UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

Similar documents
CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

SECTION TRANSFORMERS

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

Distribution Transformers

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

Howard Smart Transformer Specification Guide

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

SECTION 5 TRANSFORMERS

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

7. INSPECTION AND TEST PROCEDURES

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Distribution/Substation Transformer

Substation transformers

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

Component Requirement Specification for SGI 500XT Isolation Transformer

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

SECTION 16322B SUBSTATION TRANSFORMERS DRY-TYPE

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

Functional specification for 3-in-1 pad-mounted multi-phase 32-step voltage regulator with communication-ready controls

Section 2 Outdoor Voltage Transformers

OIL-IMMERSED ARC-SUPPRESSION COILS

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

SECTION PANELBOARDS

CITY OF TACOMA Transmission & Distribution

Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016)

Course 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC)

The Variable Threshold Neutral Isolator (VTNI)

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

SHARDA Make Harmonics Filter

INTELLIMETER REGISTER

Transformer Testing & Maintenance Fundamentals. AVO Training Institute, Inc. 2018

UFGS (August 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

The relative simplicity of transformers belies their. Transformer Fundamentals

PANELMDP Main Distribution Panel. Descriptions Energy Efficient Transformer

Transformer Factory Testing

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

Particulate Control O&M Training. APC/PCUG Conference July 12-16, 2009 The Woodlands, TX

75 kva Isolation Transformer V Delta Primary Voltage - 480Y/277 Secondary Voltage - NEMA 3R

SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK

INTERNATIONAL STANDARD

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Electrical Wiring: Commercial, Seventh Canadian Edition

Wisconsin Contractors Institute Continuing Education

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

MESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER

ULTRA-K Series 600K - he

Premium 30 Energy Efficient, Low Voltage Transformers General Purpose, Harmonic Mitigating, and K-Rated

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

SECTION DISTRIBUTION SWITCHBOARDS

Company Directive ENGINEERING SPECIFICATION EE SPEC: 5/5. Relating to 11kV Distribution Transformers

Specialty Switches. Inertia Engineering & Machine Works, Inc Hardaway Road, Stockton CA 95215

Liquid-Filled Transformers

First Draft Language

Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

S&C Series 2000 Circuit-Switchers Outdoor Transmission (69 kv through 230 kv)

35 kv Class M.O.V.E. DirectConnect elbow arrester

CSP PSYCHIATRIC SERVICES UNIT SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

K Factor Power Transformers

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

Page Electric Utility Service Specifications

ECP COMPACT AND MICRO SUBSTATION COMMISSIONING PROCEDURE

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

500 kva Isolation Transformer - 480V Delta Primary - 400Y/231 Wye Secondary - NEMA 3R

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

Basic Principles and Operation of Transformer

DTS ISOLATION TRANSFORMER SPECIFICATIONS

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

500 kva Dry-type Isolation Transformer V-Delta to 208Y/120V 3PH - NEMA 1/Indoor

CONTINUING EDUC ATION

Hands-On Transformer Testing and Maintenance

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3

HOW TO SAFE GUARD THE TRANSFORMER..???

Type DMX-N Surge Arresters Maximum System Voltage 2 to 36 kv

TIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M

ADVANTAGE OIL-COOLED LINE

Warehouse Stock Transformers

American Electrical Institute

POWER SERVICE DETAILS

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

75 kva Isolation Transformer - 480V Delta Primary - 208V Delta Secondary - NEMA 3R

Transcription:

GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers are of pad mounted construction. Special consideration can be made with approval from Owner for installation of indoor type transformers. DESIGN GUIDELINES: A. Materials 1. General 1.1. General Specifications 1.1.1. The transformer shall be outdoor rated 1.1.2. Less-flammable liquid filled 1.1.3. Pad mounted 1.1.4. Dead-front 1.1.5. Switching options for radial or loop (as coordinated with system owner) 1.1.6. Standard sizes in table below: Voltage Size kva 120/208V 75 112.5 150 225 300 500 750 1000 1500 277/480V 225 300 500 750 1000 1500 2000 1.1.7. All exterior surfaces shall be designed to prevent holding or pooling of water or liquids. 1.2. Ratings 1.2.1. kva Rating (as coordinated with system owner). 1.2.2. Nominal Primary voltage shall be 13,800 volts line-to-line, three-phase, delta connected. 1.2.3. Nominal secondary voltage 277/480Y Volts or 120/208Y Volts (4-wire wye secondary). 1.2.4. Standard kva ratings only. 1.2.5. Maximum kva for 120/208Y Volts shall be 1500kVA 1.2.6. Maximum kva for 277/408Y Volts shall be 2000kVA 1.3. Efficiency, Impedance, and Losses 1.3.1. Transformer efficiency shall meet all DOE 2010, 10 CFR Part 431 requirements. 1.3.2. Percent impedance shall meet all applicable standards. Page 1 of 7 337313

