ECE 528 Understanding Power Quality

Similar documents
Protective Relaying for DER

Babak Enayati National Grid Thursday, April 17

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

Phase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star.

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

Focused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection

E N G I N E E R I N G M A N U A L

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

BED INTERCONNECTION TECHNICAL REQUIREMENTS

This document covers common questions concerning the design of an effectively grounded system.

The Connecticut Light and Power Company

Renewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA

Generation Interconnection Requirements at Voltages 34.5 kv and Below

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

Utility Interconnection and System Protection

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

TECHNICAL GUIDELINE FOR THE INTERCONNECTION OF DISTRIBUTED ENERGY RESOURCES TO EPCOR DISTRIBUTION AND TRANSMISSION INC. S DISTRIBUTION SYSTEM

Harmonic control devices. ECE 528 Understanding Power Quality

Notes 1: Introduction to Distribution Systems

Table of Contents. Introduction... 1

2012 Grid of the Future Symposium. Impacts of the Decentralized Photovoltaic Energy Resources on the Grid

Harmonic Distortion Evaluations

Harmonic control devices

Modelling Parameters. Affect on DER Impact Study Results

Experiences in Integrating PV and Other DG to the Power System

System Protection and Control Subcommittee

Wind Power Facility Technical Requirements CHANGE HISTORY

Education & Training

ECE 528 Understanding Power Quality

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

Islanding Detection Method Based On Impedance Measurement

Course 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC)

International White Book on DER Protection: Review and Testing Procedures

Impact of High PV Penetration on Grid Operation. Yahia Baghzouz Professor of Electrical engineering University of Nevada Las Vegas

Grid Converters for Photovoltaic

EE Lecture 14 Wed Feb 8, 2017

Connection Impact Assessment Application

Distributed Solar Integration Experiences

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS

ECE 528 Understanding Power Quality. Paul Ortmann (voice) Lecture 6

Harmonic Distortion Levels Measured at The Enmax Substations

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

GENERATOR INTERCONNECTION APPLICATION Category 3 For All Projects with Aggregate Generator Output of More Than 150 kw but Less Than or Equal to 550 kw

ECE 528 Understanding Power Quality

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

GUIDE FOR GENERATOR INTERCONNECTION THE WIRES OWNER DISTRIBUTION SYSTEM

Information and Technical Requirements For the Interconnection of Distributed Energy Resources (DER)

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

Module 9. Fault Type Form 4.X RELIABILITY ACCOUNTABILITY

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

Technical Requirements For Generation Connected to The ODEC System

Solutions to Common Distribution Protection Challenges

DISTRIBUTION ENGINEERING PRACTICES

Revised IEEE 1547 Standard for Interconnecting Distributed Energy Resources with Electric Power Systems- National Grid Solar Program

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Overvoltage and undervoltage. Dr Audih 1

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance

Southern Company Interconnection Requirements for Inverter-Based Generation

INTERCONNECTION REQUIREMENTS FOR PARALLEL OPERATION OF GENERATION GREATER THAN 50 KW CONNECTED TO THE PECO DISTRIBUTION SYSTEM

FACILITY CONNECTION REQUIREMENTS

Distance Relay Response to Transformer Energization: Problems and Solutions

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY

IEEE sion/1547revision_index.html

O V E R V I E W O F T H E

Anti-IslandingStrategyforaPVPowerPlant

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:

BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP

NERC Protection Coordination Webinar Series July 15, Jon Gardell

Fuel cell power system connection. Dynamics and Control of Distributed Power Systems. DC storage. DC/DC boost converter (1)

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

Appendix C-1. Protection Requirements & Guidelines Non-Utility Generator Connection to Okanogan PUD

Summary of the Impacts of Grounding on System Protection

Protecting Feeders With Distributed Resource Scott Elling HDR Inc HDR, all rights reserved.

Substation applications

ECE 528 Understanding Power Quality

Islanding and Detection of Distributed Generation Islanding using Negative Sequence Component of Current

Embedded Generation Connection Application Form

Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Phase Shifting Transformers. Presented by

69 kv to 500 kv INTERCONNECTION REQUIREMENTS FOR TRANSMISSION FACILITIES

Protection of distributed generation interfaced networks

TABLE OF CONTENT

Implementation of Revised IEEE Standard 1547

U I. HVDC Control. LCC Reactive power characteristics

GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS

Generation and Load Interconnection Standard

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

Project Report. Project #: TIC706.1-A Islanding Risk of Synchronous Generator Based Distributed Generation Systems. Draft to be approved.

ECE 528 Understanding Power Quality

Table of Contents. 1.0 Intent and Limitations Intent Limitations Contact Information General Requirements...

