Islanding and Detection of Distributed Generation Islanding using Negative Sequence Component of Current

Similar documents
Doãn Văn Đông, College of technology _ Danang University. 2. Local Techniques a. Passive Techniques

Islanding Detection Method Based On Impedance Measurement

Anti-Islanding Protection of Distributed Generation Resources Using Negative Sequence Component of Voltage

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation

ISLANDING DETECTION FOR DISTRIBUTED GENERATION SYSTEM USING VARIOUS METHODS

Islanding Detection Techniques for Distributed Energy Resources-Review

Renewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

A Novel Islanding Detection Technique for Distributed Generation (DG) Units in Power System

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

Islanding Detection in Hybrid DG based IEEE 14 Bus System using Negative Sequence Component Analysis

Non-detection zone of LOM protection for converter connected wind turbines

Notes 1: Introduction to Distribution Systems

A NEW METHOD FOR ISLANDING DETECTION IN DISTRIBUTED GENERATION

Anti-IslandingStrategyforaPVPowerPlant

E N G I N E E R I N G M A N U A L

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

A Decision Tree Based Approach for Microgrid Islanding Detection

BED INTERCONNECTION TECHNICAL REQUIREMENTS

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

REACTIVE POWER BASED ANTI-ISLANDING SCHEME FOR SYNCHRONOUS DISTRIBUTED GENERATORS

EVALUATION OF ANTI-ISLANDING PROTECTION SCHEMES

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

Wavelet Transform Based Islanding Characterization Method for Distributed Generation

AN ANN BASED FAULT DETECTION ON ALTERNATOR

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

Generation Interconnection Requirements at Voltages 34.5 kv and Below

Pinhook 500kV Transformer Neutral CT Saturation

Low Frequency Demand Disconnection Summary

Protective Relaying for DER

Hybrid Islanding Detection Method for Distributed Generators

Feeder Protection Challenges with High Penetration of Inverter Based Distributed Generation

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.

Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants

ECE 528 Understanding Power Quality

Islanding Detection and Frequency Circuit Measurement by Power Distribution Relation Depending on the Angle

Project acronym: Multi-island

Babak Enayati National Grid Thursday, April 17

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

Passive and Active Methods of Islanding Detection for Grid Connected PV Distributed Generators

Short Circuit Calculation in Networks with a High Share of Inverter Based Distributed Generation

Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India

Loss of Mains Protection

AN ASSESSMENT OF DISTRIBUTED GENERATION ISLANDING DETECTION METHODS

International Journal of Advance Engineering and Research Development

A Hybrid Anti-Islanding Method for Inverter-Based Distributed Generation

The Connecticut Light and Power Company

Flexible Voltage Control Scheme for Distributed Generation Systems under Grid Fault

ISLANDING DETECTION IN DISTRIBUTION SYSTEM EMBEDDED WITH RENEWABLE-BASED DISTRIBUTED GENERATION. Saurabh Talwar

Optimal sizing of battery energy storage system in microgrid system considering load shedding scheme

Combination of Adaptive and Intelligent Load Shedding Techniques for Distribution Network

Tripping of circuit breakers in PV installations due to zero sequence field impedance

Introduction to HVDC in GB. Ian Cowan Simulation Engineer 12 March 2018

2012 Grid of the Future Symposium. Impacts of the Decentralized Photovoltaic Energy Resources on the Grid

Focused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection

Power System Stability. Course Notes PART-1

Table of Contents. Introduction... 1

Malfunction of Differential Relays in Wind Farms

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

A Review of Adaptive Under Frequency Load Shedding Scheme on Islanded Distribution System Using MATLAB/SIMULINK

ESB National Grid Transmission Planning Criteria

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

22.0 Harmonics in Industrial Power Systems

A cost effective hybrid HVDC transmission system with high performance in DC line fault handling

Wind Power Facility Technical Requirements CHANGE HISTORY

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

ATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for Michigan s Eastern Upper and Northern Lower Peninsulas

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

How to maximize reliability using an alternative distribution system for critical loads

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES

Busbars and lines are important elements

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

Active Power Sharing and Frequency Control of Multiple Distributed Generators in A Microgrid

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer

Discrimination of Fault from Non-Fault Event in Transformer Using Concept of Symmetrical Component

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

EH2741 Communication and Control in Electric Power Systems Lecture 2

Transmission Interconnection Requirements for Inverter-Based Generation

DG TRANSFER CONNECTION SCHEME IN ACTIVE DISTRIBUTION NETWORKS

Adaptive Relaying of Radial Distribution system with Distributed Generation

Implementation of Revised IEEE Standard 1547

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems

Detection of Fault in Fixed Series Compensated Transmission Line during Power Swing Using Wavelet Transform

