MT MOTORI ELETTRICI. Installation, operation, maintenance and safety manual for motors used in hazardous areas 1-II-2G 21-II-2D

Similar documents
INSTRUCTION MANUAL (ATEX / IECEx)

RDrive 85 servo motors. User manual

Installation & Operating Manual. iwap202

Local control stations for Zone 1 and Zone 21. Features. Description

58 SERIES. Relay interface modules 7-10 A 58.P3 58.P4

ILA2E572PC1A0 integrated drive ILA with servo motor V - EtherCAT - indus connector

Specifications. Specifications. Transfer Characteristics Accuracy at 20 C (68 F) Temperature Drift

Operating Manual. isolate501

DPharp Differential Pressure and Pressure Transmitters

iant200 iant212 iant213 iant214 iant215 iant216 iant217 iant218 iant219 iant220 iant221 iant222 Operating Manual iant2xx Series of Antennas

Intrinsically Safe Pressure Transmitter for highest pressure applications in hazardous environments Model IS-20-H

Thermistor motor protection relays

Inductive sensor slot-type SI2-K08-AP7

Snap Action Switches Technical Guide

Digital Input Output Module 24 V for Ex n Zone 2 Series 9472/35

Pressure transmitters MBS 4201, MBS 4251, MBS 4701 and MBS 4751

Incremental encoders Redundant sensing, isolated blind hollow shaft ø mm, cone shaft ø17 mm pulses per revolution

OPTIWAVE 7300 C Supplementary instructions

For use in Flammable Gas and Dust Atmospheres

Transducer transmitter BILT 4 II 2(1) G. Technical Manual

High Frequency Sinewave Guardian TM Filter

Power Supplies 3. SDN-C Compact DIN Rail Series

Lowara. Centrifugal pumps with open impeller and flanged connections. SHO Series MARKET SECTORS CIVIL, INDUSTRIAL.

LXM32MU60N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw

Instruction manual for STA 1 sectional door operator

Differential-Hall-Effect based Sensors Ex ia for Detection of Speed and Direction of Rotation in Hazardous Areas Zone 0 or 1 Series A5S1DD3 / A5S1DS3

INDUSTRY PROCESS AND AUTOMATION SOLUTIONS

LXM32MD18N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw

High Frequency SineWave Guardian TM Filter

Safety Manual. Omni-ID UHF Tags

LF Conductivity Measuring Probe

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

LXM32CD18N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw

OPTITEMP TT 10 C/R Technical Datasheet

SIMOTICS XP: Type series 1MD5 LOHER CHEMSTAR: Type series 1PS0, 1PS1, 1PS5 LOHER VARIO: Type series 1PS0, 1PS1, 1PS4, 1PS5

Absolute encoders - SSI EX approval ATEX EEx d IIC T6 Optical single and multiturn encoders 14 bit ST / 12 bit MT

Thermistor motor protection relays

Challenger 400. Instruction manual

User's Manual. ROTAMASS Total Insight Coriolis Mass Flow and Density Meter Explosion Proof Type Manual IECEx IM 01U10X02-00EN-R

Analog Universal Module HART for Zone 2 Series 9468/33

Elderfield & Hall, Inc., Kama Bandsaw AD 105S. Instruction Manual: Introduction to the Manual. General Precautions. Equipment. Machine.

Solexy USA, LLC International Blvd Cincinnati, Ohio Phone: Fax:

Temperature Input Module for Zone 1 Series 9482/32

Digital Input Module NAMUR Ex i / I.S. Inputs, 16 Channels for Zone 1 / Div. 1 Series 9470/22

LXM32AD72N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw

Digital Input Module 24 V Ex n Inputs, 16 Channels Series 9471

LXM32AD18M2 motion servo drive - Lexium 32 - single phase supply voltage 115/230V - 0.5/1kW

Differential-Hall-Effect based Sensors for Detection of Speed and Direction of Rotation with two phase-shifted speed signals Series A5S0DD4 / A5S0DS4

EX SSB 70 EX SSB 150 Protective cabinet system heating SSB

M224. M C bis. TYPE CODE M K Y 45 / 18 x 60 - / / / - #

MEDIUM-VOLTAGE MEASURING VOLTAGE TRANSFORMERS USER MANUAL

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 20 ms. 60 ms. 60 ms. Approx. 1.3 kg. Approx. 0.9 kg. Approx. 5.

