Thyristorised Real Time Power Factor Correction (TRTPFC)

Similar documents
DEVELOPMENT OF A MICROCONTROLLER-BASED POWER FACTORY CORRECTOR

Design and Implementation of Automatic Microcontroller- Based Controlling of Single Phase Power Factor Using Capacitor Banks with Load Monitoring

Monitoring And Control Over Power Factor By Using Pic Micro-Controller

Power Factor Compensation Using PIC

Power Factor Correction Using SCR and Microcontroller

ARDUINO BASED POWER FACTOR CORRECTION

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Power Factor Improvement Using Thyristor Switched Capacitor Using Microcontroller Kacholiya Saurabh 1, Phapale Sudhir 2, Satpute Yuvraj 3, Kale.S.

Automatic Power Factor Correction by Using Synchronous Condenser with Continuous Monitoring.

A Single Phase Power Factor Correction Using Programmable Interface Circuit

AUTOMATIC POWER FACTOR CORRECTION AND MONITORING BY USING PIC MICROCONTROLLER

DESIGN AND DEVELOPMENT OF CONTROLLED RECTIFIER FOR A PMDC MOTOR

Simulation & Hardware Implementation of APFC Meter to Boost Up Power Factor Maintain by Industry.

Power Factor and Power Factor Correction

Dependence of Power Factor on Inductive Loads for Microcontroller based Power Systems

A Fuzzy Controlled PWM Current Source Inverter for Wind Energy Conversion System

DSP-BASED CURRENT SHARING OF AVERAGE CURRENT CONTROLLED TWO-CELL INTERLEAVED BOOST POWER FACTOR CORRECTION CONVERTER

CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS

CHAPTER 4 HARMONICS AND POWER FACTOR

GRADE 12 SEPTEMBER 2012 ELECTRICAL TECHNOLOGY

IMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs

Introduction to Rectifiers and their Performance Parameters

Power Factor improved by Variable Speed AC Drives By Mauri Peltola, ABB Oy, Drives

LV PFC Basics. Power Factor Correction - Basics FK PC PM PFC Januar 07 Page: 1

Influence of Switching Elements on Harmonics and Power Factor Improvement

Thyristorised Automatic Power Factor

Study of Power Factor Correction in Single Phase AC-DC Converter

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

Low Voltage High Current Controlled Rectifier with IGBT A.C Controller on Primary Side of the Transformer

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar.

Power Factor Correction of Inductive Loads using PLC

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Comparative Study of Pulse Width Modulated and Phase Controlled Rectifiers

Question Paper Profile

ELECTRICITY tariff structures in Egypt are fairly complex,

World Academy of Science, Engineering and Technology International Journal of Electrical and Computer Engineering Vol:7, No:6, 2013

HARMONIC distortion complicates the computation of. The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus

Design and Implementation of a New PWM Based Active Impedance Power Factor Correction (AIPFC)

POWER FACTOR CORRECTION OF MACHINE LABORATORY AND CNC MACHINE BY USING IPFC CONTROLLER

Power Quality enhancement of a distribution line with DSTATCOM

Power Factor Improvement Using a Three Phase Shunt Active Power Filter

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)

Single Phase Bridgeless SEPIC Converter with High Power Factor

( ) ON s inductance of 10 mh. The motor draws an average current of 20A at a constant back emf of 80 V, under steady state.

POWER FACTOR CORRECTION AND ITS PITFALLS

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

IJOART. Abstract. Keywords:Capacitor banks,synchronous condenser,microcontroller,dc excitation,power factor. 1.Introduction:

Experiment No. Experiments for First Year Electrical Engg Lab

DESIGN AND SIMULATION OF AUTOMATIC POWER FACTOR CORRECTION FOR INDUSTRY APPLICATION Ararso Taye *1

Jewell DPM Power / Power Factor Size 96/96 BEST IN CLASS

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

Improvement of Power Quality by Using 28-Pulse AC-DC Converter

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication:

PF Correction Techniques in highly varying load

Power factor improvement of SMPS using PFC Boost converter

Technical News. Part 2: Harmonics. The link between harmonics and power factor. Industrial Electrical and Automation Products, Systems and Solutions

Power factor correction and harmonic filtering. Automatic power factor regulators R.1

Chapter 11. Alternating Current

Design and Implementation of Economical Power Factor Transducer

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

Harmonic distortion from induction furnace loads in a steel production plant

CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY

AC Power Instructor Notes

Power Factor. Power Factor Correction.

PFC Lite. How it works OMNIVERTER. OMNIVERTER November 14, 2015 Slide 1

Chapter 7. Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display.

