CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

Similar documents
UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

SECTION TRANSFORMERS

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

Distribution Transformers

Howard Smart Transformer Specification Guide

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

7. INSPECTION AND TEST PROCEDURES

Component Requirement Specification for SGI 500XT Isolation Transformer

Substation transformers

Distribution/Substation Transformer

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

SECTION 5 TRANSFORMERS

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

SECTION 16322B SUBSTATION TRANSFORMERS DRY-TYPE

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016)

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

CITY OF TACOMA Transmission & Distribution

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

Premium 30 Energy Efficient, Low Voltage Transformers General Purpose, Harmonic Mitigating, and K-Rated

Course 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC)

Particulate Control O&M Training. APC/PCUG Conference July 12-16, 2009 The Woodlands, TX

The Variable Threshold Neutral Isolator (VTNI)

MESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER

INTELLIMETER REGISTER

OIL-IMMERSED ARC-SUPPRESSION COILS

Liquid-Filled Transformers

PANELMDP Main Distribution Panel. Descriptions Energy Efficient Transformer

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

Transformer Testing & Maintenance Fundamentals. AVO Training Institute, Inc. 2018

SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK

Section 2 Outdoor Voltage Transformers

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3

Functional specification for 3-in-1 pad-mounted multi-phase 32-step voltage regulator with communication-ready controls

The relative simplicity of transformers belies their. Transformer Fundamentals

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V

Hands-On Transformer Testing and Maintenance

Transformer Factory Testing

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

SECTION PANELBOARDS

Page Electric Utility Service Specifications

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

DTS ISOLATION TRANSFORMER SPECIFICATIONS

Company Directive ENGINEERING SPECIFICATION EE SPEC: 5/5. Relating to 11kV Distribution Transformers

CSP PSYCHIATRIC SERVICES UNIT SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS

UFGS (August 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

SHARDA Make Harmonics Filter

SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS.

ECP COMPACT AND MICRO SUBSTATION COMMISSIONING PROCEDURE

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

POWER SERVICE DETAILS

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Customer Connection Guide Updates Effective May 2017

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

Specialty Switches. Inertia Engineering & Machine Works, Inc Hardaway Road, Stockton CA 95215

HPS Universal BUCK-BOOST TRANSFORMERS

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

B. Manufacturers: Square-D, G.E. or Westinghosue.

HOW TO SAFE GUARD THE TRANSFORMER..???

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

General Electricity Company of Libya

INTERNATIONAL STANDARD

75 kva Isolation Transformer V Delta Primary Voltage - 480Y/277 Secondary Voltage - NEMA 3R

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

Electrical Wiring: Commercial, Seventh Canadian Edition

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

TABLE OF CONTENT

Basic Principles and Operation of Transformer

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER

Customer Requirements RF Antenna Installations

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

SECTION DISTRIBUTION SWITCHBOARDS

S&C Series 2000 Circuit-Switchers Outdoor Transmission (69 kv through 230 kv)

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

EDS LV SUPPLIES TO MOBILE PHONE BASE STATIONS MOUNTED ON TRANSMISSION TOWERS

Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

Reference Number PPS 05 - (RIC Standard: EP SP)

Transcription:

GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers are of pad mounted construction. Special consideration can be made with approval from project manager for installation of dry type transformers. DESIGN GUIDELINES: Materials 1. General 1.1. General Specifications 1.1.1. The transformer shall be outdoor rated 1.1.2. Less-flammable liquid filled 1.1.3. Pad mounted 1.1.4. Live-front or Dead-front (as coordinated with system owner) 1.1.5. Switching options for radial or loop (as coordinated with system owner) 1.1.6. Standard sizes in table below 1.1.7. All exterior surfaces shall be designed to prevent holding or pooling of water or liquids. 1.2. Ratings 1.2.1. KVA Rating (as coordinated with system owner). 1.2.2. Nominal Primary voltage shall be 13,800 volts line-to-line, three-phase, delta connected. 1.2.3. Nominal secondary voltage 277/480Y Volts or 120/208Y Volts (4-wire wye secondary). 1.3. Impedance & Losses 1.3.1. Percent impedance and losses shall comply with values listed in Table below. Size (kva) Secondary Voltage Losses Not To Exceed (Watts) No Load Full Load Total Revised 9/23/2009 Page 1 of 7 337313 Impedance (in the range of) 75 120/208 225 400 625 2.5% to 4.0% 112.5 120/208 325 575 900 2.5% to 4.0% 150 120/208 450 750 1200 2.5% to 4.0% 225 120/208 550 1100 1650 2.5% to 4.0% 300 120/208 700 1650 2350 2.5% to 4.0% 500 120/208 1000 3000 4000 5% to 6% 750 120/208 1200 5000 6200 5% to 6% 1000 120/208 1700 6500 8200 5% to 6% 1500 120/208 2200 10000 12200 5% to 6% 2000 120/208 2800 13500 16300 5% to 6%

225 277/480 600 1200 1800 2.5% to 4.0% 300 277/480 750 1500 2250 2.5% to 4.0% 500 277/480 1000 2800 3800 5% to 6% 750 277/480 1200 4000 5200 5% to 6% 1000 277/480 1500 6500 8000 5% to 6% 1500 277/480 2200 9000 11200 5% to 6% 2000 277/480 2800 12000 14800 5% to 6% 1.4. Required Standards 1.4.1. All equipment shall conform to the latest revision of all applicable standards. A listing of these standards includes, but is not limited to: 1.4.1.1. NEMA 1.4.1.2. NESC 1.4.1.3. NEC 1.4.1.4. ANSI 1.4.1.5. IEEE 1.4.1.6. Federal Occupational Safety and Health Standards 1.5. Construction Features 1.5.1. Pad Mount (ANSI Standard C57.12, latest revision). 1.5.2. Compartment type 1.5.2.1. The transformer shall have high and low voltage compartments assembled side by side as an integral unit with no live parts accessible without opening the compartment doors. 1.5.2.2. The high voltage compartment shall be located on the left. 1.5.2.3. High voltage compartment shall be separated from the low voltage compartment by a metal barrier. 1.5.2.4. No bolts, screws or other fastening devices shall be externally removable. 1.5.2.5. There shall be no openings where sticks, rods or other devices could be inserted and contact live parts. 1.5.2.6. Compartments shall limit water entry. 1.5.2.7. A non-conductive, removable barrier shall be installed in the high voltage compartment in a manner which will restrict access to the live front area without lifting and removing the barrier. Barrier shall be clearly marked Danger High Voltage (Live Front Only). 1.5.2.8. Low voltage bushings shall be supported to the top of transformer to prevent oil leaking from the bushing due to the weight of the cables attached to them. 1.5.3. Liquid immersed 1.5.4. Self cooled 1.5.5. Bolt-on covers 1.5.6. Equipment must be new; re-manufactured equipment will not be accepted. 1.6. Noise level Requirement 1.6.1. IEEE/ANSI/NEMA standards 1.6.2. Not to exceed the levels given by NEMA TR1-1980 Revised 9/23/2009 Page 2 of 7 337313

