Session 2002 CIGRÉ. Evaluation of Lightning Location Data Employing Measurements of Direct Strikes to a Radio Tower

Similar documents
Review of CIGRE Report Cloud-to-Ground Lightning Parameters Derived from Lightning Location Systems The Effects of System Performance

Close and Distant Electric Fields due to Lightning Attaching to the Gaisberg Tower

LOCATION ACCURACY EVALUTION OF THE AUSTRIAN LIGHTNING LOCATION SYSTEMS ALDIS

Paper presented at the Int. Lightning Detection Conference, Tucson, Nov. 1996

Evaluation for the performance of the Guangdong- Hongkong-Macau Lightning Location System

EUCLID NETWORK PERFORMANCE AND DATA ANALYSIS

Simultaneous Records of Current and 380-km Distant Electric Field of a Bipolar Lightning Flash

A Contribution to the Direct Measurement of Lightning Currents by Means of Resistive Transducers

Performance Evaluation for a Lightning Location System Based on Observations of Artificially Triggered Lightning and Natural Lightning Flashes

THREE UNUSUAL UPWARD POSITIVE LIGHTNING TRIGGERED BY OTHER NEARBY LIGHTNING DISCHARGE ACTIVITY

An Update on the Performance Characteristics of the NLDN

PERFORMANCE CHARACTERISTICS OF THREE DISTINCT LIGHTNING DETECTION NETWORKS COVERING BELGIUM

Initial-stage pulses in upward lightning: Leader/return stroke versus M-component mode of charge transfer to ground

ELECTRIC FIELD WAVEFORMS OF UPWARD LIGHTNING FORMING HOT SPOT IN WINTER IN JAPAN

PUBLICATIONS. Journal of Geophysical Research: Atmospheres

MULTI-STATION SHORT BASELINE LIGHTNING MONITORING SYSTEM

IMPROVEMENTS OF THE FACILITIES FOR LIGHTNING RESEARCH AT MORRO DO CACHIMBO STATION

Electric and magnetic fields and field derivatives from lightning stepped leaders and first return strokes measured at distances from 100 to 1000 m

Early phase of lightning currents measured in a short tower associated with direct and nearby lightning strikes

Lightning current waves measured at short instrumented towers: The influence of sensor position

Observing Lightning Around the Globe from the Surface

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

Method to Improve Location Accuracy of the GLD360

Positive lightning flashes recorded on the Säntis tower from May 2010 to January 2012

PROFEO : PROGRAMME FRANCILIEN D ETUDES DES ORAGES. P. Blanchet, P. Lalande, P. Laroche Onera Châtillon France

Characteristics of a Negative Cloud-to-Ground Lightning Discharge Based on Locations of VHF Radiation Sources

CIGRE C4 Colloquium on Lightning and Power System, Kuala Lumpur, May, Establishment of a new lightning location system in Croatia

-149- MICROSECOND-SCALE ELECTRIC FIELD PULSES IN CLOUD LIGHTNING FLASHES

The Effect of Lightning Parameters on Induced Voltages Caused by Nearby Lightning on Overhead Distribution Conducting Line.

CHAPTER CONTENTS REFERENCES AND FURTHER READING Page

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

Data Analysis for Lightning Electromagnetics

Location Accuracy Improvements using Propagation Corrections: A Case Study of the U.S. National Lightning Detection Network

Flash Density Maps of Serbia for

THE THIRD GENERATION RELATIVE DETECTION EFFICIENCY MODEL FOR THE BRAZILIAN LIGHTNING DETECTION NETWORK (BRASILDAT)

A Review of Advances in Lightning Observations during the Past Decade in Guangdong, China

Insights into the ground attachment process of natural lightning gained from an unusual triggered-lightning stroke

GEOPHYSICAL RESEARCH LETTERS, VOL. 37, L05805, doi: /2009gl042065, 2010

COMPACT INTRACLOUD DISCHARGES: ON ESTIMATION OF PEAK CURRENTS FROM MEASURED ELECTROMAGNETIC FIELDS

Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations

GENERATION 4 HARDWARE

The Lightning Event. White Paper

OVERVOLTAGE MEASUREMENTS RELATED TO LIGHTNING- DETECTION SYSTEMS IN NORWAY

2520 Pulsed Laser Diode Test System

PUBLICATIONS. Journal of Geophysical Research: Atmospheres

Lightning and Lightning Arrester Simulation in Electrical Power Distribution Systems

Development Progress of Dual-band Lightning Locating System

The impact of recent advances on lightning measurement and detection on the protection of transmission and distribution lines

Why do some lightning return stroke models not reproduce the far-field zero crossing?

