Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages

Similar documents
Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Current monitoring relays CM-SRS.2 For single-phase AC/DC currents

Current monitoring relays CM-SRS.1 For single-phase AC/DC currents

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Current monitoring relays CM-SRS.M1 For single-phase AC/DC currents

Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

Three-phase monitoring relays CM-PVS CM-PVS.31, CM-PVS.41 and CM-PVS.81

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

Three-phase monitoring relay CM-PFS

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

Electronic timer CT-WBS.22 Impulse generating and flashing with 2 c/o (SPDT) contacts

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

Three-phase monitoring relays CM-PVS.81

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.23 and CM-MPS.43

Liquid level monitoring relay CM-ENS.2x

Electronic timer CT-MVS.12 Multifunctional with 1 c/o (SPDT) contact

Electronic timer CT-MXS.22 Multifunctional with 2 c/o (SPDT) contacts

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.23

Electronic timer CT-SDS.22

Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts

Measuring and monitoring relays CM-SRS.1 Current monitoring relays, single-phase AC/DC

Multifunctional three-phase monitoring relays CM-MPN CM-MPN.52, CM-MPN.62 and CM-MPN.72

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks.

Three-phase monitoring relay

Three-phase monitoring relay CM-PVE

Three-phase monitoring relays

Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts

Three-phase monitoring relays CM-PFE and CM-PFE.2

Three-phase monitoring relay CM-PBE

Electronic timer CT-MFS.21 Multifunctional with 2 c/o (SPDT) contacts

ABB NEW. Three-phase monitoring relays. CM-PVS.31 and CM-PVS.41 Data sheet. Features J. Approvals. Marks. Order data. Order data - Accessories

Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact

Electronic timer CT-MBS.22 Multifunctional with 2 c/o (SPDT) contacts

CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC

Electronic timer CT-YDE Star-delta change-over with 1 c/o (SPDT) contact

Electronic timer CT-MFS.21 Multifunctional with 2 c/o (SPDT) contacts

Electronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet

Electronic timer CT-EBE Flasher starting with OFF, 1 c/o (SPDT) contact

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks.

Electronic timer CT-MFS.21

Insulation monitoring relay CM-IWS.2 For unearthed AC systems up to U n = 400 V AC

Electronic timer CT-SDE Star-delta change-over with 1 n/c + 1 n/o contact

Electronic timer CT-TGD.22

Electronic timer CT-SDD.22

Coupling unit CM-IVN For expansion of the insulation monitoring relay CM-IWN.x measuring range up to U n = 690 V AC and 1000 V DC

Insulation monitoring relay CM-IWS.1 For unearthed AC, DC and mixed AC/DC systems up to U n = 250 V AC and 300 V DC

Insulation monitoring relays CM-IWN.4/5/6 For unearthed AC, DC and mixed AC/DC systems up to U n = 400 V AC and 600 V DC

Electronic timer CT-AWE Impulse-OFF with auxiliary voltage, 1 c/o (SPDT) contact

Electronic timer CT-AHE OFF-delayed with 1 c/o (SPDT) contact

Three-phase monitoring relay

Insulation monitoring relay CM-IWN.5 For unearthed AC, DC and mixed AC/DC systems up to U n = 400 V AC and 600 V DC

Power supply CP-D 12/2.1

Insulation monitoring relay CM-IWN.1 For unearthed AC, DC and mixed AC/DC systems up to U n = 400 V AC and 600 V DC

Coupling unit CM-IVN For expansion of the insulation monitoring relay CM-IWN.x measuring range up to U n = 690 V AC and 1000 V DC

Power supply CP-T 24/40.0 Primary switch mode power supply

Power supply CP-T 48/5.0 Primary switch mode power supply

Power supply CP-T 24/10.0 Primary switch mode power supply

Electronic timer CT-ERS ON-delayed with 2 c/o contacts Data sheet

Type CP-S, CP-C & CP-A Switch mode

ABB ABB 59 2CDC110004C0205. Measuring and monitoring relays. CM and C5xx range. Content

