Buletinul AGIR nr. 3/2012 iunie-august

Similar documents
Electromagnetic Shielding Analysis of Buildings Under Power Lines Hit by Lightning

APPLICATION OF THE ELECTROMAGNETIC FIELD METHOD TO STUDY A COMMUNICATION SATELLITE SITE DAMAGED BY LIGHTNING

3 Using AutoTransient to Carry Out a Simple Transient Study

ARTICLE IN PRESS. Lightning effects in the vicinity of elevated structures. F.H. Silveira, S. Visacro

SCIENCE & TECHNOLOGY

EVALUATION OF LIGHTNING-INDUCED VOLTAGES ON LOW-VOLTAGE DISTRIBUTION NETWORKS

DRIVEN ASYNCHRONOUS MOTORS

The Effect of Lightning Parameters on Induced Voltages Caused by Nearby Lightning on Overhead Distribution Conducting Line.

Fig.1. Railway signal system

Lightning current waves measured at short instrumented towers: The influence of sensor position

INFLUENCE FACTORS ON THE TRANSMITTED OVERVOLTAGES FROM HIGH VOLTAGE TO LOW VOLTAGE NETWORKS

Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line

Experimental Investigation and Numerical Modeling of Surge Currents in Lightning Protection System of a Small Residential Structure

Earthing of Electrical Devices and Safety

Effect of Soil Resistivity on Magnetic Field in the case of Lightning Strike to a Tall Structure

Lightning transient analysis in wind turbine blades

Article information: Access to this document was granted through an Emerald subscription provided by Emerald Author Access

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

High Voltage Induced By Transmission Lines Due To Lightning Case Study

Investigation on the Performance of Different Lightning Protection System Designs

An Approximate Formula for Estimating the Peak Value of Lightning-Induced Overvoltage Considering the Stratified Conducting Ground

SAG MITTIGATION TECHNICS USING DSTATCOMS

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

ATP SIMULATION OF FARADAY CAGE FOR THE ANALYSIS OF LIGHTNING SURGES

Analysis of the Electromagnetic Interferences between Overhead Power Lines and Buried Pipelines

MODERN COMPUTATIONAL METHODS FOR THE DESIGN AND ANALYSIS OF POWER SYSTEM GROUNDING

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

ELECTRIC FIELD WAVEFORMS OF UPWARD LIGHTNING FORMING HOT SPOT IN WINTER IN JAPAN

Why do some lightning return stroke models not reproduce the far-field zero crossing?

Close and Distant Electric Fields due to Lightning Attaching to the Gaisberg Tower

University of Zagreb Faculty of Electrical Engineering and Computing

ABSTRACT 1 INTRODUCTION

ACCURATE SIMULATION OF AC INTERFERENCE CAUSED BY ELECTRICAL POWER LINES: A PARAMETRIC ANALYSIS

THREE UNUSUAL UPWARD POSITIVE LIGHTNING TRIGGERED BY OTHER NEARBY LIGHTNING DISCHARGE ACTIVITY

X International Symposium on Lightning Protection

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

PUBLICATIONS. Journal of Geophysical Research: Atmospheres

About the High-Frequency Interferences produced in Systems including PWM and AC Motors

Electric Power Systems Research

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

Overview of EMC Regulations and Testing. Prof. Tzong-Lin Wu Department of Electrical Engineering National Taiwan University

FDTD-Based Lightning Surge Simulation of a Microwave Relay Station

Electricity Supply to Africa and Developing Economies. Challenges and opportunities. Technology solutions and innovations for developing economies

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

The Lightning Event. White Paper

A Simple Wideband Transmission Line Model

The Simulation Experiments on Impulse Characteristics of Tower Grounding Devices in Layered Soil

Research on State Estimation and Information Processing Method for Intelligent Substation

Return Stroke VLF Electromagnetic Wave of Oblique Lightning Channel

FDTD Analysis of Distribution Line Voltages Induced by Inclined Lightning Channel

