Operating Manual. Differential Pressure Transmitter DPS 100

Similar documents
DPS 100 DPS 100. Gauge- / Differential- / Absolute Pressure Transmitter

Operating Manual * * Differential pressure transmitter. Table of Contents. 1 Safety guidelines. 1.1 General Information

Frame through-beam sensors

DMP 343. Industrial Pressure Transmitter. Without Media Isolation. accuracy according to IEC 60770: 0.35 % FSO. Nominal pressure

Through-beam ring sensors

2-channel speed sensor GEL 247 Compact sensor for harsh applications

Data Sheet P993 Low Range Differential Pressure PCB Mount Sensor

OPERATING INSTRUCTIONS AND SPECIFICATIONS. NI 9207E 16-Channel, ±20 ma/±10 V, 24-Bit Analog Input Module

Absolute pressure gauge with output signal For the process industry Models APGT and APGT43.160, NS 100 and 160

Worldwide Manufacturer of Gas Detection Solutions. Transmitter EC 23. Operation Manual

OPTITEMP TT 20 Technical Datasheet

Operating Instructions for Pressure Sensor with Ceramic Sensor Element. Model: SEN-9601

Operating manual GTL 241 GTL 251. Temperature probe. Please keep the manual for future use.

LENORD. +BAUER... automates motion. MiniCoder GEL 2444K Speed and position sensor with metal housing and sin/cos output

Process Control Calibration Made Easy with Agilent U1401A

Instruction Manual MSC710 MSC710-U MSC710-I

DS 400 DS 400. Intelligent Electronic Pressure Switch Completely in Stainless Steel. piezoresistive stainless steel sensor

Magnetic Inductive Flow Sensor induq

TECHNICAL PROFILES CATALOGUE 2016

GT-1050A 2 GHz to 50 GHz Microwave Power Amplifier

MiniCoder GEL 2444T Sensor with square-wave signals and internal interpolation

Inclinometer Selection Guide

Baro Transmitter PTB x1.073

Catalogue NE 0506 FIXTURING SYSTEM. Modular Zero-Point Fixturing for Pallets, Workpieces and Fixtures

DP2500 DP0100 DP0250 Differential Pressure Transmitter

PHV RO High Voltage Passive Probe. Instruction Manual

34134A AC/DC DMM Current Probe. User s Guide. Publication number April 2009

OPERATING INSTRUCTIONS AND SPECIFICATIONS. NI 9211E 4-Channel Thermocouple Input Module

OPERATING INSTRUCTIONS AND SPECIFICATIONS. NI 9853E 2-Port, High-Speed CAN Module

io n Data Sheet or The P5205 is a 100 MHz Active Differential Probe capable of measuring fast rise times of signals in floating circuits. This 1,300 V

FMG90 Series Electromagnetic Flow Meter

UHF Narrow band radio data module CDT-TX/RX MHz

Analogue Demo Multimeter ADM

TRANSDUCER IN-LINE AMPLIFIER

AC 3. Active Antenna Combiner. Instruction manual

High-voltage Differential Probes

IO.AS-dP.01(ENG) APLISENS MANUFACTURE OF PRESSURE TRANSMITTERS AND CONTROL INSTRUMENTS USER S MANUAL. DIFFERENTIAL PRESSURE TRANSMITTER TYPE AS-dP

Ricochet Alphasonic Level Transmitter Model LA15/20 Owner s Manual

ProfiScale MULTI Multimeter

Bedienungsanleitung Instruction Manual. testo 815 Sound Level Meter

PHV 1000-RO High Voltage Passive Probe. Instruction Manual

OEM pressure sensor For industrial applications Models O-10 (T), O-10 (5)

USER S MANUAL. Rail-mounted temperature transmitter ATL

Operating Instructions K-POWERgrip EWL Always on the safe site.

