Power Factor Improvement Using a Three Phase Shunt Active Power Filter

Similar documents
Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

Enhancement of Power Quality Using Advanced Series Active Power Filters

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER

NEUTRAL CURRENT COMPENSATION USING FOUR LEG SHUNT ACTIVE POWER FILTER

Power Quality improvement of a three phase four wire system using UPQC

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Review on Shunt Active Power Filter for Three Phase Four Wire System

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online):

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Control Of Shunt Active Filter Based On Instantaneous Power Theory

Analysis of Advanced Techniques to Eliminate Harmonics in AC Drives

SHUNT ACTIVE POWER FILTER

Real Time Implementation of Shunt Active Power Filter (SAPF) for Harmonic suppression and Power Quality Improvement

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Three Phase Active Power Filter Based on Current Controlled Voltage Source Inverter

ISSN Vol.03,Issue.42 November-2014, Pages:

ISSN Vol.03,Issue.07, August-2015, Pages:

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

Power Quality Improvement using Shunt Passive Filter

DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF)

A Comparative Study on Four Time-Domain Harmonic Detection Methods for Active Power Filters Serving in Distorted Supply

Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation

SCIENCE & TECHNOLOGY

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

Indirect Current Control of LCL Based Shunt Active Power Filter

International Journal of Advance Research in Engineering, Science & Technology

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Mitigation of Current Harmonics with Combined p-q and Id-IqControl Strategies for Fuzzy Controller Based 3Phase 4Wire Shunt Active Filter

IMPROVING EFFICIENCY OF ACTIVE POWER FILTER FOR RENEWABLE POWER GENERATION SYSTEMS BY USING PREDICTIVE CONTROL METHOD AND FUZZY LOGIC CONTROL METHOD

Chapter 2 Shunt Active Power Filter

Three-Level Shunt Active Filter Compensating Harmonics and Reactive Power

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Index Terms Active power filter (APF), harmonics, hysteresis band, fuzzy logic control.

Assessment of Different Compensation Strategies in Hybrid Active Power Filters

Simulation Results of a Shunt Active Power Filter with Control Based on p-q Theory

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

POWER QUALITY IMPROVEMENT FOR DISTRIBUTION NETWORK BY DESIGN OF TWO CONTROL STRATEGIES FOR ACTIVE POWER FILTER.

SIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC

2020 P a g e. Figure.2: Line diagram of series active power filter.

Literature Review for Shunt Active Power Filters

Comparison of Shunt Active Power Filter Control Strategies for Harmonic Compensation in a Paper Industrial Factory

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

Kanuru; Krishna (Dt); A.P, India. DOI: / Page. 1 G. Aruna Jyothi, 2 DR. P. V. R. L.

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

PI Controller Based Shunt Active Power Filter with Cascaded Multilevel Inverter

Comparison of Various Reference Current Generation Techniques for Performance Analysis of Shunt Active Power Filter using MATLAB Simulation

SHUNT COMPENSATOR USED FOR POWER QUALITY IMPROVEMENT

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Reduction In Total Harmonic Distortion Using Active Power Filters

Mitigation of Line Current Harmonics Using Shunt Active Filter With Instantaneous Real and Reactive Power Theory

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

Nonconventional Technologies Review no. 4/2009

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System

Comparison of Control Algorithms for Shunt Active Filter for Harmonic Mitigation

Power Control and Quality Management in DG Grid Interfaced Systems

Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control

Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers

CHAPTER 7 CONCLUSIONS AND FUTURE SCOPE

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

Analysis of Reference Current Generation for Shunt Active Power Filter Using SRF Algorithm to Compensate Harmonic Current

p. 1 p. 6 p. 22 p. 46 p. 58

Svpwm Technique to Eliminate Harmonics and Power Factor Improvement Using Hybrid Power Filter and By Using Dsp Tms 320lf2407

Shunt active filter algorithms for a three phase system fed to adjustable speed drive

Harmonics Elimination Using Shunt Active Filter

Field Programmable Gate Array-Based Pulse-Width Modulation for Single Phase Active Power Filter

Power Quality Improvement using Active shunt Power filter using PI Controller

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

CHAPTER 4 DESIGN OF DC LINK VOLTAGE CONTROLLER FOR SHUNT ACTIVE POWER FILTER

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

Comparative Analysis of Harmonics with and Without Shunt Active Power Filter

PERFORMANCE EVALUATION OF THREE PHASE SCALAR CONTROLLED PWM RECTIFIER USING DIFFERENT CARRIER AND MODULATING SIGNAL

Improvement of Power Quality Using a Hybrid Interline UPQC

Reactive power compensation for linear and non linear loads by using active and passive filter for smart grid applications.

