Caution: Installation and Operation Instructions. Locking Mechanism (if supplied) Set Screws Backed Out. Mounting Orientation

Similar documents
GP-SD GENIE PROBE SMALL DIAMETER

MUELLER. Improved, Centurion Series, Modern Improved, and 107. Fire Hydrants. Inserting Extension Sections. Reliable Connections

MUELLER. Improved, Centurion Series, Modern Improved, and 107. Fire Hydrants. Inserting Extention Sections. Reliable Connections

Fisher 667 Diaphragm Actuators Size 80 and 100

General Four-Way Operation, Maintenance & Service Manual

Fisher 667 Diaphragm Actuator Sizes 30/30i 76/76i and 87

H2-50 Hydrogen Generator Field Update

SERVICE INSTRUCTIONS Model 9670 Lubricant Pump

RIPPER PEDAL. Bearing / Axle Replacement. ( Disassembly )

Mounting Instructions For 3-Piece Namur Style Mounting Bracket To 2-Way 60 Series Valves

#4500 BULLET SIZER & LUBRICATOR

Fisher 1052 Size 20 Diaphragm Rotary Actuator with H Mounting Adaptation

Series B Medical Gas Service Outlet Upgrade Kits

Engineering Data Single Reduction Parts List Item # Description Basic Single Reduction Unit 1. Gear Housing 2. Pipe Plug 3. Vent Plug 4. Splash Guard

CV Control Valves Installation and Operation Manual

STEINBERGER TRANSTREM (TYPE 2) TECHNICAL DOCUMENT

Installation, Operation & Maintenance Manual

caroma marc newson shower mixer

MSR/MSB Mechanical Setting Tool

PORTABLE PULL TESTER

Traditional Wall Mounted Potfiller

SINCE 1922 P UBLICATION N O

Fisher 657 Diaphragm Actuators Size 80 and 100

OTECO INC. MODEL ,000 PSI 4-1/16 PORT DM GATE VALVE MAINTENANCE MANUAL

Due to possible damage in shipping, the vertical stop assembly has been removed from this machine.

Quill Stop V2 Installation Guide 11/16/2014

SERIES I MILLING MACHINES

YALE FIGURE 500 & 500R CLOSURE OPERATION AND MAINTENANCE INSTRUCTIONS

MSR/MSB Mechanical Setting Tool

FIXTURE INSTALLATION GUIDE Model T21T (Low Voltage Pendant Set 120V)

Installation Instructions

Installation Instructions

PULL-THRU USER S MANUAL

Dynamic Nanospray Probe (NSI-1) Installation Guide

4.2 - PUMP MAINTENANCE MODELS: AC, AS, WC, WS

AFP Pneumatic Rotary Actuator User s Instructions

7878 K940. Checkpoint Antenna. Kit Instructions. Issue B

Technical T-A & GEN2 T-A GEN3SYS APX. Revolution & Core Drill. ASC 320 Solid Carbide. AccuPort 432. Page CONTENTS. Set-up Instructions 256

QB78 CO 2 Pellet Rifle

Removing and Replacing the Y-truck

ABM International, Inc.

400 SERIES GRINDER PUMPS 41502, 42202,43302, AND MODELS

SUPER PRO GUN & SUPER PRO GUN II

Operating, Servicing, and Safety Manual Model # 100 Standard Hydraulic Tubing Notcher Model #100-U Heavy Duty Hydraulic Tubing Notcher

Band-Master ATS Nano Pneumatic Banding Tool Operating Instructions

GlideRite Retractable Cover System For Hot Spot Spas (SE & SLX only)

Introduction... 2 Scope of Manual... 2 Description... 2 Specifications Installation... 2 Actuator Mounting... 3 Loading Connection...

MODEL SK61732 COMPRESSOR SERVICE KIT

Fig Remove chain cover plate bolts. Fig Remove hammer member. Fig Loosen set screws at base of 12-tooth sprocket.

25000 Series Lo-T TM Butterfly Control Valve Instructions

Installation and Assembly - Universal Articulating Swivel Double-Arm for 42" - 60" Plasma Screens

For additional assistance call

Additional Information

Lumber Smith. Assembly Manual. If you are having problems assembling the saw and need assistance, please contact us at:

Maintenance Information

INSTALLATION INSTRUCTIONS

w w w. h d o n l i n e s h o p. d e TIMKEN BEARING CONVERSION TOOL GENERAL INSTALLATION -J04672 REV Kit Number Models

EXIT DEVICE OPERATION FIRE DOOR LABELS, STRIKES AND FRAME SCREWS FOR INFORMATION CALL OR VISIT RITEDOOR.COM

AR15 SUPER SLIM AND ULTRA SLIM FREE FLOAT RAIL SYSTEMS

Installation and Assembly - Universal Articulating Swivel Double-Arm for 42" - 60" Plasma Screens

HOW TO TUNE A QB SERIES CO2 AIRGUN FOR NOOBS.

