.5 VA (1.5 W) Measuring Input Time setting range for starting override 0 s 10 s Time setting range for response delay 0.1 s 10 s Measured value DC, AC sinus (16.6 Hz 400 Hz) Measuring input 100 ma AC/DC 1 A AC/DC 10 A AC/DC Connection terminal blocks GND - I1(+) GND - I2(+) GND - I3(+) Overload capacity 800 ma 3 A 12 A Input resistance 470 mω 47 mω 5 mω Switching threshold max. (relative to I N ) min. (relative to I N ) 10% 100% 5%... 95% Accuracy Basic accuracy of scale end value ±5% Setting accuracy of scale end value 5% Repeat accuracy 2% Temperature influence 0.1%/K 2 102057_00_en

Contact Side (Output) Contact type Rated voltage in accordance with IEC 60664-1 Switching capacity device mounted in row (spacing < 5 mm) device not mounted in row (spacing > 5 mm) Fusing Mechanical service life Electrical service life (ohmic load 1000 VA) Switching rate in accordance with IEC 60947-5-1 max. (with ohmic load 100 VA) max. (with ohmic load 1000 VA) Floating PDT (2x) 250 V AC 750 VA (3 A/250 V AC) 1250 VA (5 A/250 V AC) 5 A fast 20 x 10 6 cycles 2 x 10 5 cycles 60/min. 6/min. Climatic Data Ambient temperature operation (IEC 60068-1/UL 508) -25 C +55 C / -25 C +40 C (-13 F... 131 F / -13 F... 104 F) storage -25 C +70 C (-13 F... 158 F) Relative humidity 15% 85% Climatic class in accordance with IEC 60721-3-3 3K3 Contamination class in accordance with IEC 60664-1 3 General Data Duty cycle 100% Recovery time 500 ms Surge voltage category in accordance with III IEC 60664-1 Rated surge voltage 4 kv Indicators Supply voltage applied: green LED Starting override: green LED Position of output relay: yellow LED Error in corresponding threshold: red LED Response delay in corresponding threshold: red LED ON Flashes ON / OFF ON / OFF Flashes 102057_00_en 3

Housing Material Polyamide PA 6.6, self-extinguishing Degree of protection IP40 Mounting On 35 mm DIN rails in accordance with EN 60715-35 Installation position As desired Dimensions (W x H x D) 22.5 mm x 90 mm x 113 mm (0.886 in. x 3.543 in. x 4.449 in.) Weight approx. 160 g Connection Terminal Blocks Touch-proof Degree of protection Torque, max. Conductor cross section with/without ferrule without ferrule with/without ferrule flexible without ferrule Yes IP20 1 Nm 1 x 0.5 2.5 mm 2 (AWG 20... 14) 1 x 4 mm 2 (AWG 12) 2 x 0.5 mm 1.5 mm 2 (AWG 20... 16) 2 x 2.5 mm 2 (AWG 14) Ordering Data Description Order Designation Order No. Current monitoring relay 28 66 02 2 4 102057_00_en

Installation Connection Examples Danger of fatal injury! Never carry out work on live parts! The monitoring module can be snapped onto all 35 mm DIN rails in accordance with EN 60715-35. An integrated wide range power supply unit allows voltage in the range of 24 V AC/DC to 240 V AC/DC to be connected. Circuit Diagram Figure 3 Measuring range 100 ma (I1) Figure 2 Circuit diagram Figure 4 Measuring range 1 A (I2) 102057_00_en 5

