A NEW METHOD FOR ISLANDING DETECTION IN DISTRIBUTED GENERATION

Similar documents
A Novel Islanding Detection Technique for Distributed Generation (DG) Units in Power System

Wavelet Transform Based Islanding Characterization Method for Distributed Generation

Islanding and Detection of Distributed Generation Islanding using Negative Sequence Component of Current

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Islanding Detection Method Based On Impedance Measurement

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

Anti-Islanding Protection of Distributed Generation Resources Using Negative Sequence Component of Voltage

Combination of Adaptive and Intelligent Load Shedding Techniques for Distribution Network

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

Protective Relaying for DER

Renewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

EH2741 Communication and Control in Electric Power Systems Lecture 2

Table of Contents. Introduction... 1

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

E N G I N E E R I N G M A N U A L

Anti-IslandingStrategyforaPVPowerPlant

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Loss of Mains Protection

Islanding Detection for Distributed Generation

ISLANDING DETECTION FOR DISTRIBUTED GENERATION SYSTEM USING VARIOUS METHODS

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1

Islanding Detection Techniques for Distributed Energy Resources-Review

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS

SCIENCE & TECHNOLOGY

Harmonic Distortion Levels Measured at The Enmax Substations

Phase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star.

ISLANDING DETECTION IN DISTRIBUTION SYSTEM EMBEDDED WITH RENEWABLE-BASED DISTRIBUTED GENERATION. Saurabh Talwar

Doãn Văn Đông, College of technology _ Danang University. 2. Local Techniques a. Passive Techniques

Generation Interconnection Requirements at Voltages 34.5 kv and Below

FUZZY LOGIC BASED OVERCURRENT PROTECTION FOR MV NETWORKS

Eliminating Power Transients When Switching Large Motors or Transformers during Power Outages or Engine Testing

Differential Protection for Microgrids with Embedded Generations

A Novel Active Anti-Islanding Protection Scheme for Grid-Interactive Roof-Top Solar PV System

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

Non-detection zone of LOM protection for converter connected wind turbines

ECE 528 Understanding Power Quality

System Protection and Control Subcommittee

An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third Zone of Distance Relays

Manjeet Baniwal 1, U.Venkata Reddy 2, Gaurav Kumar Jha 3

Adaptive Relaying of Radial Distribution system with Distributed Generation

Design and Construction of Synchronizing Check Relay

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

Introduce system protection relays like underfrequency relays, rate of change of frequency relays, reverse - power flow

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

Wind Power Facility Technical Requirements CHANGE HISTORY

BED INTERCONNECTION TECHNICAL REQUIREMENTS

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

2012 Grid of the Future Symposium. Impacts of the Decentralized Photovoltaic Energy Resources on the Grid

Distance Relay Response to Transformer Energization: Problems and Solutions

ESB National Grid Transmission Planning Criteria

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)

Embedded Generation Connection Application Form

DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS

Impact of High PV Penetration on Grid Operation. Yahia Baghzouz Professor of Electrical engineering University of Nevada Las Vegas

Embedded Generation Connection Application Form

STANDARDS/MANUALS/ GUIDELINES FOR SMALL HYDRO DEVELOPMENT

FAULT AND STABILITY ANALYSIS OF A POWER SYSTEM NETWORK BY MATLAB SIMULINK

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

Automatic Transfer Switch (ATS) Using Programmable Logic Controller (PLC)

DG TRANSFER CONNECTION SCHEME IN ACTIVE DISTRIBUTION NETWORKS

Sensitivity Analysis for 14 Bus Systems in a Distribution Network With Distributed Generators

Hamdy Faramawy Senior Application Specialist ABB Sweden

Anti-Islanding Today, Successful Islanding in the Future

Protection of Microgrids Using Differential Relays

VALIDATION THROUGH REAL TIME SIMULATION OF A CONTROL AND PROTECTION SYSTEM APPLIED TO A RESONANT EARTHED NEUTRAL NETWORK

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

[Nayak, 3(2): February, 2014] ISSN: Impact Factor: 1.852

Adaptive Autoreclosure to Increase System Stability and Reduce Stress to Circuit Breakers