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/

SET Installation and Operating Instructions. Level switch for two sensors

Safety Instructions Nivotester FTC625, FTC325

Instruction manual for STA 1 sectional door operator

Digital Input Output Module for Zone 2 Series 9470/33

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1.

Type XTSR71 Sizes

Technical Data. General specifications. Rated operating distance s n 3 mm

A rated contacts PCB mount - bifurcated terminals. Copper side view

Motor-protective circuit-breaker, 3p, Ir=40-50A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A

Siemens AG Allows easy and consistent configuration with one series of overload relays (for small to large loads)

Variable frequency drives; 1-/3-phase 230 V; 10.5 A; 2.2 kw; EMC filters; braking transistor

Product Information ECI 1319S EQI 1331S. Absolute Rotary Encoders without Integral Bearing and with DRIVE-CLiQ Interface.

RING CORE CURRENT TRANSFORMERS FOR LOW VOLTAGE TYPE AOS USER MANUAL

EN 50178, IEC

120/240 Watt AC-DC Front End with PFC W Series Convert Select 120 Convert Select 240

Intrinsically safe pressure transmitter MBS 4201, MBS 4251, MBS 4701 and MBS 4751

STAR ELECTRIC COMPANY

RoHS. High shaft load capacity. Shock / vibration resistant

Rozum Robotics has designed its RDrive servo motors to enable precision motion control in industrial and commercial applications.

Incremental encoders Blind hollow shaft or cone shaft pulses per revolution

BAR-ANT-N-N-EX. Antenna barrier for the hazardous area. Data sheet. 1 Description

Ex instruction manual. Rotamass Coriolis mass flow meter. IECEx. IM 01U10X02-00EN-R_002, 2nd edition,

Rotary Measurement Technology Incremental Encoders

Servomotor for butterfly valves VF, VFH. delta-elektrogas.com EE157-01/16

Orbital GFI Inverter Series

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS

CoriolisMaster FCB130, FCB150, FCH130, FCH150 Coriolis Mass Flowmeter

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 690 Volts, 50Hz

Intrinsically Safe Pressure Transmitter for applications in hazardous environments and shipbuilding industry Model IS-20-S, IS-21-S, IS-20-F, IS-21-F

Digital Input Output Module for Zone 2 Series 9470/33

For Immediate Delivery call KMParts.com at (866)

GETTING STARTED GUIDE NI AI, ±60 V, 24 Bit, 1 ks/s/ch Simultaneous

Isolators A3/1. Vibration Transducer Supply Unit Series

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

A6500-UM Universal Measurement Card

PRODUCT SPECIFICATION AND MODEL SELECTION GUIDE

ED701 General Industry Pressure Transmitter

Oil & Gas / Heavy Industry Type 2REX-A-NA-SSI

MINI MCR-SL-UI-I-LP-NC

1. TABLE OF CONTENT 2. ASSEMBLY ATEX. PENCOflex Installation Instructions & Service Manual

This section is specifically about safety matters

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

Ex instruction manual. Rotamass Coriolis mass flow meter ATEX. IM 01U10X01-00EN-R_002, 2nd edition,

XXXX e. X d.. X X X a

Installation and Operational Instructions for ROBA -DX Couplings Type 931.3

GETTING STARTED GUIDE NI AI, ±10 V, 24 Bit, 50 ks/s/ch Simultaneous

SWF DV/DT Solutions Sinewave Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

Transcription:

MT MOTORI ELETTRICI Installation, operation, maintenance and safety manual for motors used in hazardous areas 1-II-2G 21-II-2D TABLE OF CONTENTS 1. Introduction 2. Scope of application 3. Installation and operation 4. Maintenance 1