Figure 5 Measuring range 10 A (I3) Functional Description When supply voltage U is applied, output relay R picks up (yellow LED REL lights up) and the start override (START) begins its count down (green LED U flashes). During start override, changes in the measured current have no effect on the position of the output relay. Once the start override duration has expired, the green LED U remains permanently lit. LEDs MIN and MAX flash alternately for all functions if the minimum value selected for the measured current is greater than the maximum value. The desired function is set with the rotary switch (Figure 6): O = Overcurrent monitoring OVER U = Undercurrent monitoring UNDER W = Window function WIN / monitoring of the range between the thresholds MIN and MAX WL = WIN + LATCH / monitoring of the range between the thresholds MIN and MAX with fault memory UL = UNDER + LATCH / undercurrent monitoring with fault memory OL = OVER + LATCH / overcurrent monitoring with fault memory Figure 6 Rotary switch 6 102057_00_en

Overcurrent Monitoring OVER, OVER + LATCH Undercurrent Monitoring UNDER, UNDER + LATCH Figure 7 Overcurrent monitoring OVER, OVER + LATCH When the measured current exceeds the value set on the MAX regulator, the response delay (DELAY) starts to elapse (red LED MAX flashes). When the response delay has elapsed (red LED MAX lights up), output relay R drops out (yellow LED REL does not light up). If the measured current falls below the value set on the MIN regulator (red LED MAX does not light up), the output relay R picks up again (yellow LED REL lights up). If the fault memory is activated (OVER + LATCH) and the measured current has exceeded the value set on the MAX regulator by longer than the response delay set, output relay R does not pick up if the current sinks below the value set on the MIN regulator. After clearing the error (interrupting the supply voltage), output relay R picks up when the supply voltage is reconnected and the measuring cycle begins again after the start override duration has expired (START). Figure 8 Undercurrent monitoring UNDER, UNDER + LATCH When the measured current falls below the value set on the MIN regulator, the response delay (DELAY) starts to elapse (red LED MIN flashes). When the response delay has elapsed (red LED MIN lights up), output relay R drops out (yellow LED REL does not light up). If the measured current falls below the value set on the MAX regulator, the output relay R picks up again (yellow LED REL lights up). If the fault memory is activated (UNDER + LATCH) and the measured current has dropped below the value set on the MIN regulator for longer than the response delay set, output relay R does not pick up if the current exceeds the value set on the MAX regulator. After clearing the error (interrupting the supply voltage), output relay R picks up when the supply voltage is reconnected and the measuring cycle begins again after the start override duration has expired (START). 102057_00_en 7

Window Function WIN, WIN + LATCH If the fault memory is activated (WIN + LATCH) and the measured current has dropped below the value set on the MIN regulator for longer than the response delay set, output relay R does not pick up if the minimum value is exceeded. If the measured current has exceeded the value set on the MAX regulator by longer than the response delay set, output relay R also does not pick up if the current sinks below the maximum value. After clearing the error (interrupting the supply voltage), output relay R picks up when the supply voltage is reconnected and the measuring cycle begins again after the start override duration has expired (START). Figure 9 Window function WIN, WIN + LATCH The output relay R picks up (yellow LED REL lights up) if the measured current exceeds the value set on the MIN regulator. When the measured current exceeds the value set on the MAX regulator, the response delay (DELAY) starts to elapse (red LED MAX flashes). When the response delay has elapsed (red LED MAX lights up), output relay R drops out (yellow LED REL does not light up). The output relay R picks up again (yellow LED REL lights up) when the measured current drops below the maximum value again (red LED MAX does not light up). If the measured current falls below the value set on the MIN regulator, the response delay (DELAY) starts to elapse (red LED MIN flashes). When the response delay has elapsed (red LED MIN lights up), output relay R drops out (yellow LED REL does not light up). 8 102057_00_en

Make sure you always use the latest documentation. It can be downloaded at www.phoenixcontact.com. Phoenix Contact GmbH & Co. KG Flachsmarktstr. 8 32825 Blomberg Germany + 49 - (0) 52 35-3-00 + 49 - (0) 52 35-3-4 12 00 www.phoenixcontact.com Worldwide Locations: www.phoenixcontact.com/salesnetwork Phoenix Contact 08/2004 Technical modifications reserved 9 102057_00_en