ASTA TEST REPORT NO: HEATSHRINK TERMINATIONS 3 CORE 12kV PILC AND XLPE

Similar documents
NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations

REPORT OF PERFORMANCE TIC

This Certificate consists of 75 pages in total.

76 / 132 (145) kv 1x1200 mm 2 CU/XLPE/CWS/AL/HDPE

Comparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137

MEDIUM VOLTAGE TERMINATIONS CATALOGUE 2017

Underground System Design TADP 547

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.

Testing 320 kv HVDC XLPE Cable System

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET

Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics

ECP HV INSULATION TESTING

About us. Vision. To lead our field in innovation, quality and customer service.

Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES. 11 kv XLPE-Insulated Three-Core Underground Cables

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

Power Cables and their Application

Reference Number PCP 02 (RIC Standard: EP SP)

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

ECP HV INSULATION TESTING

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems

TT 0710/03. TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: LB.W.3SA.3.1

EI HIGH VOLTAGE INSULATION TESTING POLICY

BY JASON SOUCHAK, Megger

3MElectrical Markets Division

Energy Division. Bowthorpe LV/MV Surge Arresters

Transmission Facilities Rating Methodology for Florida

Fault location on power cables. Fault location on power cables

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3

REPORT NO. DL TYPE TEST REPORT OF A ELECTROMAGNETIC RELAY RENDERED TO

Type Test of a 145 kv Termination Type TS 145-II

CABLE JOINTING KITS &

EXTREMELY LOW MAGNETIC FIELD (ELMF) XLPE INSULATED CABLES, TYPE N2XY/FR1 0.6/1 KV

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

Field Measurement of Transmission Cable Dissipation Factor

Tests on Extruded Cables

50-SDMS-01 SPECIFICATIONS FOR

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

Technical Specification. for 1.1 KV Copper Control Cable

FERRORESONANCE - its Occurrence and Control in Electricity Distribution Networks

List of Experiments. Exp. # Experiment Title Page #

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

104 Pattanakan 69, Pravet, Bangkok Thailand A VER

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

Selection of MO surge arresters Overvoltage protection

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

PROTECTION AGAINST FAULT CURRENT

TECHNICAL SPECIFICATION

Test description for dry-type transformers chapter for special tests

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

VI 3 - i TABLE OF CONTENTS

IEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4

Power Engineering II. High Voltage Testing

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

NXCT 345 kv Test Performance Record For LAPEM

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION)

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

Test Report CESI A6/ Approved Page 1. MF Trasformatori s.r.l. - Calcinato (BS) Italy

HYDROFIRM (T) Cables. for use in Ground Water and Drinking Water

Cable diagnostic in MV underground cable networks

PRODUCT SPECIFICATION

BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES

CAST RESIN DRY TRANSFORMER

Pressure Transmitter Type AKS 32 and AKS 33 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope

IDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy

Calibration of High-Voltage Test Equipment

Datasheet Platinum Resistance Pt100 In-head (Push Button) Temperature Transmitter TX203P mA output, default range supplied C

Partial discharge diagnostics on very long and branched cable circuits

Substation HV Cables. Document Number: 1-11-FR-07

OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets

MV Power Cable Testing Training

JULY Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Resistive capacitive voltage divider

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

USING DAMPED AC VOLTAGES

HV SYSTEMS. Prysmian HV Systems Product Range 66kV & 132 kv

EDS KV TRIPLEX CABLE RATING

ANSI DESIGN TEST REPORT Report No. EU1295-H-00 Type PVN Station Class Surge Arrester

CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS

MEDIUM VOLTAGE PRODUCT. PARAMETERS GUIDE How to specify the indoor instrument transformers correctly