University of Pennsylvania Department of Electrical and Systems Engineering. ESE 206: Electrical Circuits and Systems II - Lab

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

Maintaining Voltage-Current Phase Relationships in Power Quality Monitoring Systems

UPQC (Unified Power Quality Conditioner)

Power factor correction and harmonic filtering. Automatic power factor regulators

ISSN Vol.03,Issue.42 November-2014, Pages:

SINGLE-PHASE, TWO-PULSE ELECTRONIC FIRING CIRCUIT FOR AC TO AC OR AC TO DC CONVERTER CIRCUITS APPLICATIONS

CHAPTER 4 MULTI-LEVEL INVERTER BASED DVR SYSTEM

Improve Power Factor and Reduce the Harmonics Distortion of the System

Enhancement of Power System Voltage Stability Using SVC and TCSC

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

A NEW SINGLE STAGE THREE LEVEL ISOLATED PFC CONVERTER FOR LOW POWER APPLICATIONS

Three Phase Rectifier with Power Factor Correction Controller

How Harmonics have led to 6 Power Factor Misconceptions

Power Factor Improvement Using Static VAR Compensator

MERLIN GERIN KNOW HOW. THM filtering and the management of harmonics upstream of UPS

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

Impact of Distributed Generation on Network Voltage Levels

Buck Boost AC Chopper

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD

Application Guidance Notes: Technical Information from Cummins Generator Technologies

OPTIMAL DESIGN OF A SINGLE TUNED PASSIVE FILTER TO MITIGATE HARMONICS IN POWER FREQUENCY

MIRUS International Inc.

AC VOLTAGE CONTROLLER (RMS VOLTAGE CONTROLLERS)

Introduction: TAS PowerTek Ltd. MAVROS

Chapter L Power factor correction and harmonic filtering

Construction of Inverter with Power Factor Improvement

Power Quality Monitoring and Power Metering Tutorial

ISSN: ISO 9001:2008 Certified International Journal of Engineering and Innovative Technology (IJEIT) Volume 5, Issue 11, May 2016

Development of a Single-Phase PWM AC Controller

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

Transcription:

Thyristorised Real Time Power Factor Correction (TRTPFC) Sanjay N. Patel, 2 Mulav P. Rathod, 3 Keyur C. Patel, 4 Parth H. Panchal, 5 Jaimin N. Prajapati, 2 Asst.Prof, Electrical dept., SVIT Vasad, 3, 4, 5 Students, Electrical dept., SVIT - Vasad Abstract One of the concerns to put on the energy efficiency is in relation to the system power factor. From the view of industrial practices, low power factor might cause equipment failure and higher operation costs. This paper proposes a conceptual design of microcontroller based automatic power correction (APFC Relay) for ø and 3 - ø circuit with intension to be used in power factor (either linear or non-linear) loads applications. The design of this auto adjustable power factor correction is to ensure the entire power system always preserving almost unity power factor and thus optimizing the current consumption and compared with predetermines reference value. The conceptual design of power factor correction techniques has gone through a set of simulation tests using Power System Computer Aided Design (PSCAD).The results are obtained and verified that the proposed PSCAD circuit is capable to produce a reliable output and can be further be implemented in practical application. Keywords: Energy Saving, Reduction of, Power Factor Correction inductor in parallel with a fixed capacitor as a reactive power compensating circuit [5]. The inductor current is controlled by adjusting the firing angle of two antiparallel connected thyristors or using TRIAC. The adjustment of the thyristors' firing angle is made in Accordance to the result of a comparison between the measured values of a certain system parameter with its reference value [6]. This paper proposes a real time power factor correction scheme for -Ø and 3-Ø system. The selection of the capacitor according to load value and simulation for both systems with harmonics are including in this paper. 2. Block diagram of Ø system: The figure shows the block diagram of the - Ø power factor correction system. There are two references namely Voltage and Current measured from the PT and CT. These two references are compared and their resultant angle is given as firing angle of Thyristor. Before them these references are gone through the band pass filter and zero crossing detector. ZCD converts the sinusoidal waveform into square waveforms for triggering thyristor at every zero crossing.. Introduction All Power factor is the relationship between working (active) power and total power consumed (apparent power). Essentially, power factor is a measurement of how effectively electrical power is being used. The higher the power factor, the more effectively electrical power is being used. Low power factor means poor electrical efficiency. The lower the power factor, the higher the apparent power drawn from the distribution Network. When low power factor is not corrected, the utility must provide the nonworking reactive power IN ADDITION to the working active power. This results in the use of larger generators, transformers, bus bars, wires, and other distribution system devices that otherwise would not be necessary. As the utility s capital expenditures and operating costs are going to be higher, they are going to pass these higher expenses to Industrial users in the form of power factor penalties [-4]. One of the new approaches is to use a variable Figure. Block Diagram of - Ø System

