LOAD BEHAVIOUR DURING VOLTAGE DIPS: A VOLTAGE QUALITY STUDY IN LOW VOLTAGE DISTRIBUTION SYSTEM

Similar documents
DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS

RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

INFLUENCE OF VOLTAGE SAGS ON PM SYNCHRONOUS MOTOR DRIVES

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative: Address: Fax Number:

State of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company

EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation

APPLICATION FOR INTERCONNECTION & OPERATIONS OF MEMBER-OWNED GENERATION

SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:

PART 1 OWNER/APPLICANT INFORMATION

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

APPENDIX B: Generation Interconnection Application Form

Voltage Sags in Distribution Systems with Induction Motor Loads Fed by Power Converters and Voltage Mitigation using DVR and D-STATCOM

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY

SYNCHRONOUS MACHINES

Voltage Sag Effects on the Process Continuity of a Refinery with Induction Motors Loads

A Guide to the DC Decay of Fault Current and X/R Ratios

IMPROVEMENT OF VOLTAGE SAG MITIGATION USING DYNAMIC VOLTAGE RESTORER (DVR)

Effects of Transformer Connection on Voltage Sag Characterization

UNDERSTANDING SUB-HARMONICS

ETAP PowerStation. Electrical Transient Analyzer Program. ETAP PowerStation. Short Circuit Analysis. ANSI Standard 3-Phase Fault Currents

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

Impact Assessment Generator Form

Voltage Unbalance Effects on Induction Motor Performance

APPENDIX A MATLAB CODE FOR CALCULATION OF MOTOR TORQUE

Influence of Wind Generators in Voltage Dips

Bahram Amin. Induction Motors. Analysis and Torque Control. With 41 Figures and 50 diagrams (simulation plots) Springer

VOLTAGE DIPS are generally considered a power-quality

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

Harmonic resonances due to transmission-system cables

Voltage Sag Effects on a Refinery with Induction Motors Loads

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

Induction Machine Test Case for the 34-Bus Test Feeder -Distribution Feeders Steady State and Dynamic Solutions

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

Simulation of Voltage Sag Magnitude Estimation in a Power System Network

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

ISSN Vol.03,Issue.11, December-2015, Pages:

EMERGING distributed generation technologies make it

Analysis of Indirect Temperature-Rise Tests of Induction Machines Using Time Stepping Finite Element Method

WIND FARM Flexible AC Transmission Systems

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

Unsymmetrical Fault Analysis & Protection Of The Existing Power System

TABLE OF CONTENT

We are IntechOpen, the first native scientific publisher of Open Access books. International authors and editors. Our authors are among the TOP 1%

Modeling and Simulation of Induction Motor Drive with Space Vector Control

DISCRIMINATION AND ASSESSMENT OF VOLTAGE SAG IN DISTRIBUTION NETWORKS

AGN 034 Alternator Reactance

Volume I Issue VI 2012 September-2012 ISSN

Initial Application Form for Connection of Distributed Generation (>10kW)

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance

Design Requirements for a Dynamic Voltage Restorer for Voltage Sags Mitigation in Low Voltage Distribution System

Simulation and Analysis of Voltage Sag During Transformer Energization on an Offshore Platform

The Effect of Transformer s Vector Group on Retained Voltage Magnitude and Sag Frequency at Industrial Sites Due to Faults

Prepared By Pierre Archambault, PEng Power Survey International Inc Trans Canada Hwy. St-Laurent, QC H4S 1S4 CANADA

Compensation of Different Types of Voltage Sags in Low Voltage Distribution System Using Dynamic Voltage Restorer

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

Development of New Algorithm for Voltage Sag Source Location

Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India

OVERVIEW OF IEEE STD GUIDE FOR VOLTAGE SAG INDICES

COMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N.

APPLICATION OF INVERTER BASED SHUNT DEVICE FOR VOLTAGE SAG MITIGATION DUE TO STARTING OF AN INDUCTION MOTOR LOAD

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS

VOLTAGE sag and interruption are the most important

Minimizing Plant Interruption Caused by Line Disturbances Using Active Voltage Conditioners

Voltage Sag Effects on the Process Continuity of a Refinery with Induction Motors Loads

Performance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System

Effects of Harmonic Distortion I

Appendix D Fault Levels

Power Quality Improvement in Fourteen Bus System using UPQC

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Electric Power Quality: Voltage Sags Momentary Interruptions

Modeling and Analysis of Common-Mode Voltages Generated in Medium Voltage PWM-CSI Drives