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

Transcription:

ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 22 1 Today Homework 5 questions Homework 6 discussion More on DER Power Quality, and Reliability Islanding Transformer connections DER Protective Relaying Some information for today s lecture came from Development and testing of an Approach to Anti- Islanding in Utility-Interconnected Photovoltaic Systems Sandia Report SAND 2000-1939, August 2000. Available at: http://www.osti.gov/scitech/servlets/purl/759506 Lecture 22 2 1

Operating conflicts Distribution system engineering challenges: DER will likely require changes to the distribution system protection and voltage regulation scheme Changes made to accommodate DER must still provide acceptable system protection and voltage regulation when DER is not online Complex modeling and analysis may be required to identify and resolve potential operating conflicts Lecture 22 3 Wind generation versus load (Note: vertical scales are not the same) Lecture 22 4 2

Islanding 1547: A condition in which a portion of an Area Electrical Power System (EPS) is energized solely by one or more Local EPSs through the associated PCCs while that portion of the Area EPS is electrically separated from the rest of the Area EPS on all phases to which the DER is connected. Islands may be intentional or unintentional Lecture 22 From IEEE Std.1547-2003 5 Area EPS, Local EPS, PCC, Poc Lecture 22 6 3

Issues with unintentional islands for the area EPS Safety DER could energize a portion of an Area EPS thought to be de-energized, placing line workers and the public at risk Power Quality Voltage regulation and distortion in an island may be significantly poorer than they were prior to the formation of the island Reliability Islands may increase the time required to restore normal system operation following a fault Lecture 22 7 Issues with unintentional islands for the DER Protective devices on the area EPS (reclosers, substation circuit breakers, etc.) are normally designed to protect radial systems The synchronism of any downstream DER is not checked when they reclose Reclosing on out-of-phase rotating generators or inverters could damage them The DER protection and control system must incorporate appropriate protection DER must protect itself Lecture 22 8 4

Issues with unintentional islands 1547 Synchronization limits The area EPS protective devices don t monitor these parameters Lecture 22 9 Preventing unintentional islands The Sandia destabilizing signal in inverters Inverter controls raise a rising frequency or lower a dropping frequency The power system frequency normally fluctuates very slightly, and acts to correct the inverter frequency Without the large power system to correct the frequency, the destabilizing signal in the inverter controls quickly drives the frequency to an over- or under-frequency condition, and frequency relays trip the inverter Lecture 22 10 5

Preventing unintentional islands Load/generation imbalance Relies on an intentional and significant difference between the DER output and the local load DER may be operated at constant power factor or constant reactive power, and not permitted to regulate voltage When an island forms, the mismatch between the DER and the load will quickly cause detectable voltage and/or frequency variations Lecture 22 11 Island detection difficulties It may not be possible to ensure that there is always a significant load/der imbalance Multiple DER units may act together to support an island (destabilizing signal should still work here) Multiple DER units in an area are common where some natural resource makes DER attractive In these cases, it may be necessary to use transfer trip controls a remote trip signal to simultaneously trip multiple DERs Lecture 22 12 6

DER transformer connections and power quality The transformer configuration used to connect the DER to the distribution system can have a significant impact on power quality and reliability There are several options: Grounded wye-wye Delta-wye Delta-delta or ungrounded wye-delta Grounded wye-delta Note: All connections are in system-generator order Lecture 22 13 Grounded wye-wye transformer connection G Most common transformer connection in the US Lecture 22 14 7

Grounded wye-wye transformer connection Advantages: Standard utility transformer replacements available if needed No voltage phase shift simpler relaying and fault detection Ferroresonance is not much of an issue Lecture 22 15 Grounded wye-wye transformer connection Disadvantages: DER can feed any type of primary system fault Passes zero-sequence currents Solutions: A reactor in the neutral will limit the DER contribution to a ground fault and will also reduce zero-sequence current flow between the DER and the distribution system Lecture 22 16 8

Delta-wye transformer connection G Second most common transformer connection in US Most common transformer connection in Europe Lecture 22 17 Delta-wye transformer connection Advantages: Low DER contribution to ground faults Zero sequence harmonics from the DER are blocked Primary single line-to-ground faults do not have as severe an impact on the secondary voltages Lecture 22 18 9

Delta-wye transformer connection Disadvantages: May be difficult for generator protection to detect single line-toground faults on primary system Triplen harmonics from DER may circulate in low-impedance secondary neutral Possible ferroresonance and the need for three-phase switches on the primary side of the transformer Lecture 22 19 Grounded wye-delta transformer connection G Usual connection for substation transformers and central station generators Lecture 22 20 10

Grounded wye-delta transformer connection Advantages: Primary system faults are easily detected by the generator s interconnection protection system Blocks triplen harmonics from the generator Protection scheme is standardized based on utility-owned generator protection systems Lecture 22 21 Grounded wye-delta transformer connection Disadvantages: Acts as a source for ground fault current (See PSQ fig 9.30) May interfere with existing protection systems May cause sympathetic tripping of other feeders during ground faults May make fuse saving impossible Transformer may overheat due to zero-sequence currents Lecture 22 22 11

Protective relaying for distributed generation Purpose of protective relaying Protect the generator Detect abnormal operation Block unsynchronized paralleling Prevent unintentional islands Detect primary system faults Detect conditions indicating islanding Lecture 22 23 Protective relaying for distributed generation Small generators Over/under voltage Over/under frequency Large generators same as above, plus Over/under current Negative sequence voltage and current Synchronizing Many other relays may be used depending on the generator and the particular installation Lecture 22 24 12

DER relay example: Single device incorporates: Undervoltage Overvoltage Under/over frequency Negative sequence voltage Directional power Synchronism check From Schweitzer Engineering Laboratories, SEL-547 Lecture 22 25 Next time Introduction to Industrial Control Systems Download and read: 1. Siemens STEP-training: Control Components http://www.sitrain.us/step/pdfs/control_components.pdf Read through page 18 skim the rest 2. Siemens STEP-training: PLCs http://www.sitrain.us/step/pdfs/plcs.pdf Read: 1-16, 34-51, skim the rest Links are also on PQ links page of class website Lecture 22 26 13