Optimization of Layer Thickness to Yield Predetermined Shielding Performance of Multilayer Conductor Electromagnetic Shield

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

Grounding Strategies for Solar PV Panels

Simultaneous Records of Current and 380-km Distant Electric Field of a Bipolar Lightning Flash

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

The Many Uses of Transmission Line Arresters

ABSTRACTS of SESSION 6

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

ADVANCED MODELING IN COMPUTATIONAL ELECTROMAGNETIC COMPATIBILITY

EVALUATION OF THE EARTH RESISTANCE VALUE FOR ESE LIGHTNING ARRESTOR TECHNIQUE FOR THE SOLAR PLANTS IN INDIA

Simulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines

Transmission of Electrical Energy

The Role of the Grounding System in Electronics Lightning Protection

SURGE PROPAGATION AND PROTECTION OF UNDERGROUND DISTRIBUTION CABLES

OVERVOLTAGE MEASUREMENTS RELATED TO LIGHTNING- DETECTION SYSTEMS IN NORWAY

Understanding and Optimizing Electromagnetic Compatibility in Switchmode Power Supplies

Square Planar Spiral Inductor High Frequency Field and Parameters Analysis

ANALYSIS OF DISTURBING MAGNETIC FIELD ASSOCIATED WITH ELECTROSTATIC DISCHARGES

Lightning performance of a HV/MV substation

Comparison of Two Computational Programs for the Calculation of Lightning-Induced Voltages on Distribution Systems

Paper presented at the Int. Lightning Detection Conference, Tucson, Nov. 1996

IMPROVEMENTS OF THE FACILITIES FOR LIGHTNING RESEARCH AT MORRO DO CACHIMBO STATION

Lightning Performance of Transmission Lines with Tall Sections

Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise

Review of CIGRE Report Cloud-to-Ground Lightning Parameters Derived from Lightning Location Systems The Effects of System Performance

SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING

Electromagnetic Fields Produced by Inclined Return Stroke Channel

ABSTRACT 1.0 INTRODUCTION LIST OF SYMBOLS

The line-lightning performance and mitigation studies of shielded steelstructure

Liquidmetal Electromagnetic Properties & RF Shielding Overview

Lightning Protection: History and Modern Approaches

INTERACTION NOTES NOTE 627. October 2015 STUDY OF THE PROPAGATION OF IEMI SIGNALS ALONG POWER AND COMMUNICATION LINES

M hamed Ouadah 1, 2, *, Omar Touhami 1,andRachidIbtiouen 1

Source: EMP environnement MIL-STD-464

Lightning Protection for Cellular Tower Mounted Electronics

Lightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System

A NEW METHOD FOR CALCULATING TRANSIENT ELECTROMAGNETIC RESPONSES OF AC/DC POWER SYSTEM WITH EXTERNAL ELECTROMAGNETIC PULSE INTERFERENCE

INTEGRATED METHOD IN ELECTROMAGNETIC INTERFERENCE STUDIES

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

Electromagnetic and Radio Frequency Interference (EMI/RFI) Considerations For Nuclear Power Plant Upgrades

Computation of Lightning Impulse Backflashover Outages Rates on High Voltage Transmission Lines

Grounding grid design for high voltage substations: An assessment of effectiveness for lightning currents

from ocean to cloud LAND CABLE INTERFERENCE MODEL AND CABLE CROSSINGS WITH POWER INTERCONNECTS

Simulation of Short Circuit and Lightning Transients on 110 kv Overhead and Cable Transmission Lines Using ATP-EMTP

IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, VOL. 47, NO. 3, AUGUST Yoshihiro Baba, Member, IEEE, and Vladimir A. Rakov, Fellow, IEEE

National Radio Astronomy Observatory Socorro, NM EVLA Memorandum 41 Lightning Protection for Fiber Optic Cable. T. Baldwin June 05, 2002

Transcription:

IMPACT EVALUATION OF DIRECT LIGHTNING STRIKE ON A TOWER. GROUND POTENTIAL RISE ALTERNATIVE COMPUTATIONS IMPACT EVALUATION OF DIRECT LIGHTNING STRIKE ON A TOWER. GROUND POTENTIAL RISE ALTERNATIVE COMPUTATIONS Dr. Andrei CECLAN, Prof. Dr. Eng. Vasile ŢOPA, Assoc. Prof. Dr. Eng. Dan Doru MICU, PhD. Stud. Levente CZUMBIL Technical University of Cluj-Napoca, Electrical Engineering Department, Cluj-Napoca, Romania REZUMAT. Orice structură metalică, în special cele înalte de telecomunicaţii, ii, turnuri eoliene sau alt tip de turnuri metalice pot servi ca şi canale de descărcare pentru curenţi de trăsnet de ordinul sutelor de ka şi astfel să conduca la apariţia unor potenţiale electrice periculoase p la nivelul solului. În această lucrare sunt descrise şi ş i evaluate caracteristicile principale ale câmpurilor electrice şi magnetice generate în î n stratul superior al solului lui de diferite tipuri de curenţi de trăsnet care lovesc turnuri metalice. Problema a fost abordată utilizand o platformă de simulari numerice, pentr p entru diferite scenarii - curenţi de trăsnet cu parametri diferiţi, i, geometrii diferite de turnuri, rezistivităţi i diferite de sol,, existenţa sau nu a prizelor de împământare - evaluându-se tensiunea de pas şi câmpul magnetic în î n zona din apropierea turnului lovit. Cuvinte cheie: curent de întoarcere a trăsnetului, tensiune de pas, turn metalic. ABSTRACT. Any metallic structure, especially tall ones like telecommunication, wind or other types of metallic towers can become a discharging channel nel for lightning currents (hundreds of ka) and therefore give rise to potential dangerous events on ground level. In this paper there are described and evaluated the main characteristics of the electric and magnetic fields produced in the upper soil layer by different types of lightning currents flowing through a tall metallic structure, a tower directly hit by lightning. The problem was addressed using the simulation environment of a software package. Simulations were performed for several scenarios, in order o to reflect the influence of analyzed parameters (lightning current shape, tower geometry, soil resistivity and grounding system) over the ground potential rise, step voltages and magnetic fields in the area nearby the stroked tower. Keywords: lightning return stroke current, step voltage, ground potential rise, metallic tower.. INTRODUCTION In the field of electromagnetic compatibility, negative impact of a lightning strike can be divided into direct effects (like the very high increase of temperature onto the hit object, low conductive materials deterioration or injected fault currents) and indirect effects, caused by Lightning Electro-Magnetic Pulse, LEMP low frequency noise, rise of the ground potential or radiated magnetic field that can induce considerable over-voltages [], [2], [3]. This paper approaches the problem of indirect effects of lightning, more precisely the study of Ground Potential Rise, GPR, and radiated magnetic field in the upper soil layer in the area of a metallic tower stroked by lightning. Thus, we adopted an analysis method using the simulation environment provided by a specialized software package from SES-tech, Current Distribution, Electromagnetic interference, Grounding and Soil structure analysis package, CDEGS, by combining two engineering modules, HIFREQ, which is specialized on high frequency electromagnetic fields computation and FFTSES, a module that uses the Fast Fourier Transform to obtain the frequency domain of the lightning surge and the Inverse Fourier Transform to obtain the time domain from the frequency domain of HIFREQ calculated electric and magnetic quantities. With the help of this program there have been evaluated electric potentials, electric and magnetic field intensities, step or GPR voltages produced by different types of lightning strikes in an environment with specific characteristics (soil, atmosphere) [4], []. Regarding the experimental aspects of the present study, it is worth mentioning that the tower configurations were adopted from real cases of telecommunication facilities and mobile phone companies. Also, the soil characteristics are provided from real in situ measurements. For validation purposes, the problem was addressed by an analytical procedure too [6], [7], [8]. 2. PROBLEM DESCRIPTION Through FFTSES module one can define the lightning current in the time domain and calculates its Buletinul AGIR nr. /22 ianuarie-martie 27

