University of Zagreb Faculty of Electrical Engineering and Computing

Similar documents
PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Earthing of Electrical Devices and Safety

Analysis of lightning performance of 132KV transmission line by application of surge arresters

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Transmission of Electrical Energy

Modeling insulation in high-voltage substations

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

Lightning Overvoltage Performance of 110 kv Air-Insulated Substation

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

Effective Elimination Factors to the Generated Lightning Flashover in High Voltage Transmission Network

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Lightning performance of a HV/MV substation

CIGRE C4 Colloquium on Lightning and Power System, Kuala Lumpur, May, Establishment of a new lightning location system in Croatia

Transformers connected via a cable Overvoltage protection

Substation Insulation Coordination Study

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

Insulation Co-ordination For HVDC Station

G. KOEPPL Koeppl Power Experts Switzerland

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

X International Symposium on Lightning Protection

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

ABSTRACT 1 INTRODUCTION

Selection of MO surge arresters Overvoltage protection

Lightning Flashover Rate of an Overhead Transmission Line Protected by Surge Arresters

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations

HIGH VOLTAGE Insulation Coordination

Specialists in HV and MV test and diagnostics. Testing in Substations

DC VACUUM CIRCUIT BREAKER

Tab 2 Voltage Stresses Switching Transients

Triggered-Lightning Testing of the Protective System of a Residential Building: 2004 and 2005 Results

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

INSTALLATION OF LSA ON A 400 KV DOUBLE-CIRCUIT LINE IN RUSSIA

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

Simulation of Short Circuit and Lightning Transients on 110 kv Overhead and Cable Transmission Lines Using ATP-EMTP

Utility System Lightning Protection

Modeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

ATP SIMULATION OF FARADAY CAGE FOR THE ANALYSIS OF LIGHTNING SURGES

Analysis of Electromagnetic Transients in Secondary Circuits due to Disconnector Switching in 400 kv Air-Insulated Substation

IMP/007/011 - Code of Practice for the Application of Lightning Protection

EE 1402 HIGH VOLTAGE ENGINEERING

EVALUATION OF THE EARTH RESISTANCE VALUE FOR ESE LIGHTNING ARRESTOR TECHNIQUE FOR THE SOLAR PLANTS IN INDIA

Analysis of Major Changes to Arrester Standards IEC STEVE BREWER

RESULTS OF EXPERIMENTAL HIGH CURRENT IMPULSE 4/10 s OF METAL OXIDE VARISTORS ZINC IN THE HIGH VOLTAGE 220KV SURGE ARRESTER

Roll No. :... Invigilator s Signature :.. CS/B.TECH(EE)/SEM-5/EE-502/ POWER SYSTEM-I. Time Allotted : 3 Hours Full Marks : 70

SURGE PROPAGATION AND PROTECTION OF UNDERGROUND DISTRIBUTION CABLES

Lightning overvoltage and protection of power substations

Electric Stresses on Surge Arrester Insulation under Standard and

Tab 8 Surge Arresters

High voltage engineering

Lightning transient analysis in wind turbine blades

Energy Division. Bowthorpe LV/MV Surge Arresters

BASIC PROBLEMS AND SOLUTION OF THE ENCAPSULATION OF A LOW VOLTAGE SPARK GAP WITH ARC SPLITTER CHAMBER

ABSTRACTS of SESSION 6

SIOV metal oxide varistors

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

The Lightning Event. White Paper

SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING

Power System Studies

SWITCHING OVERVOLTAGES IN A 400-KV CABLE SYSTEM

Underground System Design TADP 547

Metal-Oxide Surge Arresters Integrated in High-Voltage AIS Disconnectors An Economical Solution for Overvoltage Protection in Substations

Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage

International Journal of Advance Engineering and Research Development. Analysis of Surge Arrester using FEM

Statistical Lightning Simulations for a HV "Mixed" Overhead-Cable Line: Preliminary Studies

DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers

TECHNICAL REPORT. Insulation co-ordination

Towards an Accurate Modeling of Frequency-dependent Wind Farm Components under Transient Conditions