Feeder Protection Challenges with High Penetration of Inverter Based Distributed Generation

Survey of Operational Events

Embedded Generation Connection Application Form

Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants

Power System Stability. Course Notes PART-1

Hybrid Islanding Detection Method for Distributed Generators

Islanding Detection Technique based on Simulation of IEEE16 Bus System

Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies

Distributed Generation Stability During Fault Conditions

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG

GUIDE FOR GENERATOR INTERCONNECTION THE WIRES OWNER DISTRIBUTION SYSTEM

Improving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC)

AN ASSESSMENT OF DISTRIBUTED GENERATION ISLANDING DETECTION METHODS

IMPLEMENTATION OF ADVANCED DISTRIBUTION AUTOMATION IN U.S.A. UTILITIES

Under-Frequency Load Shedding based on PMU Estimates of Frequency and ROCOF

An Enhanced Symmetrical Fault Detection during Power Swing/Angular Instability using Park s Transformation

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1

Notes 1: Introduction to Distribution Systems

NERC Protection Coordination Webinar Series July 15, Jon Gardell

Resonances in Collection Grids of Offshore Wind Farms

Single-Core Symmetrical Phase Shifting Transformer Protection Using Multi-Resolution Analysis

A New Adaptive Method for Distribution System Protection Considering Distributed Generation Units Using Simulated Annealing Method

Transcription:

A NEW METHOD FOR ISLANDING DETECTION IN DISTRIBUTED GENERATION Eugeniusz Rosolowski Arkadiusz Burek Leszek Jedut e-mail: rose@pwr.wroc.pl e-mail: arkadiusz.burek@pwr.wroc.pl e-mail: leszek.jedut@pwr.wroc.pl Wroclaw University of Technology, Department of Electrical Power Engineering, 5-7 Wroclaw, Wybrzeze Wyspianskiego 27, Poland Key words: Power system protection, distributed generation, loss of mains detection ABSTRACT This paper presents a new reliable algorithm of loss of mains detection for distributed generation. One of the technical issues created by DG interconnection is inadvertent islanding. Islanding occurs when a portion of the distributed system becomes electrically isolated from the remainder of the power system, yet continues to be energized by DG connected to the isolated subsystem. It can be desirable to permit such islanded operation to increase customer reliability, and this is often done where the DG provides backup power to the facility where it is installed. The proposed algorithm utilizes multi-criteria approach with fuzzy logic decision- making. I. INTRODUCTION The increased expanding of distributed (dispersed) generation (DG) in utility systems has been mainly caused by the liberalization of the electricity markets, recent advances in energy conversion systems and the environmental drive to promote green energy. These recent advances in energy conversion include the emergence of cheaper and more efficient power generation systems using renewable and hybrid power schemes. The attractions of 'green energy' have been and will continue to be a powerful force in the expansion of distributed generation. The increasing presence of dispersed generators in utility networks creates problems with regards to the operation and control of the distribution system. If DG is feeding the power to the networks without the utility supply, then it produces several negative impacts on utility power system and the DG itself, such as the safety hazards to utility personnel and the public, the quality problems of electric service to the utility customers, and serious damages to the DG if utility power is wrongly restored [2], []. Therefore, during the interruptions of utility power, the connected DG must detect the loss of utility power and disconnect itself from the power grid as soon as possible. Islanding operations of DG usually occur when power supply from the main utility is interrupted due to several reasons but the DG keeps supplying power into the distribution networks. These kinds of islanding conditions cause negative impacts on protection, operation, and management of distribution systems; therefore, it is necessary to effectively detect the islanding conditions and swiftly disconnect DG from distribution network. Moreover, the islanded operation should be avoided because of safety reasons for maintenance man and power quality reasons of distributed lines. Generally, if there are large changes in loading for DG after loss of the main power supply, then islanding conditions are easily detected by monitoring several parameters: voltage magnitude, phase displacement, and frequency change. However, in case of small changes in loading for DG, the conventional methods have some difficulty in detecting such a particular islanding condition. The islanding protection for DG becomes an important and emerging issue in power system protection since the distributed resources installations are rapidly increasing and most of the installed systems are interconnected with distribution network. In order to avoid the negative impacts from islanding operations of DG to protection, operation, and management of distribution system, it is necessary to effectively detect the islanding operations of DG and disconnect it from distribution network rapidly. This paper gives an overview of islanding detection algorithms for DG effectively working in the most of loading conditions. A new method which utilizing the multi-criteria approach is also presented. II. ISLANDING OPERATION Opening the utility grid breaker causes a potential power island fed from the embedded generator and isolated from the grid supply (Figure ). If loss of grid remains undetected, the embedded generator may quickly loose synchronism with the utility grid supply. This introduces the possibility of reconnection of the two systems while their generators are out of phase. The consequences of out-of-phase re-closing are severe stresses on the embedded generator and disruption of the utility supply. There are also safety and health issues. It is possible that

