Installation and start up instructions. Paralleling relay type HAS-111DG uni-line G (UK) Synchronisation of generator to busbar

Similar documents
Installation and start up instructions. Synchroniser type FAS-115DG uni-line H (UK) Synchronisation of generator to busbar

Installation and start up instructions. Synchroniser type FAS-113DG uni-line F (UK) Synchronisation of generator to busbar

DATA SHEET. Paralleling relays, HAS-111DG ANSI code 25

Installation and start up instructions. Detection of vector shift. Detection of over- and underfrequency. Generator disconnection on mains failure

DEIF A/S. TAS-311DG Selectable AC transducer J (UK) Installation and start up instructions

Automatic synchronising relay

DATA SHEET AC current single function transducer TAC-311DG/TAC-321DG

DEIF A/S. Application note. Generators parallel with mains Multi-line 2 version 2. Application description. Power import control. Power export control

DEIF A/S. User s manual. Read synchroscope type RSQ-3. Precision LED synchronoscope. High immunity to harmonic distortion F (UK)

DATA SHEET Selectable AC transducer TAS-311DG

DATA SHEET Reverse power relays, RMP-121D ANSI code 32

Installation/operation instructions. Insulation monitor type SIM-Q/SIM-Q LF D (UK) Measuring range 1...0Mohm or 10...

RMV-122D, RMV-132D ANSI

DATA SHEET. Voltmeters and Ammeters,

Protection relays and controllers. Types TRANSAL DC-2TF, ACV-3TF, ACI-3TF, PFC-2TF TRANSAL DC-2TB, AVC- 3TB, ACI-3TB, PFC-2TB

DEIF A/S. Insulation monitor. Type SIM-Q

DEIF A/S. Insulation monitor. Type SIM-Q/SIM-Q LF

DATA SHEET. CIO multi-inputs. CAN bus-based I/O module

Function. Adjustment. Extra functions included. Modes. Housing

DEIF A/S. Description of options. Option H3 Serial communication Profibus DP Multi-line 2 version 2. Description of option. Functional description

DATA SHEET Differential current relays, RMC-131D ANSI code 87

TCM-2 Thyristor Control Module DATA SHEET

Transducers for AC measurement. Types TAP, TAQ, TMF, TAA, TAV, TAC. Measurement of: watt, var, frequency, phase angle, voltage, current

DEIF A/S. Application Notes. Basic Gen-set Controller. Single generator set. Automatic mains failure. Parallel with mains (grid)

DEIF A/S. Description of options. Option H1, CAN open communication Basic Gen-set Controller. Description of option. Functional description

DEIF A/S. Description of options. Option H1 Serial communication CAN open. Description of options. Functional description. Tables.

Summation current transformers, type KSU/SUSK

DATA SHEET. Switchboard instruments,

V AC Meas. current (In): A. Frequency range: Hz. Measuring system:

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New)

Synchronisation meters for manual or semiautomatic synchronisation Synchronization Meters SQ0114/SQ0104 Synchronization Meters SQ0214/SQ0204

SELCO T-Line Generator Control, Protection and Monitoring

Primary winding current transformer, type WSK

DEIF A/S. Application Notes. MDR-2 test procedures. Test of current measurement. Test of differential current measurement.

XUA1 - AC Voltage and phase balance relay

Phase and neutral overcurrent protection

Electronic Thermostat TE-1 Version according to EN

Angle position transmitter Type RT-2 Marine bridge instrumentation C (UK) Measuring output: DC current signal 0..20mA or 4..

Electronic potentiometer EPQ96-2

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

XU2-AC AC voltage relay. (Februar 1997) Manual XU2-AC (Revision New)

XF2 Frequency Relay. Manual XF2 (Revision A)

Electronic timer CT-AWS Impulse-OFF with 1 c/o contact Data sheet

XP2-R Power and reverse power relay. (January 2006) Manual XP2-R (Revision New)

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)

QUINT-PS-24DC/24DC/10

XP2-R Power and Reverse Power Relay

Remote Maintenance Box, RMB

Harmonic restraint earth fault or single-phase overcurrent protection

Functional Range. Synchronising Relay : UN1, FN2, SY1, SY/SP. C&S Protection & Control Ltd.

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300

for variable pitch thrusters

DESIGNER S REFERENCE HANDBOOK

PRetrans Table of contents

XI1-I Time overcurrent relay. (Januar 2007) Manual XI1-I (Revision New)

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

HEP300 ELECTRONIC POTENTIOMETER USER MANUAL

SYNCHRONISM RELAY SYNCRO-96. (Code ) INSTRUCTION MANUAL ( M / 99A ) (c) CIRCUTOR S.A.