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

DESIGN CONSIDERATION OF ELECTRICAL DISTRIBUTION AND LIGHTNING PROTECTION SYSTEMS FOR HIGH-RISE BUILDING

ABSTRACT 1.0 INTRODUCTION LIST OF SYMBOLS

Safety earthing. Sector Energy PTI NC. Copyright Siemens AG All rights reserved. Theodor Connor

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems

Chapter 6. WIRING SYSTEMS Safe Electrical Design

Precautions to be considered for use of surge arresters tested according to Class 1 of IEC

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

FERRORESONANCE - its Occurrence and Control in Electricity Distribution Networks

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

Overvoltage Protection of Light Railway Transportation Systems

Coordination of surge arresters in DC 3 kv railway traction system field tests

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE

CONTENTS. 1. Introduction Generating Stations 9 40

OVERVOLTAGE PROTECTION OF POLE MOUNTED DISTRIBUTION TRANSFORMERS

Low voltage products in high altitudes

Protection against unacceptable voltages in railway systems

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

Lightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System

Transcription:

Journal of Energy VOLUME 64 2015 journal homepage: http://journalofenergy.com/ Viktor Milardić viktor.milardic@fer.hr Ivica Pavić ivica.pavic@fer.hr University of Zagreb Faculty of Electrical Engineering and Computing ANALYSIS OF SURGE ARRESTERS FAILURES IN THE INSTALLATION OF BROADCASTING TRANSMITTER SUMMARY In the operation of the broadcasting transmitter, during a lightning storm, comes to frequent surge arrester failures in the switchgear of the broadcasting transmitter and along the 10 kv supply cable (surge arresters in the cable section boxes). Analysis of lightning strokes to the broadcasting transmitter is given in the paper. EMTP simulation of surge arresters loading was conducted. The energy overload of surge arresters is due to lightning flash with more than one lightning strokes or more lightning flashes in short time. Recommendations were also given for improvement of existing surge protection and reduction the number of surge arresters failures. Key words: broadcasting transmitter, lightning stroke, overheating, surge arrester failure 245

1. INTRODUCTION Broadcasting transmitters like all other tall objects (tall buildings, wind turbines) are exposed to frequent lightning strokes [1]. The average annual number of lightning strokes in such facilities can be hundreds of times [2]. Every lightning stroke in the facility may result in some damage. Lightning protection systems and surge protection seeks the probability of damages reduced to an acceptable value. Analysis of lightning strokes in the broadcasting transmitter (BT), analysis of surge arresters (SAs) failures in the switchgear of BT and along the route of the 10 kv supply cable and recommendations for improving the existing surge protection is given in this paper. 2. LIGHTNING STROKES IN THE BT 2.1. The BT In the operation of the BT, located at 1762 m above sea level, Figure 1, during a lightning storm, comes to frequent SA failures in the switchgear of BT, Figure 2 and along the 10 kv supply cable (SAs in the cable section boxes). BT is power supplied from 35/10 kv transformer substation using 10 kv cable line length 8.455 km. The cable is sectioned by four cable boxes (CB1, CB2, CB3 and CB6), Figure 3. In every CB are installed 2 disconnectors and 3 SA (one in phase). The SAs in CBs are UC=14 kv, line discharge class 4. SA failures have occurred in the switchgear of BT and in the cable boxes CB6 and CB3. Figure 1. BT on Biokovo maintain 1762 m above sea level 246

Figure 2. Overloaded SA TS 10/0.4 kv Biokovo CB 6 CB 3 CB 2 CB 1 TS 35/10 kv 4x1x95/16/60 418 m 4x1x95/16/60 3842 m 4x1x50/16/60 1896 m 4x1x50/16/60 979 m 4x1x95/16/60 1320 m Figure 3. Schematic diagram of the 10 kv cable line 2.2. Statistical analysis of lightning flashes In the Lightning Location System (LLS) [2], data were collected on lightning strokes at location of the BT. LLS data were collected over a period of six years, from 14th January 2009 to 5th January 2015. Lightning strokes were collected inside 2 km radius around the BT using LLS. LLS was collected a total of 3939 lightning strokes, with an average flash multiplicity of 1.63 gives the 2417 lightning flashes. The analysis of data on lightning strokes provided the following summary results, Table I. Area [km 2 ] Table I. Lightning flashes at location of BT [2] Number of Number of lightning Average flash lightning strokes to multiplicity flashes to ground ground Lightning flash density [1/km 2 year] 12.56 3939 1.63 2416 32.05 If we compare lightning flash density at the location of the BT 32.05 [1/ km 2 year], with the map of mean lightning flash density it is clear that the BT is many times more exposed to lightning flashes. On maps of mean lightning flash density the highest values are up to 4 [1/km 2 year] in Italy [3] to 6 [1/ km 2 year] in Spain [4] and to 4.84 [1/km 2 year] in Germany [5]. It should be additionally noted that the lightning flash density has been calculated for the circle radius of 2 km (12.56 km 2 area) around the BT. If we take the minor radius, e.g. 1 km, we will receive even greater lightning flash density, because lightning flashes are concentrated in the BT. 247