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Neural Network Controlled Hybrid Active Power Filter with Distorted Mains for PMSM Drive

CURRENT HARMONICS REDUCTION IN 3 PHASES 4 WIRE SYSTEM USING HYBRID FILTERS R.Saravanakumar 1#, S.Amritha 2#

Field Programmable Gate Array (FPGA) Based Pulse Width Modulation for Single Phase Hybrid Active Power Filters U. Krishna Reddy 1 Ch.

Application of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System

Control schemes for shunt active filters to mitigate harmonics injected by inverted-fed motors

POWER QUALITY IMPROVEMENT BY HARMONIC REDUCTION USING THREE PHASE SHUNT ACTIVE POWER FILTER WITH p-q & d-q CURRENT CONTROL STRATEGY

Transcription:

16 th International Conference on AEROSPACE SCIENCES & AVIATION TECHNOLOGY, ASAT - 16 May 26-28, 2015, E-Mail: asat@mtc.edu.eg Military Technical College, Kobry Elkobbah, Cairo, Egypt Tel : +(202) 24025292 24036138, Fax: +(202) 22621908 Paper: ASAT-16-009-EP Power Factor Improvement Using a Three Phase Shunt Active Power Filter S. Abdelrazik *, TH. Elshater and Y. Abdalla Abstract The increasing growth in the use of electronic equipment in recent years has resulted in a greater need to ensure that the line current harmonic content of any equipment connected to the ac mains is limited to meet regulatory standards. Shunt Active Power Filters (SAPF) are used to compensate both harmonic and reactive current component for the power supplies. It also improves the power quality and power factor on power utility. In this paper, Application of Direct Testing and Calculating Method (DTCM) in Shunt Active filters is proposed to estimate reference current signal, and apply hysteresis control to generate gate pulses. The results of simulation study of control scheme presented in this paper is found quite satisfactory for eliminate harmonics and reactive power components from utility, successful in meeting the IEEE 519 recommended harmonic standard limits. Keywords: Shunt Active Power Filters, Harmonic currents, reference Current signal, hysteresis control. Nomenclature Kᵩ displacement factor K d distortion factor i p active current component i q reactive current component i h harmonic load current I F reference current signal the estimated current I L load current signal α phase shift angle H a signal deviation Reference Current signal * Teaching Assistant, Faculty of Industrial Education, Helwan University, Cairo, Egypt, Mohamed_samar47@yahoo.com Associate Professor, Faculty of Industrial Education, Helwan University, Cairo, Egypt, elshater_thanaa@yahoo.ca Teacher, Faculty of Industrial Education, Suez University, Suez Egypt, dreng.yasser@yahoo.com 1

1. Introduction Modern electrical systems cause an increasing harmonic disturbance in the ac main currents, due to wide spread of power conversion units and power electronics equipments. These harmonic currents cause adverse effects in power systems such as overheating, perturbation of sensitive control and communication equipment, capacitor blowing, motor vibration, excessive neutral currents, resonances with the grid and low power factor [1]. The power factor values measures how much the mains efficiency is affected by both phase lag φ and harmonic content of the input current. Its value lies in the range between 0 and 1 and it is computed as the ratio of the real power to the apparent power. Power Factor can be calculated as: (1) Where, (2) Another important parameter that measure the percentage of distortion is known as the Current Total Harmonic Distortion (THD ) which is defined as follows: (3) From equations (2), (4) we get the relationship between the THD and the K d : (4) Where: (6) (5) Harmonic distortion in power distribution systems can be suppressed using two approaches namely, passive and active powering. The passive filtering is the simplest conventional solution to mitigate the harmonic distortion [2,3]. Although simple, passive filters have many disadvantages, such as large size, resonance, and fixed compensation characteristics. Therefore, it does not provide a complete solution [4]. In order to solve these problems, the concept of APF was presented. Active power filters, which compensate harmonic and reactive current component for the power supplies, can improve the power qualities and improve the power factor on power utility. In recent 40 years from APF presented, the continual innovation of control strategies mainly impels the APF techniques to be developed rapidly. In the active filter a controller determines the harmonics that are to be eliminated and generates appropriate gating signals for the inverter. Many harmonic detection techniques for active power filters have been studied. In frequency domain, Discrete Fourier Transform (DFT) and Fast Fourier Transform (FFT) have been widely used [5,6]. The main disadvantage of these techniques is the time delay associated with sampling and computation of Fourier coefficients, which makes them difficult for real-time application on dynamically varying load [7]. On the other hand, the time domain methods require less calculations and are widely 2