1.7. Transformer enclosure 1.7.1. Supplied with jacking provisions and lugs for lifting. 1.7.2. Enclosure and base constructed for sliding and rolling. 1.7.3. Enclosure shall be tamper proof. 1.7.4. Have self-starting penta-head bolts 1.7.5. Shall prevent accumulation and pooling of water 1.8. Doors 1.8.1. The secondary door shall include provisions for a lock, which must be removed to remove the penta-head bolt. 1.8.2. The primary door shall be separate and interlock with the secondary door in a manner, which the secondary door must be opened first before the primary door can be opened. 1.8.3. The primary door shall also be secured by penta-head bolts other than the bolts securing the secondary door. 1.9. Paint 1.9.1. Munsell green #7.0GY3.29/1.5 1.9.2. Minimum Thickness of 2.5 MIL 1.9.3. A small container of touch up paint shall be supplied with the transformer and given to system owner. 1.10. Fault Indicator (Loop Feed Installations only) 1.10.1. Bottom sill of primary compartment shall have a hole capable of mounting a Fisher Pierce model 1515WB-12A3-10SL-B fault indicator. 1.10.2. The hole shall have a permanent cover installed prior to shipping which can be removed only from the inside of the compartment. 2. Electrical Specifications 2.1. 3 Phase 2.2. 60 Hertz 2.3. Primary Windings 2.3.1. Copper conductors. 2.3.2. Primary windings should be transposed for reduced losses at fundamental (60Hz) and harmonic frequencies, if advisable per manufacturer. 2.3.3. Primary windings shall be designed to withstand high 3rd, 9th, and 15th harmonic circulating currents. 2.4. Secondary Windings 2.4.1. Copper Conductors 2.4.2. Secondary Windings should be transposed for reduced losses, at fundamental (60Hz) and harmonic frequencies, if advisable per manufacturer. 2.4.3. Use smaller paralleled conductors instead of one larger cross-section single conductor or a single thin tape type of conductor. 2.4.4. Individual conductors shall be insulated. 2.5. Transformer Core Revised 9/23/2009 Page 3 of 7 337313

2.5.1. Steel core stock 2.5.2. Core shall be designed and constructed to reduce eddy current losses at fundamental and harmonic frequencies. 2.6. Neutral Conductor 2.6.1. Sized to handle up to 2 times the rated phase current continuously. 2.7. Wiring Connections 2.7.1. Suitable for Copper or Aluminum termination lugs. 2.7.2. High voltage terminals shall be a two-hole lug type connection with ½ holes on 1 ¾ centers capable of connection either copper or aluminum (Live Front Only). 2.7.3. Low voltage terminals shall be tinned spade having eight (8) 9/16 holes on 1 ¾ centers for conductor connections. 2.8. Arrestors 2.8.1. Three (3) 10kV rated, 8.4kV MCOV 2.8.2. Transformer must have mountings provided for lightning arrestors. 2.9. Primary Bushings 2.9.1. Shall have a 95kV BIL rating 2.9.2. Live Front 2.9.2.1. Three (3) 15kV Live Front porcelain primary bushings, for a delta connection of 13,800V. 2.9.3. Dead Front 2.9.3.1. Six (6) - 15kV, 200A primary bushing wells, in accordance with ANSI standard C119.2, for a delta connection of 13,800V. 2.9.3.2. Bushings for 200 Amp load break elbows shall be supplied for each well. 2.9.3.3. Use other 3 bushings for arrestors if not a loop fed unit. 2.9.3.4. Bushing wells shall have covers in place for shipping and storage 2.10. Secondary bushings 2.10.1. Four secondary bushings shall be supplied for wye connections 2.10.2. Shall have a 30kV BIL rating with a tinned spade having eight (8) - 9/16@ holes on 1 ¾ centers for conductor connections 2.10.3. Shall be supported to the top of transformer to prevent oil leaking from the bushing due to the weight of the cables attached to them. 2.11. Primary Voltage Taps shall be supplied to provide five (5) - 2.5% no load tap changes, two above and two below rated voltage. 2.12. Fusing 2.12.1. Oil immersed bayonet expulsion fuses and in-tank, current limiting fuses. 2.12.2. Bayonet fuses shall be removable with a hot stick. 2.12.3. Current limiting fuses shall have an interrupting capacity greater than 40,000A 2.12.4. Fusing combination shall provide full range protection for low and high current faults Revised 9/23/2009 Page 4 of 7 337313