PRODUCT SPECIFICATION

Analysis of Major Changes to Arrester Standards IEC STEVE BREWER

ON LOAD TAP CHANGERS RSV 5.3 TECHNICAL DATA

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

PRODUCT SPECIFICATION

NATIONAL SENIOR CERTIFICATE GRADE 12

Australian Standard. Switchgear assemblies and ancillary equipment for alternating voltages above 1 kv AS

User s Manual For CT Model IMB

ON LOAD TAP CHANGERS RS 6.3 / RS 6 TECHNICAL DATA

WIRE AND CABLE ENGINEERING GUIDE

Resistive capacitive voltage divider

Transcription:

ASTA TEST REPORT NO: 2212 HEATSHRINK TERMINATIONS 3 CORE 12kV PILC AND XLPE UNIVERSAL 12kV HEATSHRINK JOINT TO SUIT 3 CORE XLPE / PILC CABLES INLINE OR TRANSITION

RECORD OF PROVING TESTS Page 1 of 6 Laboratory Reference No.AR/L/6/21 Date of Tests December 25 March 26 CONTENTS Apparatus Tested Page 2 Test Specifications Page 2 Test Arrangements Page 2 Tests Made Page 3 Test Results Page 4-6 Conclusion Page 3 DIAGRAMS TLAB/5/11a OSCILLOGRAMS Fig. 1 Fig. 2 Fig. 3 Fig. 4 TN5129/D1 D6 TN6321/D1 D6 Typical test circuit for impulse tests Calibration / Thermal Cycle Elevated temperature of the external surface during lightning impulse tests Electrical heat cycles in AIR Electrical heat cycles in WATER Lightning impulse voltage tests at elevated temperature (showing 1 st & 1 th impulse) Lightning impulse voltage tests at ambient temperature (showing 1 st & 1 th impulse) DRAWINGS Drawing No. Issue Status Description System A54 Pg 1-Pg 7 Rev.-, dated 27-7-6 Installation Instruction. Heatshrink Terminations for 3 Core Polymeric Cables 7.2kV to 36kV System A56 Pg 1-Pg 8 Rev.-, dated 27-7-6 Installation Instruction. Heatshrink Terminations for 3 Core PILC Belted / Screened Cables 12kV System A171 Pg 1-Pg 1 Rev.-,dated 27-7-6 Installation Instruction. Heatshrink Uniset Resin Joint to Suit 3 Core 12kV PILC / SWA PICAS or XLPE / SWA Cables Inline or Transition. Reference Type : SPUJ 12U PHOTOGRAPHS P/6/69 View of cables during thermal CALIBRATION tests P/6/7 View of cable during DC & AC tests at ambient temperature P/6/71 View of cable after lightning impulse voltage tests at elevated temperature P/6/72 View of cable inside a large duct during electrical heat cycling tests in air & water P/6/73 View of cable inside a large duct during electrical heat cycling tests in water P/6/74 View of cable during DC, AC, lightning impulse & AC voltage tests at ambient temperature P/6/75 View of transition joint cable during final examinations (showing being cut with bandsaw) P/6/76 View of transition joint cable during final examinations (showing section cut) P/6/77 View of transition joint cable during final examinations (showing sections of both extruded XLPE insulation and paper PILC insulation laid out for inspection) P/6/78 View of transition joint cable showing a 45 cut section in extruded XLPE insulation. (no ingress of moisture detected) P/6/79 View of transition joint cable showing a 45 cut section in paper PILC insulation. (no ingress of moisture detected) P/6/8 View of paper PILC insulation section showing samples of paper flakes immersed in cable oil at 135 C (no froth observed indicating no ingress of moisture) This is not a Certificate of Rating A. Majid.... ASTA Observer ASTA