Control module CP-A CM

Power supply CP-T 48/20.0 Primary switch mode power supply

Power supply CP-T 24/20.0 Primary switch mode power supply

Electronic timer CT-AWS Impulse-OFF with 1 c/o contact Data sheet

Power supply CP-E 24/2.5

Power supply CP-E 24/20.0

Three-phase monitoring relays Product group picture

Power supply CP-E 24/0.75

Three-phase monitoring relays Table of contents

Three-phase monitoring relays Product group picture

Power supply CP-D 24/1.3

Power supply CP-E 48/5.0 Primary switch mode power supply Data sheet

Power supply CP-E 12/10.0 Primary switch mode power supply Data sheet

Power supply CP-E 24/2.5

Power supply CP-D 24/4.2 Primary switch mode power supply

Thermistor motor protection relays

Control module CP-A CM

CP-T range Product group picture

CP-E range Benefits and advantages

Primary switch mode power supplies Product group picture

Analog signal converters CC range

Pluggable interface relays CR-U Universal relays

CP-T range Benefits and advantages

Electronic timer CT-SDE

V2UM230V10 Art.Nr.: V2UM230V10P Art.Nr.: Control elements. Tripping delay. Function selector. Status indication 230 V AC/DC

Grid feeding monitoring relay acc. VDE AR-N 4105 CM-UFD.M21

Thermistor motor protection relays

s s s 3-60 s min min 3-60 min h h 3-60 h V AC, 50/60 Hz

V2IM10AL10 Art.Nr.: V2IM10AL10P Art.Nr.: Control element. Tripping delay. Function selector. Status indication 24...

VEO. V2PF480Y/277VS01 Art.Nr.: B TECHNICAL DATA

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

Signal converters Index

Switching power supplies CP range, Linear power supplies CP-L range. Content

27/04/2015

Analog signal converters CC-E I/I

Subject to changes 11/2003 Page 1/7

Transcription:

Data sheet Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages The CM-EFS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of phase loss. All devices are available with two different terminal versions. You can choose between the proven screw connection technology (double-chamber cage connection terminals) and the completely tool-free Easy Connect Technology (Push-in terminals). Characteristics Monitoring of DC and AC voltages (3-600 V) TRMS measuring principle One device includes 4 measuring ranges Over- and undervoltage monitoring ON- or OFF-delay configurable Latching function configurable Threshold values for >U and <U adjustable Fixed hysteresis (5 %) Precise adjustment by front-face operating controls Screw connection technology or Easy Connect Technology available Housing material for highest fire protection classification UL 94 V-0 Tool-free mounting on DIN rail as well as demounting Tripping delay adjustable (0 s; 0.1-30 s) 1x2 c/o (SPDT) contacts (common signal) or 2x1 c/o (SPDT) contact (separate signals for >U and <U) configurable 22.5 mm (0.89 in) width 3 LEDs for status indication Approvals A UL 508, CAN/CSA C22.2 No.14 C GL (pending) D GOST K CB Scheme E CCC L RMRS Marks a CE b C-Tick 2CDC 251 059 V0011 Order data Voltage monitoring relay Type Rated control supply voltage Connection technology Measuring ranges Order code CM-EFS.2P 24-240 V AC/DC Push-in terminals 3-30 V, 6-60 V, 30-300 V, 60-600 V 1SVR 740 750 R0400 CM-EFS.2S 24-240 V AC/DC Screw type terminals 3-30 V, 6-60 V, 30-300 V, 60-600 V 1SVR 730 750 R0400 Accessories Type Description Order code ADP.01 Adapter for screw mounting 1SVR 430 029 R0100 MAR.12 Marker label for devices with DIP switches 1SVR 730 006 R0000 COV.11 Sealable transparent cover 1SVR 730 005 R0100

Connection technology Maintenance free Easy Connect Technology with Push-in terminals Type designation CM-xxS.yyP Approved screw connection technology with double-chamber cage connection terminals Type designation CM-xxS.yyS 2CDC 253 026 F0011 2CDC 253 025 F0011 Push-in terminals Tool-free connection of rigid and flexible wires with wire end ferrule according to DIN 46228-1-A, DIN 46228-4-E Wire size: 2 x 0.5-1.5 mm², (2 x 20-16 AWG) Easy connection of flexible wires without wire end ferrule by opening the terminals No retightening necessary One operation lever for opening both connection terminals For triggering the lever and disconnecting of wires you can use the same tool (Screwdriver according to DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in)) Constant spring force on terminal point independent of the applied wire type, wire size or ambient conditions (e. g. vibrations or temperature changes) Opening for testing the electrical contacting Gas-tight Double-chamber cage connection terminals Terminal spaces for different wire sizes: fine strand with/without wire end ferrule: 1 x 0.5-2.5 mm² (2 x 20-14 AWG), 2 x 0.5-1.5 mm² (2 x 20-16 AWG) rigid: 1 x 0.5-4 mm² (1 x 20-12 AWG), 2 x 0.5-2.5 mm² (2 x 20-14 AWG) One screw for opening and closing of both cages Pozidrive screws for pan- or crosshead screwdrivers according to DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in) Both the Easy Connect Technology with Push-in terminals and screw connection technology with double-chamber cage connection terminals have the same connection geometry as well as terminal position. 2 - Voltage monitoring relay CM-EFS.2 Data sheet

