Selection of MO surge arresters Overvoltage protection

Similar documents
Transformers connected via a cable Overvoltage protection

Analysis of Major Changes to Arrester Standards IEC STEVE BREWER

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

Type DMX-N Surge Arresters Maximum System Voltage 2 to 36 kv

Low voltage products in high altitudes

APPLICATION GUIDELINES. Overvoltage protection Metal-oxide surge arresters in medium-voltage systems

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

Energy Division. Bowthorpe LV/MV Surge Arresters

MEDIUM VOLTAGE PRODUCT. TJP 6.1, TJP 6.2 Indoor voltage transformers

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

Insulation Co-ordination For HVDC Station

INTERNATIONAL STANDARD

MEDIUM VOLTAGE PRODUCT. TPE 6x.xx Indoor supporting current transformers

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems

MEDIUM VOLTAGE PRODUCT. TJP 5.x Indoor voltage transformers

Tab 8 Surge Arresters

INTERNATIONAL STANDARD

MEDIUM VOLTAGE PRODUCT. PARAMETERS GUIDE How to specify the indoor instrument transformers correctly

Effective February 2017 Supersedes January 2012 (CP1122)

MEDIUM VOLTAGE PRODUCT. KOKM Cable current instrument transformers Instruction for Installation, use and maintenance

Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet

TECHNICAL SPECIFICATION

UltraSIL Polymer-Housed VariSTAR Normal-Duty, Heavy-Duty and Riser Pole Distribution-Class Arresters

EE 1402 HIGH VOLTAGE ENGINEERING

MEDIUM VOLTAGE PRODUCT. TJP 7.x Indoor voltage transformers

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

High voltage engineering

This document is a preview generated by EVS

Protection against unacceptable voltages in railway systems

Three-phase monitoring relay CM-PBE

IEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

Electric Stresses on Surge Arrester Insulation under Standard and

Three-phase monitoring relay CM-PVE

HIGH VOLTAGE Insulation Coordination

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks.

PRODUCT FOR HIGH VOLTAGE APPLICATION. Current transformers for Gasinsulated. Instructions for installation, use and maintenance

UltraSIL Polymer-Housed Evolution Distribution Class Surge Arrester Certified Test Report

Liquid level monitoring relay CM-ENS.2x

Multimeter 500CVD21 RTU500 series

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Coupling unit CM-IVN For expansion of the insulation monitoring relay CM-IWN.x measuring range up to U n = 690 V AC and 1000 V DC

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK

Electronic timer CT-EBE Flasher starting with OFF, 1 c/o (SPDT) contact

Electronic timer CT-YDE Star-delta change-over with 1 c/o (SPDT) contact

Three-phase monitoring relays CM-PVS.81

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

Three-phase monitoring relay CM-PFS

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

VariSTAR Type AZL heavy-duty distribution-class MOV arrester

Outdoor Instrument Transformers. Application Guide

INTERNATIONAL STANDARD

Three-phase monitoring relays CM-PFE and CM-PFE.2

Australian Standard. Instrument transformers. Part 1: Current transformers (IEC Ed.1.2 (2003) MOD) AS AS

Three-phase monitoring relays CM-PVS CM-PVS.31, CM-PVS.41 and CM-PVS.81

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

COOPER POWER. UltraSIL Polymer-Housed VariSTAR Type U2Surge Arrester for Systems through 275 kv IEC 10-kA; Line Discharge Class 2 SERIES

Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages

Electronic timer CT-SDE Star-delta change-over with 1 n/c + 1 n/o contact

Modem 9600 baud 500FSD11 EDS500 series - FSK modems

Construction zglass passivated collar zaluminum termination for pressure contact

University of Zagreb Faculty of Electrical Engineering and Computing

Three-phase monitoring relay

ISOLATING TRANSFORMERS FOR TLC PLANTS

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

Electronic timer CT-SDS.22

Our experience. Our products

Electronic timer CT-AHE OFF-delayed with 1 c/o (SPDT) contact

Fixed Series Compensation

VI 3 - i TABLE OF CONTENTS

3EE2 Special-Purpose Surge Arresters for the Protection of Motors, Generators and Furnace Transformers

LIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

Insulation co-ordination Part 1: Definitions, principales and rules. IEC 2006 Copyright - all rights reserved

Pluggable interface relays CR-U Universal relays

Time relay RXKA 1. (xx jpg) RXKA 1

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Electronic timer CT-AWE Impulse-OFF with auxiliary voltage, 1 c/o (SPDT) contact

Current monitoring relays CM-SRS.1 For single-phase AC/DC currents

MEDIUM VOLTAGE PRODUCTS. KEVA C Indoor voltage sensors for Cellpack separable connectors

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents

Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts

Network Standard NETWORK. Document No Amendment No Approved By Approval Date Review Date NW000-S0142 : : : : : Head of AEP&S 08/06/ /06/2017

Current monitoring relays CM-SRS.2 For single-phase AC/DC currents

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

RTU560. Multimeter 560CVD03. Power Measuring Display. Characteristics. Application. Data Sheet Multimeter 560CVD03

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

Installation at high altitudes

Resistive capacitive voltage divider

Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

Electronic timer CT-WBS.22 Impulse generating and flashing with 2 c/o (SPDT) contacts

Utility System Lightning Protection

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

APPROVAL SHEET 12V/2A EA1019HHUS(03) EA1019HHUS-120 APP D EDAC POWER ELECTRONICS CO., LTD. TEL: FAX:

Transcription:

A P P L I C AT I O N N OT E 1. 1 Selection of MO surge arresters Overvoltage protection

The APPLICATION NOTES (AN) are intended to be used in conjunction with the APPLICATION GUIDELINES Overvoltage protection Metal-oxide surge arresters in medium-voltage systems. Each APPLICATION NOTE gives in a concentrated form additional and more detailed information for the selection and application of MO surge arresters in general or for a specific equipment. First published December 2018

OVERVOLTAGE PROTECTION 3 Selection of MO surge arresters The task of MO surge arresters is to protect other electrical equipment against dangerous overvoltages. 1 Introduction The protection level U pl of an MO surge arrester has to be well below the LIWV of the equipment to be protected. On the other hand the MO surge arrester has to withstand all stresses from the system. Therefore, the continuous operating voltage U c has to be well above the maximum power frequency voltage of the system U s (or U TOV ). Simply said: the MO surge arrester has to protect and not to cause problems. The chosen value for U c should be in all cases higher than the minimum calculated value see Figure 1. The following Table 1 shows typical values of the lightning impulse withstand voltage LIWV of the equipment (based on U m ) and the lightning impulse protection level U pl of the MO surge arrester. As can be seen, there is in all distribution systems a safe margin between LIWV and U pl. For standardized nominal voltages U n, highest system voltages U s, highest voltage for equipment U m and withstand voltages ACWV and LIWV, see Application Note Annex 1.1 A2 and Appli cation Note Annex 1.1 A3. The selection of MO surge arresters should be done step by step according the attached flow chart. Figure 1: Comparison of the possible occurring voltages in a typical medium voltage system, the withstand voltages of the electrical equipment and the parameters of the MO surge arrester. The lightning overvoltages are decisive in medium voltage systems. That is why are shown only the parameters for the lightning overvoltages. Figure 1: LIWV Unprotected, endangered area Ks T Uc Upl Uc U p.u. 10 9 8 Lightning overvoltages 7 6 5 4 3 2 UTOV 1 UL-E Requirements of equipment, related to Um Design parameters of MO arresters System preconditions, related to Us 1 p.u. = Us 2 / 3 Table 1: Typical values of the lightning impulse withstanding voltage LIWV and the lightning impulse protection level U pl = 4 p.u. U m in 3.6 7.2 12 17.5 24 36 LIWV in kv pv 40 60 75 95 125 170 U pl in kv pv 11.8 23.5 39.2 57.2 78.4 117.6 LIWV/U pl 3.39 2.55 1.91 1.66 1.59 1.45