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Study of Effectiveness of Under-excitation Limiter in Dynamic Modeling of Diesel Generators

Generation and Load Interconnection Standard

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Power Plant and Transmission System Protection Coordination

Harmonic Reduction and Power Factor improvement in three phase three wire system by using Passive Filters

SE-502 MANUAL GROUND-FAULT GROUND-CONTINUITY DETECTOR

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Protection of Electrical Networks. Christophe Prévé

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers

Transcription:

http:// and Detection of Distributed Generation using Negative Sequence Component of Current Doan Van Dong Danang College of Technology, Danang, Vietnam Abstract - There is a renewed interest in the distributed generation (DG) mainly due to the environmental concern and electricity market liberalization. Many utilities around the world already have a significant penetration of DG in their s. But there are many issues to be resolved before DG becomes an integral part of the utilities around the world. One of the main issues with DG is islanding. occurs when a portion of the distribution becomes electrically isolated from the remainder of power yet continues to be energized by distributed generators. An important requirement to interconnect a DG to the power distributed is the capability of the DG to detect islanding. Failure to trip islanded generators can lead to a number of problems to the generators and the connected loads. The current industry practice is to disconnect all distributed generators immediately after the occurrence of islands. Typically, a distributed generator should be disconnected within 100 to 300 ms after the loss of the main supply. To achieve such a goal, this paper proposes that each distributed generator must be equipped with an islanding detection device using a negative sequence component of the current. Keywords, islanding detection, distributed generation, sequence components I. INTRODUCTION Distributed generations have been broadly used and are expected to be an important element in the future electric power s [1]. These generation s have characteristics which are different from those of conventional large capacity fossil and nuclear generation s. Distributed generations are relatively small and many of them make use of renewable energy such as a wind power or a hydraulic power. And, when the distributed generation s are operated in parallel with utility power s, especially with reverse power flow, the power quality problems become significant. Power quality problems include frequency deviation, voltage fluctuation, harmonics and reliability of the power. In addition, most important problem is an islanding protection. When a distributed generation with some loads is disconnected from the utility power, the distributed generation is going to supply the loads and, although this is rare, continue an islanded operation of power. The islanded operation should be avoided because of safety reasons for maintenance man and power quality reasons of distributed lines. To solve these problems, islanding detectors are used to detect an islanded operation and trip the circuit breaker between the power and the distributed generation [2],[3]. II. ISLANDING AND ISLADING DETECTION TECHNIQUES A. What is an islanding? A fault occurring in the power distribution is generally cleared by the protective relay that is located closest to the faulty spot (B1 opens). As a result, a distributed generation tries to supply its power to part of the distribution that has been separated from the utility's power. In most cases, this distributed generation assumes an overloaded condition, where its voltage and frequency are lowered and it is finally led to stoppage. However, though this is a rare case, a generator (or a group of generators) connected to this islanded is provided with a capacity that is large enough to feed power to all the loads accommodated in the islanded. When the loads are fed power only from the distributed generations even after the power supply is suspended from the power company, such a situation is called an "islanded operation" or "islanding". Figure 1. A part of is islanded when the B1 opens DG1 DG2 If a condition of islanded operation is continued, there can be concern about physical injury because of the inspection and restoration personnel or the public coming in contact with the live parts. In addition, when the power is supplied from the distributed generations, the quality of the fed power may be lowered as compared with the cases when the power is fed from the power company. It is often considered that the lowered quality may affect the loads adversely. At the power company, programs have been established so that the relevant circuit breaker or a switch is automatically closed at the substation after the lapse of the predetermined time period, in order to achieve prompt restoration from a service interruption. However, if the above-mentioned islanded operation is continued longer, a condition of asynchronous closure is assumed and the fault may be evolved further. This results in a further delay in the restoration from the failure. For 1067