Functions Operating controls 1 Adjustment of the threshold value >U for overvoltage 2 Adjustment of the threshold value <U for undervoltage 3 Indication of operational states U/T: control supply voltage/timing 2CDC 251 059 V0011 1 2 3 4 5 6! R: relay status U: over- / undervoltage 4 Adjustment of the measuring range 5 Adjustment of the tripping delay 6 DIP switches (see DIP switch functions) When compared with our previous version, the position of the adjustment potentiometers 4 and 5 have changed places. Application The voltage monitoring relays CM-EFS.2 are designed for use in single-phase AC and/or DC systems for the simultaneous monitoring of over- or undervoltages as well as detection of phase loss. Depending on the configuration, one c/o (SPDT) contact each or both c/o (SPDT) contacts in parallel can be used for the over- and undervoltage monitoring. The devices operate over an universal range of supply voltages and provide an adjustable tripping delay. Open or closed-circuit principle as well as ON of OFF delay tripping are configurable. Operating mode The CM-EFS.2 have 2 c/o (SPDT) contacts and include 4 measuring ranges: 3-30 V, 6-60 V, 30-300 V and 60-600 V. The units are adjusted with front-face operating controls. The selection of: ON-delay A or OFF-delay B, open- h or closed-circuit principle g, latching function ON f or OFF e and 2x1 c/o i or 1x2 c/o (SPDT) contacts j is made with DIP switches. Potentiometers, with direct reading scale, allow the adjustment of the threshold valuemax (>U) for overvoltage, the threshold valuemin (<U) for undervoltage and the tripping delay. The tripping delay is adjustable over a range of instantaneous to a 30 s delay. The hysteresis is fixed at 5 %. Timing is displayed by a flashing labelled U/T. Data sheet Voltage monitoring relay CM-EFS.2-3

Function diagrams Voltage window monitoring 1x2 c/o (SPDT) contacts j ON-delayed A without latching e Open-circuit principle h The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals A1-A2 is displayed by the glowing. If the measured value exceeds the threshold value max (>U) or drops below the threshold value min (<U), the tripping delay starts and the glows (overvoltage), or flashes W (undervoltage) respectively. Timing of is displayed by the flashing W. When is complete and the measured value still exceeds the threshold value max minus the fixed hysteresis (5 %) or is still below the threshold value min plus the fixed hysteresis (5 %), the output relays energize and the (relay energized) glows. value min plus the fixed hysteresis (5 %), the output relays de-energize and the red and s turn off. If control supply voltage is interrupted, the turns off. Closed-circuit principle g The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to terminals A1-A2, the output relays energize and the green and (relays energized) glow. If the measured value exceeds the threshold value max (>U) or drops below the threshold value min (<U), the tripping delay starts and the glows (overvoltage), or flashes W (undervoltage) respectively. Timing of is displayed by the flashing W. When is complete and the measured value still exceeds the threshold value max minus the fixed hysteresis (5 %) or is still below the threshold value min plus the fixed hysteresis (5 %), the output relays de-energize and the (relays energized) turns off. value min plus the fixed hysteresis (5 %), the output relays re-energize, the glows and the turns off. If control supply voltage is interrupted, the output relays de-energize and the yellow and s turn off. A1-A2 Threshold max Measured value Threshold min < < Open-circuit principle open Closed-circuit principle closed 2CDC 252 232 F0205 4 - Voltage monitoring relay CM-EFS.2 Data sheet

