Measuring and monitoring relays CM-SRS.1 Current monitoring relays, single-phase AC/DC

Similar documents
Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents

Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages

Electronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet

Current monitoring relays CM-SRS.1 For single-phase AC/DC currents

Current monitoring relays CM-SRS.2 For single-phase AC/DC currents

Three-phase monitoring relays

ABB NEW. Three-phase monitoring relays. CM-PVS.31 and CM-PVS.41 Data sheet. Features J. Approvals. Marks. Order data. Order data - Accessories

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC

Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages

Electronic timer CT-SDD.22

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks.

Electronic timer CT-SDS.22

Current monitoring relays CM-SRS.M1 For single-phase AC/DC currents

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

Electronic timer CT-TGD.22

Three-phase monitoring relay

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks.

Three-phase monitoring relay

Three-phase monitoring relays CM-PVS CM-PVS.31, CM-PVS.41 and CM-PVS.81

Electronic timer CT-ERS ON-delayed with 2 c/o contacts Data sheet

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

Electronic timer CT-AWS Impulse-OFF with 1 c/o contact Data sheet

Three-phase monitoring relay CM-PFS

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

Electronic timer CT-MVS.12 Multifunctional with 1 c/o (SPDT) contact

ABB ABB 59 2CDC110004C0205. Measuring and monitoring relays. CM and C5xx range. Content

Electronic timer CT-MFS.21

Electronic timer CT-WBS.22 Impulse generating and flashing with 2 c/o (SPDT) contacts

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.23 and CM-MPS.43

Electronic timer CT-SDE

Three-phase monitoring relays CM-PFE and CM-PFE.2

Three-phase monitoring relays CM-PVS.81

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

Electronic timer CT-YDE Star-delta change-over with 1 c/o (SPDT) contact

Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact

Electronic timer CT-MXS.22 Multifunctional with 2 c/o (SPDT) contacts

Three-phase monitoring relay CM-PBE

Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts

Liquid level monitoring relay CM-ENS.2x

Three-phase monitoring relay CM-PVE

Electronic timer CT-MFS.21 Multifunctional with 2 c/o (SPDT) contacts

Electronic timer CT-EBE Flasher starting with OFF, 1 c/o (SPDT) contact

Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.23

Electronic timer CT-MFS.21 Multifunctional with 2 c/o (SPDT) contacts

Electronic timer CT-SDE Star-delta change-over with 1 n/c + 1 n/o contact

Insulation monitoring relay CM-IWN.5 For unearthed AC, DC and mixed AC/DC systems up to U n = 400 V AC and 600 V DC

Multifunctional three-phase monitoring relays CM-MPN CM-MPN.52, CM-MPN.62 and CM-MPN.72

Power supply CP-E 24/0.75

Electronic timer CT-MBS.22 Multifunctional with 2 c/o (SPDT) contacts

Control module CP-A CM

Type CP-S, CP-C & CP-A Switch mode

Power supply CP-E 24/2.5

Power supply CP-D 24/1.3

Power supply CP-E 12/10.0 Primary switch mode power supply Data sheet

Power supply CP-E 24/2.5

Power supply CP-E 48/5.0 Primary switch mode power supply Data sheet

Power supply CP-E 24/20.0

Analog signal converters CC range

Control module CP-A CM

V2UM230V10 Art.Nr.: V2UM230V10P Art.Nr.: Control elements. Tripping delay. Function selector. Status indication 230 V AC/DC

Analog signal converters CC-E I/I

Insulation monitoring relays CM-IWN.4/5/6 For unearthed AC, DC and mixed AC/DC systems up to U n = 400 V AC and 600 V DC

Coupling unit CM-IVN For expansion of the insulation monitoring relay CM-IWN.x measuring range up to U n = 690 V AC and 1000 V DC

Power supply CP-D 12/2.1

Power supply CP-T 24/40.0 Primary switch mode power supply

s s s 3-60 s min min 3-60 min h h 3-60 h V AC, 50/60 Hz

V2IM10AL10 Art.Nr.: V2IM10AL10P Art.Nr.: Control element. Tripping delay. Function selector. Status indication 24...