Electric fields near triggered lightning channels measured with Pockels sensors

Triggered-Lightning Testing of the Protective System of a Residential Building: 2004 and 2005 Results

Immunity Testing for the CE Mark

Lightning transient analysis in wind turbine blades

Effect of Soil Resistivity on Magnetic Field in the case of Lightning Strike to a Tall Structure

Matching and Locating of Cloud to Ground Lightning Discharges

Lightning Protection for Cellular Tower Mounted Electronics

Measurement of the Division of Lightning Return Stroke Current Among the Multiple Arresters and Grounds of a Power Distribution Line

Power Quality Measurements the Importance of Traceable Calibration

Chapter 1 Introduction

Return stroke peak current versus charge transfer in rocket triggered lightning

Lightning Flashover Rate of an Overhead Transmission Line Protected by Surge Arresters

PHYSICS 330 LAB Operational Amplifier Frequency Response

Lightning Warning System Carlos A. Morales 1, João R. Neves 1, Evandro M. Anselmo 1, Marcio A. Mathias 2, Cesar S. Rabak 3 and Keyla Sampaio Camara 4

The line-lightning performance and mitigation studies of shielded steelstructure

Simultaneously measured current, luminosity, and electric field pulses in a rocket triggered lightning flash

Estimating the Lightning Performance of a Multi- Circuit Transmission Tower

CHAPTER -15. Communication Systems

Electromagnetic Shielding Analysis of Buildings Under Power Lines Hit by Lightning

STJ-100 TMR Magnetic Microsensor Dual In-line Package

CS110 Electric Field Meter Overview

What is the Value of a Distribution Arrester

Pulsed Measurement Capability of Copper Mountain Technologies VNAs

HIGH VOLTAGE Insulation Coordination

Return Stroke VLF Electromagnetic Wave of Oblique Lightning Channel

CHAPTER 6 DIGITAL INSTRUMENTS

Fluke Three-Phase Power Quality Recorder Topas. Class-A compliance for the most demanding power quality tests

C4-301 EXPERIMENTAL EVALUATION OF TRANSFERRED SURGES IN MV TRANSFORMERS FROM HV/LV

Notes on OR Data Math Function

PD Solutions. On-Line PD Measurement Devices

STJ-300 Single-Axis Magnetic Sensor Dual In-line Package

Abstract. 1 Introduction

Parameter Optimization for Rise Time of Sub nanosecond Pulser Based on Avalanche Transistors

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location

Imaging Lightning Progression Using VHF Broadband Radio Interferometry

Lightning Interferometer via VHF Emission (LIVE)

Coaxial Cable Protection

Modeling of Lightning Direct Effects Interaction of Continuing Current with Aluminum Skins

Correlation Considerations: Real HBM to TLP and HBM Testers

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Dev Bhoomi Institute Of Technology Department of Electronics and Communication Engineering PRACTICAL INSTRUCTION SHEET

Properties of unipolar magnetic field pulse trains generated by lightning discharges

DIRECT CURRENT COMPENSATION FIELD EXPERIENCE UNDER SERVICE CONDITIONS

University of Zagreb Faculty of Electrical Engineering and Computing

Performance Characteristics of Distinct Lightning Detection Networks Covering Belgium

Performance of the Prototype NLC RF Phase and Timing Distribution System *

Rec. ITU-R P RECOMMENDATION ITU-R P *

Infrasound pulses from lightning and electrostatic field changes: Observation and discussion

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

Positioning by an Active GPS System: Experimental Investigation of the Attainable Accuracy. Werner LIENHART, Andreas WIESER, Fritz K.

