CD-Pxx-00-0 Series Duct Mount CO 2 Transmitter

Similar documents
Installation Instructions

HLC-1000 High-limit Humidity Control

WRZ-RMT10K-0 Wireless Remote Temperature Transmitter

Instruction Manual T5140 T5141 T5145 T5240 T5241 T5245. Programmable transmitter of CO2 concentration with 4-20 ma output. with 0-10 V output

TE-6300P Series Temperature Sensors

GE Sensing. Introduction. Wiring Diagrams (Typical) Field Calibration. Installing the Sensor

CDG. Carbon Dioxide - User Manual Gas Detector. 1 Intended Use. 2 Functional Description. 3 Installation. 4 Electrical Connection.

TS-9100 Electronic Sensors and Transducers. Features and Benefits. G Wide range of enclosures and signal outputs

User Manual. PolyGard AT-2000 V3. Infrared Refrigerant Gas Transmitter Serial No. AT March, 2009

Mid-West. Instrument. Model 140 Electrical Installation and Operating Instructions. Gauge Front ELECTRICAL

WPR400 Wireless Portable Reader

SER8300 Series Terminal Equipment Controller with Optional PIR sensor Installation Guide

QPM Series Indoor Air Quality Duct Sensors

CHAPTER MAINTENANCE AND TROUBLESHOOTING. In This Chapter... Maintenance and Inspection Troubleshooting...6 3

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

DP2500 DP0100 DP0250 Differential Pressure Transmitter

Instruction Manual Model Upconverter

DP2500 DP0100 DP0250 Differential Pressure Transmitter

RSMFX-2R MULTIFUNCTIONAL

Wireless Room Temperature and Humidity Transmitter (Units without Temperature Setpoint or Override) Installation and Operating Instructions

Worldwide Manufacturer of Gas Detection Solutions. Transmitter EC 23. Operation Manual

OSMAC RDR Low-voltage Retrofit Kit

CSD Series Current Devices Solid Core with Relay

VENTI-LIGHT VLD. Ventilatie Indicator G e b r u i k e r s h a n d l e i d i n g. Ampèrestraat NL-1446 TR PURMEREND

- Wiring Brochure Universal Reset Module 423

12V Victor 888 User Manual

Wireless 900 MHz Receiver

Instruction Manual Model Upconverter

M1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL

Roline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL

BAPI-Stat 4 X-Combo, Room %RH and Temp. Sensor BA/BS4XC Installation & Operating Instructions

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

INSTALLATION AND MAINTENANCE MANUAL FOR GROUND MONITOR GM-250 COPYRIGHT 1983 AMERICAN MINE RESEARCH, INC.

Kotron Sentinel Model 804 RF Level Transmitter

AMM-1022 Digital Multimeter USER`S MANUAL

WATTNODE Pulse Output Installation and Operation Manual

SAFETY WARNINGS AND GUIDELINES INTRODUCTION

Section 1, General information Introduction... 3 Description... 3 Specifications... 4 Wiring connections... 5

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards

Technical Instructions Document No EA GQD June 23, OpenAir

IMPORTANT: READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION

IMPORTANT: THIS DEVICE MUST BE PROFESSIONALLY INSTALLED. READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION.

INSTALATION, OPERATION & MAINTENANCE MANUAL. PA-1001A Series SIGNAL CONDITIONER & CONVERTORS

NEO CAR AUDIO. Neo AUXiN AUX INPUT INTERFACE. Instruction Manual

WEL-200 O P E R A T I N G I N S T R U C T I O N S W I R E L E S S E D G E L I N K

SCC-FV01 Frequency Input Module

DM-45 Digital Multimeter

IMPORTANT: THIS DEVICE MUST BE PROFESSIONALLY INSTALLED READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION

SAFETY WARNINGS AND GUIDELINES

MODEL AT-10 ANALOG TRANSMITTER

RM24100A. *Maximum transmit power output levels and local radio frequency regulator bodies must be obeyed in the country of operation.

