See Benchmark Geomagnetic Disturbance Event Description white paper, May 12, Filed by NERC in RM15-11 on June 28,

Similar documents
See Benchmark Geomagnetic Disturbance Event Description white paper, May 12, Filed by NERC in Docket No. RM15 11 on June 28, 2016.

Screening Criterion for Transformer Thermal Impact Assessment Summary Justification Figure 1 Figure 1

Screening Criterion for Transformer Thermal Impact Assessment Summary Justification Figure 1 Figure 1

Screening Criterion for Transformer Thermal Impact Assessment Summary Justification Figure 1 Figure 1

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

TPL is a new Reliability Standard to specifically address the Stage 2 directives in Order No. 779.

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

Transformer Thermal Impact Assessment White Paper (Draft) Project (Geomagnetic Disturbance Mitigation)

Transformer Thermal Impact Assessment White Paper Project (Geomagnetic Disturbance Mitigation)

Vulnerability Assessment and Planning

TPL Project Geomagnetic Disturbance Mitigation. Technical Conference May 20, 2014

TPL Project Geomagnetic Disturbance Mitigation. Technical Conference July 17, 2014

Evaluating Transformer Heating due to Geomagnetic Disturbances

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY

The Engineering Problem. Calculating GIC Flow through the EHV System

Effects of GIC on Power Transformers and Power Systems

TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

2013 Grid of the Future Symposium. Effect of GIC and GIC Capability of EHV Power Transformers A Case Study on an AEP 765 kv Power Transformer Design

Case Study Effects of Geomagnetically Induced Current (GIC) Neutral Blocking Device

Unofficial Comment Form Project Geomagnetic Disturbance Mitigation

Geo-Magnetic Disturbance Analysis of HV and EHV Grids

Geomagnetic Disturbance Planning Guide

Transformer Technology Seminar GIC Capability of Power Transformers

IEEE PES/IAS Joint Chapter July Technical Presentation Meeting Basics of solar phenomena & How transformers react and handle events

Consolidated Edison s Experience with On-line Monitoring and Mitigation of Geomagnetic Disturbances

GMD Voltage Collapse Study

Dietrich Bonmann, ABB AG Bad Honnef, March 15, Impact of GIC on transformers and the transmission network

GIC Analysis using PSS E. K.V. PATIL Siemens Power Technologies International Schenectady, New York, USA

Supplemental Geomagnetic Disturbance Event Description

Geomagnetic Disturbances. IEEE PES Chicago Chapter Technical Presentation March 12, Alan Engelmann Transmission Planning ComEd.

GIC Calculations Using PSS E. Live Demonstration February 16, 2017

FINNISH EXPERIENCES ON GRID EFFECTS OF GIC'S

Interfacing Power System Simulators with Geomagnetically Induced Currents (GIC) Simulation Programs. Luis Marti Hydro One, Canada

MHD-EMP (E3) Assessment of the US Power Grid GIC and Transformer Thermal Assessment

Magnetohydrodynamic Electromagnetic Pulse Assessment of the Continental U.S. Electric Grid

A Process for Evaluating the Degree of Susceptibility of a fleet of Power Transformers to Effects of GIC

1

Power System Impacts of Geomagnetic Disturbances

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

Benchmark Geomagnetic Disturbance Event Description

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

High-Level Harmonic Distortion During Geomagnetic Disturbances - a Hidden Threat to Grid Security

100-year GIC event scenarios. Antti Pulkkinen and Chigomezyo Ngwira The Catholic University of America & NASA Goddard Space Flight Center

Disturbances. Their Impact on the Power Grid. By the IEEE Power & Energy Society Technical Council Task Force on

Hydro One GMD Preparedness Plan for Cycle 24

Definition of Bulk Electric System Phase 2

Bulk Electric System Definition Reference Document

Modeling and Evaluation of Geomagnetic Storms in the Electric Power System

Bulk Electric System Definition Reference Document

concerning the risks to the electric power grid from geomagnetic storms,

Bulk Electric System Definition Reference Document

NORMES DE FIABILITÉ DE LA NERC (VERSION ANGLAISE)