Transcription:

21, rue d'artois, F-75008 Paris http://www.cigre.org 33-206 Session 2002 CIGRÉ Evaluation of Lightning Location Data Employing Measurements of Direct Strikes to a Radio Tower G. Diendorfer 1, W. Hadrian 2, F. Hofbauer 3, M. Mair 2, W. Schulz 1 1 ALDIS, 2 Techn. Univ. Vienna, 3 Verbund Austria ABSTRACT A Lightning Location Systems (LLS) provides large scale information for lightning strikes to ground. In addition to the event time and strike point position, the LLS gives estimates for the lighting peak current. For the end user of LLS data it is important to know the technical limits of the applied network in terms of detection efficiency, accuracy of the stroke location and peak current estimate. To establish a ground truth reference for comparison of natural lightning current parameters and the data of ALDIS (Austrian Lightning Detection & Information System), a telecommunication tower on Gaisberg near the city of Salzburg (Austria) was instrumented for direct lightning current measurement. Since the start of the tower experiment in 1998 we have recorded more than 200 lightning flashes to the tower. Based on the analysis of the current waveforms nearly all of them are so called upward initiated discharges. GPS time synchronization of both data sets allows a precise correlation of individual events measured at the tower and reported by the lightning location network. Detection efficiency (DE) During the years 2000 and 2001 we have recorded 463 strokes to the tower with peak currents greater than 2kA. Correlation with the ALDIS data shows that the flash DE of the location system is about 94% for flashes with a at least one stroke with an amplitude exceeding 5 ka. The DE depends on the presence of current pulses of sufficient peak amplitude and di/dt. Only current pulses with sufficient electromagnetic field radiation are detected by sensors of the LLS at distances of more than 100 km. Some of the upward initiated discharges - which are typical for high towers and other elevated objects - only showed continuing current wave shapes without any pronounced current pulses. Location accuracy Distance between the strike point position determined by ALDIS and the ground truth position of the tower are in the range of some hundred meters. We observe a systematic shift of the calculated locations to the north-east by about 500 m with a median distance of 450 m. Peak current estimate Peak current estimate of a LLS is based on remotely measured peak fields. For the 295 strokes located during 2000 and 2001 we determined a relation I_ALDIS = 0,95*I_TOWER (r= 0,95). Therefore on average differences of LLS peak currents and directly measured peak currents are in the range of measuring errors of both systems. This raises the question, why the median value of the peak current distribution determined by ALDIS over a large area in Austria is in the range of 12 ka, whereas the median value specified in many lightning standards is as high as 30 ka. Keeping in mind, that the distribution of lightning peak currents is one of the most fundamental input parameters in all kind of lightning protection analysis and insulation coordination, a reexamination of lightning peak current parameters in existing standards seems to be necessary. 1. ITRODUCTIO The use of data from lightning detection networks by power utilities and other operators of large network (e.g.telecommunication) has increased heavily over the last decade. Today lightning location networks provide real-time information about the lightning activity as well as historical data for past time failure analysis. Lightning location is a complex subject where the quality of data provided to the end user is effected by various parameters like the employed type of location sensors, the setup OVE-ALDIS, Kahlenberger Str. 2a, A-1190 Vienna, Austria, Phone: +43-1-370 58 06-215, E-mail: g.diendorfer@ove.at