WORLD WORLD ENERGY ENERGY SYSTEM SYSTEM CONFERENCE CONFERENCE WESC - WESC 22 frequency spectrum. The software provides a list of lightning return stroke current models (standard type, double exponential type, etc.) characterized by specific parameters (rise time, fraction time, amplitude), as Fig. shows: Fig.. Data input interface for FFTSES. We have selected a time variation of the lightning return stroke current as being described by a standard double exponential equation [9], []: αt βt I( t) = k I ( e e ) () peak where I peak is the current amplitude, k is a correction factor and α, β are parameters associated to a specific rise time t r and a fraction (half peak value in this case) time t /2 (Fig. 2): Fig. 2. Rise and fraction time description. The model - Fast Fourier Transform - that generates the frequency domain of the lightning current is given by the well known relation [4]: + I( ω) = I( t) e dt (2) where I( ω) is the frequency response of the current, where the variable ω represents a number of computed angular frequencies obtained from the time domain current I( t ). Next, with the help of the HIFREQ module there were defined the environment characteristics: atmosphere, soil type, grounding systems and metallic structures; the conductor bars are introduced analytically and have certain selected geometry shapes with associated physical properties coatings, material, energy sources in the metallic bars. Afterwards, the problem is worked out so as to go back to the time domain of the electric and magnetic quantities, HIFREQ frequency domain computations are modulated by the lightning current amplitude in FFTSES and the time domain responses are obtained by means of the Inverse Fourier Transform [4]: V ( t) = V ( ω) e dω = V ( ω) I( ω) e dω (3) E( t) = E( ω) e dω = E ( ω) I( ω) e dω (4) H ( t) = H ( ω) e dω = H ( ω) I( ω) e dω () where V ( t ), E( t ), H ( t) are the time domain responses of the electric potential, electric and magnetic field respectively, V ( ω ), E( ω) and H ( ω) are the corresponding frequency responses of these quantities, whereas V ( ω ), E ( ω) and H ( ω ) reflect the single harmonic unit energization frequency responses of electric potential, electric and magnetic field calculated by HIFREQ. Based on this computational approach, the presented assumptions allow us to explore several scenarios defined by different types of lightning currents, different heights of the tower and soil types, in order to reflect the influence of these factors over electric and magnetic quantities that appear. It is also taken into account the influence of the grounding system, by comparison between the situations on which it exists with the ones on which it is absent [2], [3]. The problem can be studied on several types of towers, like oil extraction industry, wind or telecommunication ones. It was selected a telecommunication tower, due to multiple reports and observations of lightning strokes and also considering to be a more common structure that can be subjected to these atmospheric incidents. The tower is connected to a simple grounding system, which is located at the bottom part of the tower: four buried vertical steel bar conductors having m length, connected to the tower legs and a 3 m long horizontal copper conductor, buried at a depth of m and connected to three m long vertical grounding copper rods (fig. 3) [4]. Fig. 3. Tower and grounding system dimensions. The analyzed scenarios are defined as follows: as a starting point, the tower height, H, is considered at a constant value of m, the soil is homogeneous, semi- 2 28