4 APPLICATION NOTE SELECTION OF MO SURGE ARRESTERS 2 Required information In an ideal case all the following information should be given with inquiries. System Data Highest system voltage U s Frequency Earth fault factor or type of neutral earthing Maximum duration of earth fault (clearing time) Maximum value of U TOV Short circuit current I s of the system (per phase) Load rejection factor (in case of generator protection) Service conditions Normal ambient conditions acc. IEC? Pollution class or creepage distance Insulation withstand voltage or flash over distance Altitude Ambient temperature Abnormal earthing conditions Mechanical requirements Arrester application Connection phase to earth Connection neutral to earth (transformer) Connection phase to phase Equipment to be protected Highest voltage for equipment U m Lightning Impulse Withstand Voltage (LIWV) of equipment to be protected Type of equipment Transformer (directly connected to line or via cable) Rotating machines Cables Cable sheath (length of cable and short circuit current per phase) Capacitors Etc. 3 Selection of U c The calculation of the continuous operating voltage U c, which depends on the maximum system voltage U s and the earthing conditions, is explained in Application Note 1.2. See also Application Note 1.2 A1. As mentioned in AN 1.2, the U c should be generally chosen 10% higher than the calculated minimum, and then the next higher value from the data sheet should be taken. 4 Selection of arrester class The class is given by the nominal discharge current I n, the repetitive charge transfer rating Q rs, the thermal charge transfer rating Q th for dis tribution class arresters or the thermal energy rating W th for station class arresters, respectively. Nominal discharge current I n The choice acc. IEC 60099-4, Ed. 3.0 is between I n = 2.5 ka, 5 ka, 10 ka and 20 ka. ABB in Switzerland produces only MO surge arresters with I n = 10 ka and 20 ka. Therefore, the choice is reduced to two values. For MO surge arresters for application in medium voltage systems the nominal current is I n = 10 ka. This is true for distribution class arresters DH and all station class arresters (except for station class arresters SH with I n = 20 ka). Repetitive charge transfer rating Q rs Q rs is defined as the maximum charge transfer capability in the form of a single current impulse or group of current impulses that may be transferred through the arrester without causing mechanical damages or unacceptable electrical changes. This rating is verified on single MO resistors and, therefore, is a MO resistor-related material test. It can be compared with the long duration current withstand test (e.g. I ld, 2 ms) in the previous Ed. 2.2 of IEC 60099-4, see Table 2.

OVERVOLTAGE PROTECTION 5 Table 2: Arrester classes, Comparison IEC 60099-4, Ed. 2.2 and IEC 60099-4, Ed. 3.0 Old: classification acc. IEC 60099-4, Ed. 2.2, Line Discharge Classes (LD classes) LD 1 2 2 3 4 I n (8/20) in ka 10 10 10 10 20 I hc (4/10) in ka 100 100 100 100 100 I ld, 2 ms in A 250 500 550 800 1350 W in kj/kv, U c 3.0 5.2 5.5 9.0 13.3 ABB Type (choice) POLIM-D POLIM-K POLIM-I MWK MWD POLIM-S POLIM-H New: classification acc. IEC 60099-4, Ed. 3.0, thermal rating W th, Q th and charge transfer Q rs Class DH SL SL SM SH I n (8/20) in ka 10 10 10 10 20 Q rs in C 0.5 1.0 1.6 2.0 2.4 Q th in C 1.1 -/- -/- -/- -/- W th in kj/kv, Ur -/- 4.5 5.0 8.0 12.0 W th in kj/kv, Uc -/- 5.6 6.25 10.0 15.0 Thermal charge transfer rating Q th and thermal energy rating W th Q th and W th are the maximum thermal charge transfer rating and maximum thermal energy rating, respectively, that may be injected in an MO surge arrester without causing thermal runaway. These tests are thermal stability tests, and the results can be compared with the values of the operating duty tests (W in kj/kv, U c ) acc. Ed.2.2 of IEC 60099-4, see Table 2. Note that in IEC 60099-4, Ed. 3.0 the values for W th are given in relation to U r, while practice of ABB in Switzerland is to give the value related to U c. For comparison both values are given in the table above. 5 Selection of housing The housing of MO surge arresters has to fulfill two requirements, the creepage distance (depends on the pollution class) and the flashover distance (depends on the required external withstand voltage of the insulation). The pollution classes and the corresponding reference unified specific creepage distances (RUSCD) are specified in IEC 60507:2013 and IEC/TS 60815-1:2008, see Table 3. IEC/TS 60815-3:2008 refers to polymer insulators for AC systems. For the purpose of standardization, five classes of pollution characterizing the site severity are qualitatively defined. It is possible, however, to specify the reductions of the creepage distances for synthetic materials that have a regenerative hydrophobicity, such as silicone, towards ceramic insulations. These reductions, as seen in Table 3, are based on general recommendations given in IEC 60815-3, results from tests and field experience. Table 3: Correlation of pollution class and creepage distance. Pollution class Minimum recommended specific creepage distance in mm/kv* Possible reduction of the creepage distance with silicone insulation a Very light 22.0 30% b Light 27.8 30% c Medium 34.7 20% d Heavy 43.3 No reduction recommended e Very heavy 53.7 No reduction * the shortest specific creepage distance for insulators between phase and earth.