the remaining load from the utility system in the island would be greater than the capacity of the embedded generator. This would cause the embedded generator to be dragged down, along with the industrial process, leading to a complete outage. When embedded induction or synchronous generators are used in the system, a further consequence of loss of grid can be self-excitation. Loss of grid, or 'islanding' protection involves the automatic detection of a situation when the connection to the grid supply is lost. This allows of a dispersed generator to supply the local, isolated grid. GRID ZLINE CB Potencial Power Island ZT ZT2 Figure. Typical loss of grid scenario ZDG M DG III. ANTI ISLANDING DETECTION METHODS In a conventional situation after the connection between a local network and utility network is lost, the DG has to take charge of the remaining network and the connected loads; therefore, the loading condition of the DG is suddenly changed after islanding. For detection such a condition traditionally an under/over-voltage and under/over-frequency criteria are used. These (under/overvoltage and under/over-frequency) relays may, however, fail to detect loss of mains in situations where the islanded load is reasonably well matched to generator power output. The generator's AVR and speed governor controller may be able to compensate for the smaller load change, causing minimal change in the generators voltage and frequency. Therefore, changes of these parameters are to small in order to detect a loss of grid correctly. IV. PROPOSED DETECTION ALGORITHM To detect islanding effectively, it is necessary to have good understanding of all possible islanding conditions. Nowadays, many classical methods and novel algorithms for the islanding protection have been proposed [2]. These techniques can be divided into two categories: passive and active methods such as classical passive systems include under/over frequency and under/over voltage relays and the most widely recognized methods like the Rate of Change of Frequency (ROCOF), Voltage Vector Shift (VVS) [2-4]. The considered methods have been evaluated by using of EMTP-ATP simulations. The 5MW synchronous DG generator and local load is connected to kv utility supply network. Various loss-of-grid scenarios have been simulated by adjusting the size of the site load, and the amount of power flowing from the generator into the site load. Load changes in the modelled DG system are simulated with the use of additional load in series with the site load. Standard IEEE governor models are used together with controller fitted to the AVR. It is intended that the generator control systems are as similar to those used in the field as possible. Equivalent scheme of the considered system is outlined in Figure 2. Measurements voltage and current are taken from the Point of Common Coupling (). To facilitate comparison, a conventional rate of change of frequency signal was also implemented in the software model using volt-age samples taken from the generators terminals [8]. Fuzzy logic based relay (FLR) Generally, it is difficult to detect islanding operation by monitoring only single system parameter. The proposed fuzzy system is based on processing of three measured parameters, namely: voltage, frequency derivative (ROCOF) and active power derivative (ROCOP) [9]. The choice between these control parameters is based on the desired actions by the protection system of the dispersed generator in response to power system conditions. Criterion : change of voltage The decision as to whether voltage following is permitted under current power system conditions can only be made if the voltage is normal, otherwise voltage control is always effected. To predict the voltage dynamics it is propose to define the Rate of Change of Voltage parameter [5]. EPS BUS kv/kv BUS2 TR TR2 kv/kv TR2 DG DG U EPS Z S Z N kv BUS4 TR LOAD LOADZ Z RLC kv/6kv LOADM M Figure 2. Equivalent scheme of the considered network