Voltage window monitoring 1x2 c/o (SPDT) contacts j OFF-delayed B without latching e Open-circuit principle h The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals A1-A2 is displayed by the glowing. If the measured value exceeds the threshold value max (>U) or drops below the threshold value min (<U), the output relays energize, the (relays energized) glows and the glows (overvoltage), or flashes W (undervoltage) respectively. value min plus the fixed hysteresis (5 %), the tripping delay starts and the turns off. Timing of is displayed by the flashing W. When is complete, the output relays de-energize and the (relay energized) turns off. If control supply voltage is interrupted, the turns off. Closed-circuit principle g The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to terminals A1-A2, the output relays energize and the green and (relays energized) glow. If the measured value exceeds the threshold value max (>U) or drops below the threshold value min (<U), the output relays deenergize, the turns off and the glows (overvoltage), or flashes W (undervoltage) respectively. value min plus the fixed hysteresis (5 %), the tripping delay starts and the turns off. Timing of is displayed by the flashing W. When is complete, the output relays energize and the (relay energized) glows. If control supply voltage is interrupted, the output relays de-energize and the yellow and s turn off. A1-A2 Threshold max Measured value Threshold min Open-circuit principle open Closed-circuit principle closed 2CDC 252 233 F0205 Data sheet Voltage monitoring relay CM-EFS.2-5

Voltage window monitoring 1x2 c/o (SPDT) contacts j ON-delayed A with latching f Open-circuit principle h The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals A1-A2 is displayed by the glowing. If the measured value exceeds the threshold value max (>U) or drops below the threshold value min (<U), the tripping delay starts and the glows (overvoltage), or flashes W (undervoltage) respectively. Timing of is displayed by the flashing W. When is complete and the measured value still exceeds the threshold value max minus the fixed hysteresis (5 %) or is still below the threshold value min plus the fixed hysteresis (5 %), the output relays energize and the (relay energized) flashes Z. value min plus the fixed hysteresis (5 %), the turns off. The output relays remain energized (latching function). If control supply voltage is interrupted (reset), the output relays de-energize and the yellow and s turn off. Closed-circuit principle g The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to terminals A1-A2, the output relays energize and the green and (relays energized) glow. If the measured value exceeds the threshold value max (>U) or drops below the threshold value min (<U), the tripping delay starts and the glows (overvoltage), or flashes W (undervoltage) respectively. Timing of is displayed by the flashing W. When is complete and the measured value still exceeds the threshold value max minus the fixed hysteresis (5 %) or is still below the threshold value min plus the fixed hysteresis (5 %), the output relays de-energize and the (relays energized) flashes Y. value min plus the fixed hysteresis (5 %), the turns off. The output relays remain de-energized (latching function). If control supply voltage is interrupted (reset), the yellow and s turn off. The output relays energize again when control supply voltage is re-applied. A1-A2 Threshold max Reset Measured value Threshold min < < Open-circuit principle open Closed-circuit principle closed 2CDC 252 234 F0205 6 - Voltage monitoring relay CM-EFS.2 Data sheet

Voltage window monitoring 1x2 c/o (SPDT) contacts j OFF-delayed B with latching f Open-circuit principle h The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals A1-A2 is displayed by the glowing. If the measured value exceeds the threshold value max (>U) or drops below the threshold value min (<U), the output relays energize, the (relays energized) flashes Z and the glows (overvoltage), or flashes W (undervoltage) respectively. value min plus the fixed hysteresis (5 %), the turns off. The output relays remain energized (latching function). If control supply voltage is interrupted (reset), the output relays de-energize and the yellow and s turn off. Closed-circuit principle g The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to terminals A1-A2, the output relays energize and the green and (relays energized) glow. If the measured value exceeds the threshold value max (>U) or drops below the threshold value min (<U), the output relays de-energize, the (relays energized) flashes Y and the glows (overvoltage), or flashes W (undervoltage) respectively. value min plus the fixed hysteresis (5 %), the turns off. The output relays remain de-energized (latching function). If control supply voltage is interrupted (reset), the yellow and s turn off. The output relays energize again when control supply voltage is re-applied. A1-A2 Threshold max Reset Measured value Threshold min Open-circuit principle open Closed-circuit principle closed 2CDC 252 235 F0205 Data sheet Voltage monitoring relay CM-EFS.2-7