Investigation of Geomagnetic Induced Current Effects on Power Transformer

Standard Development Timeline

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction. See the Implementation Plan for PRC

Comprehensive Study on Magnetization Current Harmonics of Power Transformers due to GICs

Loss prophet. Predicting stray losses in power transformers and optimization of tank shielding using FEM

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer

Operational Experiences of an HV Transformer Neutral Blocking Device

Model, Monitor & Mitigate Geomagnetically Induced Currents

Application Guide. Computing Geomagnetically-Induced Current in the Bulk-Power System. December 2013

Final ballot January BOT adoption February 2015

Minnesota Power Systems Conference 2015 Improving System Protection Reliability and Security

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction

(Circuits Subject to Requirements R1 R5) Generator Owner with load-responsive phase protection systems as described in

Demagnetization of Power Transformers Following a DC Resistance Testing

MITIGATING GEOMAGNETIC INDUCED CURRENTS USING SURGE ARRESTERS. Alberto Ramirez Orquin Vanessa Ramirez Resilient Grids, LLC.

ITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

Picture perfect. Electromagnetic simulations of transformers

Power Quality Requirements for Connection to the Transmission System

DUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES. Transmission Planning

Space Weather Impact on the Scandinavian Interconnected Power Transmission System

Protecting power transformers from common adverse conditions

DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER

Standard PRC Coordination of Generating Unit or Plant Capabilities, Voltage Regulating Controls, and Protection

AS/NZS :2013 (IEC , , MOD)

Final ballot January BOT adoption February 2015

MidAmerican Energy Company 100 kv and Above Facility Ratings Methodology

Optimization of power transformers based on operative service conditions for improved performance

Standard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules. 45-day Formal Comment Period with Initial Ballot June July 2014

Standard MOD Verification of Models and Data for Generator Excitation Control System or Plant Volt/Var Control Functions

(2) New Standard IEEE P (3) Core : (4) Windings :

PHYSICAL PHENOMENA EXISTING IN THE TURBOGENERATOR DURING FAULTY SYNCHRONIZATION WITH INVERSE PHASE SEQUENCE*

Standard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules

Unit Auxiliary Transformer Overcurrent Relay Loadability During a Transmission Depressed Voltage Condition

Standard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules

GIC Neutral Blocking System Prototype to Production

Importance of Transformer Demagnetization

Summary of Relaying Reviews Reporting

Standard Development Timeline

IEEE Major Revision of Interconnection Standard

SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces

Standard MOD Verification of Models and Data for Generator Excitation Control Sys tem or Plant Volt/Var Control Functions

CHAPTER 4 MULTI-LEVEL INVERTER BASED DVR SYSTEM

Transformer Factory Testing

IEEE sion/1547revision_index.html

Transcription:

Screening Criterion for Transformer Thermal Impact Assessment Project 2013-03 (Geomagnetic Disturbance Mitigation) TPL-007-12 Transmission System Planned Performance for Geomagnetic Disturbance Events Summary Proposed standard TPL-007-1 Transmission System Planned Performance for Geomagnetic Disturbance Events requires applicable entities to conduct assessments of the potential impact of benchmark GMD events on their systems. The standard requires transformer thermal impact assessments to be performed on power transformers with high side, wye-grounded windings with terminal voltage greater than 200 kv. Transformers are exempt from the thermal impact assessment requirement if the maximum effective geomagnetically-induced current (GIC) in the transformer is less than75 A per phase as determined by GIC analysis of the system. Based on published power transformer measurement data as described below, an effective GIC of 75 A per phase is a conservative screening criterion. To provide an added measure of conservatism, the 75 A per phase threshold, although derived from measurements in single-phase units, is applicable to transformers with all core types (e.g., three-limb, three-phase). Proposed TPL-007-2 includes requirements for entities to perform two types of GMD Vulnerability Assessments to evaluate the potential impacts of GMD events on the Bulk Electric System (BES): The benchmark GMD Vulnerability Assessment is based on the benchmark GMD event associated with TPL-007-1 which was approved by the Federal Energy Regulatory Commission (FERC) in Order No. 830 in September 2016. The benchmark GMD event is derived from spatially-averaged geoelectric field values to address potential wide-area effects that could be caused by a severe 1-in- 100 year GMD event. 1 The supplemental GMD Vulnerability Assessment, based on the supplemental GMD event, is used by entities to evaluate risks that localized peaks in geomagnetic field during a severe GMD event "could potentially affect the reliable operation of the Bulk-Power System". 2 Localized enhancements of geomagnetic field can result in geoelectric field values above the spatiallyaveraged benchmark in a local area. 1 See Benchmark Geomagnetic Disturbance Event Description white paper, May 12, 2016. Filed by NERC in RM15-11 on June 28, 2016. 2 See Order No. 830 P. 47. On September 22, 2016, FERC directed NERC to develop modifications to the benchmark GMD event, included in TPL-007-1, such that assessments would not be based solely on spatially averaged data. The characteristics of a GMD event for this assessment are in the Supplemental GMD Event Description white paper.

The standard requires transformer thermal impact assessments to be performed on BES power transformers with high side, wye-grounded windings with terminal voltage greater than 200 kv. Identified BES transformers must undergo a thermal impact assessment if the maximum effective geomagneticallyinduced current (GIC) in the transformer is equal to or greater than: 75 A per phase for the benchmark GMD event 85 A per phase for the supplemental GMD event Based on published power transformer measurement data as described below, the respective screening criteria are conservative and, although derived from measurements in single-phase units, are applicable to transformers with all core types (e.g., three-limb, three-phase). Outside of the differing screening criteria, the only difference between the thermal impact assessment for the benchmark GMD event and the supplemental GMD event is that a different waveform is used, therefore peak metallic hot spot temperatures are slightly different for a given GIC in the transformer. Justification for the Benchmark Screening Criterion Applicable entities are required to carry out a thermal assessment with GIC(t) calculated using the benchmark GMD event geomagnetic field time series or waveshapewaveform for effective GIC values above a screening threshold. The calculated GIC(t) for every transformer will be different because the length and orientation of transmission circuits connected to each transformer will be different even if the geoelectric field is assumed to be uniform. However, for a given thermal model and maximum effective GIC there are upper and lower bounds for the peak hot spot temperatures. These are shown in Figure 1 using three available thermal models based on direct temperature measurements. The results shown in Figure 1 summarize the peak metallic hot spot temperatures when GIC(t) is calculated using (1), and systematically varying GICE and GICN to account for all possible orientation of circuits connected to a transformer. The transformer GIC (in A/phase) for any value of EE(t) and EN(t) can be calculated using equation (1) from reference [1]. where { GIC sin( ϕ ( t)) + GIC cos( ϕ( ))} GIC( t) = E( t) t (1) E N E( t) 2 2 = E ( t) E ( t) (2) N + E 1 E E ( t) ϕ ( t) = tan (3) EN ( t) 2017 2

GIC( t) = E ( t) GIC + E ( t) GIC (4) E E N N GICN is the effective GIC due to a northward geoelectric field of 1 V/km, and GICE is the effective GIC due to an eastward geoelectric field of 1 V/km. The units for GICN and GICE are A/phase/ per V/km. It should be emphasized that with the thermal models used and the benchmark GMD event geomagnetic field waveshapewaveform, peak metallic hot spot temperatures mustwill lie below the envelope shown in black in Figure 1. The x-axis in Figure 1 corresponds to the absolute value of peak GIC(t). Effective maximum GIC for a transformer corresponds to a worst-case geoelectric field orientation, which is network-specific. Figure 1 represents a possible range, not the specific thermal response for a given effective GIC and orientation. Figure 1: Metallic hot spot temperatures calculated using the benchmark GMD event. Red: SVC coupling transformer model [2]. Blue: Fingrid model [3]. Green: Autotransformer model [4]. Red: SVC coupling transformer model [2]. Blue: Fingrid model [3]. Green: Autotransformer model [4]. Consequently, with the most conservative thermal models known at this point in time, the peak metallic hot spot temperature obtained with the benchmark GMD event waveshapewaveform assuming an effective GIC magnitude of 75 A per phase will result in a peak temperature between 160 C and 172 C when the bulk oil temperature is 80 C (full load bulk oil temperature). The upper boundary of 172 C remains well 2017 3