Criterion 2: ROCOF Rate of Change of Frequency as control parameter is more stable than the voltage under grid connected conditions and therefore gives useful information about the nature of the connected network. In particular, this parameter is used to indicate the stiffness of the network system and to assess the relationship between the system frequency and the active power flow from the dispersed generator [5,7]. Criterion - ROCOP Rate of Change of Active Power is used to assess the impact that active power fluctuations have on the connected network's frequency and voltage. When the inertia of the connected system is high, such as when the dispersed generator is operating in parallel with the grid the impact is negligible. This is, however, not true under isolated operation. The rate of change of active power is used taking into account of the state of the system voltage and frequency. This algorithm remains stable during local load changes and during wide range of power system fault condition [6]. Measurement unit The simplified block diagram of the considered FLR for power generator is presented in Figure. The sampled voltage and currents from sides of the protected unit are measured as well as at the terminal. GRID TR DG Fuzzy logic rules Each of criteria (processed system parameters) can be used alone for loss of grid detection. However, no one separate criterion does not ensure that it would be able to properly detection and not nuisance operation during normal load variation. Authors put forward to fuzzy logic rule approach because of its flexibility for enhancement and update []. The fuzzy logic rules for islanding detection are applied only if the situation is not clear or uncertain. Voltage magnitude should consists between limits described below: U. U r oru. 9 U r THEN A () Similarly with frequency derivative, ROCOF: df ROCOF THEN B (2) And the Rate of Change of active Power: dp ROCOP THEN C () where: A,B,C are the decision criteria terms of each parameter. The proposed multi-criteria approach is more stable and gives the correct decision for almost all possible situations. u(n) i(n) measurement unit C C2 C U dp/ df/ Fuzzy settings µ µ2 µ w w2 w ω ω2 ω min δ> Multi-criteria decision making If the situation is clear, the signals µ, µ2, µ called the member functions are reduced to Boolean logic variables and equal either or. Under uncertain conditions, however, they may take values from the interval -, and thus, partly support certain hypotheses. Moreover, there may be contradictions between the recognition given by the particular criteria. In addition, the criteria in terms of quality of provided recognition are in some cases more, and in another less reliable. In order to resolve this and balance the decisions made by the criteria with the criteria powers, the multi-criteria decision-making methods are recommended []. The algorithm should rule-out all the non-islanding conditions, the signals ω l, ω 2, ω are aggregated into the overall tripping support d, by means of a kind of continuous logic AND-operator: ( ω, ω ω ) δ = min (4) 2, Figure. Block diagram of multi-criteria relay of antiislanding protection The measuring unit forms the signals and measurements is based on Finite Impulse Response (FIR) full-cycle orthogonal filters designed using the khz sampling rate. The tripping is initiated if d overreaches a constant timevarying or tripping threshold : ( ) = δ (5)

V. SIMULATION STUDIES To demonstrate the performance of a loss of mains algorithm, a number of studies are required. The simulation studies were carried out using EMTP-ATP program [8]. Standard EMTP libraries were used. The test of investigated algorithm was conducted with several network condition. There was simulated specific kind of islanding conditions - with neglecting changes in the load of DG after islanding operation (Figures 4, 5). The islanding was initiating after changing of 2.5% of the nominal DG power (Figure 4)...999.998 5.5 5 49.5 4 5 6 7 8 9..9 5.5 5 49.5 5 4 2.4.6.8.2.4.6.8 x 4.4.6.8.2.4.6.8 x 4.4.6.8.2.4.6.8 x 4 Figure 6. Effect of connecting the additional loads ZRLC. 49 5 5 4 5 6 7 8 9 P [kw] 5.9 5 5 5 2 25 5 4 5 6 7 8 9 Figure 4. Loss of grid with small variation in DG loading The algorithm was tested not only with islanding operation condition of DG but also with normal network load variation (Figure 6), induction motor starting (Figures 7, 8) which are sometimes confused with islanding condition to show that the algorithm works correctly..2.998.5 df/ dp/ -.5 4 5 6 7 8 9 4 5 6 7 8 9 4 5 6 7 8 9 4 5 6 7 8 9 Figure 5 The response of algorithm during loss of grid with small variation in DG loading A normal operation condition during load fluctuation, causing voltage and frequency dip, during parallel operation of DG with the grid. 5 49 2 5 5 2 25 5 5 5 2 25 5 Figure 7. The result for increasing network load by starting the induction motor df/..9 -.2 -.4 dp/ -.5 5 5 2 25 5 5 5 2 25 5 5 5 2 25 5 5 5 2 25 5 Figure 8. The response of algorithm during ZRLC load connection