2.12.5. Three spare bayonet fuses shall be supplied with the transformer. (This totals six bayonet fuses.) 2.12.6. The let-through current of the in-tank current limiting fuse cannot exceed the interrupting rating of the switch specified 3. Insulating Media and Ratings 3.1. Maximum average winding temperature rise of 65 degrees C 3.2. Winding insulation shall have a rating of 120 degrees C 3.3. Transformer shall have ambient temperature rating of 40 degrees C 3.4. Transformer shall be filled with a nonflammable fluid (mineral oil is not acceptable). 3.4.1. Liquid level indicator shall be supplied and located inside the low voltage compartment. 3.4.2. Drain valve and sampling device shall be installed in the primary compartment. 3.4.3. Pressure relief valve 3.4.3.1. A pressure relief valve shall be supplied. 3.4.3.2. Qualitrol series 201 pressure relief valve or approved equal for NEC code 450-23 application 3.4.3.3. Volume of valve must meet all applicable codes 3.4.4. Temperature indicator shall be supplied. 4. Switching 4.1. Switching needs for radial fed configuration 4.1.1. One 300A in-tank two position load break radial switch 4.1.2. One switch on primary to turn the transformer on/off 4.2. Switching needs for loop fed configuration (Dead Front Only) 4.2.1. Three 300A load break switches 4.2.2. This allows for transformer on/off and two line terminals each with on/off 4.3. Switch must be rated to interrupt the current for the transformer 4.4. Switch must be capable of being operated with a hot stick 5. Grounding 5.1. Three grounding connections, each with two (2) 1/2@-13 UNC tapped holes 5.1.1. Primary compartment 5.1.2. Secondary compartment 5.1.3. Outside of the tank 5.2. A copper connection strap from the neutral to ground shall be supplied. 6. Nameplate 6.1. The nameplate shall be engraved. Revised 9/23/2009 Page 5 of 7 337313

6.2. An addition to normal information, the following items shall be included on the nameplate of each unit: 6.2.1. kva ratings 6.2.2. Primary voltage 6.2.3. Secondary voltage 6.2.4. BIL ratings 6.2.5. Temperature ratings 6.2.6. Primary and Secondary voltages for each tap setting 6.2.7. Date of Manufacture. 6.2.8. Name of Manufacturer. 6.2.9. Transformer K factor (if rated) 6.2.10. Type of conductor in windings. 6.2.11. Impedance expressed in percentage. 6.2.12. Detail circuit diagrams of primary switch configuration and switch ratings. 6.2.13. Delta - wye or delta -delta diagram detailing the relationship of primary to secondary bushings. 6.2.14. Statement Transformer filled with less-flammable fluid. 6.2.15. Statement Transformer filled with fluid containing no detectable PCB s at time of manufacture. 6.2.16. Total weight of unit expressed in pounds. 6.2.17. Weight of unit without oil. 7. Labeling 7.1. Standard labeling for pad-mounted equipment 7.2. Transformer shall have a blue CONTAINS NO PCBs label placed inside of the secondary compartment door and another same label placed on the outside of the tank 7.3. Transformer shall have a Danger-High Voltage label on the outside of the primary compartment door meeting all applicable standards 8. Submittials 8.1. MU Only: Campus Facilities - Energy Management Electric Distribution must approve the construction drawings prior to construction of each type of transformer supplied. 8.2. A completed Transformer Losses in Watts data sheet (see attached) must be completed and included in submittal for each type of transformer 8.2.1. Losses cannot exceed the values listed in the table above 8.2.2. A duly authorized officer of the transformer supplier company must sign the data sheet Installation 1. Refer to Transformer Pad Detail.dwg for foundation and mounting requirements 1.1. Care shall be taken during lifting/moving not to damage or bump the transformer. 1.2. Must have 8 clear area in front of doors and 3 clear area on the sides 1.3. Locate unit in accessible location for maintenance, operation, and replacement Revised 9/23/2009 Page 6 of 7 337313

1.4. Bollards may be needed 1.5. Number and location of transformers coordinated with Energy Management Electric Distribution 2. Grounding 2.1. Must have one ground rod in opening Testing 1. Tested impedance of the supplied transformer shall be in the range as specified in the table above prior to delivery 2. System owner unit will perform TTR, Megger, and Ground testing prior energizing the transformer Commissioning 1. MU Only: System owner will set the proper tap on the transformer, energize the transformer and check for proper voltage. REFERENCES Revised 9/23/2009 Page 7 of 7 337313