PHASE locked loops (PLL) with all ac/dc converters take

Fault Analysis. EE 340 Spring 2012

Simulation of Speed Control of Induction Motor with DTC Scheme Patel Divyaben Lalitbhai 1 Prof. C. A. Patel 2 Mr. B. R. Nanecha 3

Ferroresonance Experience in UK: Simulations and Measurements

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

Frequency Converter Influence on Induction Motor Rotor Faults Detection Using Motor Current Signature Analysis Experimental Research

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)

PARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 2, APRIL

An Introduction to Power Quality

A Power Control Scheme for UPQC for Power Quality Improvement

FLYWHEEL BASED ENERGY STORAGE SYSTEM FOR VOLTAGE SAG CORRECTION AND DETECTION

INTERCONNECTION REQUEST FOR A LARGE GENERATING FACILITY

Manjeet Baniwal 1, U.Venkata Reddy 2, Gaurav Kumar Jha 3

Application of Distribution Static Synchronous Compensator in Electrical Distribution System

PI734F - Winding 07. Technical Data Sheet APPROVED DOCUMENT

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

PI734F - Winding 28. Technical Data Sheet APPROVED DOCUMENT

Fault Induced Delayed Voltage Recovery (FIDVR) Advisory

New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage

Chapter 2: Transformers

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

In Class Examples (ICE)

Transcription:

LOAD BEHAVIOUR DURING VOLTAGE DIPS: A VOLTAGE QUALITY STUDY IN LOW VOLTAGE DISTRIBUTION SYSTEM I. Rendroyoko R.E. Morrison Peter K.C. Wong* Department of Electrical & Computer Science Monash University, PO BOX 35, CLAYTON, VICTORIA 38 Phone: 61-3-9953465, Fax: 61-3-9953454 Ignatius.rendroyoko@eng.monash.edu.au * United Energy Ltd., PO BOX 1185, Moorabbin, VIC 3189 Abstract Over the last ten years, many studies have been performed on voltage dip characteristics in industrial, commercial and residential systems. The characteristic of each voltage dip is unique and particular to each electrical system. This paper presents a study of load behaviour during voltage dips on a low voltage distribution system, consisting of light commercial and residential customers. The recorded voltage dip measurements were used to analyze the system voltage dip characteristic. The Power System Blockset (PSB) from MATLAB was used in modeling the distribution system components and simulating the voltage dips caused by faults. The influence of loads on voltage dips during faults, especially during the winter and summer season, is presented. It is concluded that the load may influence the voltage dip characterization and that load effects must be accounted for to achieve high modeling accuracy. 1. INTRODUCTION Voltage dips have become a major concern in power quality in the past decade. The cost of economical loses and inconveniences caused by voltage dips have triggered some studies and research activities. Many experts have tried to characterise voltage dips [1,2,3]. The existing standard on voltage dip characterises the voltage dips in terms of magnitude and duration. The characterisation of the standard is based on the assumption that faults will cause rectangular voltage dips. It is also assumed that the voltage drops to a certain low value immediately and when the fault is cleared, the voltage recovers back to normal immediately. The assumption of rectangular voltage dips, however, is not correct in a realistic system, which largely consists of rotating machines or motors. When a fault occurs, all the rotating machines in the system slow down and after the fault is cleared, the motors will accelerate to the normal condition. During acceleration, motor will draw high current from the system and thus prolong the voltage dip. This paper will discuss load behaviour on a system during and after a voltage dip. For the purpose of this paper, one sub-system in south-eastern Victoria was selected. This sub-system has significant differences in load characteristics between the summer and winter season. In the summer season, there is an increase of energy consumption, which is mostly due to the operation of air conditioners. Therefore, part of the load consists of electrical rotating machines. 2. SYSTEM COMPONENTS The distribution system under study is presented in fig. 1. A main 66kV bus bar supplies the 22kV distribution system trough 2 66/22kV 3-MVA transformers and the sub-system is supplied at 415 V from a 22/.415kV 4-kVA transformer. The transmission and distribution systems supply electric power to a south-east area of Melbourne in the geographical distribution area of United Energy Ltd. (UE). The sub-system supplies mostly commercial customers, and a few residential and light industrial customers.