Voltage window monitoring 2x1 c/o (SPDT) contact i ON-delayed A without latching e Open-circuit principle h The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals A1-A2 is displayed by the glowing. If the measured value exceeds the threshold value max (>U) or drops below the threshold value min (<U), the tripping delay starts and the glows (overvoltage), or flashes W (undervoltage) respectively. Timing of is displayed by the flashing W. When is complete and the measured value still exceeds the threshold value max minus the fixed hysteresis (5 %) or is still below the threshold value min plus the fixed hysteresis (5 %), the output relay 11 15-12 16 /14 18 (>U), or 21 25-22 26 /24 28 (<U) respectively, energizes and the (relay energized) glows. value min plus the fixed hysteresis (5 %), the output relay 11 15-12 16 /14 18 (>U), or 21 25-22 26 /24 28 (<U) respectively, deenergizes and the red and s turn off. If control supply voltage is interrupted, the turns off. Closed-circuit principle g The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to terminals A1-A2, the output relays energize and the green and (relays energized) glow. If the measured value exceeds the threshold value max (>U) or drops below the threshold value min (<U), the tripping delay starts and the glows (overvoltage), or flashes W (undervoltage) respectively. Timing of is displayed by the flashing W. When is complete and the measured value still exceeds the threshold value max minus the fixed hysteresis (5 %) or is still below the threshold value min plus the fixed hysteresis (5 %), the output relay 11 15-12 16 /14 18 (>U), or 21 25-22 26 /24 28 (<U) respectively, de-energizes and the (relays energized) turns off. value min plus the fixed hysteresis (5 %), the output relay 11 15-12 16 /14 18 (>U), or 21 25-22 26 /24 28 (<U) respectively, reenergizes, the glows and the turns off. If control supply voltage is interrupted, the output relays de-energize and the yellow and s turn off. A1-A2 Threshold max Measured value Threshold min < < Open-circuit principle open >U: <U: Closed-circuit principle closed >U: <U: 2CDC 252 236 F0205 8 - Voltage monitoring relay CM-EFS.2 Data sheet

Voltage window monitoring 2x1 c/o (SPDT) contact i OFF-delayed B without latching e Open-circuit principle h The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals A1-A2 is displayed by the glowing. If the measured value exceeds the threshold value max (>U) or drops below the threshold value min (<U), the output relay 11 15-12 16 /14 18 (>U), or 21 25-22 26 /24 28 (<U) respectively, energizes, the (relays energized) glows and the glows (overvoltage), or flashes W (undervoltage) respectively. value min plus the fixed hysteresis (5 %), the tripping delay starts and the turns off. Timing of is displayed by the flashing W. When is complete, the output relay 11 15-12 16 /14 18 (>U), or 21 25-22 26 /24 28 (<U) respectively, de-energizes and the (relay energized) turns off. If control supply voltage is interrupted, the turns off. Closed-circuit principle g The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to terminals A1-A2, the output relays energize and the green and (relays energized) glow. If the measured value exceeds the threshold value max (>U) or drops below the threshold value min (<U), the output relay 11 15-12 16 /14 18 (>U), or 21 25-22 26 /24 28 (<U) respectively, de-energizes, the turns off and the glows (overvoltage), or flashes W (undervoltage) respectively. value min plus the fixed hysteresis (5 %), the tripping delay starts and the turns off. Timing of is displayed by the flashing W. When is complete, the output relay 11 15-12 16 /14 18 (>U), or 21 25-22 26 /24 28 (<U) respectively, energizes and the (relay energized) glows. If control supply voltage is interrupted, the output relays de-energize and the yellow and s turn off. A1-A2 Threshold max Measured value Threshold min Open-circuit principle open >U: <U: Closed-circuit principle closed >U: <U: 2CDC 252 237 F0205 Data sheet Voltage monitoring relay CM-EFS.2-9