followed for computing the reference current. The time-domain methods include, instantaneous reactive power theory p-q method [1 and 7-11], Synchronous Reference Frame (SRF) [12, 13], Direct Testing and Calculating Method (DTCM) and Notch Filtering. This paper presents modeling and simulation of a direct testing and calculating control algorithm of active power filter using MATLAB Simulink. Direct testing and calculating control algorithm offers an advantage to compensate the harmonics generated through the load application [14]. The proposed scheme provides an additional feature over compensating harmonics only by compensating both harmonics and reactive power simultaneously. 2. SAPF Operating Principles Many researches have been carried out to find the best performed control strategy for the shunt APF. However, before developing the controller, the basic concept of active filter control used in the design has to be defined. Operating principle of shunt APF depends on providing reactive power and harmonic components of load current. By this way, filter and load together behaves like a resistive load and only fundamental component of load current in phase with voltage is drawn from ac mains [15]. If the load current (I L ) is i p + i q + i h where i p is the fundamental active component, i q is the reactive component and i h is the harmonic load current, then the SAPF should inject a negative current of amplitude ( i q + i h ) to obtain the active component i p only, which is sinusoidal and in phase with the mains voltage. A description of the SAPF components as shown in Fig.1 is the voltage source inverter (VSI), the control unit, the modulation unit, the DC link is a capacitor (C) as storage energy, and the inductors (L f ). The control unit generates the reference currents of the shunt APF. The reference current signal (I F ) and the estimated current ( ) are the inputs to the modulation unit to generate the gating signals for the VSI [16]. Utility L f DC link Inverter I L Nonlinear load Gating signal Modulation Unit I F Control Unit V S I L Fig. 1 Three-phase shunt APF 3. Proposed Method The control strategies of the active filters are implemented mainly in three steps: Signal measuring, generating the reference signal and generation of gating signals for switching devices. The proposed method for generating the reference current signal is Direct Testing and Calculating Method (DTCM). Which is used widely in the signal processing in recent 3

years. This reference current signal is fed to the hysteresis current control to have the PWM pulses. Fig. 2 Shows block diagram of the proposed system. V s PLL Hysteresis control I L Sin ω RMS Peak + Value error + Gating signal Fig. 2 Block diagram of the proposed system The proposed scheme provides an additional feature over compensating harmonics only [14] by compensating both harmonics and reactive power simultaneously. The PLL generates a signal (ω) synchronized with the fundamental component of load current (I 1rms ) [14]. The power factor (P.F) in this case is less than unity as explained in the following equations. (7) Where Where α is phase shift angle of required source current ( ) and in phase with load current. While in our case the power factor is equal to unity. Where (9) Where α is phase shift angle of required source current ( ) and in phase with source voltage. (8) 3.1. Direct Testing and Calculating Method (DTCM) The aim of reference current signal generator is to separate the harmonic and reactive components from the load current. The main characteristic of this method is the direct derivation of the compensating component from the load current, without the use of any reference frame transformation [17]. The block diagram of the direct testing and calculating method is shown in Fig. 3. In the circuit, the distorted load current (I L ) is filtered to extract the fundamental component by low pass filter (LPF) then multiplies by peak value to produce (I M ). PLL generates a signal (ω) synchronized with the source voltage (V S ). The calculated current signal (I M ) is synchronized with the respective source voltage (V S ) through the application of PLL. The output signal from PLL (ω) is then multiplied by the amplitude of the fundamental component to obtain the 4

required source current ( ). The calculated current ( ) is subtracted from the load current (I L ) to have the required filter current (Reference Current signal). V s I L LPF PLL I RMS Peak value Sin ω I L I M Fig. 3 Block diagram of the direct testing and calculating method 3.2. Hysteresis current control conclusion The third stage of the shunt APF control circuit is generating appropriate gating signals for the power switches that forces the filter current ( ) signal to follow its estimated reference current signal ( ) within a certain tolerance band to reduce the current error. This control scheme is shown in Fig. 4. In this control scheme, a signal deviation (H) is designed and imposed on to form the upper and lower limits of a hysteresis band. Hysteresis current controller with a fixed H. To obtain a compensation current ( ) with switching ripples as small as possible, the value of H can be reduced. However, doing so results in higher switching frequency. Thus, increases losses on the switching transistors. The advantages of using the Current hysteresis control are its excellent dynamic performance and controllability of the peak-to-peak current ripple within a specified hysteresis [18]. Fig. 5 Shows the Gating signal generation by hysteresis current control technique. An error signal (e) is used to control the switches in an inverter. This error is the difference between the desired filter current ( ) and its estimated reference current signal ( ) as (e= I= - ). When the error reaches an upper limit as I H/2, the transistors are switched to force the current down. When the error reaches a lower limit as I -H/2, the current is forced to increase. Hysteresis band comparator + - error -H/2 +H/2 Gatig signal error Active power Filter Fig. 4 Block diagram of current hysteresis control technique 5