INSTALLATION INSTRUCTIONS

FLOE DOCK FURNITURE WARNING ASSEMBLY INSTRUCTIONS

U.S. Rack, Inc Falcon Drive, Madera, CA APR17 INSTALLATION AND USE INSTRUCTIONS for SIDE-MOUNT LADDER RACK

Bath Accessory Installation

INSTALLATION INSTRUCTIONS

MALEKO WALL-MOUNT FAUCET INSTALLATION

Installation Instructions

Installation, Operation & Maintenance Manual

caroma marc newson wall basin mixer

LPK1550 Hydraulic Crimping Tool 15-ton

Strata. urniture. Adriana Instructions. Parts in the Arm Box: Parts in the Body Box: Watch our assembly videos at

M14 MODULAR CHASSIS SYSTEM (MOD 1) INSTRUCTION MANUAL. West Springfield, MA Phone: (866) FAX: (413)

STRINGING MACHINE OWNER'S MANUAL. Copyright 1998 GAMMA Sports - All Rights Reserved

Cut-True 16M Manual Paper Cutter

ONASSIS SHOWER SET INSTALLATION

M14 MODULAR CHASSIS SYSTEM (MOD 1) INSTRUCTION MANUAL. West Springfield, MA Phone: (866) FAX: (413)

AXIOM Rifle Stock. Owner s Manual. Installation Instructions

WILLIS WIDESPREAD FAUCET

ASSEMBLY GUIDE. Mia Narrow Bookcase

Product Overview. Model RP-2 ( ) Utilized poppet style checks and a CDHS-20 relief valve.

VICTORIAN WIDESPREAD FAUCET

Stuff-Your-Stuff Platform Bed (Twin and Full)

BBF Series Blower Base Frame Assembly Instructions Rev.: BFA-9105

GlideRite Retractable Cover System For HotSpring & Tiger River Spas (except Classic & pre-2000 Landmark Spas)

Reliance SG800 Series Steel Water Gage Valves

Reliance SG777 Series Steel Water Gage Valves

The Virgo/Libra Steam Engine

Installation Instructions 8115F 8115SF

MantelMount. TM1A Installation Instructions IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS

RTI TECHNOLOGIES, INC.

model tsa-sa48 Sliding Crosscut Table installation guide

Setup & Operating INSTRUCTIONS. for (FOR PIN FITTING AND ROD RECONDITIONING)

For installation assistance, contact SARGENT at DOORS SHOWN HERE SWING IN FOR ILLUSTRATION PURPOSES ONLY.

SE5a Instrument Board part 2 - rev 1.1

INSTALLATION OF WELLS SUPER QUICK CHUCK LEFT HAND ON RED WING LATHE

Hollywood Swing Away 2 and 4 Bike Racks Assembly and Installation Guide

SECTION 7. SAFETYING

400A 40113V, 401A 40120V, & 401AL 40120VL ALUMINUM VERTICAL 4000 LB LIFT INCLUDES SCREW LEG ASSEMBLY INSTRUCTIONS

TECHNICAL INSTRUCTIONS

Transcription:

Genie Probe Regulator (GPR)/ Genie Probe (GP2)/ Genie Probe for Composite Sampler (CSA)/ And (Model H) Installation and Operation Instructions Caution: Not designed for external fire. Prior to use in a system, a properly sized relief device is to be installed which limits the use to 110% of the MAWP. Revision 0514 s Locking Mechanism for Genie Probe Regulator or Genie Probe Locking Mechanism (if supplied) Set Screws Backed Out Vertical Set Screws To ensure that the is never accidentally loosened or removed a Locking Mechanism is provided. Horizontal Set Screws Set Screw A+ Corporation s Locking Mechanism ensures that the can only be removed intentionally or knowingly. TOP VIEW Set Screws Fully Engaged CUP POINT SOCKET SET SCREW BOTTOM VIEW Foot 3 4 Locking Mechanism Thread Sealant Area for Genie Probe Regulator Or Genie Probe Turn locking mechanism on the housing (counter-clockwise) until it is at its extreme upper position. Apply thread sealant to thread area below vertical slot in threads. Recommended thread sealant: 4 wraps of Mil Spec A-A 58092 nickel Teflon Tape thread sealant Mounting Orientation Vertical (preferred), or 45 maximum angle relative to vertical required Do not allow thread sealant to invade slot, otherwise it may interfere with locking mechanism. 5 6 1