subsystem could be due to air conditioners. In summer, the sub-system will have more rotating machines. 5 45 4 Subsystem Max Load KVAR1 KW1 KVA1 KVAR2 KW2 KVA2 35 3 Load 25 2 15 1 Figure 1 One-line diagram of the sub-system under study The circuit parameters of the distribution system under study are shown on table 1. Circuit Voltage Postv Seq-%on 1MVA Zero Seq-%on 1MVA From To No kv Type R1 X1 B1 R X B Source NW66kV 66 Generator/Source 2.5% 6.99% 2.11% 17.95% NW66kV NW22kV 1 66/22 Trfr - 2/3MVA 1.98% 51.36% 7.92% 2.54% NW66kV NW22kV 2 66/22 Trfr - 2/3MVA 1.93% 5.96% 7.72% 2.38% NW22kV WHORSE-SVLE 1 22 O/H- 19/3.25AAC.19.33 1.75.34 1.59.67 22kV/433V 4kVA 1 22/.433 Trfr - 4KVA 4.% 4.% Cap Banks NW22kV 1 22 4.7 Mvar Cap Banks NW22kV 2 22 6. Mvar Table 1 Sub-system's Circuit Parameters For monitoring and measurement purposes, UE has installed power quality monitoring equipment at the 22kV bus and 415V bus. Thus, every fault occurring in the system will be recorded. 3. SUMMER AND WINTER LOADS The subsystem under study has a specific characteristic in load trend. To some extent, the amount of load is different between summer and winter seasons. Usually, in summer, the system has more loads than in winter. The load variation between summer and winter is shown in fig. 2. Since, the subsystem consists of residential, commercial and light industrial customers, the difference of load between summer and winter in this 5 1 : Winter 1 load 2 : Summer load 7 8 9 1 11 12 13 14 Days Figure 2 Summer and Winter Max Load Variation 4. VOLTAGE RECOVERY Faults in the distribution system might cause voltage dips. The location of fault, type of fault, fault clearing time and the electrical system configuration will also affect the voltage dip [3]. A Voltage dip is normally characterised by a magnitude and duration, however, another researcher also mentioned phase angle jump and post fault dip as a further important characteristics [4]. A voltage dip occurring in a system that has resistive loads, will have rectangular shaped dips. When the fault occurs, the voltage directly reduces to a particular value, and when the fault is cleared, the voltage recovers back to its original level immediately [1]. This does not happen when parts of the load consist of rotating machines such as induction motors or air conditioner motors. One of the results of the voltage dip recording is shown in figure 3. Figure 3 shows 415V bus voltage due to a fault of 2ms on a 22kV distribution system. The fault which has occurred on the 22kV system is a single phase to ground fault. However, it is seen in the low voltage side as a two phase to ground fault because of transformer vector connection (delta/star). The voltage dip was recorded at 2:51:34, on 1 December 2. When the fault occurred, the bus voltage dip did not follow step change but instead decreased to a certain point and then decaying to a lower rapidly voltage

levels during the short circuit period. After the fault is cleared, the voltage did not directly recover to its level before fault. The voltage need a longer time to recover back and this could be caused by air conditioning motor loads. 5.1 Balanced Fault During a 3Ph-G fault in the 22kV system, the 415V bus bar voltage also drops in magnitude. Some of the simulation results are shown below: 27 5 4 V3 26 3 25 2 24 1 23 1 2 22 3 21.15.2.25.3.35.4.45.5 Figure 3 Voltage dips in the subsystem 5. SIMULATION OF POST FAULT LOAD BEHAVIOUR 4 8 6 Figure 4 Voltage dip for a 3Ph-G fault Load Current during I3 In order to evaluate and analyse the rotating machine's influence to the sub-system, a simulation model of the sub-system has been developed. The simulation uses the power system blockset tools within the MATLAB package. For simulation purposes, a SLGF and a 3Ph-G fault are simulated at both 22kV and 415V. In the model, the subsystem mimics the real subsystem shown in figure 1. There are six feeders supplying electricity to consumers consisting of resistive loads and rotating motor load models. The air conditioning motor load is 27% of the load in the subsystem. The typical air conditioning motor parameters used in the simulation are given below: Phase 1 Ph Motor 3Ph Motor Rated Capacity 1 Hp 8 HP Power Supply 24 V 415 V Frequency 5 Hz 5 Hz Rs (stator resistance) 1.2 Xs (stator reactance) 4.14 1.8 Rr (rotor resistance).9.4 Xr (rotor reactance) 4.14 1.8 Xm (magnetizing reactance) 69.11 38.2 J (rotor inertia).146 1 Table 2 Air conditioning motor parameters 4 2 2 4 6 8 Figure 5 Load current during 3Ph-G fault Figure 4 and 5 show the 415V-bus voltage and load current during a 3Ph-G fault in the 22kV system. At the 3Ph-G fault, the bus voltage will be suppressed until the fault is cleared. The characteristics of the airconditioning motor load affects the voltage drop and voltage recovery. The subsystem voltage may swing for a few cycles before returning to normal. These swings lengthen the duration of the recovery process [3]. 5.2 Unbalanced Fault Most of the faults on a medium voltage system are single-phase to ground faults [5]. Single-phase faults