Voltage window monitoring 2x1 c/o (SPDT) contact i ON-delayed A with latching f Open-circuit principle h The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals A1-A2 is displayed by the glowing. If the measured value exceeds the threshold value max (>U) or drops below the threshold value min (<U), the tripping delay starts and the glows (overvoltage), or flashes W (undervoltage) respectively. Timing of is displayed by the flashing W. When is complete and the measured value still exceeds the threshold value max minus the fixed hysteresis (5 %) or is still below the threshold value min plus the fixed hysteresis (5 %), the output relay 11 15-12 16 /14 18 (>U), or 21 25-22 26 /24 28 (<U) respectively, energizes and the (relay energized) flashes Z. value min plus the fixed hysteresis (5 %), the turns off. The output relay 11 15-12 16 /14 18 (>U), or 21 25-22 26 /24 28 (<U) respectively, remains energized (latching function). If control supply voltage is interrupted (reset), the output relay 11 15-12 16 /14 18 (>U), or 21 25-22 26 /24 28 (<U) respectively, deenergizes and the yellow and s turn off. Closed-circuit principle g The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to terminals A1-A2, the output relays energize and the green and (relays energized) glow. If the measured value exceeds the threshold value max (>U) or drops below the threshold value min (<U), the tripping delay starts and the glows (overvoltage), or flashes W (undervoltage) respectively. Timing of is displayed by the flashing W. When is complete and the measured value still exceeds the threshold value max minus the fixed hysteresis (5 %) or is still below the threshold value min plus the fixed hysteresis (5 %), the output relay 11 15-12 16 /14 18 (>U), or 21 25-22 26 /24 28 (<U) respectively, de-energizes and the (relays energized) flashes Y. value min plus the fixed hysteresis (5 %), the turns off. The output relay 11 15-12 16 /14 18 (>U), or 21 25-22 26 /24 28 (<U) respectively, remains de-energized (latching function). If control supply voltage is interrupted (reset), the yellow and s turn off. The output relays energize again when control supply voltage is re-applied. A1-A2 Threshold max Reset Measured value < Threshold min < Open-circuit principle open >U: <U: Closed-circuit principle closed >U: <U: 2CDC 252 238 F0205 10 - Voltage monitoring relay CM-EFS.2 Data sheet

Voltage window monitoring 2x1 c/o (SPDT) contact i OFF-delayed B with latching f Open-circuit principle h The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals A1-A2 is displayed by the glowing. If the measured value exceeds the threshold value max (>U) or drops below the threshold value min (<U), the output relay 11 15-12 16 /14 18 (>U), or 21 25-22 26 /24 28 (<U) respectively, energizes, the (relays energized) flashes Z and the red LED glows (overvoltage), or flashes W (undervoltage) respectively. value min plus the fixed hysteresis (5 %), the turns off. The output relay 11 15-12 16 /14 18 (>U), or 21 25-22 26 /24 28 (<U) respectively, remains energized (latching function). If control supply voltage is interrupted (reset), the output relays de-energize and the yellow and s turn off. Closed-circuit principle g The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to terminals A1-A2, the output relays energize and the green and (relays energized) glow. If the measured value exceeds the threshold value max (>U) or drops below the threshold value min (<U), the output relay 11 15-12 16 /14 18 (>U), or 21 25-22 26 /24 28 (<U) respectively, de-energizes, the (relays energized) flashes Y and the glows (overvoltage), or flashes W (undervoltage) respectively. value min plus the fixed hysteresis (5 %), the turns off. The output relay 11 15-12 16 /14 18 (>U), or 21 25-22 26 /24 28 (<U) respectively, remains de-energized (latching function). If control supply voltage is interrupted (reset), the yellow and s turn off. The output relays energize again when control supply voltage is re-applied. A1-A2 Threshold max Reset Measured value Threshold min Open-circuit principle open >U: <U: Closed-circuit principle closed >U: <U: 2CDC 252 239 F0205 Data sheet Voltage monitoring relay CM-EFS.2-11

Electrical connection A1 11 15 21 25 B B 11 15 21 25 A1-A2 Rated control supply voltage B-C Measuring ranges: 3-30 V, 6-60 V, 30-300 V, 60-600 V 11 15-12 16 /14 18 Output contacts - open- or closed-circuit principle 21 25-22 26 /24 28 C A1 A2 12 16 14 18 22 26 24 28 14 18 12 16 C 24 28 22 26 A2 2CDC 252 207 F0005 Connection diagram DIP switches Position 4 3 2 1 ON OFF 2x1 c/o 1x2 c/o closed open 2CDC 252 274 F0005 1 ON OFF-delay OFF ON-delay 2 ON Closed-circuit principle OFF Open-circuit principle 3 ON Latching function activated OFF Latching function not activated 4 ON 2x1 c/o (SPDT) contact OFF 1x2 c/o (SPDT) contacts OFF = Default 12 - Voltage monitoring relay CM-EFS.2 Data sheet