The analysis of the distribution of the peak values of the lightning current (3939 lightning strokes) gets the cumulative distribution shown in Figure 4. 100% The cumulative distributtion of peak value of lightning current 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% 1 10 100 Peak value of lightning current (ka) Figure 4. The cumulative distribution of peak value of lightning current (3939 lightning strokes) [2] From Figure 4 can be read that 37.6% of all lightning strokes have a peak value greater than 10 ka. Less than 10% of lightning strokes have a peak value greater than 17 ka, and the peak value of lightning strokes greater than 37 ka, is less than 1%. The maximum peak value of lightning strokes (148.9 ka) was measured on 19 th December 2011. This statistical analysis shows that the peak value of lightning strokes significantly deviating from those stated in Table A.1 in the IEC 62305-1 [6]. As previously stated, the BT like all other tall objects is exposed to frequent lightning strokes. As an example, lightning strokes from 4 PM 22 nd November 2013 to 4 PM 23 rd November 2013 and concentration of lightning strokes in the BT are shown in Figure 5. Lightning strokes inside 2 km radius around the BT in time between 23:26:24 and 24:00:00, 22 nd November 2013 are in Table II. From Table II, we can see: a) There are not lightning strokes with high peak value of current; b) There are a large number of lightning strokes in a very short time interval. 248

Table II. Lightning strokes inside 2 km radius around BT in time between 23:26:24 and 24:00:00, 22 nd November 2013 [2] TIME (UTC) Figure 6 shows the concentration of lightning strokes for a longer period of time. The different colors in Figure 6 indicate the range of peak value of lightning currents obtained from Linet LLS: I 3 ka 3 ka < I 5 ka 5 ka < I 10 ka 10 ka < I 16 ka I > 16 ka CURRENT 22/11/2013/ 23:26:24,6370000-7,3 22/11/2013/ 23:26:24,6760000-19,2 22/11/2013/ 23:26:24,8530000-15,8 22/11/2013/ 23:26:24,8880000-13,2 22/11/2013/ 23:26:24,8960000-9,8 22/11/2013/ 23:26:24,9200000-6,2 22/11/2013/ 23:26:24,9750000-5,5 22/11/2013/ 23:26:24,9970000-10,1 22/11/2013/ 23:26:25,0500000-17,6 22/11/2013/ 23:26:25,1010000-4,8 22/11/2013/ 23:26:25,1450000-15,1 22/11/2013/ 23:29:34,3230000-9,3 22/11/2013/ 23:29:34,3610000-7,7 22/11/2013/ 23:29:34,4050000-10,7 22/11/2013/ 23:29:34,5020000 9,3 22/11/2013/ 23:30:57,0220000 4,1 22/11/2013/ 23:30:57,0320000-9,6 22/11/2013/ 23:32:23,5520000-3,9 22/11/2013/ 23:32:23,6190000-5,7 22/11/2013/ 23:32:23,6340000-14,9 22/11/2013/ 23:32:23,6430000-6,8 22/11/2013/ 23:32:23,6500000-9,5 22/11/2013/ 23:50:14,2110000-9,9 22/11/2013/ 23:50:14,2520000-9,2 22/11/2013/ 23:50:14,2660000-4,5 22/11/2013/ 23:50:14,2810000-4,5 22/11/2013/ 23:51:12,7370000-4,2 22/11/2013/ 23:51:12,7690000-4,5 22/11/2013/ 23:51:12,7810000-3,9 22/11/2013/ 23:51:12,7930000-4,5 22/11/2013/ 23:51:12,8090000-9,2 22/11/2013/ 23:51:12,8330000-4,1 22/11/2013/ 23:51:12,8560000-5,0 22/11/2013/ 23:51:12,9170000-9,0 22/11/2013/ 23:51:12,9200000-9,7 22/11/2013/ 23:51:12,9420000-8,4 22/11/2013/ 23:51:12,9670000-9,6 22/11/2013/ 23:51:12,9850000-7,9 22/11/2013/ 23:51:13,0250000-21,9 22/11/2013/ 23:51:13,2310000-4,4 22/11/2013/ 23:55:27,9280000-10,4 22/11/2013/ 23:55:27,9450000-4,7 22/11/2013/ 23:55:27,9630000-4,7 22/11/2013/ 23:59:28,0590000-8,2 249