parameters of the central analyzer and effects to lightning electromagnetic fields propagation over ground of finite conductivity. For an appropriate application of data from LLS by the user it is important to know the performance limits of the used location system. In literature we can find data for peak current distributions, flash density maps, values for maximum lightning peak currents from various location systems that are often quite different in their mean values and maximum detected peak currents. In this paper we will mainly focus on the three major performance parameters of a LLS as (1) detection efficiency (DE), (2) location accuracy (LA) and (3) accuracy of peak current estimate. We limit our analysis to the magnetic direction finding (MDF) and time of arrival (TOA) technology used by the sensor types IMPACT, LPATS III and LPATS IV, respectively, manufactured by Global Atmospherics Inc. (GAI), Tucson, although other commercial and/or experimental systems exist. Many networks of this manufacturer of different size (a few sensors up to large scale networks of more than 100 sensors) are installed in various countries all over the world. dependency of the DE from peak current amplitude was observed. 2. DIRECT LIGHTIG CURRET MEASUREMET In 1998 we started in Austria to measure currents when lightning strikes a radio tower (Fig.1). The radio tower on Gaisberg with a height of about 100 m is located 1287 m above sea level about 5 km east of the city of Salzburg. This tower was selected because analysis of historical data from the lightning location system ALDIS showed a flash rate of about 40 50 flashes per year to the tower. The distances to the 8 IMPACT sensors of the ALDIS system are in the range from 32 km to 261 km. To the north-west several LPATS sensors of the German LLS BLIDS are installed and participate frequently in the location of lightning strikes to the tower. The overall setup of the measurement system for direct lightning current registration is shown in Fig.2. An appropriate air termination was installed on top of the tower in order to capture most of the lightning discharges to the tower (Fig.3). The lightning current is measured at the base of the air termination by a wide band current viewing resistor (shunt) of 0.25 mω with a bandwidth of 0 Hz to 3.2 MHz, manufactured by T&M Research Products Inc. A fiber optic link for data transmission and the recording system were installed in a building next to the tower. Current viewing resistor E/0 Highspeed video system Field mill E/0 Modem GPS receiver GPS receiver. 200 m Fig.1: Gaisberg Tower In the past different approaches have been made to evaluate the performance of LLS. As an example IDOE et al. (1998a) used a large set of video observations of cloud-to-ground lightning. A strong Fig.2: Schematic overview of the experimental measuring setup at Gaisberg tower (E/O: Electrical/Optical signal converter).

Air termination system Shunt 0.25 mohm Electrical/Optical Converter Fig.3: Installed equipment on the tower top Due to the wide range of expected current peak amplitudes two separate fiber optic channels of different sensitivity are installed: Channel 1: 0-2.1 ka Channel 2: 0-40 ka The shunt output signal is recorded by an 8 bit digitizing board installed in a Personal Computer. The digitizing board (ational Instruments PCI- 5102) with a bandwidth of 15 MHz and a memory of 16 MB per channel is operated with a sampling rate of 20 MS/s. The trigger of the recording system is set to a corresponding lightning current level of ±200A. All recorded waveforms are time stamped using the time information provided by a GPS clock (Meinberg GPS167PC) in order to be able to time correlate them with the data from the lightning location system. GPS timing is appropriate to identify correspondence of individual strokes recorded at the tower and located by ALDIS. In summer 1999 some additional measurement equipment for recording the static atmospheric electric field (field mill) and a high-speed video system was installed at a distance of about 200 m from the tower (Fig.2). than 90% and the projected location accuracy is better than 500 m all over Austria. 4. AALYSIS OF THE DETECTIO EFFICIECY The objective is to establish the flash and stroke DE of ALDIS for the lightning strikes to the instrumented tower. It is worth to note that elevated objects like the radio tower experience primarily upward initiated discharges similar to rocket-triggered lightning. Typical for this upward initiated discharges is a so called initial continuing current (ICC) with a duration of some hundred milliseconds and an amplitude of some tens to some hundred of amperes, often followed by one ore more downward leader - upward return stroke sequences. There is still the question of whether current pulses occurring during the ICC stage, that is, pulses superimposed on the long-lasting, lowlevel continuous current, are due to return strokes or due to an M-component-type lightning process. In many of the upward initiated discharges all the superimposed current pulses have amplitudes of a few hundred amperes up to 1-2 ka. Often these current pulses of even higher amplitudes show a very slow rising front and therefore do not radiate electromagnetic field pulses of sufficient magnitude to be detected by the LLS-sensors (see Fig.4). 100 ms 500 A Fig. 4a: ICC-current with 5 ICC pulses flash #182 3. ALDIS SYSTEM The Austrian Lightning Detection & Information System (ALDIS) started operation in 1992. A comprehensive description of the ALDIS network can be found in Diendorfer et al. (1998). Today eight IMPACT type sensors provide coverage of the Austrian territory. Since 1998 ALDIS participates in the European Cooperation for Lightning Detection (EUCLID), a network of about 100 sensors in 14 countries all over Europe. Projected Detection Efficiency (DE) of the EUCLID network is better 500 A Meas.-Limit Fig. 4b: ICC-pulse # 3 I peak = -3 ka 500 µs