below the metallic hot spot 200 C threshold for short-time emergency loading suggested in IEEE Std C57.91-2011 [5] (see Table 1). Guide for Loading Mineral-Oil-Immersed Transformers and Step-Voltage Regulators [5]. TABLE 1: Excerpt from Maximum Temperature Limits Suggested in IEEE C57.91-2011 Planned loading Normal life beyond Long-time Short-time expectancy nameplate emergency emergency loading rating loading loading Insulated conductor hottest-spot temperature C Other metallic hot-spot temperature (in contact and not in contact with insulation), C 120 130 140 180 140 150 160 200 Top-oil temperature C 105 110 110 110 The selection of the 75 A per phase screening threshold is based on the following considerations: A thermal assessment using, which uses the most conservative thermal models known to date, indicates that a GIC of 75A will not result in peak metallic hot spot temperatures above 172 C. Transformer thermal assessments should not be required by Reliability Standards when results will fall well below IEEE Std C57.91-2011 limits. Applicable entities may choose to carry out a thermal assessment when the effective GIC is below 75 A per phase to take into account the age or condition of specific transformers where IEEE Std C57.91-2011 limits could be assumed to be lower than 200 C. Refer to IEEE Standard C57.163-2015 Guide for Establishing Power Transformer Capability while under Geomagnetic Disturbances for additional information [6]. The models used to determine the 75 A per phase screening threshold are known to be conservative at higher values of effective GIC, especially the SVC coupling transformer model in [2]. Thermal models in peer-reviewed technical literature, especially those calculated models without experimental validation, are less conservative than the models used to determine the screening threshold. Therefore, a technically-justified thermal assessment for effective GIC below 75 A per phase using the benchmark GMD event geomagnetic field waveshapewaveform will always result in a pass on the basis of the state of the knowledge at this point in time. Based on simulations, the 75 A per phase screening threshold will result in a maximum instantaneous peak hot spot temperature of 172 C. However, IEEE Std C57.91-2011 limits assume short term emergency operation (typically 30 minutes). As illustrated in Figure 2, simulations of the 75 A per phase screening threshold result in 30-minute duration hot spot temperatures of about 2017 4

155 C. The threshold provides an added measure of conservatism in not taking into account the duration of hot spot temperatures. The models used in the determination of the threshold are conservative but technically justified. Winding hot spots are not the limiting factor in terms of hot spots due to half-cycle saturation, therefore the screening criterion is focused on metallic part hot spots only. The 75 A per phase screening threshold was determined using single-phase transformers, but is applicable tobeing applied as a screening criterion for all types of transformer construction. While it is known that some transformer types such as three-limb, three-phase transformers are intrinsically less susceptible to GIC, it is not known by how much, on the basis of experimentally-supported models. Figure 2: Metallic hot spot temperatures calculated using the benchmark GMD event. Red: metallic hot spot temperature. Blue: GIC(t) that produces the maximum hot spot temperature with peak GIC(t) scaled to 75 A/phase. Red: metallic hot spot temperature. Blue: GIC(t) that produces the maximum hot spot temperature with peak GIC(t) scaled to 75 A/phase. Justification for the Supplemental Screening Criterion As in the case for the benchmark GMD event discussed above, applicable entities are required to carry out thermal assessments on their BES power transformers when the effective GIC values are above a screening threshold. GIC(t) for supplemental thermal assessments is calculated using the supplemental GMD event geomagnetic field time series or waveform. 2017 5