RECORD OF PROVING TESTS Page 2 of 6 Laboratory Reference No. AR/L/6/21 Date of Tests December 25 March 26 Client's Ref. No. Q25/242 1. Apparatus Tested 12kV 3 core 95mm 2 8m length indoor cable fitted with a universal straight joint and PILC (impregnated paper) terminations on one end and XLPE (polymeric) terminations at the other end. Transition joint connecting extruded (XLPE) insulation cable to impregnated paper (PILC) insulated cable Uo = 6.35kV the rated power frequency voltage between conductor and earth Um = 12kV the maximum value of the highest system voltage for which the cable accessory may be used The apparatus under test was constructed in accordance with the installation instructions listed on page 1 2. Test Specification The tests were made to client s instructions and generally in accordance with : BS 7888 4.2 : 1998, Table 1 (Test Sequence A1) & Table 3 (Test Sequence B1) 3. Test Arrangements Due to laboratory limitations testing of cables were conducted at Southampton University and were witnessed by Mr Abdul Majid, NaREC Testing Authority Observer. Calibration of test cable conductor temperature To determine cable conductor temperature, a temperature calibration test was made in accordance with BS 7888 2, Annex B.2, by direct injection of a given current. Thermocouples were used to measure the cable inner conductor and external surface temperatures in accordance with BS 7888 2, Annex B, Figures B.1 & B.2. The cable was heated until the cable conductor temperature reached the maximum rated conductor temperature as specified in BS 7888 3, Table 1 for impregnated paper (8 C+ K 5K). The heating continued until the conductor and external surface temperatures had stabilised and did not show any variation greater than 2K within a 2hr period. The corresponding external cable surface temperature (measured) was used during the elevated temperature tests. Fig. 1 Calibration / thermal cycle Fig. 2 Elevated temperature of the external surface during lightning impulse tests Fig. 3 Electrical heat cycles in Air Fig. 4 Electrical heat cycles in Water Note on electrical heat cycles Initial 63 cycles were made in AIR on both terminations and universal straight joint. Then a further 63 cycles were made with terminations being in AIR and universal straight joint in WATER - thus completing the 126 cycles. Each cycle consisted of an 8-hour duration (Figure 1) in accordance with BS7888 2, sub-clauses 9.1 & 9.2 This is not a Certificate of Rating A. Majid.... ASTA Observer ASTA

RECORD OF PROVING TESTS Page 3 of 6 Laboratory Reference No.AR/L/6/21 Date of Tests December 25 March 26 4. Tests Made Tests to BS7888 4.2, Table 1 (indoor terminations for impregnated paper insulated cables - Test Seq. A1) 1. DC dry negative polarity voltage test at 38.1kV for 15 minutes 2. AC dry voltage test at 28.6kV for 5 minutes 3. Ten (positive & negative) lightning impulse voltages at 95kVpk (at elevated temperature) 4. 126 electrical heat cycles in air energised at 9.5kV 5. AC dry voltage test at 19.1kV for 4 hours 9. Ten (positive & negative) lightning impulse voltages at 95kVpk (at ambient temperature) 1. AC dry voltage test at 15.9kV for 15 minutes 12. Examination Tests to BS7888 4.2, Table 3 Joints & transition joints for impregnated paper insulated cables (Test Seq. B1) 1. DC dry negative polarity voltage test at 38.1kV for 15 minutes 2. AC dry voltage test at 28.6kV for 5 minutes 4. Ten (positive & negative) lightning impulse voltages at 95kVpk (at elevated temperature) 5. 63 electrical heat cycles in air energised at 9.5kV 6. 63 electrical heat cycles in water energised at 9.5kV 7. AC dry voltage test at 15.9kV for 4 hours 11. Ten (positive & negative) lightning impulse voltages at 95kVpk (at ambient temperature) 12. AC dry voltage test at 15.9kV for 15 minutes 13. Examination 5. Test Results Recorded atmospheric conditions are detailed on Table 1 Results of DC voltage tests are detailed on Table 2 Results of AC voltage tests at 4.5Uo are detailed on Table 3 Sample of results of cable conductor, external surface and ambient temperature during 2hr stabilization period as detailed in Table 4 Results of lightning impulse voltage tests at elevated temperature are detailed on Table 5 Results of AC voltage tests at 3Uo are detailed on Table 6 Results of lightning impulse voltage tests at ambient temperature are detailed on Table 7 Results of AC voltage tests at 2.5Uo are detailed on Table 8 Examination Visual inspection of encapsulation exposed at the section end of the joints showed no cracks or large voids 45 cut on PILC (paper) end showed no ingress of water on the inside insulation 45 cut on XLPE (polymeric) end showed no ingress of water on the inside insulation No froth was observed on unrolled insulation paper put into 135 C hot oil, indicating that there was no moisture entered into the paper during the electrical heat cycling in water. 6. Conclusion The results of the tests show that the MV cable has satisfactorily satisfied the criteria of tests from BS 7888 4.2, Tables 1 & 3 This is not a Certificate of Rating A. Majid.... ASTA Observer ASTA