Technical data Data at T a = 25 C and rated values, unless otherwise indicated Input circuits Supply circuit A1-A2 Rated control supply voltage U s 24-240 V AC Rated control supply voltage U s tolerance -15...+10 % Rated frequency 50/60 Hz Typical current / power consumption 24 V DC 30 ma / 0.75 W 115 V AC 17 ma / 1.9 VA 230 V AC 11 ma / 2.6 VA Power failure buffering time 20 ms Transient overvoltage protection varistors Measuring circuit B-C Monitoring function Over- and undervoltage monitoring Measuring method TRMS measuring principle Measuring inputs terminal connection B-C measuring range 3-30 V, 6-60 V, 30-300 V, 60-600 V input resistance 600 kω pulse overload capacity t < 1 s 800 V continuous capacity 660 V Threshold value >U and <U adjustable within the indicated measuring range Tolerance of the adjusted threshold value 10 % of the range end value related to the threshold value 5 % fixed Measuring signal frequency range DC / 15 Hz - 2 khz Rated measuring signal frequency range DC / 50-60 Hz Maximum response time AC 80 ms DC 120 ms Accuracy within the rated control supply voltage tolerance ΔU 0.5 % Accuracy within the temperature range ΔU 0.06 % / C Transient overvoltage protection varistors Timing circuit Time delay 0 s or 0.1-30 s adjustable Repeat accuracy (constant parameters) ±0.07 % of full scale Tolerance of the adjusted time delay - Accuracy within the rated control supply voltage tolerance Δt 0.5 % Accuracy within temperature range Δt 0.06 % / C User interface Indication of operational states Control supply voltage U/T: V: control supply voltage applied W: tripping delay active Measured value U: V: overvoltage W: undervoltage Relay status R: V: output relay energized, no latching function Z: output relay energized, active latching function Y: output relay de-energized, active latching function Data sheet Voltage monitoring relay CM-EFS.2-13

Output circuits Kind of output 11-12/14 21-22/24 Operating principle Contact material Rated operational voltage U e (VDE 0110, IEC/EN 60947-1) Minimum switching voltage / Minimum switching current Maximum switching voltage / Maximum switching current Rated operational current I e AC12 (resistive) at 230 V (IEC/EN 60947-5-1) AC15 (inductive) at 230 V DC12 (resistive) at 24 V DC13 (inductive) at 24 V relay, 1st c/o (SPDT) contact relay, 2nd c/o (SPDT) contact 1 x 2 c/o (SPDT) contacts (common signal) or 2 x 1 c/o (SPDT) contact (separate signal for >U and <U) configurable open- or closed-circuit principle configurable (opencircuit principle: output relays energize if the measured value exceeds d / falls below c the adjusted threshold value, closed-circuit principle: output relays de-energize if measured value exceeds d / falls below c the adjusted threshold value) AgNi 250 V 24 V / 10 ma 250 V AC / 4 A AC 4 A 3 A 4 A 2 A AC rating (UL 508) utilization category (Control Circuit Rating Code) B 300 max. rated operational voltage 300 V AC max. continuous thermal current at B 300 5 A max. making/breaking 3600/360 VA apparent power at B 300 Mechanical lifetime 30 x 10 6 switching cycles Electrical lifetime AC12, 230 V, 4 A 0.1 x 10 6 switching cycles Maximum fuse rating to achieve n/c contact 6 A fast-acting short-circuit protection n/o contact 10 A fast-acting General data MTBF on request Duty time 100 % Dimensions (W x H x D) product dimensions 22.5 x 85.6 x 103.7 mm (0.89 x 3.37 x 4.08 in) packaging dimensions 97 x 109 x 30 mm (3.82 x 4.29 x 1.18 in) Weight Screw connection technology Easy Connect Technology (Push-in) Net weight 0.157 kg (0.346 lb) 0.146 kg (0.322 lb) Gross weight 0.179 kg (0.395 lb) 0.168 kg (0.370 lb) Mounting DIN rail (IEC/EN 60715), snap-on mounting without any tool Mounting position any Material of housing UL 94 V-0 Degree of protection housing IP50 terminals IP20 14 - Voltage monitoring relay CM-EFS.2 Data sheet