Industrial Pressure Transducers

Flush pressure transmitter For viscous and solids-containing media Model S-11

6688 OCXO Frequency Reference 6689 Rubidium Frequency Reference. User's Manual

EN Official Journal of the European Communities

Melt pressure Transmitter GREENLINE Type DTAI with Temperature element

English. Operating manual. Temperature measuring transducer MU125. Save for later reference. Company / brands of GHM

3B SCIENTIFIC PHYSICS

RSMFX-2R MULTIFUNCTIONAL

Problem-free economical and safe use of bulk materials

Transducer for Measurement Bridges SCM90, SIGS15

Intrinsically safe pressure transmitter For applications in hazardous areas Models IS-20-S, IS-21-S, IS-20-F, IS-21-F

Intrinsically safe pressure transmitter For applications in hazardous areas Models IS-20-S, IS-21-S, IS-20-F, IS-21-F

Operating Instructions CAMILLE BAUER METRAWATT METRAOHM /9.97. Low impedance resistance meas. instrument

Analogue temperature transmitter Model T91.10, head mounting version DIN form B Model T91.20, head mounting version form J

Walkie Talkie APMP300. User manual

Antenna Splitter ASA 1. Instruction manual

PKT 512A-RO High Impedance Passive Cable Divider

Series T. General Eastern Differential Pressure Transmitters. GE Sensing. Description

Solutions for Solar Cell and Module Testing

Multichannel amplifier Model 9235/36

SCXI High-Voltage Terminal Block

Pressure transmitter For general industrial applications Model A-10

WATERFLUX 3000 Quick Start

INSTRUCTION MANUAL LKG 601 Electrical Safety Analyzer

WATERFLUX 3000 Quick Start

Out 1 sin / cos 1Vpp. sin / cos 1Vpp. Out 3. sin / cos 1Vpp. Out 4 sin / cos 1Vpp. Interface type SV211 SinCos signal splitter with 4 SinCos outputs

Magnetic Inductive Flow Sensor

MAVOWATT 4 Multifunction Power Meter

R180. AVRs. Installation and maintenance

Agilent N4000A, N4001A, N4002A SNS Series Noise Sources 10 MHz to 26.5 GHz

Series T. Amphenol Advanced Sensors. Differential Pressure Transmitters

Process Control HPP-25

Installation and Operating Manual

Digital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version

Welcome to the IFR Press Conference 30 August 2012, Taipei

High-quality pressure transmitter For general industrial applications Model S-10

PRetrans Table of contents

TETRIS 1000 High Impedance Active Probe. Instruction Manual

OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO E

45EMD Portable Calibrator User Manual

2018/2019 HCT Transition Period OFFICIAL COMPETITION RULES

CD770 DIGITAL MULTIMETER INSTRUCTION MANUAL

Sure Cross Radio Certifications

FMG70B Series Magnetic Inductive Flow Sensor

External brake resistor AX2090-BW5x

DP2500 DP0100 DP0250 Differential Pressure Transmitter

433 MHZ TEMPERATURE STATION Instruction Manual

WIRELESS 868 MHz TEMPERATURE STATION Instruction Manual

Passive High Voltage Probes P5100A-TPP0850-P5122-P5150-P6015A Datasheet

Alfa Laval Conductivity Sensor

Agilent N8480 Series Thermocouple Power Sensors. Technical Overview

Ambient Weather F007TP 8-Channel Wireless Probe Thermometer User Manual

TA MHz oscilloscope probe TA MHz oscilloscope probe

R&S SMZ Frequency Multiplier Precise andadjustable output levels from 50 GHz to 110 GHz

Colorado Series. CR-30 Portable Conductivity / Temperature / TDS / Salinity Meter Operation Manual

PES Eddy Current Proximity Sensor User s Manual P/N M8A-100

Transcription:

Operating Manual Differential Pressure Transmitter DPS 100 Important notes: Please read this operating manual carefully before installing and starting up the pressure transmitter. This operating manual must be kept at an accessible location for further use. The device may only be installed, used and serviced by persons who are familiar with this operating manual as well as with the applicable regulations on occupational safety and accident prevention. BD SENSORS GmbH BD-Sensors-Straße 1 Telefon +49 (0) 92 35 / 98 11-0 www.bdsensors.de D - 95199 Thierstein Telefax +49 (0) 92 35 / 98 11-11 info@bdsensors.de

Table of contents 1. General notes...3 1.1 Information on the intended use...3 1.2 Target group...3 1.3 Symbols used...3 1.4 Safety notes...4 1.5 Package contents...4 2. Installation...4 3. Electrical installation...4 4. Transport and storage...5 5. Units with 2-wire-system...5 5.1 Dimensions for units with 2-wire-system...5 5.2 Recalibration for units with 2-wire-system...6 6. Units with 3- and 4-wire-system...7 6.1 Dimensions for units with 3- and 4-wire-system...7 6.2 Recalibration for units with 3- and 4-wire-system...7 7. Placing out of service...8 8. Service...8 9. Recalibration...8 10. Repair...9 11. Disposal...9 12. Warranty conditions...9 13. Appendix...10 pressure measurement 2

1. General notes 1.1 Information on the intended use The pressure transmitter DPS 100 is suited for measuring gauge pressure, vacuum, and differential pressure of non-aggressive gases. The basic element of the DPS 100 is a wearless inductive pressure sensor that ensures almost no maintenance. The temperature drift of the sensor is reduced to a minimum. For measuring pressure ranges, which will change very often, the device is equipped with a damping. The DPS 100 has to be supplied with 24 V DC (reverse polarity protection) or 230 V AC (optional 110 V AC, 24 V AC ). The robust construction allows the usage in laboratories and under industrial conditions. Important criteria like long time stability, linearity and good repeatability are warranted by solid mechanics. Due to the temperature compensation of the sensor, a compensated output from 10 up to 50 C is available. Preferred areas of use are: - heating and air conditioning - clean room technology, medical equipment - filter technology, flow measurement - level measurement (via air column) - flow velocity measurement - pitot tube, orifice plate The device shall be used according to these areas of application specified above! Furthermore, compatibility with the medium to be measured has to be ensured. No liability is assumed and warranty claims are excluded in case of improper application, modification of or damage to the device. 1.2 Target group This operating manual is addressed to qualified technical personnel. 1.3 Symbols used : Caution! : Note 3 www.bdsensors.de

1.4 Safety notes The following notes must be observed to avoid hazards for the operator and his environment: The device may only be installed, used, and serviced by persons who are familiar with this operating manual! Applicable regulations regarding occupational safety, accident prevention, and national installation standards must be complied with! The product must only be used within the specifications! (Compare the technical data in the current data sheet.) Never install the device under pressure! Always depressurize the supply lines before installation and service work. 1.5 Package contents Please verify that all listed parts are included in the delivery and check the consistency specified in your order: Differential Pressure Transmitter DPS 100 Operating manual "DPS 100" 2. Installation Mount the device stationary on a suitable fixing location by using both straps. Corresponding dimensions are given under "5.1 and 6.1". Avoid interference sources (transformers, transmitters, motors etc.) or heat sources in the surroundings. Shocks or vibrations at the mounting connection can cause distortions to the output signals. Connections should be vertical, i. e. the pressure connections should point downwards. The sensors are calibrated in the factory for these mounting conditions. In addition, the formation of condensation in the pressure tubing of the sensor is also reduced. 3. Electrical installation Open the top cover and establish the electrical connection of the device according to the following description. Screw the top cover onto the box again. 2-wire-system (DC-Supply; 12-32 Volt smoothed DC) Minus to terminal 1 Plus to terminal 2 3-wire-system (DC-power supply, for power supply range see type plate on device) Power supply: Terminal 1: 0; Terminal 2: VDC Output: Terminal 3: 0; Terminal 4: Output A (current or voltage) Terminals 1 and 3 are internally connected 4-wire-system (AC-power supply; for power supply range see type plate on device) Power supply: Terminal 1: N; Terminal 2: L 1 Output: Terminal 3: 0; Terminal 4: Output A (current or voltage) pressure measurement 4