Fig. 4c: ICC-pulse # 5 I peak = -1,2 ka In our evaluation of the DE of the LLS therefore in a first step we have selected directly measured strokes to the tower with amplitudes greater than 2 ka. Only strokes of negative polarity are considered, because very few discharges to the tower have been either of positive polarity or showed bipolar pulses. In Table 1 the results of a comparison to the parameters of directly measured lightning current pulses and the time correlated data reported by ALDIS are summarized. The analysis was done for directly measured minimum peak currents of 2kA, 4kA, 6kA, 8kA and 10 ka respectively. Table 1: umber of flashes/strokes measured at the tower and located by ALDIS in year 2000 and 2001 (Fl...Flashes, St...Strokes) Tower 500 µs ALDIS 200 A I_min [ka] Fl. St. Fl. St. DE Fl. DE St. 2 77 463 66 296 86% 64% 4 68 365 63 282 93% 77% 6 62 272 58 234 94% 86% 8 51 206 50 187 98% 91% 10 47 147 46 137 98% 93% Obviously from Table1 and Fig.5 the LLS has a DE of 94% for flashes with at least one stroke of a peak current amplitude greater then 6 ka. As expected the stoke DE is smaller than the flash DE and is 86% for all strokes of peak currents greater than 6 ka. For the detection of a flash with several strokes it is sufficient to detect at least one of the strokes. When we lower in our analysis the minimum peak current of a stroke to 2 ka the Flash DE reduces to 86%, whereas the Stroke DE reduces to 64%. The reason is, that several small peak current strokes that are detected by only one or two sensors close to the tower site, don t provide sufficient information for a location and therefore are missed by the LLS. DE 100% 80% 60% 40% 20% 0% Fig.5: 86% 64% 93% 94% 86% 77% 98% 98% 91% 93% Flash DE Stroke DE 2 4 6 8 10 I_min in [ka] ALDIS flash and stroke detection efficiency as a function of minimum peak current These results are similar to those reported by IDOE et al. (1998), where also a steadily drop of likelihood of detection with decreasing current was observed. When strokes of less than 4 ka were excluded, the ALDIS flash DE of 93% (I_min > 4kA) is significantly higher than the flash DE of 84% for the LD reported by IDOE at al.(1998). This higher flash DE is most likely a result of the shorter baselines between sensors in the ALDIS network which provide a higher sensitivity of the network to small electromagnetic field pulses. We have to note, that a high fraction of the directly measured strokes with amplitudes between 2 ka and 10 ka not located by ALDIS exhibit waveforms very similar to the current pulse shown in Fig. 4b with a maximum di/dt values of less than 2-3 ka/µs. This current wave shape with its slow rising front is expected to radiate an electromagnetic field pulse of insufficient amplitude to be detected by two or more sensors at distances of more than 100 km. 5. AALYSIS OF THE LOCATIO ACCURACY The radio tower provides a perfect ground truth reference for the evaluation of the location accuracy. In Fig.6 we have plotted the striking point locations provided by ALDIS for the set of correlated strokes to the tower.

1000 500 0-1000 -500 0 500 1000 Fig.6: -500-1000 Plot of ALDIS locations for correlated strokes - the tower is located in the origin As shown in Fig.6 the majority of the ALDIS locations are shifted to the north-east from the tower location (0/0) by about 500 m. The source of this systematic error in the locations is still unknown. The corresponding distribution of location distances is shown in Fig.7. The resulting median value of 450 meters is within the expected location accuracy range of 500 meters. Percentage Fig.7: 12% 10% 8% 6% 4% 2% 0% 0 200 400 600 800 Merdian = 450 m = 285 1000 1200 Distance im [m] 1400 1600 1800 Distribution of distances between ALDIS location and tower site In case of a successful elimination of the systematic shift of locations to the north-east the median value of location error could be reduced to about 200 m. 6. AALYSIS OF THE PEAK CURRET ESTIMATES Estimation of the lightning peak current by ALDIS is based on a range-normalized electromagnetic field pulse amplitude S n i p = 0,23. S n 2000 where i p is the lightning peak current in ka and S n is the mean of the signal strengths from the DF's participating in the location in LLP-units rangenormalized to 100 km. The coefficient 0.23 is the standard setting proposed by the manufacturer for a high-gain network. To test the validity of the above mentioned relation between electromagnetic field pulses measured by the sensor and the estimated peak current amplitude, we have plotted in Fig.8 the directly measured peak currents I_TOWER versus the peak amplitudes reported by ALDIS. Calculation of a linear regression line results in I_ALDIS = 0,95*I_TOWER with a correlation coefficient r = 0,954, with the fit forced to go through the origin. I_ALDIS [ka] 40 30 20 10 0 Fig.8: I_ALDIS = 0.95 * I_TOWER = 295 r = 0.954 2000/2001 Data 0 10 20 30 40 I_TOWER [ka] Comparison of directly measured currents I_TOWER with the current estimates from ALDIS OTE: Absolute values of negative stroke peak currents are plotted This result shows, that on average ALDIS underestimates the lightning peak current amplitude by about 5% compared to the directly measured current amplitude at the instrumented tower. This is within the range of the estimated accuracy of the current measurement system (+/- 10%). Considering this evidence of an acceptable estimate of peak current by ALDIS raises the question how the observed significant differences between the distribution of lightning peak currents reported by ALDIS and the peak current distribution specified by CIGRE (e.g. Anderson et al. 1980) shown in Fig. 9 could be explained.