RECORD OF PROVING TESTS Page 4 of 6 Laboratory Reference No.AR/L/6/21 Date of Tests December 25 March 26 Atmospheric Conditions Table 1 Recorded atmospheric conditions Date of Test(s) 8 12 25 9 12 25 2 3 26 Atmospheric Pressure (millibar) 759.7 775.5 756.7 Ambient Temperature ( C) 16.5 15. 15. Table 2 Results of DC voltage tests at 6Uo Test Arrangement DC Test Voltage (kv) Test Duration (minutes) Comments Test Number HT on commoned phases L1, L2, L3 with cable screen EARTHED 38.1 15 Withstand TN5128/D1 Table 3 Results of AC voltage tests at 4.5Uo Test Arrangement Test Voltage (kvrms) Test Duration (minutes) Comments Test Number L3 28.6 5. Withstand TN5128/D2 L2 28.6 5. Withstand TN5128/D3 L1 28.6 5. Withstand TN5128/D4 Note HT applied to each phase in turn with the other two phases and screen EARTHED This is not a Certificate of Rating A. Majid.... ASTA Observer ASTA

RECORD OF PROVING TESTS Page 5 of 6 Laboratory Reference No.AR/L/6/21 Date of Tests 9 December 25 Table 4 Sample of results of cable conductor, external surface and ambient temperature during 2hr stabilization period Time (seconds) Conductor Temperature ( C) External surface Temperature ( C) Ambient Temperature ( C) 18 82.13 63.15 15.65 118 82.9 63.3 16.18 128 82.29 63.56 15.9 138 82.4 63.42 15.94 148 82.16 63.44 16.5 158 81.41 63.61 16.6 168 82.34 63.48 16.8 178 82.28 63.13 16.9 188 81.8 62.69 16.24 Note: For the elevated temperature tests, the cable is energised and heated to the stabilized external surface temperature for at least 2hrs (i.e to 63 C) before application lightning impulse tests Test Arrangement Table 5 Results of lightning impulse voltage tests at elevated temperature (63 C) Applied Test Voltage (kvpk) Polarity ± 1 2 3 4 5 6 7 8 9 1 Test Number L3 96.1 96. 95.2 95.8 94.9 95.2 95.4 95.2 95.6 95.4 TN5129/D1 + 95. 94.5 94.8 94.6 95.4 95.5 95.5 95.7 95.6 95.2 TN5129/D2 L2 + 95. 95.5 95.7 95.6 95.3 95.9 94.5 95.4 95.3 94.7 TN5129/D3 95.1 95.7 95.9 95.7 95.4 95.3 95.4 95.5 95.4 95.6 TN5129/D4 L1 + 95. 95.5 95.7 95.6 95.3 95.9 94.5 94.4 95.3 94.7 TN5129/D5 94.7 94.5 94.9 95.1 95.2 94.9 95.2 95.3 94.2 95.4 TN5129/D6 This is not a Certificate of Rating A. Majid.... ASTA Observer ASTA