After switching on the power supply, the output signal can be measured. Variations in the output signals may have two possible causes: 1) The warm-up time of the sensor is about one hour. After this period, the sensor signal should be stable for zero differential pressure and constant ambient temperature. 2) For small pressure ranges, a slightly deviation in the zero point due to ambient conditions can occur. This error can be corrected by adjusting the zero-point potentiometer of the sensor after the warm-up time. (Set the output signal of the sensor with both pressure inputs open to the nominal value.) Connecting the pressure to be measured The pressure to be measured should be connected to the "+" input. Do not blow into this pressure connection, as sensors up to 100 mbar could thus be damaged or destroyed! 4. Transport and storage Permissible temperature for storage: -10 C to + 70 C For transport make sure that both pressure inputs of differential pressure sensors are open. Air transport of absolute pressure sensors should only be done in a pressure compensated cabin. 5. Units with 2-wire-system 5.1 Dimensions for units with 2-wire-system terminal diagram: 1 = 0 2 = + 12-32VDC 5 www.bdsensors.de

5.2 Recalibration for units with 2-wire-system Equipment: Pressure reference: Pressure source: Power supply: Measuring instruments: e. g. precision manometer, digital manometer e. g. pump, bellows, etc 12-32 VDC smooth amperemeter to measure the output signal Pressure source Amperemeter Pressure reference Supply Steps: 1. Connect the power supply (12 32 VDC) and a suitable amperemeter in series to terminals 1 (minus) and 2 (plus). Please take the permissible load from the data sheet. 2. Wait for the sensor to warm up (approx. 1 hour). 3. Zero adjustment (TP 1): To adjust the zero, both pressure ports must be open to the ambient pressure. Set trimmer TP 1, so that the amperemeter reads 4 ma. 4. Span adjustment (TP 2): Connect the nominal pressure via a T-connector to the nominal pressure range, the reference pressure, and the pressure port. Now adjust TP 2, so that the amperemeter reads 20 ma. Note: There are further trimmers fitted (TP 3 / TP 4 / TP5) for other options. TP 3: Symmetry adjustment for sensors with plus / minus ranges. TP 4: Adjustment trimmer for special ranges or special output modes. TP 5: The ranging and matching of digital read-outs. These trimmers are factory set. Adjusting these trimmers should only be done after talking to the supplier. Any re-adjustment of zero and span as described above is only necessary to adjust trimmers TP 1 and TP 2. A re-adjustment of the trimmers TP 3 to TP 5 is not required. pressure measurement 6

6. Units with 3- and 4-wire-system 6.1 Dimensions for units with 3- and 4-wire-system There are different housings depending on the chosen options and pressure ranges. Those types are shown here: terminal diagram: 3-wire-system: Supply Output 1 = 0 3 = 0 2 = VDC 4 = Output 4-wire-system: Supply Output 1 = N 3 = 0 2 = L1 4 = Output 6.2 Recalibration for units with 3- and 4-wire-system Equipment: Reference pressure: e. g. precision manometer, digital manometer Pressure source: e. g. pumps, bellows Power supply: depending on the pressure measuring transducers (see type plate) Measuring instruments: multimeter to measure the output current or voltage signals Pressure source Supply Pressure reference Multimeter 7 www.bdsensors.de