IMPACT EVALUATION OF DIRECT LIGHTNING STRIKE ON A TOWER. GROUND POTENTIAL RISE ALTERNATIVE COMPUTATIONS infinite conductive medium with a specific resistivity of ρ soil = Ω m and vacuum permittivity, characteristic to breeding grounds; the lightning current amplitude is established at I peak = ka, the rise time at t r = µ s and a fraction time of t /2 = 2 µ s. The time domain of the analysis is considered to be µ s and initially the tower has no grounding system. Then these parameters are to be varied, to show their influence over the electromagnetic fields of the lightning current (Table I) [], [6]. Table Description of the simulated scenarios 3. ALTERNATE ANALYTICAL EVALUATION According to [6] the step voltages can be calculated using the near zone horizontal electric field method. Therefore, applying the method on our study, the following model of the electric field near the tower was considered: H µ Er ( ω, r) = derp ( ω, r) dhϕ p ( ω, r) (6) H ε + σ / jω where: 2 2 I ( ω) dh k R + j3kr + 3 derp ( ω, r) = ( z h) r j4πωε R e jkr 2 2 I ( ω) dh k R + j3kr + 3 + ( z h) r j4πωε R jkr Scenarios Parameters SC I SC II SC III SC IV SC V I peak (ka) 3 6 t r ( µ s) t /2( µ s) 2 2 H(m) ρ soil ( Ω m) 9 Grounding system (7) e I( ω) dh jkr r + r jk ( ) R I ω dh dhϕ p ( ω, r) = 3 e + 4π R 4π (8) jkr r + r jkr 3 e R The parameters that appear in equations (6), (7) and (8) are described as follows: H, height of the lightning channel (7 m in this case); 2 2 2 7 No No No No 2 Yes/ No E r, is the radial electric field near the lightning channel, given by the electric component E rp and magnetic component H φp ; ω, lightning current angular frequency; r, is the distance between the lightning channel and the observation point (a value of 8 m was considered); ε, σ = / ρsoil represent electric soil permittivity and conductivity already described above; 2 2 k = ω / c, k = jωµ ( σ + jωε ), where c = 3 8 m/s is the speed of light; 2 ( ) 2 2 R = r + h + z and R ( ) 2 = r + h z, where z is the axial coordinate of the observation point; The frequency lightning current I(ω) was analytically obtained by applying the Fourier Transform to time domain current described by equation (), resulting: k I peak 2α 2β I( ω) = + 2 2 2 2 α + ω β + ω The frequency domain step voltage results from [6]: r+ s Us( ω) Er ( ω, r) dr r (9) = () where s is the selected step as being m in this case. In order to obtain the time domain variation of U s, the numerical version of Inverse Fourier Transform was used. 4. EXPERIMENTAL RESULTS The following results attend a detailed description on the effects of lightning current parameters variation, over the generated and induced electric potential and magnetic fields, according to the first scenario. Fig. 4 and illustrate how the step voltages values change as the amplitude of the lightning current increases. Thus, the step voltage increases from 2 V (taking one meter between the measuring points) for an amplitude of ka, at the distance of 8 meters far from the tower, up to 9 V for an amplitude of 3 ka and rises exponentially by decreasing the distance. Fig. 4. Step voltages for amplitudes of ka (SC I). Buletinul AGIR nr. /22 ianuarie-martie 3 29