1.4. Required Standards 1.4.1. All equipment shall conform to the latest revision of all applicable standards. A listing of these standards includes, but is not limited to: 1.4.1.1. NEMA 1.4.1.2. NESC 1.4.1.3. NEC 1.4.1.4. ANSI 1.4.1.5. IEEE 1.4.1.6. Federal Occupational Safety and Health Standards 2. Construction Features 2.1. Pad Mount (ANSI Standard C57.12, latest revision). 2.2. Compartment type 2.2.1. The transformer shall have high and low voltage compartments assembled side by side as an integral unit with no live parts accessible without opening the compartment doors. 2.2.2. Depth of compartment shall be 24 inches minimum. 2.2.3. The high voltage compartment shall be located on the left. 2.2.4. High voltage compartment shall be separated from the low voltage compartment by a metal barrier. 2.2.5. No bolts, screws or other fastening devices shall be externally removable. 2.2.6. There shall be no openings where sticks, rods or other devices could be inserted and contact live parts. 2.2.7. Compartments shall limit water entry. 2.2.8. A clear, non-conductive, hinged barrier with latching mechanism shall be installed in the low voltage compartment in a manner which will completely restrict access to the low voltage compartment with barrier in closed position. Barrier shall be clearly marked Danger Arc Flash Hazard. 2.2.9. Low voltage bushings shall be supported to the top of transformer to prevent oil leaking from the bushing due to the weight of the cables attached to them. 2.3 Liquid immersed 2.4 Self cooled 2.5 Bolt-on covers 2.6 Equipment must be new; re-manufactured equipment will not be accepted. 2.7 Noise level Requirement 2.7.1 IEEE/ANSI/NEMA standards 2.7.2 Not to exceed the levels given by NEMA TR1-1980 2.8 Transformer enclosure 2.8.1 Supplied with jacking provisions and lugs for lifting. 2.8.2 Enclosure and base constructed for sliding and rolling. 2.8.3 Enclosure shall be tamper proof. 2.8.4 Have self-starting penta-head bolts 2.8.5 Shall prevent accumulation and pooling of water. Page 2 of 7 337313

2.9 Doors 2.9.1 The secondary door shall include provisions for a lock, which must be removed to remove the penta-head bolt. 2.9.2 The primary door shall be separate and interlock with the secondary door in a manner, which the secondary door must be opened first before the primary door can be opened. 2.9.3 The primary door shall also be secured by penta-head bolts other than the bolts securing the secondary door. 2.10 Paint 2.10.1 Munsell green #7.0GY3.29/1.5 2.10.2 Minimum Thickness of 2.5 MIL 2.10.3 A small container of touch up paint shall be supplied with the transformer and given to system owner. 2.11 Fault Indicator (Loop Feed Installations only) 2.11.1 Bottom sill of primary compartment shall have a hole capable of mounting a Fisher Pierce model 1515WB-12A3-10SL-B fault indicator. 2.11.2 The hole shall have a permanent cover installed prior to shipping which can be removed only from the inside of the compartment. 3. Electrical Specifications 3.1. 3 Phase 3.2. 60 Hertz 3.3. Primary Windings 3.3.1. Copper conductors. 3.3.2. Primary windings should be transposed for reduced losses at fundamental (60Hz) and harmonic frequencies, if advisable per manufacturer. 3.3.3. Primary windings shall be designed to withstand high 3rd, 9th, and 15th harmonic circulating currents. 3.4. Secondary Windings 3.4.1. Copper Conductors 3.4.2. Secondary Windings should be transposed for reduced losses, at fundamental (60Hz) and harmonic frequencies, if advisable per manufacturer. 3.4.3. Use smaller paralleled conductors instead of one larger cross-section single conductor or a single thin tape type of conductor. 3.4.4. Individual conductors shall be insulated. Page 3 of 7 337313

3.5. Transformer Core 3.5.1. Steel core stock 3.5.2. Core shall be designed and constructed to reduce eddy current losses at fundamental and harmonic frequencies. 3.6. Neutral Conductor 3.6.1. Sized to handle up to 2 times the rated phase current continuously. 3.7. Wiring Connections 3.7.1. Suitable for Copper or Aluminum termination lugs. 3.7.2. Low voltage terminals shall be tinned spade having eight (8) 9/16 holes on 1 ¾ centers for conductor connections. 3.8. Arrestors 3.8.1. Three (3) 10kV rated, 8.4kV MCOV, elbow type. 3.8.2. Transformer must have mountings provided for lightning arrestors. 3.9. Primary Bushings 3.9.1. Shall have a 95kV BIL rating 3.9.2. Shall have 15kVA, 600A bushings for no-load break, bolted elbow connection 3.9.3. Shall conform to ANSI/IEEE Standard 386 (ANSI Standard C119.2) 3.9.4. Shall include a semi-conductive coating. 3.9.5. Shall be mounted in such a way that the semiconductive coating is solidly grounded to the tank. 3.9.6. Shall have covers in place for shipping and storage. 3.9.7. Dead Front 3.9.7.1. Radial Feed 3.9.7.1.1. (1) Three (3) - 600A primary bushing, suitable for delta connection of 13,800V dead break elbow connectors. 3.9.7.2 Loop Feed 3.9.7.2.1 (1) Six (6) - 600A primary bushing, suitable for delta connection of 13,800V dead break elbow connectors 3.10. Secondary bushings 3.10.1. Four secondary bushings shall be supplied for wye connections 3.10.2. Shall have a 30kV BIL rating with a tinned spade having eight (8) - 9/16 holes on 1 ¾ centers for conductor connections 3.10.3. Shall be supported to the top of transformer to prevent oil leaking from the bushing due to the weight of the cables attached to them. 3.11. Primary Voltage Taps shall be supplied to provide five (5) - 2.5% no load tap changes, two above and two below rated voltage. 3.12. Fusing 3.12.1. Oil immersed bayonet expulsion fuses and in-tank, current limiting fuses. 3.12.2. Bayonet fuses shall be removable with a hot stick. Page 4 of 7 337313