6 APPLICATION NOTE SELECTION OF MO SURGE ARRESTERS Note: The creepage distance for a MO surge arrester is sometimes specified in relation to the con tinuous operating voltage U c. Therefore, it is important to carefully consider the voltage to which the creepage requirements are related. The flashover distance of the external insulation is generally not critical for MO surge arresters for application in distribution systems. The required values of the designs are verified during the insulation withstand tests under dry and wet conditions. MO surge arresters made by ABB in Switzerland can be used without any housing adjustment up to a height of 1,800 m above sea level. Care has to be taken if the MO surge arresters are installed in altitudes higher than 1,800 m above sea level. In such cases the required flashover distance has to be recalculated, using an altitude correction factor. It is proposed that for every 1,000 m above 1,800 m above sea level an increase of the flashover distance by 10 percent should be considered. For example, at an altitude of 3,300 m above sea level the flashover distance of the housing should be 15 percent longer than that of a standard arrester. It is necessary to observe here that the flashover distances of surge arresters for lower voltage levels are initially relatively large, exceeding the minimum requirements of the withstand voltage. Thus, in each individual case it should be checked whether the normal housing possesses a sufficient withstand voltage for application at higher altitudes. 6 Mechanical requirements The mechanical requirements for MO surge arresters in distribution systems are generally not critical. Normally the short circuit requirements are given by the customer in the inquiries, or not mentioned at all. Seismic loads can be normally neglected. Wind loads are not critical, terminal loads in standard applications are not critical as well. In all cases the requirements are given in the inquiries. 7 Final check As a final check the following should be considered: Is the required ambient temperature higher than the standard value of 40 C? If yes, the continuous operating voltage has to be increased accordingly, or the MO arrester (thermal rating W th or Q th, respectively) derated. Installation in altitudes above 1,800 m? If yes, check if flash over distance has to be increased. Check if the residual voltage U pl is well below the required LIWV of the equipment. Any other special requirements by the client?

OVERVOLTAGE PROTECTION 7 APPLICATION NOTE ANNEX 1.1 A1 Flow chart selection of MO surge arresters for medium-voltage 3-phase a.c. systems System preconditions, information needed 1. Selection of active part electrical data Comments Highest system voltage U s Earth fault factor k TOV requirements Ambient temperature a) Continuous operating voltage U c b) Rated voltage U r See AN 1.2 U r = 1.25 x U c, fixed ratio, see also data sheets. Lightning activity c) Nominal discharge current I n I n = 10 ka for all MO arresters, except for station class SH (POLIM-H..N): I n = 20 ka. Energy or charge requirements d) Charge and thermal rating Q rs, W th, Q th See Application Guidelines section 3. Maximum voltage for equipment U m e) Check lightning impulse protection level U pl and withstand voltage LIWV Generally not critical in medium voltage distribution systems. Active part selected 2. Selection of arrester housing mechanical data Pollution degree f) Creepage distance See data sheets. Altitude g) Flashover distance Generally not critical. Only to be considered if installed in altitudes above 1800 m. Short circuit requirements h) Consider short circuit rating I s See data sheets. Mechanical requirements Wind load Terminal loads Seismic loads i) Consider mechanical loads See data sheets. Arrester selected