Insulation monitoring relay CM-IWS.2 For unearthed AC systems up to U n = 400 V AC

Coupling unit CM-IVN For expansion of the insulation monitoring relay CM-IWN.x measuring range up to U n = 690 V AC and 1000 V DC

Insulation monitoring relay CM-IWS.1 For unearthed AC, DC and mixed AC/DC systems up to U n = 250 V AC and 300 V DC

Power supply CP-T 24/10.0 Primary switch mode power supply

Thermistor motor protection relays

Electronic timer CT-AHE OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AWE Impulse-OFF with auxiliary voltage, 1 c/o (SPDT) contact

Primary switch mode power supplies Product group picture

CP-T range Product group picture

Power supply CP-T 48/5.0 Primary switch mode power supply

VEO. V2PF480Y/277VS01 Art.Nr.: B TECHNICAL DATA

Three-phase monitoring relays Product group picture

Power supply CP-T 24/20.0 Primary switch mode power supply

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

CP-T range Benefits and advantages

CP-E range Benefits and advantages

Power supply CP-T 48/20.0 Primary switch mode power supply

Zelio Control Measurement Relays

Three-phase monitoring relays Table of contents

Three-phase monitoring relays Product group picture

27/04/2015

Pluggable interface relays CR-P Pcb relays

Signal converters Index

Thermistor motor protection relays

Power supply CP-D 24/4.2 Primary switch mode power supply

Insulation monitoring relay CM-IWN.1 For unearthed AC, DC and mixed AC/DC systems up to U n = 400 V AC and 600 V DC


Subject to changes 11/2003 Page 1/7

Transcription:

2CDC 251 244 F0t05 Characteristics Monitoring of DC and AC currents: RMS measuring principle One device includes 3 measuring ranges Over- or undercurrent monitoring configurable Hysteresis adjustable from 3-30 % 3 supply voltage versions 1 c/o contact 22.5 mm width 3 LEDs for status indication CM-SRS.11: 3 ma - 1 A CM-SRS.12: 0.3-15 A CM-SRS.1 Threshold value adjustment (MIN = Default) Hysteresis adjustment (MIN = Default) DIP switches (see DIP switch functions) U/T: green LED - control supply voltage, timing R: yellow LED - relay status I: red LED - over- / undercurrent Approvals A UL 508, CAN/CSA C22.2 No. 14 C GL (pending) D GOST K CB Scheme E CCC L RMRS Marks a CE b C-Tick Order data Type Control supply voltage Order code Measuring ranges: 3-30 ma; 10-100 ma; 0.1-1 A 24-240 V AC/DC CM-SRS.11 110-130 V AC Measuring ranges: 0.3-1.5 A; 1-5 A; 3-15 A CM-SRS.12 24-240 V AC/DC 110-130 V AC 1SVR 430 840 R0200 1SVR 430 841 R0200 1SVR 430 841 R1200 1SVR 430 840 R0300 1SVR 430 841 R0300 1SVR 430 841 R1300 Order data (Accessories) Type Description Order code ADP.01 Adapter for screw mounting 1SVR 430 029 R0100 MAR.01 Marker label 1SVR 366 017 R0100 COV.01 Sealable transparent cover 1SVR 430 005 R0100 1

Application Depending on the configuration, the current monitoring relays CM-SRS.1 can be used for over- b or undercurrent monitoring a in single-phase AC and/or DC systems. The devices work according the open-circuit principle. Operating mode The CM-SRS.1 has 1 c/o contact. There are 2 versions available, CM-SRS.11 with 3 measuring ranges: 3-30 ma, 10-100 ma, 0,1-1 A and CM-SRS.12 with ranges: 0.3-1.5 A, 1-5 A, 3-15 A. The measuring range is selected by connecting the monitored wire to the corresponding terminal B1/B2/B3-C. The unit is adjusted with potentiometers and switches on the top of the unit. The selection of over- b or undercurrent monitoring a is made with a DIP switch. A potentiometer, with direct reading scale, allows the adjustment of the threshold value I and of the hysteresis %. The hysteresis % is adjustable within a range of 3 to 30 % of the threshold value. Function diagrams Overcurrent monitoring b The current to be monitored (measured value) is applied to terminals B1/B2/B3-C. The supply voltage applied to terminals A1-A2 is displayed by the glowing green LED. If the measured value exceeds the adjusted threshold value, the output relay energizes and the red LED (overcurrent) and the yellow LED (relay energized) glow. If the measured value drops below the threshold value minus the adjusted hysteresis, the output relay de-energizes and the red and yellow LEDs turn off. A1-A2 Threshold Hysteresis Measured value 11-14 (15-18) 11-12 (15-16) green LED red LED yellow LED 2CDC 252 208 F0205 Undercurrent monitoring a The current to be monitored (measured value) is applied to terminals B1/B2/B3-C. The supply voltage applied to terminals A1-A2 is displayed by the glowing green LED. If the measured value drops below the adjusted threshold value, the output relay energizes, the red LED flashes W (undercurrent) and the yellow LED (relay energized) glows. If the measured value exceeds the threshold value plus the adjusted hysteresis, the output relay de-energizes and the red and yellow LEDs turn off. A1-A2 Measured value Hysteresis Threshold 11-14 (15-18) 11-12 (15-16) green LED red LED yellow LED 2CDC 252 209 F0205 2