WORLD WORLD ENERGY ENERGY SYSTEM SYSTEM CONFERENCE CONFERENCE WESC - WESC 22 Fig.. Step voltages for amplitudes of 3 ka (SC I). Fig. 6 and 7 show how the electric potential values decrease in time, measured in observation points placed at the tower base and at a distance of 2 m from it, respectively for different amplitudes of the lightning current. fraction time, the lightning current remains at high values for longer time, therefore forcing the variation rate of induced electric potential to rise. An increase of the tower height has been determined to considerably influence the effect over the evaluated electric potentials and step voltages. Capture 4 already showed, together with 9 and, presented below, indicate how the electric potential varies when the height of the tower increases from to m; the parameters are described in the third scenario, SC III: Fig. 9. Step voltages for 7 m tall towers (SC III). Fig. 6. Electric potential variation, at the tower base (SC I) Fig. 7. Electric potential variation, at a distance of 2 m from the tower base (SC I). As indicated in these captures, electric potential values do not rise linearly by increasing the amplitude, but more like by a parabolic curve, reaching 3 kv for an amplitude of 6 ka, compared to 9 kv for an amplitude of 3 ka, both observation points placed at 2 m far from the tower. Next it is illustrated how the variation of the fraction time affects the calculated electric potentials and step voltages, keeping the other parameters constant (SC II). Two fraction time samples of 2 and microseconds were considered. Fig.. Step voltages for m tall towers (SC III). As it can be noticed, step voltages reach considerably high values, as the height of the tower increases (3 V for m tall towers m between measuring points). Pursuing the experimental simulations, we deduct that the type of the soil on which the tower is built has also a significant influence on the electric potential values that appear onto the ground level. The following captures and 2 illustrate how soil resistivity influences the step voltages near the tower. Soil resistivity values of 9, and 2 were considered, correspondent to soils with low drainage (salty water), arable lands, respectively mountain and rocky arid areas, as described by the fourth scenario. Telecommunication towers can be found on all of these soil terrains, near power stations, or far away from any kind of infrastructure. Fig. 8. Step voltages for different values of the fraction time(sc II). As it can be seen, step voltage values tend to rise faster, as the fraction time is increased. Step voltages (fig. 8) go from 2 V for t /2 = 2 µs and reach values of 4 V for t /2 = µs. As expected, by increasing the Fig.. Step voltages for low drainage areas (SC IV). 4 3

IMPACT EVALUATION OF DIRECT LIGHTNING STRIKE ON A TOWER. GROUND POTENTIAL RISE ALTERNATIVE COMPUTATIONS Fig. 2. Step voltages for mountain areas (SC IV). It should be emphasized that step voltage values get higher as the soil resistivity increases. For a better perspective over the differences between electric potentials in different soils, figure 3 was introduced: Comparing the two captures, we observe that the step voltages fall drastically when a grounding system is connected from 2 V to 4, V; for a distance of m between the measuring points. As compared to the electric potential, the magnetic field strenght varies exactly the opposite direction, by recording higher values when the grounding system is present, as it is shown in capture 6 from below: Fig. 3. Electric potential for different soil resistivities, 2 m far from the tower (SC IV). Given that, magnetic fields depends only on the ground characteristics through its magnetic permeability and assuming that relative magnetic permeability of soil is generally equal with the unit, which is mostly true, changing the soil type will have no effect over the evaluated magnetic quantities. By using a grounding system the leakage currents are directly led into the ground, avoiding most negative effects. Next figs. 4 and make evidence of how the grounding system affects step voltages created by lightning currents, to much smaller values (SC V). Fig. 6. Magnetic field intensity 2 m far from the tower, with or without grounding system (SC V). The difference is due to the fact that the lightning current finds a dedicated path to flow and thus generate concentric magnetic fields, i.e. the appearance of a new conductor, which means a new route for the lightning current - the grounding system itself.. SUMMARY AND CONCLUSIONS Figure 7 presents a comparison between the step voltages evaluated analytically and simulated numerically by the software package, in the conditions described by Scenario I. Fig. 4. Step voltages 8 m far from the tower, when there is no grounding system (SC V). Fig.. Step voltages 8 m far from the tower, when the grounding system is present (SC V). Fig. 7. Analytical and numerical step voltage evaluation. It is to be noticed a major difference at the triggering moment of the transient regime and also at the end of the lightning discharge, between the two alternative step voltage computation. In our investigations we have found one reference in the literature that appears consistent with the exposed inference and comparison []. We suggest that more data needs to be accumulated in order to adequately validate the models and to improve them in order to reproduce as closely as possible any experimental measurements. This paper presented an analysis of the electric and magnetic fields produced in the upper soil layer, nearby Buletinul AGIR nr. /22 ianuarie-martie 3