CAP. I Introduction 2G-2D user's and maintenance manual 07-10-2016 rev. 1 MT Motori Elettrici motors to be used in hazardous areas and explosive atmospheres (1-II-2G; 21-II-2D) are built in compliance with the ATEX 2014/34/EU European directive and with the main European standards on protection devices and systems for explosive atmospheres. More specifically, not only are they compliant with the main regulations defining the electrical and mechanical requirements for standard motors, but motors for explosive atmospheres also meet the following EN/IEC regulations: Table 1.1 Regulatory framework Title Electric apparatus for explosive atmospheres caused by gas Part 0: General rules Electric apparatus for explosive atmospheres caused by gas Part 7: Protection method with increased "e" safety Electric apparatus for explosive atmospheres caused by gas Part 15: n protection method Explosive atmospheres. Equipment dust ignition protection by enclosure "t". EU International CENELEC IEC EN 60079-0 IEC 60079-0 EN 60079-7 IEC 60079-7 EN 60079-15 IEC 60079-15 EN 60079-31 IEC 60079-31 Rotating electric machines Part 1: Nominal and operating features EN 60034-1 IEC 60034-1 Rotating electric machines Part 2: Methods for the determination, based EN 60034-2 IEC 60034-2 on evidence, of leaks and rotating electric machines efficiency Rotating electric machines Part 5: Protection class for rotating machines EN 60034-5 IEC 60034-5 case Rotating electric machines Part 6: Cooling methods EN 60034-6 IEC 60034-6 Rotating electric machines Part 7: Classification of construction forms EN 60034-7 IEC 60034-7 and installation types as well as position of terminal boards Rotating electric machines Part 9: Noise limits EN 60034-9 IEC 60034-9 Rotating electric machines Part 12: Starting features of asynchronous EN 60034-12 IEC 60034-12 single-speed cage motors Case protection class EN 60259 IEC 60259 Electric apparatus to be used with combustible dusts Part 0: General EN 61241-0 IEC 61241-0 prescriptions Electric apparatus to be used with combustible dusts Part 1: Protection EN 61241-1 IEC 61241-1 with td cases The instructions contained in this manual refer to motors installed and stored with temperature between - 20 C and 40 C. Motors to be used in hazardous areas and potentially explosive atmospheres are designed and built in compliance with the aforementioned requirements. If the motors are used improperly, modified and tampered with, MT - Motori Elettrici will not guarantee their efficiency. It is necessary to comply with the regulations on connections and on the use of the devices in hazardous areas. Only skilled and specialized staff is therefore allowed to operate with the aforementioned motors. 2

1.1 Hazardous areas classification (presence of explosive atmosphere) In the following table different hazardous areas, groups, categories and protection classes are indicated. Gas Dusts Table 1.2 Classification of hazardous areas Marking for potentially explosive areas Presence of explosive atmosphere 0 1 2 20 21 22 Continuous presence for long periods of time Occasional presence during normal operation Rare presence for short periods of time Continuous presence for long periods of time Occasional presence during normal operation Rare presence for short periods of time Group Category Protection Gas group IP class II 1G Ex ia intrinsic safety IIA, IIB, IIC IP20 Ex ma II - Incapsulamento II 2G Ex e increased safety II IP54 Ex d explosion-proof IIA, IIB, - cases IIC Ex ib intrinsic safety IIA, IIB, IP20 IIC Ex mb "encapsulation - - Ex o oil-cooled II - Ex p pressurized II IP4X cases Ex q "protection with II IP54 filling" II 3G Ex na Non-sparking II IP54 Ex nc IIA, IIB, IP54 IIC Ex nl limited energy IIA, IIB, IP54 IIC Ex nr limited II IP54 breathing II 1D Ex id intrinsic safety" - IP6X II 2D Ex tb tb cases - IP6X Ex md Encapsulation - IP6X Ex pd pd pressurized cases - IP6X II 3D Ex td td cases - IP6X Gas/dust surface temperature T1=450 C T2=300 C T3=200 C T4=135 C T5=100 C T6=85 C T450 C T300 C T200 C T135 C T100 C T85 C The main features of this user's and maintenance manual are highlighted in bold. 3

Chapter II Scope of application This manual applies to the following motors manufactured by MT Motori Elettrici. Series TN 2 poles 56 200 Series TN 4 poles 56 200 Series TN 4 poles 56 200 Series DN 2-4 poles 63 160 Series DN 4-6 poles 71 160 Series DN 4-8 poles 63 160 Series DN 2-6 poles 71 160 Series DN 2-8 poles 63 160 Series DN 6-8 poles 71 160 Series MN 2 poles 56 100 Series MN 4 poles 56 100 Series MN 6 poles 63 100 TN = three-phase single speed motors DN = three-phase double speed motors MN = single-phase single speed motors These motors will be operated in hazardous areas 1 and 21 (see table 1.2). As to single-phase motors, the capacitor must be placed in a safe area with no explosion hazard. 2.1 Designation Motor designation is composed of different alphanumeric fields (see also annex 2): type: 2 letters identifying the motor family/series; frame size: 2 or 3 numbers and - sometimes - a letter, identifying the motor frame size based on the IEC standard; variant: 1 letter indicates a different power for the same motor class and speed; poles: composed of a slash and one or more numbers indicating the motor poles. Example: TN90LB/4 4