Cumultive Frequency 100% 80% 60% 40% 20% 0% ALDIS CIGRE 0 20 40 60 80 100 Amplitude in [ka] Lightning Location Systems provide a full set of information about several parameters of natural lightning discharges to ground over large areas. This is the only type of lightning relevant for general lightning protection issues. In all our discussions about the validity of data from LLS we have also to be aware of the limitations and possible errors in the data from historical experiments. Some of these experiments have been performed decades ago with measuring equipment much different from what is available today. owadays fiber optic communication, high speed digitizers and GPS time synchronization is available for experiments in an extreme electromagnetic environment existing nearby the lightning channel. Fig.9: CIGRE: Median 30 ka, Sigma-log 0,32 ALDIS: Median 12 ka, 98%-value 58 ka Differences between lightning peak current distributions specified by CIGRE and provided by ALDIS for neg. discharges The peak current distribution reported by ALDIS for first strokes in negative flashes in 1995-1997 with a median value of about 12 ka and a 98%-value of 58 ka is much different from the CIGRE distribution with a median of 30 ka. We do not see any reason that could explain such a big difference by the performance of the location system. When ALDIS is within an accuracy of 10% for strokes to the Gaisberg tower, why should there be an error of about 100% and more for strokes to ground all over the country. Keeping in mind the importance of peak current distributions for different areas of lightning protection and insulation coordination a reexamination of lightning parameters seems appropriate. DISCUSSIO Systematic comparison of directly measured lightning peak currents with the corresponding reports from a LLS provides some insight in the performance of a location system. LLS have developed over the last decades to a new valuable source of information about lightning activity and individual stroke parameters. Tower measurements and triggered lightning experiments are always limited to single stations and a more specific type of lightning (upward initiated). We conclude from our analysis, that there is still a number of open questions to be addressed like the performance of LLS for positive lightning. We are convinced that a combined evaluation of data from triggered lightning, tower measurements and LLS will help to make some steps forward to provide a better understanding of the lightning phenomenon. Acknowledgements The Gaisberg tower experiment is supported by VERBUD and KELAG (contract V08/4500021357), by the Austrian Science Fund (Project r. P12977-TEC) and by Hochschuljubiläumsstiftung der Stadt Wien (Project H77/98). The authors would also like to thank the staff of the Austrian Broadcasting Corporation (ORF) for their support and hospitality at the tower site. References: IDOE, V. P. ; DAVIS, D. A. ; MOORE, P. K. ; WAG, Y. ; HEDERSO, R. W. ; RIES, M. ; JAMASO, P. F. Performance evaluation of the U. S. ational Lightning Detection etwork in eastern ew York, 1, Detection efficiency. J. Geophys. Res. Vol. 103, o. D8, p. 9045, 1998 DIEDORFER G., SCHULZ W., RAKOV A.V.: Lightning Characteristics Based on Data from the Austrian Lightning Locating System. IEEE Transactions on Electromagnetic Compatibility (EMC), Vol. 40, o. 4, ov. 1998