DESCRIPTION NOTE MODEL 2200VM

Similar documents
DESCRIPTION NOTE. Power Supply MODEL 2200A PM

DESCRIPTION MODEL 1450 NOTE

DUAL 4-20 MA NETWORK BRIDGE. Voltage. Regulator. Neuron CPU. Ohm Sense Resistor. Model 1400A Block

A local 3.5 mm network jack allows a convenient way to connect an installation or diagnostic tool to the network without disconnecting any wires.

NEUROLOGIC RESEARCH CORPORATION

FTT-10A Free Topology Twisted Pair Transceiver Model 50051

Installation & Operation Manual

n FRONT PANEL CONFIGURATIONS

Connecting a Neuron 5000 Processor to an External Transceiver

Jaguar Motor Controller (Stellaris Brushed DC Motor Control Module with CAN)

R7L-YV2. DC VOLTAGE OUTPUT MODULE, 2 points MODEL BEFORE USE... POINTS OF CAUTION COMPONENT IDENTIFICATION INSTRUCTION MANUAL R7L-YV2

SMX Transceivers Models 77010, 77030, 77040, 77050, and 77162

H LONTalk Integration Node For Use With Enercept H8036 Power Meters H NOTICE DANGER INSTALLATION GUIDE METER DATA NETWORK VARIABLES

PACSystems* RX3i IC695MDL765

LVTX-10 Series Ultrasonic Sensor Installation and Operation Guide

Brushed DC Motor Control. Module with CAN (MDL-BDC24)

T6+ Analog I/O Section. Installation booklet for part numbers: 5/4-80A-115 5/4-90A-115 5/4-80A /4-90A-1224

HC900 Hybrid Controller

Lonbox PIO4014 Users Manual

E3 Adjustable Speed Drive Engineering Specification

TECHNICAL DATASHEET #TDAX ISOLATED DUAL CHANNEL UNIVERSAL SIGNAL CONVERTER

Brushless DC Motor Controller Specification Assemblies 025F0248

GEMINI PRESETTABLE DUAL RATE INDICATOR WITH RATIO (A/B)

maxon document number:

NMEA Protocol Converter 2 Plus 3 Users Guide

HB-25 Motor Controller (#29144)

MNL-5Rxx. Application. Model Chart. TAC I/A Series MicroNet MN 50 Controller Installation Instructions

TEAM DIGITAL. SC82 Servo Controller

F4-04DA-1 4-Channel Analog Current Output

ISO 9001 CERTIFIED. 607 NW 27th Ave Ocala, FL Phone: (352) or Fax: (352) OPERATION MANUAL

Milliamp Calibrator. Model 434. General description. Calibrate with laboratory accuracy. All 4 to 20 ma loop functions

Autonomous Robot Control Circuit

UniStream Uni-I/O Modules

DLVP A OPERATOR S MANUAL

815-BR SERVO AMPLIFIER FOR BRUSH SERVOMOTORS

G201X STEP MOTOR DRIVE REV 5: SEPTEMBER 13, 2010

Inverter Drive /Vector Drive Motors & Controls

PolyGard Digital Transmitter DGC DT-02

AF91 Adjustable Frequency Drives Series B

The wireless alternative to expensive cabling...

Applications: Power generation, Cogeneration, Stationary power Large engines

DELTAplus. DIN Rail Mounted electricity meters. Technical Documentation

Product overview. Features. Product specifications. Order codes. 1kΩ Resistance Output Module

PACSystems* RX3i IC695MDL664-BB

Continental Hydraulics Installation Manual CEM-RA-A

VersaMax Mixed Discrete / High-Speed Counter Module

USER S MANUAL PULSE INPUTS MODULE WITH PROVER SUPPORT

Programmable K-Factor Scaler B and Programming Software Kit B

VersaMax Mixed Discrete / High-Speed Counter Module

NT240 TIMER. PROGRAMMABLE TIMER INSTRUCTIONS MANUAL V20x G TIMER OUTPUTS INTRODUCTION SPECIFICATIONS AUXILIARY SUPPLY OUTPUT INSTALLATION TIMER INPUTS

P/N: AX Applications: Typical applications can include: test stands; and industrial automation.