Upper limit = H/2 Actual signal Reference signal t Lower limit =-H/2 Gating Signal Uneven frequency f s Fig. 5 Gating signal generation by hysteresis current control technique Start Measure I F, I L, V S V S shape I L peak Sin ω I L I L -I * S I * S I * f I= -I * f I H/2 No No change No I - H/2 Yes No change Yes Gating signal ON Gating signal OFF Gating signal generation Inverter Fig. 6 Flow chart for the proposed control process 6

4. Simulation Results The Matlab/Simulink simulation tool [19] used to develop a model that allow the simulation and testing of the DTC theory calculations Fig. 6 Shows Flow chart for the controller of the shunt active power filter. The flow chart procedures are described in steps: a) Measured the variable parameters (I F, I L,V S ). b) Extract the fundamental component of load current peak value (I L peak) from the measured I L. c) Extract the shape of source voltage (V S shape) from the measured V S. d) Generate the reference source current signal ( ) by multiply the second and third steps. e) Generate the reference filter current signal ( ) by subtract the reference source current signal ( ) from the load current signal (I L ). f) Subtract the reference filter current signal ( ) from the filter current signal (I F ) to obtain error signal ( I). g) If the error signal ( ) equal or greater than the half value of signal deviation (H) then the gating signal off will be obtained. h) If the error signal ( I) don t equal or greater than the half value of signal deviation (H) then no change. i) If the error signal ( I) equal or smaller than the negative half value of signal deviation (H) then the gating signal on will be obtained. j) If the error signal ( I) don t equal or smaller than the negative half value of signal deviation (H) then no change. k) The pulses generated through steps 7 and 9 will be obtained to delivered to the inverter switches and the steps will be repeated as well as the system under operation. Shunt Active Filtering (SAF) operation has been simulated using the MATLAB/SIMULINK. The system parameters considered for the study of APF for DTCM controller with hysteresis current controller are given in Table 1 Table 1 APF System Parameters System Parameters Line Voltage Supply Frequency Source Impedance:(Resistance Rs, Inductance Ls) Diode rectifier load resistance ( R1, R2) Filter Impedance:(Resistance R f, inductance L f ) Dc side capacitance Value 380 V 50 HZ (1 Ω, 1mH) 30 Ω, 15 Ω (1 Ω, 1mH) 250μF Fig. 7 shows the simulation results V s, I s and I L of the system before compensation. Fig. 8 presents the simulation results after compensation. As seen I s is sinusoidal and in phase with V s. Fig. 9 shows simulation results for I s harmonic spectrum before and after compensation. Before harmonic compensation the THD of the supply current was 15.71% and after the harmonic compensation, it was reduced to 3.37% which complies with the IEEE 519 harmonic standards [20]. The power factor is increase from 0.51 before compensation to 0.989 after compensation. 7

Fig. 7 simulation results for source voltage (V s ), source current (I s ) and load current (I L ) before compensatin Fig. 8 waveforms of source voltage, source current, load current and filter current after compensating Fig. 9 (a) Input current harmonic spectrum before compensating (b) Input current harmonic spectrum after compensating 5. Conclusion In this paper a direct testing and calculating (DTC) approach theory based three-phase shunt active power filter has been proposed. The simulating results demonstrate the validity of the proposed SAPF for compensating reactive power and current harmonic components to improve the power factor. The THD of the source current is reduced below the 5% limit imposed by IEEE STD. 519-1992 standard and the power factor close to unity for nonlinear load using the SAPF. 8