2. Circuit Diagram of 3-ø System Figure 2.Waveform of leading pf In figure, i s is the Source current; Vs is the Source voltage; i, i 2, i 3 are the load current, Capacitive branch current, Inductive branch current respectively. Figure 2 and 3 are theoretical waveforms of the Ø system. I s and V s are the output current and voltage of the ZCD respectively. Figure 4. Block Diagram of 3 - Ø System This figure 4 seems that power circuit diagram of RTPFC panel. This control circuit will control the load power factor by sensing various parameters like switching devise thyristor, inductors, capacitor banks etc. And generally this will have one incoming switch like MCB. In this figure 4 3- Ø supply is given through MCB and C.T is connected to the line which is measured the current, And secondary terminal of C.T is connected in terminal (s and s2) of APFC relay s terminal (YL and YM).Phase angle will be measured by pick controller in APFC relay which is given to the zero crossing device. And this thyristor switched devise TRTPFC is switch at zero crossing device. Power factor correction is the process of compensating for the lagging current by creating a leading current by connecting capacitor in parallel to the supply. Figure 3. Waveform of legging pf 2

3. Simulations and Results: The following figure shows the power circuit diagram of the Ø system. The anti parallel connected thyristors are used as the control element for the p.f. correction. Figure 5. Power Circuit of - Ø System The following figure shows the control circuit for the Ø system. There are two references which are compared and the angle difference is given as the firing angle for one thyristor and 80 o phase shift phase angle for the other thyristor. Figure 7.Waveforms of - Ø System The following figure shows the control circuit diagram for analysis of Ø system. Figure 8. Control circuit of - Ø System with Figure 6. Control circuit of - Ø System The following figure shows the simulated waveforms for Ø system. In figure 7, V rms and I rms are the voltage and current of system respectively which are equivalent to theoretical waveforms (Figure 2). G and G2 are the gate signals for anti parallel connected thyristors or TRIAC. E 0 and I 0 are the simulated output waveforms of the - Ø system. Figure 9. Waveforms of - Ø System with Figure 9 shows the harmonics are present at source side and after applying the TRTPFC control technique for nonlinear load, all higher order load harmonics are eliminate effectively. 3

Per phase capacitance KVAR = KVAR Icph = Vph Xc = Vph 2πfC = Vph x 2πfC 3 KVAR/ Ph = Vph Iph 000 After simulating 3 Ø circuit as shown in figure-0. Following results are obtained. As in figure-2.3-ø input voltage, input current, output voltage, output current and voltage is nearly same as input voltage and current. Figure 0. Power Circuit of 3 - Ø System Figure 2. Control circuit of 3 - Ø System The following figure shows the gating signals for3 Ø system. Figure. Control circuit of 3 - Ø System The following figure shows the control circuit diagram for 3 Ø system. In 3 Ø system, phase angle for each phase is given at 0 o, 20 o and 240 o. The value of capacitor is depending on the value of load. So, selection of the capacitor value is based upon following relation. KVAR of Capacitor = P x (Tan Φ - Tan Φ2) Where P is value of load in kw Φ is actual angle between Voltage and current Φ2 is required angle between voltage and current Figure 3. Waveforms of Gate signals of 3 -Ø The figure -4 shows the control circuit for3 Ø system for Analysis. 4

5. References Figure 4. Control circuit of 3 - Ø System with The following figure shows the harmonics waveforms for 3 Ø system. []Alexander.C.K and Sadiku, M.N.O.(2000). Fundamentals of Electric Circuit United States of America: McGraw-Hill Companies.inc. [2] Stephen, J.C.(999). Electric Machinery and Power System Fundamental. 3 rd.ed. United State of America: McGraw-Hill Companies, Inc. [3] John J. Grainger, William D. Stevenson (994). Power System Analysis. New York: McGraw-Hill. [4]Jos Arrillaga, NevilleR.Watson (2003). Power System 2 nd.ed. Chichester: John Wiley. [5]J.E.Miller (982). Reactive Power Control in Electric System. New York: Wiley [6] H.M. El-Bolok, M.E.Masoud.and M.M.Mahmoud (990). A Microprocessor Based Adaptive Power Factor Corrector for Nonlinear Loads Faculty of Engineering and Technology, University of Helwan, Cairo, Egypt. [7] Electrical Power System,V.K. Mehta and Rohit Mehta. Figure 5. Waveforms of 3 - Ø System with Figure-5 shows the harmonics are present and load harmonics are effectively eliminated by applying TRTPFC control technique. 4. Conclusion PFC preregulators are needed to improve output voltage dynamics. In under load condition, voltage leads the current due to capacitive effect and in overload condition; system draws more current due to inductive effect that produces the harmonics. By using TRTPFC technique, that improve output voltage and eliminates the harmonics which shown in simulation results. TRTPFC also improves the power factor almost to unity which saves the energy. TRTPFC technique is easily implemented in practical system. 5