RECORD OF PROVING TESTS Page 6 of 6 Laboratory Reference No.AR/L/6/21 Date of Tests 21 March 25 Table 6 Results of AC voltage tests at 3.Uo Test Arrangement Test Voltage (kvrms) Test Duration (hours) Comments Test Number L1 19.1 4. Withstand TN5128/D4 L2 19.1 4. Withstand TN5128/D5 L3 19.1 4. Withstand TN5128/D6 Note HT applied to each phase in turn with the other two phases and screen EARTHED Test Arrangement Table 7 Results of lightning impulse voltage tests at ambient temperature (15 C) Applied Test Voltage (kvpk) Polarity ± 1 2 3 4 5 6 7 8 9 1 Test Number L2 95. 95.2 95.4 95.3 95.2 95.1 95.1 95.1 95.2 95.2 TN6321/D1 + 94.5 94.8 94.8 94.6 95.2 95.1 95.2 94.9 95. 95.1 TN6321/D2 L1 + 94.7 94.7 94.6 94.7 94.8 94.8 94.7 94.6 94.8 94.6 TN6321/D3 94.6 95.2 95.5 95.7 95.5 95.3 95.3 95.2 95.4 95.3 TN6321/D4 L3 95.5 95.4 95.3 95.6 95.4 95.5 95.5 95.2 95.5 95.4 TN6321/D5 + 94.6 95. 95.2 94.1 94.8 95. 94.8 95.4 95. 95.4 TN6321/D6 Table 8 Results of AC voltage tests at 2.5Uo Test Arrangement Test Voltage (kvrms) Test Duration (minutes) Comments Test Number L1 15.9 15. Withstand TN6321/D7 L2 15.9 15. Withstand TN6321/D8 L3 15.9 15. Withstand TN6321/D9 Note HT applied to each phase in turn with the other two phases and screen EARTHED This is not a Certificate of Rating A. Majid.... ASTA Observer ASTA

Impulse Generator Number of Stages - Variable Stage Capacitors - C1,C2, etc. Tail Resistors - Rt Front Resistor - Rf Charging Resistors - Rc Voltage Divider Rf Rt C2 Divider C1 Rt Rc Test Specimen Rc Charging Unit Resistance Divider V Stage kv Meter Measuring System Typical Test Circuit for Impulse Tests TLAB/5/11a

9 8 7 6 5 4 3 2 1 Calibration / Thermal Cycle Conductor Insulation Ambient 169 338 57 676 845 114 1183 1352 1521 169 1859 228 2197 2366 Time (seconds) Fig. 1 Temperature (degc)

Elevated temperature of the external surface during lightning impulse tests 7 Temperature (degc) 6 5 4 3 2 1 14 28 42 56 7 84 98 112 126 14 154 168 182 Time (minutes) Fig. 2

7 6 5 4 3 2 1 Electrical heat cycles in AIR 18 36 54 72 9 18 126 144 162 18 198 216 234 252 27 288 Time (seconds) Fig. 3 Temperature (degc)

Electrical heat cycles in WATER 7 6 5 4 3 2 1 28 416 624 832 14 1248 1456 1664 1872 28 2288 2496 274 2912 Time (seconds) Fig. 4 Loop 2 Temperature (degc)

L3 lightning impulse voltage test at elevated temperature shot 1 of 1 Vpk = -96.1kV ; T1=1.44µs ; T2=48µs (TN5129/D1) -1-2 -3-4 -5-6 -7-8 -9-1 2 4 6 8 1

-1-2 -3-4 -5-6 -7-8 -9-1 L3 lightning impulse voltage test at elevated temperature shot 1 of 1 Vpk = -95.4kV ; T1=1.44µs ; T2=48µs (TN5129/D1) 2 4 6 8 1

L3 lightning impulse voltage test at elevated temperature shot 1 of 1 Vpk = +95.kV ; T1=1.44µs ; T2=48µs (TN5129/D2) 1 9 8 7 6 5 4 3 2 1 2 4 6 8 1