Figure 5. Concentration of lightning strokes in the BT, from 4 PM 22nd to 4 PM 23rd November 2013 [2] 6 250

Figure 6. Concentration of lightning strokes in the BT from 14 th January 2009 to 5 th January 2015 [2] Analysis of lightning strokes by months is following. Lightning strokes were collected inside 2 km radius around the BT using LLS [2]. Figure 7 shows the average monthly number of lightning flashes calculated using an average multiplicity 1.63. Lightning strokes were collected in the period January 2009 until January 2015. It can be concluded that the greatest number of lightning flashes in the BT were in October, November, December and May, Figure 7. Accordingly, the largest number of SAs failures was in those months. 90 The average monthly number of lightning flashes 80 70 60 50 40 30 20 10 0 Figure 7. The average monthly number of lightning flashes The average yearly number of lightning flashes inside 2 km radius around the BT is shown on Figure 8. It is clear that the number of lightning flashes varies considerably from year to year, and that 2013 was an extreme year by lightning flashes at the location of the BT. 1000 900 800 700 600 500 400 300 200 100 0 The average yearly number of lightning flashes Figure 8. The average yearly number of lightning flashes 251

3. SAs FAILURES IN THE INSTALLATION OF BT 3.1. Theoretical analysis When lightning strikes BT, the lightning current flows through the earth electrode of BT and increase its potential to the reference earth. The occurrence of high transient potential of the earth electrode creates the transient voltage between the earth electrode and the phase conductors of 10 kv cables. Installed SAs limit the transient voltage conducting a part of lightning current from the earth electrode of BT to the phase conductors of 10 kv cables. In this way, the main insulation of 10 kv cables is protected. SA is heated by passing current through it. Thermal energy absorption capability is defined as the maximum level of energy injected into the SA at which it can still cool back down to its normal operating temperature. Figure 9 explains the problem of the thermal stability of SA. The electrical power loss resulting from the continuously applied power-frequency voltage is temperaturedependent. It rises over proportionally as the temperature increases. On the other hand, because of its design, the SA can only dissipate a certain limited amount of heat into the surroundings. Indeed, this heat-flow value also rises with the temperature, however, not nearly as much as the electrical power loss does. Both power curves have two common points of intersection. The left one is stable operating point. At this point exactly as much heat is dissipated to the outside, as is produced in the MO resistors i.e. a thermal balance prevails. A discharge operation disturbs this balance. The energy which is introduced increases the temperature of MO resistors rapidly, and the operating point moves to the right on the power loss curve, as is shown with an arrow in Figure 9. As long as the right point of intersection of the curves is not reached, the heat generated by electrical power loss can easily be dissipated, and the SA can return to the stable operating point. If, however, the right point of intersection is reached or exceeded, then cooling is no longer possible. The SA then becomes thermally unstable and heats up until it selfdestroys. This point of intersection, therefore, represents the thermal stability limit. The thermal energy absorption capability is specified in such a way that the related temperature increase bring the SA to a temperature which exhibits an adequate safety margin to the thermal stability limit. The actual thermal stability limit depends on the overall design of SA and has a value of typically between 170 0 C and 200 0 C. Generally speaking, SA with molded polymeric housing dissipates the heat of the MO resistors better into the surrounding (comparing to porcelain-housed SA) and therefore its thermal stability limit is at slightly higher temperatures. On the other hand, the characteristics of MO materials (electrical losses and their temperature dependence) have an impact. 252