Using the supplemental GMD event waveform, a thermal analysis was completed for the two transformers that were limiting for the benchmark waveform. The results are shown in Figure 3. Peak metallic hot spot temperatures for the supplemental GMD event will lie below the envelope shown by the black line trace in Figure 3. Because the supplemental waveform has a sharper peak, the peak metallic hot spot temperatures are slightly lower than those associated with the benchmark waveform. Applying the most conservative thermal models known at this point in time, the peak metallic hot spot temperature obtained with the supplemental GMD event waveform assuming an effective GIC magnitude of 85 A per phase will result in a peak temperature of 172 C when the bulk oil temperature is 80 C (full load bulk oil temperature). 3 Thus, 85 A per phase is the screening level for the supplemental waveform. Figure 3: Metallic hot spot temperatures calculated using the supplemental GMD event. Green: SVC coupling transformer model [2]. Red: Autotransformer model [4] 3 The temperature 172 C was selected as the screening criteria for the benchmark waveform as described in the preceding section. 2017 6

Appendix I - Transformer Thermal Models Used in the Development of the Screening Criteria The envelope used for thermal screening (Figure 1) is derived from two thermal models. The first is based on laboratory measurements carried out on 500/16.5 kv 400 MVA single-phase Static Var Compensator (SVC) coupling transformer [2]. Temperature measurements were carried out at relatively small values of GIC (see Figure 3I-1). The asymptotic thermal response for this model is the linear extrapolation of the known measurement values. Although the near-linear behavior of the asymptotic thermal response is consistent with the measurements made on a Fingrid 400 kv 400 MVA five-leg core-type fully-wound transformer [3] (see Figures 4I-2 and 5I-3), the extrapolation from low values of GIC is very conservative, but reasonable for screening purposes. The second transformer model is based on a combination of measurements and modeling for a 400 kv 400 MVA single-phase core-type autotransformer [4] (see Figures 6I-4 and 7I-5). The asymptotic thermal behavior of this transformer shows a down-turn at high values of GIC as the tie plate increasingly saturates but relatively high temperatures for lower values of GIC. The hot spot temperatures are higher than for the two other models for GIC less than 125 A per phase. 18 16 Temperature (deg. C) 14 12 10 8 6 4 2 0 0 5 10 15 20 25 30 Time (min) Figure 3: I-1: Thermal step response of the tie plate of a 500 kv 400 MVA single-phase SVC coupling transformer to a 5 A per phase dc step. 2017 7

35 30 Temperature (deg. C) 25 20 15 10 5 0 0 5 10 15 20 25 30 35 40 45 Time (min) Figure 4I-2: Step thermal response of the top yoke clamp of a 400 kv 400 MVA five-leg coretype fully-wound transformer to a 16.67 A per phase dc step. Temperature (deg. C) 200 180 160 140 120 100 80 60 40 20 0 0 10 20 30 40 50 60 70 80 90 100 GIC (A/phase) Figure 5: I-3: Asymptotic thermal response of the top yoke clamp of a 400 kv 400 MVA fiveleg core-type fully-wound transformer. 2017 8

60 Temperature (deg. C) 50 40 30 20 10 0 0 5 10 15 20 25 30 Time (min) 70 Temperature (deg. C) 60 50 40 30 20 10 0 0 10 20 30 Time (min) Figure 6I-4: Step thermal response of the tie plate of a 400 kv 400 MVA single-phase coretype autotransformer to a 10 A per phase dc step. 2017 9