References [1] Adam, G., Stan, A. and Livinţ, G., A Matlab-Simulink Approach To Shunt Active Power Filters, Proceedings of 25th European Conference on Modelling and Simulation 2011, pp. 205-210. [2] Alex, S. L. and Braz, F., Analysis of Passive Filters for High Power Three-level Rectifiers, Industrial Electronics, IECON, 34th Annual Conference of IEEE, Nov 10-13 2008, pp. 3207-3212. [3] Rachid, D. and Slimane, S., Power quality and cost improvement by passive power filters synthesis using ant colony algorithm, Journal of Theoretical and Applied Information Technology, published by JATIT & LLS 2005-2011, pp. 70-79. [4] Pottker, F. and Barbi, I., Power Factor Correction of Non-Linear Loads Employing a Single Phase Active Power Filter: Control Strategy, Design Methodology and Experimentation, PESC, (IEEE), Jun 22 27, 1997, pp. 412-417. [5] Imani, J. H. R., Mohamed, A., Shareef, H. and Subiyanto., A New Method for Calculating the Reference Current of Shunt Active Power Filters Based on Recursive Discrete Fourier Transform, International Review on Modelling and Simulations, Aug 2012, pp. 1439-1446. [6] Kirti, K., Anil, K. C. and Veeresh, C., Modeling of Frequency Domain Control of Shunt Active Power Filter Using MATLAB/Simulink and Power System Blockset, International Journal of Engineering Research and Applications, Vol. 3, Issue 4, Jul-Aug 2013, pp. 2109-2114. [7] Siyu, L., Wenxin, L. and David, C., Active power filter for three-phase current harmonic cancellation and reactive power compensation, American Control Conference, MO, USA, Jun 10-12, 2009, pp. 2140-2147. [8] Metin, K. and Ozdemir, E., Operation of shunt active power filter under unbalanced and distorted load conditions, Electrical and Electronics Engineering, ELECO, International Conference on. IEEE, 2009, pp. 1-92-1-96. [9] Moinuddin, K. S. and Sanker, B. R., Instantaneous Power theory based Active Power Filter: A Matlab/Simulink approach, Journal of Theoretical and Applied Information Technology, 2008, pp. 536-541. [10] Rathika, P. and Devaraj, D., Fuzzy Logic Based Approach for Adaptive Hysteresis Band and DC Voltage Control in Shunt Active Filter, International Journal of Computer and Electrical Engineering, Vol. 2, No. 3, Jun, 2010, pp. 1793-8163. [11] Emílio, F. C., Júlio, S. M. and João, L. A., Simulation Results of a Shunt Active Power Filter with Control Based on p-q Theory, International Conference on Renewable Energies and Power Quality Vigo, Espanha, Abril 9-12, 2003, pp. 1-6. [12] Charles, S. and Bhuvaneswari, G., Comparison of Three Phase Shunt Active Power Filter Algorithms, International Journal of Computer and Electrical Engineering, IEEE, Vol. 2, No. 1, February, 2010, pp. 175-180. [13] Murat, K. and Ozdemir, E., An adaptive hysteresis band current controller for shunt active power filter, Journal of Electric power systems research, elsevier, science direct, 2005, pp. 113 119. [14] SmitaSinghai., Bharti, D. and Dimat, R., Implementation of Active Harmonic Filter with MATLAB/Simulink to compensate Non-Linear Loads, International Journal of Digital Application and Contemporary research Vol. 1, Issue 9, April 2013. [15] Doğan, H. and Akkaya R., A Simple Control Scheme for Single-Phase Shunt Active Power Filter with Fuzzy Logic Based DC Bus Voltage Controller, Proceedings of the International Multi Conference of Engineers and Computer Scientists, Vol. II IMECS, Hong Kong, March 18-20, 2009. 9

[16] El-Kholy, E. E., El-Sabbe, A., El-Hefnawy, A. and Mharous, H. M., Three-phase active power filter based on current controlled voltage source inverter, International Journal of Electrical Power & Energy Systems, 2006, pp. 537-547. [17] Donghua, C. and Shaojun, X., Review of the control strategies applied to active power filters, IEEE International Conference on Electric Utility Deregulation Restructuring and Power Technologies, Hong Kong, April 2004, pp. 666-670. [18] Zainal, S., Tan, P. C. and Awang, J., Harmonics Mitigation Using Active Power Filter: A Technological Review, journal of Faculty of Electrical Engineering Universiti Teknologi Malaysia, Vol. 8, No. 2, 2006, pp.17 26. [19] Simulink Model-Based and System-Based Design, Modelling, Simulation, Implementation, version 6.5, The MathWorks. [20] IEEE 519-1992 Standard. Power System Harmonics. Bulletin No. 8803PD9402, Raleigh, NC, U.S.A, August 1994. 10