often result from lightning, wind, tree-branch contact or insulator failure. The behaviour of the sub-system under study during an unbalanced fault is more complicated than during a three-phase to ground balanced fault. The results of this process are shown in figure 8 and 9 below. 4 35 5 4 V3 3 25 3 2 2 1 1 15 1 5 V 2 3 4 5 4 Figure 6 Voltage dip for a 1Ph-G fault Load Current during I3 Figure 8 Positive, negative and zero sequence voltage for the single phase to ground fault shown in fig. 6 8 7 6 I 3 2 5 4 1 3 2 1 1 2 3 4 Figure 7 Load Current during 1Ph-G fault The busbar voltage during a single phase to ground fault at 22kV line is shown in fig. 6. The 22/.415kV transformer connection makes the voltage dip seen as a 2Ph-G fault at the 415V busbar voltage. Single phase to ground faults give less severe problems to motor loads than 3Ph-G faults. However, voltage recovery after the fault is still affected. Using symmetrical components, the characteristics of the voltage waveform can be clearly seen by dividing them into positive, negative and zero sequence voltage components. 2.3 2.4 Figure 9 Positive, negative and zero sequence current for the single phase to ground fault shown in fig. 7 After fault initiation, the positive-sequence voltage decreases while the negative-sequence voltage increases. In fig. 9, the positive-sequence current drops after fault initiation and suddenly jumps to almost three times than normal load current before its slowly decays to a steady level during the fault. This phenomenon is caused by the air conditioning motor characteristics. When the fault occurs, the motors slow down causing a decrease in positivesequence impedance. This decrease in positivesequence impedance is the cause of the increase in positive-sequence current and the decrease in positive-

sequence voltage. The effect is probably due to speed reduction of the motor. 6. CONCLUSIONS It has been reported that voltage dips which occur on a system with no rotating machines result in a rectangular profile dip. The voltage directly drops to a particular level during fault. After the fault is cleared, the voltage returns to the level present before the fault occurred. 1973 to 1983 and at Staffordshire University from 1983 to 1997. He joined Monash University, Australia in 1997 as director of The Centre for Electrical Power Engineering. Peter KC Wong received his BSc in Electrical Engineering from the University of Hong Kong in 1983. He is currently the Protection & Planning Manager, United Energy, where he is responsible for protection strategy and long-term system planning of the electricity and natural gas distribution networks. He is a member of IEE and IEAust. A different phenomenon can be found in a system with rotating machine loads. When a fault occurs, the voltage does not directly drop to its minimum level but it decays until reaching a steady condition before the fault is cleared. At that time, the voltage does not directly return, but recovers slowly until reaching its original level. From these two results, it can be concluded that load influences the voltage dip characteristization. 7. REFERENCES 1. Math H.J Bollen, "Understanding Power Quality Problems: Voltage Sags and Interruptions", IEEE Press, New York, 2. 2. Math H.J Bollen, The Influence of Motor Reacceleration on Voltage sags, IEEE Trans. on Ind. Applicat., Vol. 31, No. 4, July/August 1995. 3. J.C Das, The effects of momentary voltage dips on the operation of induction and synchronous motors, IEEE Trans. Ind. Applicat., vol.26, pp.711-718, 199. 4. Lidong Zhang; Math H.J. Bollen, Characteristic of (Sags) in Power Systems, 8 th International Conference on Harmonics and Quality of Power ICHQP 98, 1998, pp. 555-56. 5. McGranaghan, Mark F., Mueller, David R., Samotyj Marek J., Voltage Sags in Industrial Systems, IEEE Trans. on Ind. Applicat., Vol. 29, No. 2, March/April 1993 6. Shaffer, John W., Air Conditioner Response to Transmission Faults, IEEE Transactions on Power Systems, Vol.12, No.2, May 1997 Ignatius Rendroyoko, a student member of IEEE, was born in Indonesia in 197. He graduated from the Institute Technology of Bandung, Indonesia in 1994 and served as an electrical engineer in PLN since 1995. He is currently working towards a M.Eng.Sc. degree at Monash University, Australia. Professor RE Morrison was born in Stoke on Trent, United Kingdom in 1951. He received his BSc degree and PhD degree from University of Staffordshire University, UK in 1973 and 1981 respectively. Professor Morrison worked for ALSTOM (UK) from