http:// the reasons described above, the distributed generations and the protective devices applied to the connecting point of their are required to trip the circuit breaker located at this connecting point, by sensing such a condition when the power supply from the is lost. This function is referred to as the "islanding detection" or "loss-of-mains protection." B. detection techniques detection techniques can be divided into remote and local techniques and local techniques can further be divided into passive, active techniques as shown in Figure 2. b. Active techniques Can detect islanding even in a perfect match between generation and demand in the islanded. Introduce perturbation in the Detection time is slow as a result of extra time needed to see the response for perturbation Perturbation often degrades the power quantity and if significant enough, it may degrade the stability even when connected to Reactive power export error detection Impedance measurement Scheme Phase (or frequency) shift s Figure 2. detection techniques Table 1. Summarize the islanding detection techniques, their advantage and disadvantage, and examples [4]. Detection 1. Remote 2. Local a. Passive Advantages Disadvantages Examples Highly reliable Short detection time Do not perturb the Accurate when there is a large mismatch in generation and demand in the islanded. Expensive to implement especially for small s. Difficult to detect islanding when the load and generation in the islanded closely match Special care has to be taken while setting the thresholds If the setting is too aggressive then it could result in nuisance tripping Transfer trip Power line signaling output power frequency frequency over power Change of impedance Voltage unbalance Scheme Harmonic distortion C. Proposed islanding detection method Integrations of Distributed Generations (DGs) in the distribution network are expected to play an increasingly important role in the electric power infrastructure and market. As more DG s become part of the power grid, there is an increased safety hazard for personnel and an increased risk of damage to the power. Despite the favorable aspect grid-connected DGs can provide to the distribution, a critical demanding concern is islanding detection and prevention. Failure to trip islanded DG can lead to a number of problems for these resources and the connected loads, which includes power quality, safety and operation problems. Therefore, the current industry practice is to disconnect all DGs immediately after the occurrence of islands. The disconnection is normally performed by a special protection called islanding detection relays which can be implemented using different techniques. Recently pattern recognition technique based on Wavelet Transform [5-7] has been found to be an effective tool in monitoring and analyzing power disturbances including power quality assessment and protection against faults. This paper investigates the time-localization property of Wavelet transform for islanding detection by processing negative sequence components of current signals retrieved at the target DG location. As negative sequence components provide vital information in case of unbalanced conditions in power, thus the same has been considered for the proposed islanding detection technique which is subjected to disturbance during islanding process such as deviations in frequency, voltage, current and active power etc. As shown in figure 3, phase voltage of the DG to change an instant way [8]. This change happened on the voltage waveform at different times for each phase. With regard to the unbalance between these phases of the voltage as figure 3, the negative sequence component of current will exist during islanding. Inverse order components of the current signal are separated from the current in the location of DG connection on. The method of detecting the fault suitable isolation is to compare the value negative sequence component of current value is defaulted. A method based on negative sequence component of current combined with a damping characteristic of this component has the ability to distinguish 1068

http:// the condition happens the islanding with the other operators in the case of even when the problem is not symmetric. Figure 3. Three-Phases voltage signal under Condition retrieved at the target DG location III. SIMULATION MODEL In order to investigate the performance of the different techniques during various contingencies a simulation model was implemented. It is important that the model reflects a real in all vital parts. The behavior of the simulated must be similar to what happens in a real situation. How this has been achieved is described in the following. The grid is presented in figure 4 include 110 kv power transmission and 50 Hz short circuit capacity of 100 MVA is illustrated by a voltage source and resistor. Grid is connected to a distribution through a transformer 110/22 kv. DG1 and DG2 is scattered sources, each source including 3 generator has a capacity of 1.5 MW. Capacitors have a capacity of 3 MVAr. Load 1: PD1 = 6 MW, QD1 = 2,5 MVAr. Load 2: PD2 = 3 MW, QD2 = 1 MVAr. Load3: PD3= 9 MW, QD3= 4,5 MVAr. + nnect the capacitor + Asymmetric load + Short circuit asymmetry Simulation results 1. nnect a circuit of parallel lines Suppose that at the time of 0.5 s we trip a circuit of parallel lines (DL1) out of the by opening the breaker MC1. Figure 6 shows that at the time of 0.5 s the value negative sequence component of current begins to rise and its characteristic off gradually over time. Continue measuring the value negative sequence component of current at the moment that way current components reaches the maximum value after 0.1 s (5 cycles) and then get this value. Figure 6. Negative sequence component values of the current and the characteristic of this component when disconnects a circuit of parallel lines Figure 4. The studied Power Distribution network with multiple DGs Figure 7. Negative sequence component values of the current and the characteristic of this component when connects a circuit of parallel lines 2. Disconnect the DG with the distribution grid. This is the islanding condition. Figure 5. MATLAB/SIMULINK MODEL To distinguish the islanding condition with the other conditions, we analyze the case of the following operators: + nnect a circuit of parallel lines + Disconnect the DG with the distribution grid, this case is islanding operation + nnect DGs to + Change the load in power Figure 8. Negative sequence component values of the current and the characteristic of this component when during islanding 1069