DU3 Ultrasonic Vehicle Detector

Installation and Operation Manual MSI. Multi-Sensor Interface Hub. Interface Module for all Sensors Network and Wireless CAUTION

ANT400 OPTIONAL REMOTE ANTENNA MODULE

IRIS \ IRIS-I QUICK SET-UP GUIDE STEP 1 INSTALL

Owner s Manual S10 SERIES ELECTRONIC STEP CONTROLLER WITH VERNIER CONTROL

Series 500. Owner s Manual. Analog Transmitters by Data Industrial. Data Industrial. Data Industrial 2/95 PN 72806

USER'S MANUAL DMR-6700

User Manual. PolyGard ADTD Infrared Carbon Dioxide Transmitter Serial No. SM03_00X. October, 2011

Contents. Instruction Leaflet IL E Effective March HMi VU Series Instruction Leaflet. Description... Page. Preface...

USER MANUAL. WBP314P71 active power transducer. (3-phase 4-wired)

IS7705. Installation & Operation Manual AUDIO INTEGRATION KIT. TranzIt LINK

INSTALLATION AND OPERATING INSTRUCTIONS MODEL SIVF. KB Part No Signal Isolator for KBVF Controls. See Page 1 Pending

Electronic Controls For general purpose and multi stages controls. Features and Benefits

12 24 VAC/VDC ±10% (inhibited when voltage is applied) min. pulse width duration = 50 ms. Normal mode or Background Analysis mode

2- and 4-port Transceivers Piercing, N-type, and BNC

How to install your ecobee Switch+

LZS-A500-3 POWER SUPPLY Installation, Operation, and Maintenance Manual. IM-LZSA500-3 January 2008 Revision H

MS2030 CAT III 600 V A V AUTO RS232

TAG5000 WIRELESS PHASER. Instruction Manual HD ELECTRIC COMPANY 1475 LAKESIDE DRIVE WAUKEGAN, ILLINOIS U.S.A.

TE-7700 Series Radio Frequency (RF) Wireless Room Temperature Sensing System

DIN 22.5/17.5 Size Lineup of A Wide Range of Measuring and Monitoring Relays. Model Number Structure

PEN TYPE DIGITAL MULTIMETER OPERATION MANUAL T8211D

Disclaimers. Important Notice

OVEN INDUSTRIES, INC. Model 5C7-362

Document # Rev. C October, GEMINI EXPRESS MULTIPLEXER User s Guide

Ricochet Alphasonic Level Transmitter Model LA15/20 Owner s Manual

User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters

Series R48 Single Zone Load Sequenced Economizer System: Installation & Troubleshooting

H7625A, H7635A, H7626A, H7636A Series 2000 Humidity/Temperature Sensors

Milliamp Calibrator. Model 434. General description. Calibrate with laboratory accuracy. All 4 to 20 ma loop functions

GETTING STARTED GUIDE NI AI, ±60 V, 24 Bit, 1 ks/s/ch Simultaneous

Subject: P0052 Bed Locator Installation Instructions

Global Water Instrumentation, Inc.

Isolated RTD Modules Product Specifications and Installation Data

VSD Series II Variable Speed Micro Drives (VSM II) FS1 FS5

RM24100D. Introduction. Features. 2.4GHz 100mW RS232 / RS485 / RS422 DSSS Radio Modem (IEEE compliant) Operating Manual English 1.

Kotron Sentinel Model 804 RF Level Transmitter

OPTITEMP TT 20 Technical Datasheet

MS8211 DIGITAL MULTIMETER INSTRUCTION MANUAL

USERS GUIDE MATRIX P/N SINGLE DIGITAL INDUCTIVE LOOP SENSOR

TECHNICAL DATASHEET #TD1400AX PWM Controlled Solenoid Driver (DIN rail mount) P/N: PWMC-DR-2A, PWMC-DR-1.2A

Stand Alone Rudder Angle Indicator System

LUDLUM MODEL 182 RADON FLASK COUNTER. June 2011 Serial Number PR and Succeeding Serial Numbers

Technical Instructions Document No EA GQD October 25, OpenAir GQD Series

1. SAFETY INFORMATION.1 2. DESCRIPTION SPECIFICATIONS.6 4. OPERATING INSTRUCTION Voltage measurement Current measurement 10

Model Number Structure

SCADA and Telemetry Solutions. SCADALink IO900. Modular Wireless I/O System. User Manual Version V1.3 for SCADALink IO900 BENTEK SYSTEMS LTD

Global Water Instrumentation, Inc.