L3 lightning impulse voltage test at elevated temperature shot 1 of 1 Vpk = +95.2kV ; T1=1.44µs ; T2=48µs (TN5129/D2) 1 9 8 7 6 5 4 3 2 1 2 4 6 8 1

L2 lightning impulse voltage test at elevated temperature shot 1 of 1 Vpk = +95.kV ; T1=1.44µs ; T2=48µs (TN5129/D3) 1 9 8 7 6 5 4 3 2 1 2 4 6 8 1

L2 lightning impulse voltage test at elevated temperature shot 1 of 1 Vpk = +94.7kV ; T1=1.44µs ; T2=48µs (TN5129/D3) 1 9 8 7 6 5 4 3 2 1 2 4 6 8 1

-1-2 -3-4 -5-6 -7-8 -9-1 L2 lightning impulse voltage test at elevated temperature shot 1 of 1 Vpk = -95.1kV ; T1=1.44µs ; T2=48µs (TN5129/D4) 2 4 6 8 1

-1-2 -3-4 -5-6 -7-8 -9-1 L2 lightning impulse voltage test at elevated temperature shot 1 of 1 Vpk = -95.6kV ; T1=1.44µs ; T2=48µs (TN5129/D4) 2 4 6 8 1

L1 lightning impulse voltage test at elevated temperature shot 1 of 1 Vpk = +95.kV ; T1=1.44µs ; T2=48µs (TN5129/D5) 1 9 8 7 6 5 4 3 2 1 2 4 6 8 1

L1 lightning impulse voltage test at elevated temperature shot 1 of 1 Vpk = +94.7kV ; T1=1.44µs ; T2=48µs (TN5129/D5) 1 9 8 7 6 5 4 3 2 1 2 4 6 8 1

-1-2 -3-4 -5-6 -7-8 -9-1 L1 lightning impulse voltage test at elevated temperature shot 1 of 1 Vpk = -94.7kV ; T1=1.44µs ; T2=48µs (TN5129/D6) 2 4 6 8 1

-1-2 -3-4 -5-6 -7-8 -9-1 L1 lightning impulse voltage test at elevated temperature shot 1 of 1 Vpk = -95.4kV ; T1=1.44µs ; T2=48µs (TN5129/D6) 2 4 6 8 1

L2 lightning impulse voltage test at ambient temperature shot 1 of 1 Vpk = -95.kV ; T1=1.14µs ; T2=47.4µs (TN6321/D1) -1-2 -3-4 -5-6 -7-8 -9-1 2 4 6 8 1

L2 lightning impulse voltage test at ambient temperature shot 1 of 1 Vpk = -95.2kV ; T1=1.14µs ; T2=47.4µs (TN6321/D1) -1-2 -3-4 -5-6 -7-8 -9-1 2 4 6 8 1

L2 lightning impulse voltage test at ambient temperature shot 1 of 1 Vpk = +94.5kV ; T1=1.14µs ; T2=47.4µs (TN6321/D2) 1 9 8 7 6 5 4 3 2 1 2 4 6 8 1

L2 lightning impulse voltage test at ambient temperature shot 1 of 1 Vpk = +95.1kV ; T1=1.14µs ; T2=47.4µs (TN6321/D2) 1 9 8 7 6 5 4 3 2 1 2 4 6 8 1

L1 lightning impulse voltage test at ambient temperature shot 1 of 1 Vpk = +94.7kV ; T1=1.14µs ; T2=47.4µs (TN6321/D3) 1 9 8 7 6 5 4 3 2 1 2 4 6 8 1

L1 lightning impulse voltage test at ambient temperature shot 1 of 1 Vpk = +94.6kV ; T1=1.14µs ; T2=47.4µs (TN6321/D3) 1 9 8 7 6 5 4 3 2 1 2 4 6 8 1