WORLD WORLD ENERGY ENERGY SYSTEM SYSTEM CONFERENCE CONFERENCE WESC - WESC 22 a lightning stroked metallic tower, in different scenarios, described by parameters like tower geometry and grounding system, soil resistivity, lightning current characteristics. One important task and contribution was to determine the induced step voltages nearby the stroked tower area and to show how do the above parameters affect their values. The results indicate that step voltages rise considerably with the amplitude of the lightning current, with the height of the tower. The impact of the soil type or tower geometry are considerable (step voltages vary from.2 to 7 kv); it is also important to know that the grounding system neutralizes high step voltages, but leads to an increase of the magnetic field intensity values. It should be emphasized that in the behavior study of the grounding systems one must account both the frequency dependence and the nonlinearity due to the soil ionization []. Improvements can be brought to the selected grounding system. The one we selected constitutes a basic system, knowing that the lightning protection for such towers may be constructed using a concentric system (circles of connected conductors) that surrounds the tower, minimizing considerably the step voltages. Acknowledgment This paper was supported by the project "Progress and development through post-doctoral research and innovation in engineering and applied sciences PRiDE - Contract no. POSDRU/89/./S/783", project co-funded from European Social Fund through Sectorial Operational Program Human Resources 27-23. BIBLIOGRAPHY [] Rakov, V.A., Rachidi, F., Overview of Recent Progress in Lightning Research and Lightning Protection, IEEE Trans. on EMC, Vol. (3), pp. 428-442, 29. [2] *** Protection Against Lightning, Part : General Principles, IEC-623-, 26. [3] Theethayi, N., Thottappillil, R., Some issues concerning lightning strikes to communication towers, Journal of Electrostatics, Vol. 6, pp. 689 73, 27. [4] *** Safe Engineering Services & technologies ltd., et al., Engineering Guide Lightning Transient Study of a Communication Tower, 26. [] Sun, Z., Wang, J., Qie, X., Xiang, N., Fang, C., Chen, J., Observation of Lightning Current and Ground Potential Rise in Artificially Trigged Lightning Experiment, ICHVE, Chongqing, China, pp. 277 28, November 9-2, 28. [6] Bihua, Z., Heming, R., Lihua, S., Cheng, G., Calculation of Step Voltage Near Lightning Current, Asia-Pacific Radion Science Conference, Qingdao, China, pp. 646 649, August 24-27, 24. [7] Baba, Y., Ishii, M., Numerical electromagnetic field analysis of lightning current in tall structures, IEEE Trans. Power Del., Vol. 6(2), pp. 324 328, 2. [8] Baba, Y., Rakov, V.A., Influences of the presence of a tall grounded strike object and an upward connecting leader on lightning currents and electro-magnetic fields, IEEE Trans. On EMC, Vol. 49(4), pp. 886 892, 27. [9] Baba, Y., Rakov, V.A., Applications of Electromagnetic Models of the Lightning Return Stroke, IEEE Trans. on Power Del., Vol. 23(2), pp. 8-8, 28. [] Ceclan, A., Czumbil. L,, Micu, D.D., On some return stroke lightning identification procedures by inverse formulation and regularization, ICLP, Cagliari, Sept. 2. [] Pavanello, D., Electromagnetic Radiation from Lightning Return Strokes to Tall Structures, Ph. D. Thesis, No. 373, EPFL, Lausanne, 27. [2] Baba, Y., Rakov, V.A., Influence of strike object grounding on close lightning electric fields, J. Geophys. Res., Vol. 3 (D29), 28. [3] Chisholm, W.A., Petrache, E., Bologna, F., Grounding of Overhead Transmission Lines for Improved Lightning Protection, Transmission and Distribution Conference, New Orleans, USA, Aprilie 9-22, 2. [4] Bermudez, J.L., Lightning currents and electromagnetic fields associated with return strokes to elevated strike objects, Ph. D. Thesis, No. 274, EPFL, Lausanne, 23. [] Rachidi, F., Nucci, C.A., Ianoz, M.V., Mazzetti, C., Influence of a lossy ground on lightning-induced voltages on overhead lines, IEEE Trans. on EMC, Vol. 38(3), pp. 2-263, 996. 6 32