Steps: 1. Connect the correct power supply between terminals 1 and 2 2. Connect a suitable multimeter to measure the output signals (current or voltage) between terminals 3 and 4 3. Wait for the sensor to warm up (approx. 1 hour) 4. Adjusting the zero-point (TP 1): To adjust the zero-point, both pressure inputs must be open. Set the display of the multimeter to 0 Volt (for current output 0 (4) ma) by using the trimmer TP 1. 5. Adjusting the full-scale deflection (TP 2): Connect the nominal pressure via a T-connector to the nominal pressure range, the reference pressure, and the pressure port. Now adjust TP 2, so that the amperemeter reads 10 Volt (for current output 20 ma). Note: Additional trimmers (TP 3 to TP 7) are installed in some options. TP 3: Matching trimmer for sensors with " ± " measurement ranges TP 4 Adjustment of the internal resistance for current output TP 5/TP 6: Adjustment trimmer for special pressure ranges and special output signals TP 7: Scaling and matching of analogue and digital displays These trimmers are factory set. Adjusting these trimmers should only be done after talking to the supplier. Any re-adjustment of zero and span as described above is only necessary to adjust trimmers TP 1 and TP 2. A re-adjustment of the trimmers TP 3 to TP 7 is not required. Time constant: C 14 Capacitor for electronic attenuation Response times: τ R * C R 50 kohm 7. Placing out of service When dismantling the device, it must always be done in the depressurized and currentless condition! 8. Service This device is maintenance-free. If desired, the device can be cleaned using non-aggressive cleaning solutions. 9. Recalibration During the life-time of a transmitter, the offset may shift. As a consequence, a deviating signal value in reference to the nominal pressure range starting point may be transmitted. The full scale may also shift. This would cause a signal value that deviates from the end point of the nominal pressure range. If one of these two phenomena occurs after prolonged use, a recalibration is recommended to ensure furthermore high accuracy. You can send us the device for recalibration. pressure measurement 8

10. Repair DPS 100 If there are malfunctions which cannot be eliminated the device should be sent to us for repair. Before that the device has to be cleaned carefully and packed shatter-proofed. You have to enclose a note of return with detailed defect description when sending the device. If your device came in contact with harmful substances, a declaration of decontamination is additionally required. Appropriate forms can be downloaded from our homepage www.bdsensors.com. Should you dispatch a device without a declaration of decontamination and if there are any doubts in our service department regarding the used medium, repair will not be started until an acceptable declaration is sent. If the device came in contact with hazardous substances, certain precautions have to be complied with for purification! Our service address: BD SENSORS GmbH Serviceabteilung BD-Sensors-Str. 1 95199 Thierstein Germany 11. Disposal The device must be disposed according to the European Directives 2002/96/EC and 2003/108/EC (on waste electrical and electronic equipment). Waste of electrical and electronic equipment may not be disposed by domestic refuse. Special consideration is required for the disposal if the device has been in contact with hazardous substances! 12. Warranty conditions The warranty conditions are subject to the legal warranty period of 24 months from the date of delivery. In case of improper use, modifications of or damages to the device, we do not accept warranty claims. Furthermore, defects due to normal wear are not subject to warranty services. 9 www.bdsensors.de

13. Appendix pressure measurement 10

11 www.bdsensors.de

BD SENSORS GmbH BD-Sensors-Str. 1 95199 Thierstein Germany Phone + 49 (0) 92 35 / 98 11-0 Fax + 49 (0) 92 35 / 98 11-11 The addresses of our 'Distribution Partners' are listed on our homepage www.bdsensors.com. It is possible to download data sheets, operating manuals, ordering codes and certificates, as well. further agencies in: EUROPE Belgium Denmark Germany England France Greece Italy Lithuania Luxembourg Netherlands Norway Poland Romania Russia Sweden Switzerland Slovakia Spain Czech Republic Turkey Ukraine ASIA Iran Israel Kazakhstan Taiwan Thailand AUSTRALIA Queensland The contents of this operating manual reflect the version available at the time of printing. It has been issued to our best knowledge and belief. However, errors may still be included. For incorrect statements and their consequences, liability cannot be assumed by BD SENSORS. Technical modifications reserved Telefon +49 (0) 92 35 / 98 11-0 Telefax +49 (0) 92 35 / 98 11-11 pressure measurement www.bdsensors.de info@bdsensors.de DPS 100_E_010107 12