http:// 3. nnect DGs to 5. nnect the capacitor Figure 9. Negative sequence component values of the current and the characteristic of this component when disconnects DG with the power Figure 13. Negative sequence component values of the current and the characteristic of this component when disconnects capacitor with the power Figure 10. Negative sequence component values of the current and the characteristic of this component when connects DG with the power 4. Change the load in power. This is the sudden load change condition. Where suddenly load is changed up to 50%. Figure 14. Negative sequence component values of the current and the characteristic of this component when connects capacitor with the power 6. Asymmetric load Figure 11. Negative sequence component values of the current and the characteristic of this component when reduces the load to 50% Figure 15. Negative sequence component values of the current and the characteristic of this component when the load is asymmetrical 7. Short circuit asymmetry Figure 12. Negative sequence component values of the current and the characteristic of this component when increases the load to 50% Figure 16. Negative sequence component values of the current and the characteristic of this component when the occurs short circuit asymmetry 1070

http:// From the assumed the operation of the above condition, we have the general simulation results as table 2. Table 2: General table the results measured after simulations The cases of operation nnect a circuit of parallel lines nnect DGs to Change the load in power nnect the capacitor to Disconnect a circuit of parallel lines Connect a circuit of parallel lines Disconnect DG2 with the power Connect DG2 with the power Reduces the load to 50% Increases the load to 50% Disconnect the capacitor to the grid Connect the capacitor to the grid The maximum value of negative sequence component of the current(pu) The value negative sequence component of current at the moment that way current components reaches the maximum value after 0.1 s (5 cycles) (pu) 0.0012 9.7843e-005 0.0013 9.0816e-005 0.0012 9.5656e-005 0.0012 9.7264e-005 Asymmetric load The maximum value 0.0013 9.7843e-005 condition Disconnect the DG with the distribution grid 0.0034 6.7996e-005 Short circuit asymmetry 0.0095 0.0083 From table 2, we see that the maximum value of negative sequence component of current is 0.0013 pu and the value of negative sequence component of current at the moment that way current components reaches the maximum value after 0.1 s (5 cycles) is 9.7843e-005 pu (except the islanding operation case and the short circuit asymmetry case). For the case of asymmetric short circuit, the value of negative sequence component of current is largest. This value is almost not reduced after 0.1 seconds since the power occurs the asymmetric short circuit and the overcurrent protection relay will recognize this fault case. Therefore, to distinguish the islanding operation case with the case of asymmetric short circuit and these cases of another operation that has been in the simulation, we give the value threshold to detect the islanding condition as follows: 0.0013pu < I 2set 0.0034pu IV. CONCLUSION Based on the measurement of electrical parameters of generator position, the article has presented a method using the negative sequence component of current combined with a damping characteristic of this component to detect the islanding condition. The negative sequence component of current is separated from the current signal in distributed generations. This method was simulated with the different operating conditions above. An islanding detection method using a negative sequence component of current combined with a damping characteristic of this component can detect the islanding condition exact and doesn't operate wrong when occurs the disturbance in power. REFERENCES [1] H.L.Willis and W.G.Scott, Distributed Power Generation Planning and Evaluation, Marcel Dekker, 2000 [2] N.Jenkins, R.Allan, P.Crossley, D.Kirschen and G.Strbsac, Distributed Generation, IEE, 2000 [3] A.Borbely and J.F.Kreider, Distributed Generation, CRC Press, 2001 [4] Pukar Mahat, Zhe Chen and Birgitte Bak-Jensen Review of Detection Methods for Distributed Generation DRPT2008 6-9 April 2008 Nanjing China. [5] O.A.S. Youssef, New algorithms for phase selection based on wavelet transforms, IEEE Trans. Power Deliv. 17 (2002) 908 914. [6] A.H. Osman, O.P. Malik, Transmission line protection based on wavelet transforms, IEEE Trans. Power Deliv. 19 (2) (2004) 515 523. [7] D. Chanda, N.K. Kishore, A.K. Sinha, A wavelet multiresolution analysis for location of faults on transmission lines, Electr. Power Energy Syst. 25 (2003) 59 69. [8] V. Menon, M. H. Nehrir (2007), A hybrid islanding detection technique using voltage unbalance and frequency set point, IEEE Tran. Power Systems, Vol. 22, No.1, pp. 442-448, Feb. 2007. 1071