YES 12 Charging Wall Cabinet for Mini-laptops

Transcription:

Installation Instructions CD-Pxx-00-0 Issue Date February 4, 006 CD-Pxx-00-0 Series Duct Mount CO Transmitter Application Requirements FCC Compliance Statement This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense. Canadian Compliance Statement This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. Installation IMPORTANT: The CD-Pxx-00-0 Series transmitters are intended to provide input to equipment under normal operating conditions. Where failure or malfunction of the transmitter could lead to an abnormal operating condition that could cause personal injury or damage to the equipment or other property, other devices (limit or safety controls) or systems (alarm or supervisory) intended to warn of, or protect against, failure or malfunction of the transmitter must be incorporated into and maintained as part of the control system. Parts Included The duct mount CO transmitter is shipped assembled. It consists of three main parts: base and Printed Circuit Board (PCB), cover, and mounting flange with four screws (for probe depth adjustment). A conduit adaptor is also included. Mounting Location Considerations When selecting a location for the transmitter, note the following: The transmitter is designed for duct mounting in any position. The probe is best mounted in the return airstream. The device should penetrate the duct by a minimum of 3.0 in. (76. mm) to ensure the sensing part of the element is fully in the airstream. The transmitter should be placed in an area free of condensation. The transmitter is duct mounted using a flange. The mounting flange adjusts the distance between the probe and the inner duct wall. Fasten the mounting flange with the four screws as follows: 1. Loosen the probe retention screw, and separate the flange from the assembled unit.. Drill a hole 7/8 to 1 in. ( to 5 mm) diameter in the duct for the transmitter s probe. 3. Using the mounting flange as a template centered on the hole, drill four 1/8 in. (3.18 mm) holes for the mounting screws positioned as in Figure 1. 1.54 (4) 0.87 () 006 Johnson Controls, Inc. 1 Part No. 4-09601-0, Rev. A www.johnsoncontrols.com Center Hole 1.65 (4) Figure 1: Mounting Holes on the Flange Dimensions in. (mm) 4. Fasten the mounting flange onto the duct using the four screws provided. 5. Insert the probe a minimum of 3.0 in. (76. mm), and tighten the probe retention screw on the mounting flange.

Wiring Power Supply Requirements The transmitter requires a 4 AC/DC, Class power supply maintaining voltages of 18 to 30 DC or 0 to 30 AC. Although the power input includes a halfwave rectifier, using a DC supply is recommended to avoid excessive current peaks (current consumption: peak, 170 ma; average, 85 ma). 4 AC Power Supply Connections When more than one transmitter is connected to one 4 AC transformer, a common loop is formed at the controller, and the risk of a short circuit increases. All commons must be at the same potential. Note: To avoid a short circuit, isolate the 4 power supply by providing a separate transformer for each transmitter as shown in Figure. 4 AC Supply 4 AC Supply Output CO Transmitter Signals Controller ma or + - CO Transmitter + - 0 ma or 0 Shared Common Line Figure : Connecting Separate AC Supplies (Recommended) If several transmitters share one transformer, the phase ( ) must always be the same at each transmitter to maintain polarity and avoid a short circuit via a shared common line at the controller, as shown in Figure 3. 4 AC Supply Supply Output CO Transmitter Signals Controller + ma or - 0 CO Transmitter + - ma or 0 Shared Common Line Connecting the Conduit Adaptor 1. Align the nut with the opening inside the enclosure, and hold it in place.. Insert the adaptor body into the transmitter conduit opening. 3. Manually tighten the adaptor into the nut, turning in a Clockwise (CW) direction (see Figure 4). Nut Adaptor Body Adaptor Figure 4: Inserting the Conduit Adaptor IMPORTANT: Do not overtighten the conduit adaptor to prevent damage or displacement of the PCB. 4. Insert the wires through the conduit adaptor body opening. 5. Tighten the adaptor onto the adaptor body by turning the adaptor in a CW direction. Wiring the PCB To wire the PCB s input and output connections: 1. Open the transmitter cover.. Insert the wire carefully through the conduit adapter and then strip 1/4 in. (6.35 mm) of the wire insulation to prepare the wire for connection to the terminal block. 3. Connect the 4 supply between the positive ( ) and negative () terminals as shown in Figure 5. Figure 3: Connecting One AC Supply to Several Transmitters (Not Recommended) CD-Pxx-00-0 Series Duct Mount CO Transmitter Installation Instructions