XN2 - Mains decoupling relay. Manual XN2 (Revision C)

EMD-FL-3V-400. Electronic monitoring relay for voltage monitoring in three-phase networks. INTERFACE Data sheet _en_03. 1 Description.

XN2 - Mains decoupling relay

Instruction Manual TABLE OF CONTENTS 1 PRINCIPLE OF OPERATION Limitations INSTALLATION Mains connection...

Electronic Amplifier Model VT 3017 and VT 3018 (Series 3X) for the control of proportional directional valves, without positional feedback

Assembly. Front view. DIP switch. LED yellow: Relay output I. LED yellow: Relay output II. Potentiometer Hysteresis relay I Power Rail

HAWK5000 Operators Manual

MINI-PS AC/24DC/1.3

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

Electronic timer CT-ERS ON-delayed with 2 c/o contacts Data sheet


Current and voltage measuring relays RXIK 1, RXEEB 1 and RXIB 24

Feed back element in high performance gradient amplifiers Feed back element in precision current regulated power supplies

KSR-Level sensor KSR-Schwimmer-Magnetschalter KSR Contact Protection Relays

05/09/2012

Coupling Relays and Converters

PARAMETER LIST PARAMETER LIST

3 PHASE ENERGY ELECTRONIC METERS MKT & MKT2. (Code to ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A.

MODEL: M2MNV MODEL: M2MNV-[1][2]-[3][4]

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

Moeller Electric Corporation

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents

Electronic amplifier for the control of proportional valves without position control Model VT 3006, Series 3X H/A 4240/94 VT X

Capacitor Switching Contactors

SIGMA S6100 S/LS Module

QUINT-PS AC/24DC/40

Electronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet

Pulse Scaler for DIN Rail Attachment

GTT 25A - 40A - 60A - 90A - 120A POWER SOLID STATE RELAYS WITH ANALOG CONTROL

Option D1 Voltage/var/cos phi control Description of option Functional description

Measuring and monitoring relays CM-SRS.1 Current monitoring relays, single-phase AC/DC

Switching power supplies CP range, Linear power supplies CP-L range. Content

Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

Generator Digital CONTROLLER Automatic synchronizer ASY-96/ ASY-96-A

High-Voltage Isolation Amplifiers / Shunt Isolators. VariTrans P TRMS

Electronic amplifier for the control of proportional valves without position control Model VT 3024, Series 3X H/A 4149/94 VT X

Technical Description. DCF77 Receiver-Module 4460

CM-IWM.11 Insulation monitoring relay

Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages

MODEL: M2MNV MODEL: M2MNV-[1][2]-[3][4]

Transcription:

Installation and start up instructions Paralleling relay type HAS-111DG uni-line 4189340146G (UK) Synchronisation of generator to busbar Setting of phase angle difference Setting of frequency and voltage difference LED indication of status DEIF A/S LED indication for synchronising signal 35 mm DIN rail or base mounting DEIF A/S Tel.: (+45) 9614 9614 Frisenborgvej 33, DK-7800 Skive Fax: (+45) 9614 9615 Denmark E-mail: deif@deif.com

1. Description This paralleling relay type HAS-111DG forms part of a complete DEIF series (the uniline) of relays for protection and control of generators. HAS-111DG paralleling relay is applied to check the synchronisation conditions or to synchronise a generator to the mains. The paralleling relay transmits a synchronisation pulse when the phase angle, frequency and voltage deviations are within the limits set. 2. Label The parallelling relay is provided with a label with the following data: Measuring voltage Type designation DEIF s order ack. no. To be stated when contacting DEIF Mounted voltage module Supply voltage (E.g. special circuit breaker time, etc.) Distributor s ID no. Filled in by distributor when customizing the unit Highest voltage in relation to earth Installation category 3. Mounting instructions HAS-111DG is designed for panel mounting, and is to be mounted on a 35 mm DIN rail, or by means of two 4-mm screws. Weight: approx. 0.75 kg The design of the paralleling relay makes it possible to mount it close to other uni-line units. However make sure there are min. 50 mm between the top and the bottom of this relay and other relays/units. The DIN rail must always be placed horizontally when several relays are mounted on the same rail. Page 2 of 6 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com