2.2 Plate Find the different items indicated on Ex e (II-2G zone) and Ex tb (II-2D zone) motor plates below. Table 2.1 Plate data Item Description Type Set of alphanumeric digits identifying motor frame size and poles (see par. 2.3). Nr. Motor serial number Prot. IP IP protection class Serv. Service type In compliance with EN 60034-1. cosφ Power factor Is.Cl. Isolation class (F or H) V Δ/Y Voltage supply Hz Frequency HP Power in HP kw Power in kw min -1 Nominal rotation speed A Δ/Y Current intensity value Compliance with European directives mark Explosion protection mark II Group (surface systems other than mines) 2 Category (high protection class) G Explosive atmosphere due to the presence of gas D Explosive atmosphere due to the presence of dust Ex e Protection type (gas) Ex tb Protection type (dust) T3-T4 Motor temperature class T amb Ambient temperature I A /I N Starting and nominal current ratio Time required for a current carrying stator or rotor winding with alternating current I A, t E to reach the maximum temperature starting from balance temperature under standard operating conditions with maximum ambient temperature. The following information is also provided on the plate: the number of the body releasing product quality warranty; the certification number; the warning WARNING DO NOT OPEN WHEN ENERGIZED. 5

Chapter III Installation and operation Always check the information written in the technical documents and make sure it matches the features of the environment where the motor will be installed. MT Motori Elettrici supplies tested motors, which are ready to be installed. 3.1 Reception and storage It is recommended to check the motor upon reception in order to make sure there are no transport damages. Do not operate motors that display damages or are not considered as suitable for the intended use. In case of doubt, please contact MT Motori Elettrici. Carefully check the motor plate data in order to make sure the motor meets the requirements specified in the order and that the motor has the right features for the installation. More specifically, check that the wording on the use in potentially explosive atmospheres is correct for the use required. If the motor is not operated immediately, it has to be stored indoor, in a safe and dry place, without any dust, vibrations and corrosive agents. Before starting the motor after long periods of inactivity or storage, it is recommendable to check insulation to ground by testing it with the specific tool for dielectric strength. Perform the aforementioned check outside of potentially explosive areas. 3.2 Installation Do not work on the motor if energized. Perform all installation operations outside of potentially explosive areas. Always check certifications and technical data. Verify compatibility between motor, atmosphere and zone. Install the motor in compliance with the EN 1127-1 standard (explosive atmospheres - Explosion prevention and explosion protection - main notions and methods); IEC/EN 60079-14 (electric constructions for explosive atmospheres due to the presence of gas Part 14: Electric systems in environments with explosion hazard due to the presence of gas (other than mines); IEC/EN 60079-17 (check and maintenance of electric systems); IEC/EN 61241-14 (electric constructions to be used in presence of combustible dust Part 14: selection and installation). Install the motor in a well-ventilated environment, avoiding installing it close to walls or other machines preventing air to flow. Accurately avoid every situation that can compromise thermal exchange between motor and surrounding environment (heat sources nearby; air channels bottlenecks, etc.). For outdoor installations, protect the motor against weather events and sunlight. For vertical axis installation with fan cover on top, undertake the necessary measures to protect the motor against fluid infiltrations or object infiltrations through the fan cover holes. Plan regular inspections and maintenance during operation. The motor must always be perfectly aligned: make sure the coupling joint is stable and has no vibrations, which may damage the bearings. Motor pulleys coupling must be carefully balanced and mounted with particular care in order to avoid bearing damages. Mount and remove the motor avoiding impacts and shocks, which may damage both visible external parts of the motor and non-visible internal parts, such as - for instance - the bearings. In case of direct coupling, make sure the motor shaft is aligned with the coupled unit shaft (e.g. gearbox); in case of belt drive, keep the smallest clearance as possible and avoid excessive tensions in order not to apply excessive radial loads onto the bearings (tables 3.5 and 3.6). 6

