No. SSIEC-PRC SHINSUNG. Polymer Recloser SIREC SERIES 15kV, 27kV, 38kV 400A, 630A, 800A

Similar documents
No. SSIEC-SEW SHINSUNG. Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

OUTDOOR VOLTAGE TRANSFORMERS (Indoor units available) Description:

Notes 1: Introduction to Distribution Systems

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström

Distribution/Substation Transformer

EE Lecture 14 Wed Feb 8, 2017

NOVA-TS Triple-Single Recloser and Form 5/TS Control Frequently Asked Questions

Protective Relaying for DER

Distribution Feeder Principles

Single Line Diagram of Substations

LV/MV/HV CIRCUIT BREAKERS (SWITCH GEAR) DESIGN, INSPECTION, MAINTENANCE, REPAIR & TROUBLESHOOTING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS

Smart Grid Smarter Protection: Lessons Learned

Automatic reclosing function for high voltage networks

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

Medium voltage circuit breaker technical guide

Unit 2. Single Line Diagram of Substations

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

System Protection and Control Seminar

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

IMPLEMENTATION OF ADVANCED DISTRIBUTION AUTOMATION IN U.S.A. UTILITIES

ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES

Power Quality Basics. Presented by. Scott Peele PE

Distance Protection for Distribution Feeders. Presented By: Yordan Kyosev, P.Eng. & Curtis Ruff, P.Eng.

SUBJECT HEADING: Switching Programmes ISSUE: 18

How to maximize reliability using an alternative distribution system for critical loads

Time over/underfrequency relay with protection assemblies

A New Use for Fault Indicators SEL Revolutionizes Distribution System Protection. Steve T. Watt, Shankar V. Achanta, and Peter Selejan

Module 9. Fault Type Form 4.X RELIABILITY ACCOUNTABILITY

EE030: Circuit Breaker & Switchgears Inspection, Maintenance, Design, Repair & Troubleshooting

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES

StarSine Power Quality Products

Solutions to Common Distribution Protection Challenges

Transmission Protection Overview

TS RES - OUTSTANDING ISSUES

Protection of Electrical Networks. Christophe Prévé

Detecting and Managing Geomagnetically Induced Currents With Relays

Solutions to Common Distribution Protection Challenges

Transmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes

ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring

Table of Contents. Introduction... 1

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

E N G I N E E R I N G M A N U A L

MAINTENANCE MANUAL 1B170K17 FOUR SHOT AUTO RECLOSE RELAY

Generation Interconnection Requirements at Voltages 34.5 kv and Below

ON LOAD TAP CHANGERS RSV 5.3 TECHNICAL DATA

The Use of Vacuum Interruption at Transmission Voltages

CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS

PLAN... RESPOND... RESTORE! Utility Automation & Information Technology... Automation Rising

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

On-Load Tap Changer Type M

ENOSERV 2014 Relay & Protection Training Conference Course Descriptions

INTERNATIONAL DRIVE DISTRIBUTION AUTOMATION AND PROTECTION

High voltage engineering

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

Arizona Public Service Company and the Transmission Partnership for National Electric Power Company of Jordan

Lightning test in lab. Symmetrical fault and protection. Olof Samuelsson

SEATTLE CITY LIGHT DISTRIBUTION AUTOMATION

BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY

Technical features table for miniature circuit-breakers SH 200 Series

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment

PD300. Transformer, generator and motor protection Data sheet

S&C Series 2000 Circuit-Switchers Outdoor Transmission (69 kv through 230 kv)

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Advanced Test Equipment Rentals ATEC (2832)

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing

EE Lecture 15 (recorded Feb 9, 2011) Fri Feb 15, 2013

Comparison of recloser and breaker standards

Fixed Series Compensation

Alberta Interconnected Electric System Protection Standard

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

Earthing of Electrical Devices and Safety

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

VI 3 - i TABLE OF CONTENTS

Towards a transient earth fault clearing scheme for medium voltage networks

ekor.rpg.ci & ekor.rpt.ci

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Replacement solution

ON LOAD TAP CHANGERS RS 6.3 / RS 6 TECHNICAL DATA

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

Hamdy Faramawy Senior Application Specialist ABB Sweden

ODEN AT Primary Current Injection Test System

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated

In order to minimise distribution (11 and 22 kv) feeder breaker

Substation Preventive Maintenance

Overcurrent Protection / 7SJ45

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

MV network design & devices selection EXERCISE BOOK

N. TEST TEST DESCRIPTION

Utility Interconnection and System Protection

A short introduction to Protection and Automation Philosophy

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

Transcription:

No. SSIEC-PRC-00803-1 SHINSUNG Polymer Recloser SIREC SERIES 15kV, 27kV, 38kV 400A, 630A, 800A

Introduction SIREC(Solid Insulated Recloser) is designed for outdoor application with lightweight, longlife, maximum reliability and enviromental friendly products. Controller with built-in RTU functions can perform the self restoration and feeder automation even without communication. Features Hotline Manual Close (Optional Item) Available manual close operation in live line status. HCEP (Hydrophobic Cycloaliphatic Epoxy) More Durability with Water-Resistance Maintenance free, Oil free, SF6 gas free PMA Application (Permanent Magnetic Actuator) More than 10,000 mechanical operations Applied Standard IEC62271-111 Maintenance Free Cost-effective maintenance of labor and time etc by cycloaliphatic Solid Insulation, reliable operation with PMA application. Advanced Self Healing Scheme Source side fault lockout feature Reduced trip shots to lockout when the fault is at load side Normal open recloser lockout feature when the fault is at adjacent section (No forced fault making) Automatic setting group change from normal to reduced load Maintain the normal setting group of source side recloser during increased load condition through load encroachment logic. Sympathetic trip restraint feature during source side faults. Adaptive protection and measurements according to the power direction: VIT recloser control use the directional element and the polarity is automatically changed according to the power direction. 1