Figure 9. Explanation of the thermal stability of SA [7] Failure of the SAs occurs by heating above the thermal stability limit. Therefore, if the SA is heated above the thermal stability limit, it leads to the thermal destruction of the SA and ultimately to earth fault (line-to-earth fault). Thermal destruction of SAs in the switchgear of BT occurs as a result of large number of lightning strokes in a very short time interval, table II. Every lightning stroke increases the temperature of MO resistors. There is not enough time for cooling of MO resistors between the lightning strokes or to return to a stable operating point. It leads to overheating and thermal destruction of the SA. 3.2. EMTP-ATP analyze ATPDraw [8] simple model, shown in Figure 10, is formed for simulation of lightning stroke in the BT. Lightning stroke is simulated as the injected current. SAs of continuous operating voltage UC = 14 kv and UC = 12 kv, line discharge class 4, are modeled with their protective characteristics, Table III. SA can absorb about 186 kj (UC = 14 kv) and about 160 kj (UC = 12 kv). The connections of SAs to the earth electrodes are modeled as R=1 mω and L= 1 µh (or L= 2 µh in dependence of their length). MV cables are modeled using JMarti model and electrical and geometrical parameters of the cable. Earth electrode resistances of the BT and of the CBs are not known. They had been measured but the sheath and the armor of the cables had not been disconnected. Because of that, resistances of certain earth electrode are not known. The assumption is that the earth electrode resistances of each one CB is 10 Ω and the earth electrode resistances of the BT is considered as parameter: 5 Ω, 10 Ω and 20 Ω. The earth electrode resistance of the BT is not necessary to modeled as nonlinear [9] according to equation (1) because the limiting current to initiate sufficient soli ionization, equation (2), in given case are: 159.16 ka (R=20 Ω), 636.6 ka (R=10 Ω) i 2546.5 ka (R=5 Ω). 253

R i = R 0 I 1+ I g (1) I g ρ E = (2) 2 π R 0 2 0 In accordance to Figure 4 lightning strokes with so large peak value of current are unlikely. V LCC V LCC V LCC V LCC V LCC V 0.418 km 3.842 km 1.896 km 0.979 km 1.32 km + v - H 14 H 14 H 14 H 14 H 14 H 12 UI UI UI UI UI 5 10 10 10 10 2 BCT Figure 10. ATPDraw model The lightning current 200 ka, 10/350 µs is simulated according to [6] and the absorbed energy of SAs in all three phases are calculated. Obtained values are in Table IV (for SAs in BT), Table V (for SAs in CB6) and Table VI (for SAs in CB3). SA with UC = 14 kv, line discharge class 4, can absorb about 186 kj, as previously was told. It is clear that energy-overload of all three SAs (in the switchgear of BT) will occur for any value of earth electrode resistance in the range (5-20) Ω. Energyoverload of all three SAs (in CB6) will occur for value of earth electrode resistance in range just above 5 Ω. Such case of failure of all three SAs in the switchgear of BT has not been occurred. 254

Table III. Protective characteristics of SAs: UC = 14 kv AND UC = 12 kv, Line discharge Class 4 SAs with 14 kv 12 kv UC I (A) U (kv) U (kv) 0.001 19.8 16.97 0.01 22.5 19.28 0.1 25.2 21.58 1 27.9 23.89 10 30.6 26.19 100 33.3 28.50 1000 36.0 30.80 2000 37.1 31.80 5000 38.9 33.40 10000 40.6 34.80 20000 44.3 38.00 40000 49.6 42.50 Table IV. energy of SAs in the Switchgear of BT (Lightning stroke 200 ka, 10/350) Earth electrode resistance of BT (Ω) phase A (kj) phase B (kj) phase C (kj) 20 920 939 941 10 755 780 787 5 534 562 572 Table V. energy of SAs in CB6 (Lightning stroke 200 ka, 10/350) Earth electrode resistance of BT (Ω) phase A (kj) phase B (kj) phase C (kj) 20 303 323 334 10 238 254 262 5 161 169 175 255