180 160 Temperature (deg. C) 140 120 100 80 60 40 20 0 0 10 20 30 40 50 60 70 80 90 100 GIC (A/phase) Figure 7I-5: Asymptotic thermal response of the tie plate of a 400 kv 400 MVA single-phase core-type autotransformer. The envelope in Figure 1 can be used as a conservative thermal assessment for effective GIC values of 75 A per phase and greaterassociated with the benchmark waveform (see Table 21). Table 21: Upper Bound of Peak Metallic Hot Spot Temperatures Calculated Using the Benchmark GMD Event Effective GIC (A/phase) Metallic hot spot Temperature ( C ) Effective GIC (A/phase) Metallic hot spot Temperature ( C ) 0 80 100 182 10 107 110 186 20 128 120 190 30 139 130 193 40 148 140 204 50 157 150 213 60 169 160 221 70 170 170 230 75 172 180 234 80 175 190 241 90 179 200 247 2017 10

For instance, if effective GIC is 130 A per phase and oil temperature is assumed to be 80 C, peak hot spot temperature is 193 C. This value is below the 200 C IEEE Std C57.91-2011 threshold for short time emergency loading and this transformer will have passed the thermal assessment. If the full heat run oil temperature is 67 C at maximum ambient temperature, then 150 A per phase of effective GIC translates into a peak hot spot temperature of 200 C and the transformer will have passed. If the limit is lowered to 180 C to account for the condition of the transformer, then this would be an indication to sharpen the pencil and perform a detailed assessment. Some methods are described in Reference [1]. The temperature envelope in Figure 1 corresponds to the values of effective GIC that result in the highest temperature for the benchmark GMD event. Different values of effective GIC could result in lower temperatures using the same model. For instance, the difference in upper and lower bounds of peak temperatures for the SVC coupling transformer model for 150 A per phase is approximately 30 C. In this case, GIC(t) should be generated to calculate the peak temperatures for the actual configuration of the transformer within the system as described in Reference [1]. Alternatively, a more precise thermal assessment could be carried out with a thermal model that more closely represents the thermal behavior of the transformer under consideration. Similar to the discussion above, the envelope in Figure 3 can be used as a conservative thermal assessment for effective GIC values of associated with the supplemental waveform (see Table 2). Because the supplemental waveform has a sharper peak, the peak metallic hot spot temperatures associated with the supplemental waveform are slightly lower than those associated with the benchmark waveform. Comparing Tables 1 and 2 shows the magnitude of this difference. Table 2: Upper Bound of Peak Metallic Hot Spot Temperatures Calculated Using the Supplemental GMD Event Effective GIC (A/phase) Metallic hot spot Temperature ( C ) Effective GIC(A/phase) Metallic hot spot Temperature ( C ) 0 80 120 188 10 107 130 191 20 124 140 194 30 137 150 198 40 147 160 203 50 156 170 209 60 161 180 214 70 162 190 229 75 165 200 237 80 169 220 248 85 172 230 253 90 177 250 276 2017 11

100 181 275 298 110 185 300 316 2017 12

References [1] Transformer Thermal Impact Assessment white paper. Developed by the Project 2013-03 (Geomagnetic Disturbance) standard drafting team. Available at: http://www.nerc.com/pa/stand/pages/project-2013-03-geomagnetic-disturbance- Mitigation.aspxhttp://www.nerc.com/pa/stand/Pages/TPL0071RI.aspx [2] Marti, L., Rezaei-Zare, A., Narang, A., "Simulation of Transformer Hotspot Heating due to Geomagnetically Induced Currents," IEEE Transactions on Power Delivery, vol.28, no.1, pp.320-327, Jan. 2013. [3] Lahtinen, Matti. Jarmo Elovaara. GIC occurrences and GIC test for 400 kv system transformer. IEEE Transactions on Power Delivery, Vol. 17, No. 2. April 2002. [4] J. Raith, S. Ausserhofer: GIC Strength verification of Power Transformers in a High Voltage Laboratory, GIC Workshop, Cape Town, April 2014 [5] [5] "IEEE Guide for loading mineral-oil-immersed transformersloading Mineral-Oil-Immersed Transformers and step-voltage regulatorsstep-voltage Regulators." IEEE Std C57.91-2011 (Revision of IEEE Std C57.91-1995). [6] IEEE Guide for Establishing Power Transformer Capability while under Geomagnetic Disturbances. IEEE Std C57.163-2015. 2017 13