.8.6.4.2 5 4 5 6 7 8 9 and algorithm is capable to detect correctly and with good selectivity the islanding and non-islanding conditions. Authors are conducting the further research on islanding detection. They intend to adopt the self adjusting of the fuzzy setting and the weight factors and tripping threshold in order to improve FLR operation. 48 46 5-5 4 5 6 7 8 9 4 5 6 7 8 9 Figure 9. Parameter changes during remote phase-toground fault df/.5 -.2 -.4 dp/ -.5 4 5 6 7 8 9 4 5 6 7 8 9 4 5 6 7 8 9 4 5 6 7 8 9 Figure. Parameter changes during remote phase-toground fault Operation during transient (remote phase ground fault in GRID) fault conditions was simulated too (Figures 9, ). VI. CONCLUSIONS In the paper, the novel islanding detection method was presented. The algorithm monitors changes of the proposed three parameters and detects the islanding operations by fuzzy logic rules. The loss of grid decision is based on multi-criteria algorithm for distributed resources that are interconnected with distribution network. The proposed method using the radial distribution network with rotating type distributed generations, and different kind of loads was verified and evaluated. The test results show that the proposed criteria REFERENCES. A.M. Bobrey, J.F. Kreider, Distributed Generation The Power Paradigm for the New Millennium, CRC Press LLC, 2. 2. M.G. Bartlett, M.A. Redfern, A Review of Techniques for the Protection of Distributed Generation against Loss of Grid, UPEC2, September 6-8, Belfast, UK.. P.D. Hopewell, N. Jenkins, A.D. Cross, Loss-of- Mains Detection for Small Generators, IEE Proceedings, Electrical Power Applications, vol.4, no., May 996, pp. 225-2. 4. M.A. Redfern, O. Usta, G. Fielding, Protection against loss of utility grid supply for a dispersed storage and generation unit. IEEE Transaction on Power Delivery, Vol. 8, No., pp. 948-954, July 99. 5. N. Jenkins, R. Allan, P. Crossley, D. Kirschen, G. Strbsac, Embedded Generation, IEE, London 2 6. M.A. Redfern, J.I. Barrett, O. Usta. A New loss of grid protection based on power measurements, Developments in Power System Protection, 25-27th March 997, Conference Publication No.44, pp. 9-94. 7. A. Burek, E. Rosolowski, Anti-islanding protection in distributed networks with DG, Distributed Power Networks 24, Conference Publication, pp. 97-4, Wroclaw, September 24 (in polish). 8. H.W. Dommel, Electromagnetic Transients Program. Reference Manual (EMTP theory book). Bonneville Power Administration, Portland 986. 9. E. Rosolowski, J. Iżykowski, A. Burek, Islanding detection methods for distributed generation. Technicna Elektrodinamika (Tech. Elektrodinamika) 26 part 2, pp. 5-5.. E. Rosolowski, Digital signal processing for Power System Relaying, Akademicka Oficyna Wydawnicza EXIT, Warszawa 22 (in polish).. A. Burek, E. Rosolowski, Modern approach to protection of distributed network with dispersed generation. Proceedings of the International Symposium on Modern Electric Power Systems, MEPS 6, Wroclaw, Sept. 6-8, 26, pp. 24-28.