Electrical connection Screw connection technology Easy Connect Technology (Push-in) Wire size fine strand with(out) 1 x 0.5-2.5 mm² 2 x 0.5-1.5 mm² wire end ferrule (1 x 20-14 AWG) (2 x 20-16 AWG) 2 x 0.5-1.5 mm² (2 x 20-16 AWG) rigid 1 x 0.5-4 mm² 2 x 0.5-1.5 mm² (1 x 20-12 AWG) (2 x 20-16 AWG) 2 x 0.5-2.5 mm² (2 x 20-14 AWG) Stripping length 8 mm (0.32 in) Tightening torque 0.6-0.8 Nm - (5.31-7.08 lb.in) Environmental data Ambient temperature ranges operation -20...+60 C storage -40...+85 C Damp heat, cyclic (IEC 60068-2-30) 55 C, 6 cycle Vibration, sinusoidal (IEC/EN 60255-21-1) class 2 Shock (IEC/EN 60255-21-2) class 2 Isolation data Rated insulation voltage U i supply / measuring circuit / output 600 V (VDE 0110, IEC/EN 60947-1, IEC/EN 60255-5) supply / output 1 / output 2 250 V Rated impulse withstand voltage U imp supply / measuring circuit / output 6 kv 1.2/50 μs (IEC/EN 60947-1, IEC/EN 60255-5) supply / output 1 / output 2 4 kv 1.2/50 μs Test voltage between all isolated circuits rated insulation voltage 250 V 2.0 kv, 50 Hz (type test) rated insulation voltage 600 V 2.5 kv, 50 Hz Pollution degree (VDE 0110, IEC/EN 60664, IEC/EN 60255-5) 3 Overvoltage category (VDE 0110, IEC/EN 60664, IEC/EN 60255-5) III Standards Product standard IEC/EN 60255-6 Low Voltage Directive EMC Directive RoHS Directive 2006/95/EC 2004/108/EC 2002/95/EC Electromagnetic compatibility Interference immunity to IEC/EN 61000-6-2 electrostatic discharge IEC/EN 61000-4-2 Level 3 radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 Level 3 electrical fast transient / burst IEC/EN 61000-4-4 Level 3 surge IEC/EN 61000-4-5 Level 3 conducted disturbances, induced by IEC/EN 61000-4-6 Level 3 radio-frequency fields Interference emission IEC/EN 61000-6-3 high-frequency radiated IEC/CISPR 22, EN 55022 Class B high-frequency conducted IEC/CISPR 22, EN 55022 Class B Data sheet Voltage monitoring relay CM-EFS.2-15

Technical diagrams Load limit curves V V 300 200 100 80 60 50 40 30 20 10 0.1 0.2 0.5 resistive load 1 2 4 6 10 I A 2CDC 252 194 F0205 V V 300 200 100 80 60 50 40 30 20 10 0.1 0.2 0.5 resistive load 1 2 4 6 10 I A 2CDC 252 193 F0205 AC load (resistive) DC load (resistive) F 1.0 0.9 0.8 0.7 0.6 Switching cycles 250 V resistive load 0.5 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 cos ϕ Derating factor F for inductive AC load 2CDC 252 192 F0205 Switching current [A] 2CDC 252 148 F0206 Contact lifetime 16 - Voltage monitoring relay CM-EFS.2 Data sheet

Dimensions in mm and inches 113.4 4.47 105.9 4.17 22.5 0.89 85.6 3.37 103.7 4.08 2CDC 252 009 F0011 Accessories in mm and inches 22.5 0.89 8 0.32 4.8 0.19 6.5 0.256 62.5 2.461 60 2.362 70 2.756 10 11.5 0.394 0.453 20 0.787 2CDC 252 008 F0010 22.2 0.874 4T22 19.9 0.783 7.85 0.309 2CDC 252 020 F0011 68 2.68 front to back 110.5 4.31 2CDC 252 010 F0011 ADP.01 Adapter for screw mounting MAR.12 Marker label for devices with DIP switches COV.11 Sealable transparent cover Further documentation Document title Document type Document number Electronic products and relays Technical catalogue 2CDC 110 004 C020x CM-EFS.2 Instruction manual 1SVC 730 570 M0000 You can find the documentation on the internet at www.abb.com/lowvoltage -> Control Products -> Electronic Relays and Controls -> Single Phase Monitors Data sheet Voltage monitoring relay CM-EFS.2-17

Contact us ABB STOTZ-KONTAKT GmbH P. O. Box 10 16 80 69006 Heidelberg, Germany Phone: +49 (0) 6221 7 01-0 Fax: +49 (0) 6221 7 01-13 25 E-mail: info.desto@de.abb.com You can find the address of your local sales organisation on the ABB home page http://www.abb.com/contacts -> Low Voltage Products and Systems Document number 2CDC 112 174 D0201 (11.2011) Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 2010 ABB All rights reserved