Instruction Manual ABM HART Gateway Software. Instruction Manual Revision A.1

Hardware Manual. PCD3.F240/PCD2.F2400 LON interface module for TP/FT-10 channel. Hardware Manual PCD3.F240/PCD2.F2400, LON interface module

G210X STEP MOTOR DRIVE REV 5: March 25, 2011

Ametek, Inc. Rotron Technical Products Division. 100 East Erie St., Suite 200 Kent, Ohio User's Guide. Number Revision F

PCAN-MicroMod Evaluation Test and Development Environment for the PCAN-MicroMod. User Manual. Document version ( )

CT435. PC Board Mount Temperature Controller

Metaphase ULC-2. Technologies ULC. Metaphase. Technologies Version 7.X August 2015 USER MANUAL. metaphase-tech.com. pg. 1

NetBiter I/O Extender 4RO 6RTD 8DIO - DAIO User Manual Revision 1.00

TECHNICAL DATASHEET #TDAX022420

with Electronic Assistant

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters

Model FLSC-C1-LIQ. Microprocessor Based Loop Powered Transmitter

SOUTHERN AVIONICS COMPANY. SE125 Transmitter. SE125 Transmitter 1-1

CCE Image may differ from the actual product By Martin Labbé, eng., Jasmin Goupil & Louis Perreault

Temperature Monitoring and Fan Control with Platform Manager 2

MA7200 PLUS INVERTER SERIES PID Quick Start Manual For Fan and Pump Applications

DC-DC Converter Module

BATCHMATE 1500 Batch Control Computer Technical Bulletin

Installation & Operation Manual

SKIM USER S GUIDE SMART KAN INTERFACE MODULE 2 & 8 I/O

TD_485 Transceiver Modules Application Guide 2017

AMU-214 Auxiliary Monitor Unit Operations Manual

Fits Tiger 320 Series UNIVERSAL FREQ/COUNTER INPUT MODULE

TECHNICAL PRODUCT DATASHEET

Programmable with Electronic Assistant Simulink

TECHNICAL DATASHEET #TDAX INPUTS, 5 OUTPUTS VALVE CONTROLLER

K-FACTOR SCALER B & B

Cyclops User s Manual

DET-TRONICS SPECIFICATION DATA. Eagle Quantum Premier 8 Channel Enhanced Discrete Input/Output Module (EDIO) EQ3730EDIO DESCRIPTION

ECL-VAV-N. Features & Benefits

SX9Z-B SX5L SERIES. LONWORKS Communication Terminals. User s Manual

DCM20 Series. Three-Function DC Power Meters. DCM20 DISPLAY PRODUCT OVERVIEW FEATURES

Ordering Part Numbers: SAE J1939 version Controller: AX022400

CAP6637A AC-DC Open Loop Converter

VF-nC1 Adjustable Speed Drive Engineering Specification

Galil Motion Control. DMC 3x01x. Datasheet

Asia-Pacific North America Europe, Middle East Bel Power Solutions, Inc. BCD.

GS1 Parameter Summary Detailed Parameter Listings...4 9

BAPI-Stat 4 X-Combo, Room %RH and Temp. Sensor BA/BS4XC Installation & Operating Instructions

with Electronic Assistant

Analog Servo Drive 25A20DD

S662 Preset Batch/Dual Counter

IntesisBox ME-AC-LON-1 v

Heliotrack Programmable Wind Alarm Switch V1.0 Developed in partnership with Inspeed.com, LLC

SilverMax Datasheet. QuickSilver Controls, Inc. NEMA 23 Servomotors.

For additional PowerFlex 4 and 40 data and general drive information, refer to the following publications:

MICROFUSION FEATURES OPTIONS CERTIFICATIONS THREE PHASE SCR POWER CONTROLLERS

TECHNICAL DATASHEET #TDAX Universal Signal Inputs CAN Controller V, ma, Digital, PWM, Hz/RPM, Counter Inputs CANopen P/N: AX030121

BAP1551 Gate Drive Board

Transcription:

Instantly integrate any volume measurement meter such as water or gas meters into the LonWorks digital network. The firmware executes on a NeuroLogic Research Model 2200 and provides a low-cost interface to two meters with no additional hardware. Total volume is saved to non-volatile memory every 30 seconds and is available in liters via a Standard Network Variable Type, SNVT_vol_f. Number of firmware restarts is available via output network variable to log power or network interruptions. Flow rate, in liters per second, can be averaged over a user configurable period of one-second to two hours. It is available using a Standard Network Variable type of SNVT_flow_f. Flow rate is additionally available as a percent, SVNT_lev_percent, to easily interface to other LonWorks devices. Accumulated pulse count and input state are available for diagnostics or other applications. Internal pulse accumulator has a capacity of 2,147,483,648 counts and can handle input frequencies up to 65 KHz DESCRIPTION NeuroLogic Research s Model 2200 is a pulse count input node that is housed in a compact DIN rail enclosure. It allows integration of up to 2 digital pulse inputs into the LonWorks distributed digital network. This datasheet describes the functionality of the 2200VM. It is a special program that tailors the Model 2200 for volume monitoring such as in gas or water metering applications. The firmware executes on a standard Model 2200 and is available at no charge. It is downloaded to a base Model 2200 via a LonWorks Network Installation Tool such as LonMaker or preloaded if ordered as Model 2200VM Pulse meters with a dry contact, NPN transistor, or a voltage output can be connected directly to the Model 2200. An input frequency of up to 65 KHz can be captured. The internal pulse accumulator has a capacity of 2,147,483,648. In case power is lost, the accumulated pulse count is saved internally once every 30 seconds. The amount of volume per pulse, in liters, for each meter is entered as a configuration parameter. It is used to calculate the total volume in liters. The amount of volume measured is averaged over a user configurable period of 1 to 7200 seconds. The average volume is used to calculate the flow rate. The calculated flow rate is made available via Standard Network Variable Types in liters per second and as a percentage value. The percentage output allows a simple interface to other LonWorks devices. NOTE This PDF datasheet has attachments. To access them, it may be necessary to use an actual Adobe Reader. since some readers built into internet browsers do not allow access to attachments. 1 / 8

WIRING AND INSTALLATION Input power and network communication is done via two identical 4-position terminal blocks at the upper end of the enclosure. The terminal blocks are duplicated to allow easy in/out bus wiring of multiple units. Please see the wiring table below for attaching power and network wiring. If the upper connectors are used to daisy chain multiple devices, please keep the overall current going through any one Model 2200 to less than 3 amps. The Model 2200 can be powered by a voltage source between 12 and 36 VDC. The on-board Service switch and LED allow installation on to the LonWorks network. The Service LED is in the upper left hand corner The Service Switch can be found under the top cover. The top cover can be removed using a small screwdriver and gently pulling up on the side of the top cover. Upper Terminal Blocks Connection Note: Both connected for Daisy Chaining NetA: Position 1 and 2 labeled NetA and NetB connect the Model 2200 1 to the LonWorks FTT-10 network. These wires are not polarity sensitive. 2 NetB: See above VIN+: Positive end of input voltage source to power the unit. 12 36 VDC is allowed. This voltage after being fused and reverse voltage 3 protected is supplied to the VOUT+ connectors on IN1& IN2 terminal blocks. VIN-: Negative connection of DC input voltage source. This terminal is 4 essentially connected directly to the VOUT- terminals of IN1 & IN2. Lower Terminal Blocks 1 2 3&4 Pop cover off here to access Service Sw Connection Note: Left = Channel 1, Right = Chanel 2 VOUT+: Output voltage source to pulse input devices. This output is essentially the voltage at the VIN+ terminal on A/B terminal blocks minus about 1 volt. The VOUT+ terminal is individually fused with 100 ma resettable fuse and reverse voltage protected. INP 1/2: This pin is where the input signal is applied to the Model 2200. Please see the wiring diagrams that follow. VOUT-: Negative connection of output DC voltage source. This terminal is essentially connected directly to the VIN- terminals of A/B. Each pulse input is attached to the Model 2200 via a 4- position removable terminal block on the lower portion of the enclosure. Please see the table above for identification of each position on the terminal blocks. Not all connections are used on all installation. There is one such terminal block for each of the 2 inputs. Each terminal block is used to provide output power as well as connection of the actual input signal. Please see the following sections for a complete explanation of how the Model 2200 processes the input signal as well as wiring diagram for different input types. 2 / 8

Dry Contact Input Connection Diagram VOUT + Fuse Reverse Protection Diode Model 2200 Internal Circuits VIN + +5V Threshold to 4.0 Volts Up Hysterisis to 3.0 Volts Dry Contact from Meter IN -Up Enabled -Down Disabled Input Signal Processing NEURON CPU VOUT - Down Invert OFF VIN - NPN Transistor Input Connection Diagram VOUT + Fuse Reverse Protection Diode Model 2200 Internal Circuits VIN + +5V Threshold to 4.0 Volts Up Hysterisis to 3.0 Volts NPN Opto- Isolator Out from Meter IN -Up Enabled -Down Disabled Input Signal Processing NEURON CPU - VOUT - Down Invert OFF VIN - 3 / 8