Construction 2 1 4 1 Terminal 2 Vacuum Interrupter 3 Insulation Rod 4 Bird Guard Cap 5 Manual Close Handle (Optional Item) 6 Hook Stick- Operated manual trip and lockout control 7 Mechanical On/Off position indicator 3 5 6 7 Technical Data Description SIREC-27 SIREC-38 Maximum System Voltage 15/27kV 38kV Rated Continuous Current 400/630A 800A Rated Frequency 50/60Hz 50/60Hz Rated Interrupting Current 16kA 16kA Lightning Impulse Withstand (BIL) 125kV 170kV Power Frequency Withstand Voltage (dry/1min) 60kV 70kV Power Frequency Withstand Voltage (wet/10sec) 50kV 60kV Short-Time Withstand Current 16kA/1sec 16kA/1sec Recloser body/tank weight 120kg 208kg Recloser control weight 63kg 63kg * Other ratings are available upon request 2

Layout < Recloser Body> < Recloser Control> 3

Typical Pole-Mounting Installation 4

Substation Mounting Installation 5

Recloser Control Overview Two types are recloser controls available; one is that R6 is μ-processor control with built-in RTU as a conventional protection functions and the other is that VIT R6 as a optional function is designed for the advanced protective application including conventional functions to fulfill the feeder automation without using communication in a radial and loop network as well. It has many advanced features compared with conventional current controlled recloser and as powerful self-restoration system it is best matched with VIT LBS. When the VIT Recloser is used with VIT LBS, it can identify and isolate the faulted section without limitation of sectionalizing points, and can restore the service by itself without any communication-assisted computer system. It can be used at radial system, loop system and also radial-loop mixed system. There are loop system using 3 or 5 reclosers, but the limitation are limited sectionalizing points, limited setting group change and forced fault making when the fault is at the adjacent section of normally open recloser. Main Features of VIT Recloser control Conventional recloser functions Directional ground fault protection Fast, delay curve combination Sequence coordination Cold load pick up / Directional SEF protection Directional negative sequence current protection Sympathetic trip restraint feature Event reports / Measurements Load profile CB wear monitoring function / DNP3.0 Additional functions Source side fault lockout feature Reduced trip shots to lockout when the fault is at load side Normal open recloser lockout feature when the fault is at adjacent section (No forced fault making) Automatic setting group change from normal to reduced load Maintain the normal setting group of source side recloser during increased load condition through load encroachment logic. Sympathetic trip restraint feature during source side faults. Adaptive protection and measurements according to the power direction: VIT recloser control uses the directional element and the polarity is automatically changed according to the power direction. Hybrid Feeder Automation System using VIT Recloser Even in communication-assisted feeder automation system, the CB-Recloser coordination scheme can reduce the outage area during temporary and permanent fault. So the large section is protected first by conventional CB-recloser scheme and the small section can be isolated through the FTU of the load break switch. After deciding and isolating the faulted section, it send close command to the normal open switch to restore the service. Automatic setting group change During loop operation the recloser of the unfaulted feeder (source side recloser) should supply more current and the recloser of faulted feeder (load side recloser) may supply reduced current. 6

If the correct setting group can not change automatically, then the computer system has to change the source side, load side recloser settings before sending close command to the normal open switch. The VIT recloser control uses the load encroachment logics for source side recloser and changes the setting group of load side recloser according to the power direction. The load encroachment logics qualify not only current amplitude, but also the power factor, so even the load current exceeds the pickup level, still it can supply the power but if there is actual fault, it trips and protects the distribution line. From the normal load pickup current (1 st level) to the increased load pickup current (2 nd level) the load encroachment logic qualifies the fault and after increased load pickup current, the fault current amplitude qualifies the fault. Self Restoration System using VIT Recloser and VIT LBS The self restoration system can achieve the same or better result than the communication assisted hybrid feeder automation system in the aspect of speed, reliability, expandability, cost, etc. The large section is protected by substation circuit breaker and distribution line recloser and if the fault is permanent after one or two trip of CB, recloser, the VIT LBS open simultaneously and close one by one to identify and to isolate the fault. It can isolate the faulted and can restore the service by itself without communication. The additional functions of VIT recloser are designed to achieve the best performance of the self restoration system matched with VIT LBS but even without the VIT LBS it solve the problem of conventional loop system using recloser likes forced fault making and lockout, non automatic setting group change, difficulty of directional protection during reverse power flow etc. Operation Mode Normal Recloser Mode In normal recloser mode, the operation is exactly the same with conventional recloser. If the load side of recloser just has sectionalizers, the recloser should operate according to normal recloser mode. Radial Line Mode Basic functions are the same with normal recloser mode If the recloser is coordinated with 2 or 3 sectionalizers, then the radial line mode is not necessary If the down stream of recloser use more than 2 or 3 sectionalizers, the VIT LBS is recommended The radial line mode will be best matched with VIT LBS self restoration scheme Unlike conventional recloser, if the adjacent load side of recloser is a faulted section, then the recloser goes to lockout with one reduced trips. Loop Line Mode Basic functions are the same with normal recloser mode Source side fault lockout feature Load side fault lockout feature with reduced number of trips Loss of voltage lockout feature Normal open (Tie) recloser adjacent fault lockout feature Tie recloser close function during one side voltage lost Automatic setting group change from normal setting group to load side setting group and vice versa according to power direction The normal setting group can supply more current without tripping, without scarifying the sensitivity during loop operation. The load encroachment logics current amplitude and also power factor together. So even the current increased more than min pick up current during loop operation, the control will not start the trip timer until the power factor is out of load zone. 7