3.12.3. Current limiting fuses shall have an interrupting capacity greater than 40,000A 3.12.4. Fusing combination shall provide full range protection for low and high current faults 3.12.5. Three spare bayonet fuses shall be supplied with the transformer. (This totals six bayonet fuses.) 3.12.6. The let-through current of the in-tank current limiting fuse cannot exceed the interrupting rating of the switch specified 4. Insulating Media and Ratings 4.1. Maximum average winding temperature rise of 65 degrees C 4.2. Winding insulation shall have a rating of 120 degrees C 4.3. Transformer shall have ambient temperature rating of 40 degrees C 4.4. Transformer shall be filled with a nonflammable fluid (mineral oil is not acceptable). 4.4.1. Liquid level indicator shall be supplied and located inside the low voltage compartment. 4.4.2. Drain valve and sampling device shall be installed in the primary compartment. 4.4.3. Pressure relief valve 4.4.3.1. A pressure relief valve shall be supplied. 4.4.3.2. Qualitrol series 201 pressure relief valve or approved equal for NEC code 450-23 application 4.4.3.3. Volume of valve must meet all applicable codes 4.4.4. Temperature indicator shall be supplied. 5. Switching 5.1. Switching needs for radial fed configuration 5.1.1. One 300A in-tank two position load break radial switch to turn the transformer on/off. 5.2. Switching needs for loop fed configuration 5.2.1. Three 300A load break switches 5.2.2. This allows for transformer on/off and two line terminals each with on/off 5.3. Switch must be rated to interrupt the current for the transformer 5.4. Switch must be capable of being operated with a hot stick 6. Grounding 6.1. Three grounding connections, each with two (2) ½ -13 UNC tapped holes 6.1.1. Primary compartment 6.1.2. Secondary compartment 6.1.3. Outside of the tank Page 5 of 7 337313

6.2. A copper connection strap from the neutral to ground shall be supplied. 7. Nameplate 7.1. The nameplate shall be engraved. 7.2. In addition to normal information, the following items shall be included on the nameplate of each unit: 7.2.1. kva ratings 7.2.2. Primary voltage 7.2.3. Secondary voltage 7.2.4. BIL ratings 7.2.5. Temperature ratings 7.2.6. Primary and Secondary voltages for each tap setting 7.2.7. Date of Manufacture. 7.2.8. Name of Manufacturer. 7.2.9. Transformer K factor (if rated) 7.2.10. Type of conductor in windings. 7.2.11. Impedance expressed in percentage. 7.2.12. Detail circuit diagrams of primary switch configuration and switch ratings. 7.2.13. Delta - wye or delta -delta diagram detailing the relationship of primary to secondary bushings. 7.2.14. Statement Transformer filled with less-flammable fluid. 7.2.15. Statement Transformer filled with fluid containing no detectable PCB s at time of manufacture. 7.2.16. Total weight of unit expressed in pounds. 7.2.17. Weight of unit without oil. 8. Labeling 8.1. Standard labeling for pad-mounted equipment 8.2. Transformer shall have a blue CONTAINS NO PCB s label placed inside of the secondary compartment door and another same label placed on the outside of the tank 8.3. Transformer shall have a Danger-High Voltage label on the outside of the primary compartment door meeting all applicable standards 8.4. Transformer shall have Secondary Barrier Installed label installed on the outside of the secondary compartment door. 9. Submittials 9.1. MU Only: Campus Facilities - Energy Management Electric Distribution must approve the construction drawings prior to construction of each type of transformer supplied. Page 6 of 7 337313

B. Installation 1. Refer to Transformer Pad Detail drawing for foundation and mounting requirements. 1.1. Care shall be taken during lifting/moving not to damage or bump the transformer. 1.2. Must have 8 clear area in front of doors and 3 clear area on the sides. 1.3. Locate unit in accessible location for maintenance, operation, and replacement. 1.4. Bollards may be needed. 1.5. Number and location of transformers coordinated with Owner s Representative. 2. Grounding 2.1. Must have one ground rod in opening C. Testing 1. Tested impedance of the supplied transformer shall be in the range as specified. 2. MU Only: System owner unit perform TTR, Megger, and Ground testing prior energizing the transformer D. Commissioning 1. MU Only: System owner will set the proper tap on the transformer, energize the transformer and check for proper voltage. REFERENCES Page 7 of 7 337313