8 APPLICATION NOTE SELECTION OF MO SURGE ARRESTERS APPLICATION NOTE ANNEX 1.1 A2 Voltages in 3phase a.c. distribution systems above 1000 V System IEC 60038 Equipment IEC 60071-1 U n U s U m ACWV 3 3.6 3.6 10 20 40 6 7.2 7.2 20 40 60 10 12 12 28 60 75 95 15 17.5 17.5 38 75 95 20 24 24 50 95 125 145 30 36 36 70 145 170 LIWV kv peak U n U s nominal system voltage highest voltage of a system, needed for estimation of U c highest voltage for equipment U m ACWV standard rated short-duration (60 s) power frequency withstand voltage of an equipment or insulation configuration LIWV standard rated lightning impulse withstand voltage of an equipment or insulation configuration, needed to check lightning impulse protection level U pl of MO surge arrester SIWV standard rated switching impulse withstand voltage of an equipment or insulation The above table is an extract of the more complete table given in Application Note Annex 1.1 A3. For practical use in distribution systems the above table is sufficient. The columns U s and LIWV give the needed figures for the calculation of the continuous operating voltage U c and for the needed lightning impulse protection level U pl of the MO surge arresters. The following commonly used voltage ranges are given for completeness, see also Application Note Annex 1.1 A3. System voltages acc. IEC 60038: IEC standard voltages Distribution: voltage range between U s = 3.6 kv and U s = 40.5 kv Sub transmission: voltage range between U s = 3.6 kv and U s = 145 kv Transmission: voltage range between U s = 170 kv and U s = 1200 kv Voltages for equipment acc. IEC 60071-1: Insulation co-ordination Range I: voltage range between U m = 3.6 kv and U m = 245 kv Range II: voltage range between U m = 300 kv and U m = 1200 kv

OVERVOLTAGE PROTECTION 9 APPLICATION NOTE ANNEX 1.1 A3 Nominal voltages (and related voltages) above 1000 V a.c., 3phase systems System IEC 60038 Equipment IEC 60071-1 U n U s U m ACWV SIWV kv peak LIWV kv peak 3 3.6 3.6 10 -/- 20 / 40 6 7.2 7.2 20 -/- 40 / 60 Distribution Subtransmission 10 12 12 28 -/- 60 / 75 / 95 15 17.5 17.5 38 -/- 75 / 95 20 24 24 50 -/- 95 / 125 / 145 30 36 36 70 -/- 145 / 170 35 40.5 40.5 -/- -/- -/- 45 52 52 95 -/- 250 66 72.5 72.5 140 -/- 325 Range I -/- -/- 100 185 -/- 450 110 123 123 230 -/- 550 132 145 145 230 275 -/- 550 650 150 170 170 275 325 -/- 650 750 220 245 245 360 395 460 -/- 850 950 -/- 300 300 -/- 750 850 850 950 -/- 362 362 -/- 850 950 950 1175 Transmission 380 420 420 -/- 850 950 -/- 550 550 -/- 950 1175 -/- 800 800 -/- 1300 1425 1550 1175 1300 1425 1175 1300 1425 1550 1675 1800 1950 2100 Range II -/- 1100 1100 -/- 1550 1675 1800 2100 2250 2400 2550 -/- 1200 1200 -/- 1675 1800 1950 2100 2250 2400 2550 2700 For more and detailed information see IEC 60071-1, Edition 8.1 2011-03, Table 2 and Table 3.

ABB Switzerland Ltd. PGHV Surge Arresters Jurastrasse 45 CH-5430 Wettingen/Switzerland Tel. + 41 58585 2911 Fax + 41 58585 5570 Email: sales.sa@ch.abb.com abb.com/arrestersonline Additional information We reserve the right to make technical changes or modify the content of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 2018 ABB. All rights reserved Specifications subject to change without notice 1HC0138860 EN AA