Voltage Input Connection Diagram Note, the hardware can handle an input voltage range up to the input power supply voltage, VIN+, without damage. An input pulse is counted when it drops below 1.0 volts and must go above 4.0 volts before the next pulse can be detected. VOUT + Fuse Reverse Protection Diode +5V Threshold to 4.0 Volts Up Model 2200 Internal Circuits Hysterisis to 3.0 Volts VIN + Voltage Input from Meter NOTE For best results, signal should be positive with respect to VOUT-. Model 2200 will work properly with signals up to 8 volts below VOUT-. - IN VOUT - Down -Up Enabled -Down Disabled Input Signal Processing Invert OFF NEURON CPU VIN - How The Pulse/Volume Accumulator Works The 2200VM firmware configures each input with a threshold voltage of 4.0 volts and 3.0 volts of hysterisis. The internal 1500-Ohm pull-up resistor is always enabled. With this configuration, an input voltage less than 1.0 volt is considered ON while a voltage higher than 4.0 volts is considered OFF. Since the internal 1500-Ohm resistor is pulling the input up to an internal 5.0 volts supply, the input need only pull the input below 1.0 volt to be counted. The OFF to ON transitions are counted. Please see the Model 2200 datasheet if more information is required regarding the hardware s capabilities. The internal pulse accumulator has a count capacity of 2,147,483,648. The Standard Network Variable Type of SNVT_count has a capacity of only 65535. This data is available using the nvocount network variable. When the maximum value is reached, the nvocount will rollover and start again from 0. The 2200VM firmware makes a second network variable available, nvocountoverflow. It will increment once each time the nvocount value rolls over. By looking at both values, very large count accumulations can be realized. The actual value of the total count is nvocountoverflow *65535 + nvocount. Volume meters output a pulse each time a particular amount of volume is measured. The number of liters per second per pulse is entered via the ncivolperpulse configuration network variable. Total accumulated volume is calculated and is available via the nvovolume output network variable. It is in liters. In case power is lost, the accumulated volume is saved every 30 seconds to non-volatile memory. When power is restored, the firmware will resume counting from the last saved value. To keep track of restarts, the neorestarts network variable is incremented every time the firmware is restarted. Firmware restarts can occur due to power interruptions or commands received over the network that may put the firmware online after being taken offline. Finally, the user can actually reset the count to any starting value by writing to the nvivolstart. When this value is written, the actual internal accumulator is updated with the value written into nvivolstart divided by the ncivolperpulse. 4 / 8

How Flow Rate Measurement Works Input pulses are accumulated over a user configurable period of 1 to 7200 seconds. The 2200VM firmware will support input pulses having a frequency up to 65 KHz. The averaging period is configured via the nciflowavgsecs configuration network variable. This large dynamic range allows many types of meters to be supported. If the average period is less or equal to 400 seconds, a maximum frequency of 65 KHz can be supported. For slower inputs the average period can be setup between 401 seconds and 7200 seconds. However, the input frequency will be limited to 3600 Hz. Unit Conversion Factors The 2200VM firmware uses Standard Network Variable Types for maximum compatibility. The following conversion factors are handy when configuring the firmware and interpreting the volume and flow rate. Looking at Input as a Discrete Digital For steady state input signals, the nvostate ouput network variable reports the ON / OFF state of the input The average flow rate is calculated over the specified period and is available via the nvoflow network variable. Additionally, the flow rate is available as percentage value via the nvoflowpercent network variable. The percentage output is scaled using two configuration network variables. The nciflowmin defines the value that represent 0% and nciflowmax defines the value that represent 100%. This Unit Equals this 1 gallon 3.785412 liters 1 ounce 0.0295735 liters 1 pint 0.4731765 liters 1 quart 0.9463530 liters 1 cubic inch 0.016387 liters 1 cubic foot 28.31685 liters 100 cubic feet 1 ccf 2831.685 liters 0.0353 cubic feet/second 2.1189 cubic feet/minute 127.1328 cubic feet/hour 1 liter/second 1.27133 ccf/hour 0.26417 gallons/second 15.85032 gallons/minute 951.019 gallons/hour signal. The digital state is sampled by the firmware 10 times per second. 5 / 8