¾ NPT Confirm that the pipeline has been depressurized. Insert the housing into the depressurized pipeline thru a ¾ NPT An optional 1 NPT is available. 7 The GP-Gage Tool can be used as a gage in s to help install the NPT threaded portion of the properly into the pipeline. The GP Gage Tool is designed to move freely up and down in the housing (ie. The housing is not collapsed indicating that the housing has not been over tightened). Refer to the GP-Gage Installation and Operation Instructions. Optional Accessory Bottom of First Vertical Locking Mechanism Foot valve Dowel Dowel 8 s Using a wrench and the wrench flats, turn the housing until it is secure and sealed. s Wrench flats 180 0 apart DO NOT OVERTIGHTEN Typically 3-5 turns is sufficient. The may be damaged if over tightening causes the housing to swage. Locking mechanism Turn the locking mechanism clockwise until it first touches the top of the. To position the housing or to seal, a maximum of one additional turn can be used. 9 10 Thread Allen screw 1/8 Allen wrench Turn the locking mechanism counterclockwise until the Allen screw is aligned with the thread slot. Using a 1/8 Allen wrench, tighten the Allen screw until its tip is tight against the slot. Do not over tighten Allen screw, otherwise wall may become indented. (3/32) Allen Wrench Using a (3/32) Allen wrench, tighten the Allen screws on the locking mechanism s surface until their tips are firmly set into the s upper surface. 11 Set screws 12 2

Set screw tip The housing is now installed. The locking mechanism should prevent the housing from becoming unintentionally unscrewed from the thread-olet. The pipeline may now be repressurized. Once the is installed, the GPR can now be inserted as per the instructions beginning with Slide #13. Install the Weather Head or stainless steel plug that prevents foreign objects from entering cavity on the if the Probe will not be installed at this time. Weather Head or GPR/GP Plug 13 14 The Weather Head or stainless steel plug that prevents foreign objects from entering cavity should have been installed on the. Weather Head GPR/GP2 Probe or GPR/GP Plug 15 16 If present remove the weather head or plug and confirm that no foreign objects are in the cavity. Use a light source (flashlight) to view the top of the Foot and stem. Protection begins with the Robust Foot design. Foot Foot Opened Closed 1 st Vertical Look inside cavity A stainless steel spring provides the initial upward force to close the foot valve. The process pressure provides additional force after the foot valve is closed. Horizontal 2 nd Vertical 17 18 3

GP2 & GPR HOUSING With 2 sets of Zig-Zag s Confirm that the allen cap screw head s hollow hex cavity is free from foreign material (I.e. Confirm that it is clean.) 19 Allen cap screw 20 Confirm that the Allen cap screw that holds the Ferrule is torqued wrench-tight. The torque value should be 10 inch/lb. If the allen cap screw is only hand tight, not wrench tight to the appropriate torque value, the screw may protrude excessively. The extra Probe length may prematurely actuate the Foot when the Probe is installed into the. Step #1 Screw Gauge GPR Probe Rotate the pressure adjustment screw fully counter- clockwise (unscrew it) until it rotates freely Close the ball valve on the regulator outlet if so equipped. (Handle at 90 0 angle) Ball 21 22 Outlet Port Flats GP2 Probe First install a valve in the GP2 outlet port (1/8 NPT female) as shown. Close the valve before inserting the GP2 into its housing. CAUTION Failure to install and close the valve will result in full line pressure at the outlet port, and the unrestricted flow could damage the foot valve o-ring. Use a backup wrench on the wrench flats during valve installation. 21 Composite Sampler Inlet Composite Sampler Adapter CSA Probe = GP2 Probe with Composite Sampler Adapter attached CSA Probe Install the Composite Sampler with its inlet valve closed onto the Probe. The valve must be closed before inserting the Probe into its housing. CAUTION Failure to install and close the valve will result in full line pressure at the outlet port, and the unrestricted flow could damage the foot valve o-ring. Use a backup wrench on the wrench flats during valve installation. 22 4