Table VI. energy of SAs in CB3 (Lightning stroke 200 ka, 10/350) Earth electrode resistance of BT (Ω) phase A (kj) phase B (kj) phase C (kj) 20 117.1 118.2 117.7 10 94.3 91.6 89.8 5 65.6 60.6 58.7 Lightning current 37 ka, 10/350 µs is simulated next, because less than 1% of peak value of lightning strokes are greater than 37 ka according to Figure 4. The absorbed energy of SAs in the switchgear of BT are calculated, Table VII. Different values of absorbed energy in phases occur due to different values of the powerfrequency voltage at the time of stroke. From Table VII it is clear that the energy overload of SAs in case of one lightning stroke is unlikely. Therefore, the energy overload of SAs is due to lightning flash with more than one lightning stroke or more lightning flashes in short time. Table VII. energy of SAs in all three phases (Lightning stroke 37 ka, 10/350) Earth electrode resistance of BT (Ω) phase A (kj) phase B (kj) phase C (kj) 20 114.0 127.0 130.7 10 80.0 94.0 98.0 5 39.3 53.0 56.7 There are 44 lightning strokes in less than 34 minutes, Table II. Every lightning stroke causes the current though the SAs and increases the temperature of MO resistors. There is not enough time for cooling of MO resistors between the lightning strokes or to return to a stable operating point. Such events can cause the overload of one or more SAs. 3.3. Recommendations What can be done to avoid failures of SAs or minimize the number of failures? Solutions are as follows: 1. Reduction of earth electrode resistance of the BT, what increases the part of the lightning current flowing through the earth electrode and decreases the part of the lightning current flowing through the SAs. This solution requires considerable financial costs. It includes the rehabilitation of the earth electrode of the BT, replacement of existing and laying new earth rods in adequately prepared channels. 2. Increase the thermal energy absorption capability of SAs (several SAs of the same type in parallel). One set of 3 SAs are installed directly at the power 256

transformer and the second set of 3 SAs at the point of arrival of 10 kv cable to the BT. These SAs are approximately in parallel, in phases. For this application SAs must be selected and tested in the factory accordingly to verify equal current distribution among them. For example, if the protective characteristics of parallel connected SAs differ only 1% one SA will absorb 64.45 kj and other one 68.77 kj (in one scenario of lightning stroke). Therefore, the protective characteristics of SA must be different under 1% in order to ensure equal current distribution in two parallel connected SAs. 3. Increase the cooling of SA (avoid squeezed closed spaces as places for installation). In the described case, recommendations 2 and 3 are implemented. In the further monitoring of the BT operation will be decided whether to reduce the earth electrode resistance. 4. CONCLUSION Recommendations for improvement of existing surge protection of the switchgear of BT and reduction the number of SAs failures are: - Reduction of earth electrode resistance of the BT; - Increase the thermal energy absorption capability of SAs (two SAs of the same type in parallel pro phases); - Increase the cooling of SAs; - Further monitoring of the surge protection of the switchgear of BT and the 10 kv supply cable. 5. REFERENCES [1] IEC 61400-24 ed. 1.0 (2010), Wind turbines - Part 24: Lightning protection [2] Lightning Location System http://lls.zvne.fer.hr/lls/ [3] CEI 81-3 : "Valori medi del numero dei fulmini a terra per anno e per chilometro quadrato dei Comuni d'italia, in ordine alfabetico."maggio 1999. [4] www.arqui.com/ayuda/tekton3d/modulos/capitulos/su8/datos/mapa DensImpac.htm [5] DEHN: Lightning Protection Guide, 2nd updated edition, 2007. [6] IEC 62305-1 ed. 2.0. (2010-12) Protection against lightning Part 1: General princiles [7] V. Hinrichsen: MO Energy Handling Capability, V1.1., 10.3.2009. [8] ATPDraw, Windows version 5.6p6, NTNU/SINTEF, Norway. [9] IEEE Working Group: A Simplified method for estimating lightning performance of transmission Lines, IEEE Transactions on Power Apparatus and Systems, vol. 104, no. 4, July 1985. 257