NETWORK INTERFACE The Model 2200 uses the Echelon FT-10 network transceiver interface with DC blocking capacitor so it can also be directly connected to LPT-10 networks. Before the Model 2200 can be used, it must first be installed into a LonWorks network. This procedure is slightly different for each system. It often involves telling the system to add a new device. The system will then ask the user to press the Service button on the device. When pressed, the Model 2200 will transmit its unique physical Neuron ID. The System then assigns a logical address to the unit and then data from the device is available. The data is available using Standard Network Variable formats that have been defined by the LonMark Association. The Model 2200 has self documentation of the network interface enabled and it can be uploaded by the installation tool. Additionally, an XIF is also attached to this PDF datasheet. NOTE NOTE If you purchased a Model 2200PM, 2200VM or 2200 they can be converted to the type described in this datasheet by downloading the attached.nxe file over the LonWorks network. This is accomplished using your network installation tool when you install the device. If your network tool does not support this function we can do this for you at the factory, please contact us. This PDF datasheet has attachments. To access them, it may be necessary to use an actual Adobe Reader. since some readers built into internet browsers do not allow access to attachments. Configuration Network Variables Network Variable Format Defaults Description ncivolperpulse[2] SNVT_vol_f 1.0 Defines the liters per input pulse ncivolsnddelta[2] SNVT_vol_f 1.0 Minimum change required before nvovolume, nvocount, and nvocountoverflow are updated nciflowavgsecs[2] SNVT_count 60.0 Sec Number of seconds used to calculate average flow rate, nvoflow. Values are limited between 1 and 7200 seconds. nciflowsnddelta[2] SNVT_flow_f 1.0 Minimum change required before nvoflow and nvoflowpercent are updated nciflowmin[2] SNVT_flow_f 0.0 Value equal to 0% for nvoflowpercent nciflowmax[2] SNVT_flow_f 100.0 Value equal to 100% for nvoflowpercent nciminsendt SNVT_time_sec 15.0 Sec Minimum elapsed time before a network update is sent even if the configured delta change has been met. ncimaxsendt SNVT_time_sec 30.0 Sec Maximum elapsed time before a network update whether or not the configured delta change has been met. 6 / 8

Output Network Variables Network Variable Format Description nvovolume[2] SNVT_vol_f Total accumulated Volume in liters nvoflow[2] SNVT_flow_f Flow rate averaged over a user configurable period of 1 to 7200 seconds. See nciflowavgsecs. nvoflowpercent[2] SNVT_lev_percent Flow rate represented a percent value. See nciflowmin and nciflowmax to configure. nvocount[2] SNVT_count Accumulated raw count. Value is between 0 and 65535. nvocountoverflow[2] SNVT_count Number of time nvocount[] Overflows. Total accumulated count is nvocountoverflow*65536 + nvocount nvostate[2] SNVT_lev_disc Status of the discrete input. Can be used for diagnostics or to interface to standard switch closure neorestarts SNVT_count Non-volatile variable that is incremented every time the firmware restarts. Usually due to a power loss, however, it will also occur if the unit is placed online via a network command. Input Network Variables Network Variable Format Description nvivolstart[2] SNVT_vol_f Allows the nvovolume[] accumulator to be reset or started at any value. 7 / 8

SPECIFICATION General CPU Neuron FT5000 Operating Temperature -40 85 C Operating Humidity 0-95% Relative Humidity non-condensing Input Power 12 to 36 VDC Input Power Protection Input power is fused and transient voltage protected. (Fuses do not need to be replaced) Current Consumption 35 ma typical plus power used by external sensors. Network Transceiver Type Echelon TP/FT10 transceiver at 78 kbps. DC blocking capacitors for LPT10 network. Input Power and Network Wiring Removable terminal blocks. Accepts up to 20 GA wire. Input power is reverse voltage protected. Network wiring is polarity insensitive. Inputs Inputs 2 Input Types Dry contact, NPN transistor, 0-5 volts input minimum Input Voltage Range 0-36 VDC. Input voltage signal must be capable of sinking 3.5 ma due to internal 1500 resistor. Threshold Voltage Range < 1.0 Volts indicates input is ON > 4.0 Volts indicates input is OFF Internal -Up 1500 Ohms to 5 Volts DC Flow Rate Averaging 1 7200 seconds Frequency Input Range 0 65 KHz for averaging period less or equal to 400 seconds 0 3600 Hz for averaging period 401-7200 seconds. Pulse Accumulator Capacity 2147483648 Dimension and Materials External Dimension Enclosure Type Enclosure Material 36 mm (1.8 ) W x 90 mm (3.54 ) L x 58 mm (2.28 ) H DIN rail mount to 35 mm rail Grey frame retardant Noryl UL94_V0 ORDERING INFORMATION 2200VM Model 2200VM LonWorks Dual Volumetric/Gas/Water Pulse Metr Interface Echelon, LON, LonWorks, Neuron, 3120, 3150, LONMARK are trademarks of Echelon Corporation. 8 / 8