Step #2 Probe Step #3 Probe 1 st Vertical Spring Guard Horizontal 2 nd Vertical Position the membrane end of Probe above the installed housing Slowly and carefully, lower the Probe into the. (Avoid membrane contact with upper section of housing.) Do not apply any downward force. The Probe should easily slide into the. Base Plate Only lower the probe far enough to thread the insertion nut one complete thread. Do not apply any downward force by hand to the Probe. Do not unscrew the in this procedure once it has been engaged. (The pins are in the 1st vertical slot.) 25 26 Step #4 Probe Step #5 Probe Thread the down by hand, lowering the Probe until the insertion washer pins slide to the bottom of the the first vertical slot. The threaded nut on the ensures that if all other safety procedures are disregarded, it is mechanically impossible to remove the Probe. (The pins are at the bottom of the 1st vertical slot.) Rotate Probe counter clockwise until the pins are to the far right in the horizontal slot. At this point the Probe is sealed against the interior wall. (The pins are in the middle of the 2nd vertical slot.) 27 28 Step #6 Probe Loosen the until it is above the top of 2 nd vertical slot. The Probe should not rise to the top of the 2 nd Vertical. If the Probe rises in the 2 nd Vertical slot, the Foot O-ring may have been damaged or attacked by the process. The threaded nut on the ensures that it is mechanically impossible to remove the Probe. Perform the next step regardless of the status of the Foot O-ring. (The pins are in the middle of the 2nd vertical slot.) 29 Step #7 *Threaded Atm. Reference option (not shown) *The Genie port that is not labeled is an atmospheric reference port for the regulator. It is threaded so that optional tubing can be connected to this port to enable a captured vent if so required; however, this port should NOT be plugged or the performance of the regulator will be affected. Probe Tighten the (by hand) until it is against the again. Using a wrench, tighten the against the so that the s are at the bottom of the 2 nd Vertical slot. At this point the Foot opens and the insertion process is complete. (Perform this step regardless of the status of the Foot O- ring) (The pins are at the bottom of the 2nd vertical slot.) 30 5

Step #8 Screw Lock Gauge Ball GPR Probe At this point the sample pressure can be adjusted to the desired value. This is accomplished by turning the pressure adjustment screw clockwise. To allow sample flow, slowly open external valving. Step #9 Screw Lock Gauge Ball GPR Probe At high supply pressure, a sudden change may be observed on the downstream pressure gauge as the valve stem moves away from the seat. Slight readjustments may be necessary until the pressure and flow have equilibrated. Tighten the pressure adjustment screw lock nut firmly against the washer to prevent unintended changes in pressure adjustment. 31 32 GPR Probe Installed into its Screw Gauge Lock GPR Probe Ball The GPR/GP2 can be easily retracted from its. GPR/GP 33 34 Step #1 Shut flow completely off by closing external valving before beginning to retract the GPR or GP2 Probe. CAUTION-Failure to shut off sample flow may result in damage to housing foot valve seal. Confirm that the adjustment screw is completely counter clockwise on GPR or the valve connected to the Outlet Port on GP2 Probes is closed. Using a wrench, loosen the nut by rotating it counterclockwise until it can be turned by hand. Step #2 Loosen nut further by hand until the nut just clears the insertion washer. Do not unscrew the nut beyond the top of the 2 nd vertical slot. The pins will now be at the top of the second vertical slot. They are held there by the force of supply gas trapped between the foot valve and probe housing seals. (The pins are at the bottom of the 2nd vertical slot.) The foot valve is closed at this point. 35 (The pins are at the top of the 2nd vertical slot.) 36 6

Step #3 Bleed down the sample pressure by allowing sample to flow externally. The Probe should fall until the pins align with the horizontal slot indicating that the Foot is closed and the o-ring is sealed properly Once you have utilized the safety feature of the 2 nd Vertical to confirm the status of the Foot O-ring, only then can you remove the Probe. The thread engagement of the and the safety feature of the 2 nd Vertical slot ensure that the Probe can not exit the any other way than the correct retraction method. (The pins are in the middle of the 2nd vertical slot.) 37 Horizontal (Not visible in photo) Retraction The sample pressure is relieved by allowing sample to flow externally. The Probe can now be easily pushed downward until the pins align with the horizontal slots, confirming the foot valve closed correctly Even if Foot failure would possibly occur, the Foot leak rate would prevent you from pushing the probe downward until the pins align with the horizontal slots. 38 Step #4 CAUTION: If the pressure is not reduced to zero,use the wrench to tighten the nut pushing the probe back into the housing and contact A+ Corporation or its representative. Rotate the Probe clockwise until the pins enter first vertical slots. Make sure the stays threaded on the. (The pins are at the bottom of the 1st vertical slot.) 39 40 Step #5 Step #6 Confirm that no upward force from the supply pressure is present. (I.e. the is not forced against the as it is unthreaded.) After confirmation that no upward force from the supply pressure is present, completely unthread the and lift the Probe upward from the housing. (The pins are in the middle of the 1st vertical slot.) Spring Guard During the retraction, keep the Probe centered in the housing to avoid membrane damage by contact with the upper section of the housing. 41 42 7

Step #7 screw Regulator housing Once the Probe clears the housing it may be placed on its side on a flat surface. washer ferrule Locking nut 43 8