3.3 Electric connection Electric connections must exclusively be carried out by specialized and skilled staff in compliance with current standards - more specifically EN 60079-14 and EN 60079-17. Motor metal parts must be connected to the ground with a cable having a suitable cross-section and using the specific connection positions in the terminal board and outside on the case, marked with the ground symbol. The ground connection must be carried out in compliance with local regulations before powering the motor. Once the connection has been carried out, it is always necessary to close the terminal board cover by suitably fastening the four fastening screws. The power and ground cables must be compliant with cable connection requirements and the section of cables contained in EN60204-1 (Machinery safety - Electric equipment for machines Part 1: General rules). As to the selection of cables to be connected to the terminal board, we hereby report a table showing the motor power absorption in the left column (also indicated on the plate), whereas the cable length is indicated in the first line (known to the installer). Table 3.1 Selection of cables based on their length and motor Amps absorption 0-1 m 1-2 m 2-3 m 3-4 m 4-5 m 5-6 m 6-7 m 7-8 m 240-350 A 1 AWG 1 AWG 1 AWG 1 AWG 1 AWG 1 AWG 1 AWG 1 AWG 180-240 A 2 AWG 2 AWG 2 AWG 1 AWG 1 AWG 1 AWG 1 AWG 1 AWG 150-180 A 2 AWG 2 AWG 2 AWG 2 AWG 1 AWG 1 AWG 1 AWG 1 AWG 120-150 A 5 AWG 5 AWG 2 AWG 2 AWG 2 AWG 2 AWG 2 AWG 1 AWG 100-120 A 5 AWG 5 AWG 5 AWG 2 AWG 2 AWG 2 AWG 2 AWG 2 AWG 80-100 A 5 AWG 5 AWG 5 AWG 5 AWG 2 AWG 2 AWG 2 AWG 2 AWG 60-80 A 8 AWG 8 AWG 8 AWG 5 AWG 5 AWG 5 AWG 2 AWG 2 AWG 40-60 A 8 AWG 8 AWG 8 AWG 8 AWG 5 AWG 5 AWG 5 AWG 5 AWG 20-40 A 10 AWG 8 AWG 8 AWG 8 AWG 8 AWG 8 AWG 8 AWG 5 AWG 8-20 A 14 AWG 10 AWG 10 AWG 10 AWG 10 AWG 10 AWG 8 AWG 8 AWG 0-8 A 14 AWG 14 AWG 14 AWG 14 AWG 14 AWG 14 AWG 14 AWG 14 AWG 1 AWG = 42mm 2 2 AWG = 33 mm 2 5 AWG = 17 mm 2 8 AWG = 8 mm 2 10 AWG = 6 mm 2 14 AWG = 2 mm 2 Depending on the line conductor section, the ground conductor section must be: 3.2 Ground connection S - Line conductor section H Ground conductor section S 16 mm 2 H = S 16 mm 2 < S 35 mm 2 16 mm 2 S < 35 mm 2 H 0,5 S Table 3.3 Wiring diagram three-phase single speed motor 7

Table 3.4 Wiring diagram three-phase double speed motor with single winding Table 3.5 Wiring diagram three-phase double speed motor with double winding Table 3.6 Wiring diagram single-phase motor (put the capacitor in a safe zone with no explosion hazard). Standard Symmetric All motors to be mounted in hazardous areas must be protected by overloads (IEC/EN 60079-14 and IEC/EN 61241-14). Install thermal overload protections in compliance with the maximum operation time t E indicated on the plate. Always check that the seal between cover and terminal board and between terminal board and case are in good conditions. When the motor is connected to the power network it is necessary to comply with the following requirements: 8

Make sure there is no explosive atmosphere; Make sure the power cable is not being energized when connecting it to the terminal board; Do not loosen the bolts fastening the motor winding cables during power connection operations in order to avoid reducing the distance between neighbouring cables and in order not to create play between bolt and cable; Make sure the cable connection is stable; Fasten the cable gland/s well; 3.4 Operation MT Motori Elettrici motors are designed and built to operate in environments with temperature values ranging from 20 C and 40 C; maximum 1000 m altitude above sea level; tolerance for voltage supply +/- 5% and for frequency +/- 2% (EN 60034-1). Only use the motor for the applications it was designed and built for. Comply with plate data. Non-compliance with the instructions provided in this manual and with the reference standards may make the motor not suitable for use in hazardous areas. Always comply with the prescriptions in order not to compromise safety. 3.5 Inverter use MT - Motori Elettrici motors that can be used with inverter belong to the TN and DN series and range from frame size 56 to 200. All single-phase motors are therefore excluded. Motors to be used with an inverter must be equipped with three passive thermal overload protections embedded in the windings (one for each phase). These protections must be connected to a suitable release device that can cut off motor power in case the winding temperature reaches the protection threshold temperature. It is possible to supply thermal overload protections with different threshold values, always in compliance with the maximum motor surface temperature value. In case of operation of the thermal overload protection, the motor must not be powered automatically again. To select a motor for inverter use, it is necessary to know the use of the motor, more specifically the relationship between resistive load and frequency of use. To this purpose an operation chart of MT Motori Elettrici motors with inverter has been drafted, where the applicable load for the motor is indicated. The load can be constantly applied (and it is represented as the ratio between the actual torque and the nominal torque, also defined as nominal torque de-rating coefficient C) depending on the inverter output frequency. 9