X6 0/4mA X7 ma 0 + Wiring the Relay Model CD-PR0-00-0 is shipped with a relay module. To wire the relay, refer to Figure 6, and attach the relay wires to the relay PCB s two screw terminals. Screw Terminals SERIAL COM X5 X3 Figure 5: Transmitter PCB 7 10 Configuring the Output The transmitter is capable of generating either voltage or current output. To select, refer to Figure 5, and: 1. Connect the common wire to Terminal 0.. Connect the other wire to: Terminal (for voltage output) Terminal ma (for current output) and configure the pins marked 0/4mA as follows: - 4 to 0 ma: connect the jumper so that it shorts the pins (default) - 0 to 0 ma: disconnect (do not discard) the jumper 3. If the unit has an optional relay accessory, follow the procedure described in the Wiring the Relay section and then reposition the cover. Connect to X5 Connect to X3 Figure 6: Relay PCB The relay has two setpoint values: the On level and the Off level. These provide hysteresis and desired control function. The On level must be higher than the Off level. When CO concentration is increasing, the relay closes at the On level, and the relay opens when concentration is reduced to the Off level. Note: The default relay setpoints are 1,000 ppm On and 950 ppm Off. Change these settings by entering new values using the Relay Setpoint Software ACC-CD-S. Setup and Adjustments Commissioning Johnson Controls Carbon Dioxide (CO ) transmitters come from the factory calibrated for the following: output signal (0 to 10) proportional to CO concentration (0 to,000 parts per million [ppm]) altitude range of 0 to 1,969 ft (0 to 600m) above sea level without compensation default relay output trigger point of 1,000 ppm CD-Pxx-00-0 Series Duct Mount CO Transmitter Installation Instructions 3

Altitude Compensation The sensors are calibrated for an altitude of 984 ft (300m) above sea level and are intended for applications within the range of 0 to 1,969 ft (0 to 600m) without compensation. For altitudes above 1,969 ft (600m) where optimum accuracy of the CO concentration measurement is essential, modify the Building Automation System (BAS) controller s Analog Input (AI) high range to compensate for sensor placement at other than the standard calibration altitude. Note: For altitude compensation, only adjust the AI high range. The AI low range should remain at zero. To do this, reset the,000 ppm value using the controller s Compensation Factor (CF) shown in Figure 7 or Figure 8 as follows: Corrected alue = CF x,000 For example, if the sensor is situated at an altitude of 3,000 ft (914.4m) above sea level, CF, from either Figure 7 or Figure 8, is 1.10. The new value is calculated as follows: Corrected alue = (1.10)(,000 ppm) =,00 ppm 1.30 1.5 1.0 1.15 CF 1.10 1.05 1.00 0.95 0.90 0 1,000,000 3,000 4,000 6,000 7,000 Altitude (Feet) 1.30 Figure 7: Altitude Compensation in Feet Above Sea Level 1.5 1.0 1.15 CF 1.10 1.05 1.00 0.95 0.90 0 00 400 600 800 1,000 1,00 1,400 1,600 1,800,000,00 Altitude (Meters) Figure 8: Altitude Compensation in Meters Above Sea Level 4 CD-Pxx-00-0 Series Duct Mount CO Transmitter Installation Instructions