Installation and start up instructions HAS-111DG 4. Connection diagram A 2A fuse may protect all voltage inputs. The paralleling relay is protected against ESD (electrostatic electricity), and further special protection against this during the mounting of the unit is not necessary. HAS-111DG may be connected between 2 phases or between 1 phase and neutral. The paralleling relay is to be configured so that the input of HAS-111DG corresponds to the connected voltages. The generator circuit breaker is connected to the synchronising relay to terminals Nos. 8, 9 and 10 (mrk. SYNC ). During start up it is recommended to leave these terminals open. When HAS-111DG is applied for simultaneous synchronisation of all generators of a plant to the busbar, the FS line of the load sharing units types LSU-112/113/114 DG is connected to terminals Nos. 36 and 35. A contact is connected to the digital input terminals Nos. 34 and 35. On activation of this input, HAS-111DG will control the generator frequency to a value lower than the busbar frequency. On deactivation of the input, it will control the frequency to a value higher than the busbar frequency. The unit is equipped with a self-monitoring function. The self-monitoring function supervises the microprocessor and hereby verifies if the programme is running correctly. Supply voltage not connected or not acceptable. Supply voltage is accepted and the unit is working correctly. Supply voltage is accepted but the unit is working wrongly. Power LED OFF Constant green light Flashing green light 2-3Hz Status output OFF ON OFF GL applications only: For applications approved by Germanischer Lloyd the status output must be connected to an alarm system. For applications with more than one uni-line product the status outputs of the units can be connected in series to the same alarm input. When the units are connected in series the flashing green power LED will indicate the unit which is defective. 4189340146G (UK)

5. Start up instructions 5.1 Setting and indication Setting of Range Acceptable phase angle difference Negative: -25-5 el. Positive: 5...25 el. Acceptable frequency difference Negative: -1 0Hz Positive: 0 1Hz Acceptable voltage difference ±2 ±12% of U n LEDs U G Generator voltage* U BB Busbar voltage* Δf Frequency difference* ΔU Voltage difference* SYNC Synchronising Light Green, when value is within the acceptable range. Switched off, if outside this range. Yellow, when relay is activated. *) When all 4 LEDs are lit, the conditions for transmission of the synchronisation pulse are fulfilled. FREQUENCY The FREQUENCY potentiometers determine the maximum frequency difference at the time of synchronisation. If the potentiometers are set symmetrically, synchronisation pulse will be emitted both at supersynchronous and undersynchronous slip frequency. If supersynchronous synchronisation is wanted, the potentiometer for Hz is set to 0 and the potentiometer for +Hz (positive slip frequency) to the selected value. Information about the closing time of the applied circuit breaker is applied as starting point for the setting of the maximum slip frequency. If the circuit breaker has a closing time of 200msec, a maximum slip frequency of 0.2Hz is recommended as starting point. If the circuit breaker has a closing time of 50msec, a slip frequency of 0.8Hz can be applied as starting point. If the above settings lead to a hard synchronisation, the suggested settings are reduced. Note, the lower value selected for these potentiometers, the longer synchronisation time. If both are set to 0Hz, the generator will never be synchronized to the mains. PHASE Page 4 of 6 If both undersynchronous and supersynchronous synchronisation is selected, both PHASE potentiometers are typically set to the same value. The setting depends on the stability of the system and the size of the generator. It is recommended to start with a setting of ±10. If supersynchronous synchronisation is selected, the negative PHASE potentiometer is set to 15 as starting point and the positive to 5. If undersynchronous synchronisation is selected, the two PHASE potentiometers are set vice versa. If the synchronisation time is too long with the above settings, the PHASE potentiometers are set to a larger acceptance area. Vice versa, if the settings lead to a hard synchronisation, the acceptance area is reduced, or the Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com

Installation and start up instructions HAS-111DG FREQUENCY potentiometers are set to a lower slip frequency. Note, the relay pulse to the circuit breaker is only emitted, if there is room for a 100msec relay pulse as a minimum in the selected PHASE window. To make room for the relay pulse the slip frequency is reduced, alternatively the PHASE window is increased. For supersynchronous connection only, the following settings are typical: PHASE Negative: -15 Positive: 5 FREQUENCY Negative: 0Hz Positive: 0.5Hz VOLTAGE Determines the acceptable difference between busbar and generator voltages. Set to: ±2% when synchronising a powerful generator to a stable network. ±12% when synchronising a generator to unstable busbars. ±5% typical starting point. 4189340146G (UK)

6. Technical specifications Measuring voltage: 57.7-63.5-100-110-127-200-220-230-240-380-400- 415-440-450-660-690V AC ±20% Load: 2kΩ/V Frequency range: Digital input: 40 45 65 70Hz Potential-free contact. Open: 5V. Closed: 5mA Synchronisation pulse output: 1 changeover switch Frequency difference output: Contact ratings: Contact voltage: Galvanic separation: Consumption: Status output: 1 analog output, -10 0 10V DC corr. to -5 0 5Hz 250V-8A-2000A (AC), 24V-8A-200W (DC) Max. 250V (AC). Max. 150V (DC) Between inputs and outputs: 3250V-50Hz-1 min. (Aux. supply) 3.5VA/2W Open: 10 30V DC Closed: Max. 5mA Page 6 of 6 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com