MT Motori Elettrici motors corresponding to the type and series mentioned at the beginning of this paragraph are designed to operate in frequency ranges from 5 100 Hz. It is however recommended to use forced ventilation in applications where the frequency goes below 40 Hz, due to the scarce air inflow provided by self-ventilation at low rotation speed levels. Table 3.7 Temperature classes and thermal overload protections Temperature class T4 T3 θ thermal overload protection 120 ±5 % C 170 ±5 % C operation 3.6 Special conditions for safe use In case of delivery of the motor without cable glands the user must use proper ATEX certified devices; The temperature of the cable must be at least 80 C; The use of motor with brakes is not possible without the ATEX certification of the whole assembly; The electric motors can be powered by frequency converter certified as a safety device under the ATEX Directive 2014/34/EU. These inverters must be marked with the following minimum marking II (2) G. These inverters must guarantee an overcurrent protection in compliance with the te time or a maximum temperature protection through the acquisition of the signal to be installed on the thermal motor. protection. 10

Chapter IV Maintenance Overhaul and repair operations can only be carried out by skilled and specialized staff in compliance with EN 60079-17 and EN 60079-19 standards on repair and maintenance of electric apparatuses in hazardous areas. Only skilled staff knowing all of the regulations and standard on connection and use of electric devices in zones with potentially explosive areas are authorized to operate this kind of apparatuses. Do not open the motor nor the terminal board while the motor is being energized and in an explosive atmosphere. It is necessary to keep the motor and any possible accessories clean and have no traces of dust, oil, dirt or other impurities. Always make sure the air channel for cooling is not obstructed in order to avoid overheating Inspect the motor on a regular basis. Make sure the motor works without any vibrations or strange noise. Make sure the tension of any possible drive belts is correct. Make sure the motor fastening elements are fastened correctly. Check the shaft seal conditions and, if necessary, replace the seals. For Ex tb motors it is necessary to carry out a detailed inspection in compliance with IEC/EN 60079-17. 4.1 Bearings Bearings are shielded and self-lubricated for life. It is therefore not necessary to have additional lubrication. Table 3.5 Bearing average life with ambient temperature ranging from 25 C to 40 C Motor Poles Operating hours at 25 C Operating hours at 40 C 71 2 67000 42000 71 4-8 100000 56000 80-90 2 100000 65000 80-90 4-8 100000 96000 100-112 2 89000 56000 100-112 4-8 100000 89000 132 2 67000 42000 132 4-8 100000 77000 160 2 60000 38000 160 4-8 100000 74000 180 2 55000 34000 180 4-8 100000 70000 200 2 41000 25000 200 4-8 95000 60000 The life of bearings also depends on axial and radial loads applied onto the shaft. The table below shows maimum radial loads (N) Table 3.6 Maximum radial and axial loads on the centre line of the motor shaft overhang. RPM Motor size 56 63 71 80 90 100 112 132 160 180 200 Rad Ass Rad Ass Rad Ass Rad Ass Rad Ass Rad Ass Rad Ass Rad Ass Rad Ass Rad Ass Rad Ass 3000 240 100 300 120 470 190 600 250 650 330 1000 470 1300 600 2000 1000 2500 1200 3000 1500 4200 1900 1500 310 140 360 160 530 250 700 330 850 450 1200 630 1600 800 2500 1300 3100 1700 4000 2000 5300 2500 1000 350 170 370 200 550 310 750 400 950 560 1400 800 1900 1000 3000 1600 3700 2000 4500 2300 6000 3100 750 380 190 400 220 600 330 800 450 1000 600 1510 850 2000 1100 3100 1800 4000 2300 5000 2600 6700 3500 4.2 Spare parts 11

Spare parts must be original, with suitable certification and approved by MT Motori Elettrici. In case of doubt, contact MT Motori Elettrici for all parts. 12