Troubleshooting General The transmitter is not field repairable. In the event the unit is not functioning properly, use the following checklist to identify the symptoms and determine a solution. 1. erify that the unit is mounted properly and the appropriate output jumper is selected.. erify that all wiring is correct. 3. erify that the power supply voltage level is 0 to 30 AC or 18 to 30 DC. Note: The diagnostic Light-Emitting Diodes (LEDs) shown in the lower right-hand corner of Figure 5 indicate operational status: 7 lights up if the self-diagnostics procedure detects an abnormality. 10 pulses to indicate that the device is operational. If the transmitter will not operate after completing these steps, replace the unit. Testing the Relay Module To confirm that the relay is operating correctly, perform the following procedure: IMPORTANT: To expose the sensing portion of the probe, loosen the probe retention screw, and remove the probe from the duct. After testing is complete, reinstall the probe, and tighten the probe retention screw. 5. Determine whether the contacts are open or closed. If the contacts are closed, the relay is functioning properly, and no further testing is necessary. If the contacts are open, increase the CO concentration by exhaling near the probe, looking for a change in the resistance value. If no change is noted, confirm that the CO concentration has been raised above the trip point. - Check the transmitter output signal with a voltmeter to make sure the signal has risen above the 1,000 ppm relay trip point. - If the output signal has not reached the trip point, it may be necessary to further increase the CO concentration. If the contacts are open after exceeding the trip point, replace the unit with the appropriate module, and restart this procedure. 6. Disconnect power to the transmitter. 7. Disconnect the multimeter from the relay terminals. 8. Reconnect the wires to the relay screw terminal. 9. Reconnect power to the transmitter. 10. Reposition the cover. 1. Temporarily shut off power to the unit.. Temporarily remove wires connected to the relay screw terminal. 3. Connect a multimeter to the relay terminals. 4. Read the resistance level to determine whether the contacts are open or closed. If the contacts are closed, replace the unit with the appropriate relay module, and restart this procedure. If the contacts are open, apply power to the transmitter. CD-Pxx-00-0 Series Duct Mount CO Transmitter Installation Instructions 5

Technical Data Product CD-Pxx-00-0 Series Duct Mount CO Transmitter Measuring Range 0 to,000 ppm CO Accuracy at 77 F (5 C) Non-Linearity Temperature Dependence of Output Long-Term Stability Response Time (0 to 63%) Operating Temperature Range Storage Temperature Range Humidity Range Transmitter Output Signal < ±[30 ppm CO +.0% of reading] (includes manufacturing deviation and drift). All accuracy specifications reflect testing the transmitters using high-grade, certified gases. Transmitters are intended for an altitude range of 0 to 1,969 ft (0 to 600 m) above sea level without compensation. < 0.5% of Full Scale < 0.056% of Full Scale/F (< 0.1% of Full Scale/C ) < ±5.0% of Full Scale/5 Years 1 Minute 3 to 113 F (-5 to 45 C) -4 to 158 F (-0 to 70 C) 0 to 85% RH (non-condensing) CO Jumper Selectable: 0 to 0 ma or 4 to 0 ma or 0 to 10 DC (Default) Maximum Output Current: 5 ma; Maximum Output : 1.5 Relay Output (Optional) Maximum 30, 0.5A, Class Recommended External Current Output: Maximum 500 ohms Load Resistance Load Output: Minimum 1,000 ohms Load Resistance Power Supply Range 0 to 30 AC (18 to 30 DC), Class Power Consumption Warm-up Time Air Flow Range Duct Probe Material Housing Material Dimensions (H x W x D) Shipping Weight Agency Listings <.5 W Average, 4.1 A < 5 Minutes 0 to 7,500 ft/minute (0 to,86 m/minute) Duct Probe Meets Plenum Rating Requirements of UL 1995, Heating and Cooling Equipment ABS Plastic 3-5/3 x 3-3/16 x 8 in. (80 x 81 x 04 mm) 0.3 lb (140g) UL Listed, CCN XAPX (US) and XAPX7 (Canada); EMC Directive (CE Mark), 89/336/EEC; FCC and DOC Compliant The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Controls Group 507 E. Michigan Street P.O. Box 43 Milwaukee, WI 5301 Printed in U.S.A www.johnsoncontrols.com 6 CD-Pxx-00-0 Series Duct Mount CO Transmitter Installation Instructions