Connection diagram A1 11 15 C B1 B2 B3 B1 B2 B3 11 15 C A1 A2 12 16 14 18 14 18 12 16 A2 2CDC 252 204 F0005 A1-A2 Control supply voltage B1-C Measuring range 1: CM-SRS.11: 3-30 ma CM-SRS.12: 0.3-1.5 A B2-C Measuring range 2: CM-SRS.11 10-100 ma CM-SRS.12: 1-5 A B3-C Measuring range 3: CM-SRS.11: 0.1-1 A CM-SRS.12: 3-15 A 11 15-12 16 /14 18 Output contact - open-circuit principle DIP switch functions 2CDC 252 272 F0005 1 ON Undercurrent monitoring OFF Overcurrent monitoring OFF = Default 3

Technical data Type CM-SRS.1 Input circuit - Supply circuit A1-A2 Rated control supply voltage U S 110-130 V AC 24-240 V AC/DC Rated control supply voltage tolerance -15...+10 % Rated frequency AC versions 50/60 Hz AC/DC versions 50/60 Hz or DC Current / power consumption 24 V DC 115 V AC 230 V AC 110-130 V AC - 24 ma / 2.6 VA - - - 12 ma / 2.6 VA 24-240 V AC/DC 30 ma / 0.75 W 17 ma / 1.9 VA 11 ma / 2.6 VA On-period 100 % Power failure buffering 20 ms Transient overvoltage protection Varistors Input circuit - Measuring circuit B1/B2/B3-C Monitoring function over- or undercurrent monitoring configurable Measuring method RMS measuring principle Measuring inputs CM-SRS.11 CM-SRS.12 Terminal connection B1-C B2-C B3-C B1-C B2-C B3-C Measuring range 3-30 ma 10-100 ma 0.1-1 A 0.3-1.5 A 1-5 A 3-15 A 2) Input resistance 3.3 1 0,1 0.05 0.01 0.0025 Pulse overload capacity t < 1 s 500 ma 1 A 10 A 15 A 50 A 100 A Continous capacity 50 ma 150 ma 1.5 A 2 A 7 A 17 A Threshold value adjustable within the indicated measuring range Tolerance of the adjusted threshold value 10 % of the range end value Hysteresis related to the threshold value 3-30 % adjustable Maximum voltage within measuring circuit factor 1.5 of full scale Measuring signal frequency range DC / 15 Hz - 2 khz Rated measuring signal frequency range DC / 50-60 Hz Maximum response time AC: 80 ms, DC 120 ms Measuring error within the control supply voltage tolerance 0.5 % Measuring error within the temperature range 0.06 % / C Timing circuit Start-up delay T S none Tripping delay T V none Repeat accuracy (constant parameters) 0.07 % of full scale Timing error within control supply voltage tolerance - Timing error within temperature range - Indication of operational states Control supply voltage U/T: green LED V: control supply voltage applied Measured value I: red LED V: overcurrent W: undercurrent Relay status R: yellow LED V: relay energized Output circuits 11(15)-12(16)/14(18) Kind of output relay, 1 c/o contact Operating principle 1) open-circuit principle Contact material AgNi Rated voltage (VDE 0110, IEC 947-1) Minimum switching voltage / minimum switching current 24 V / 10 ma Maximum switching voltage / maximum switching current AC / 4 A AC Rated operational AC12 (resistive) at 230 V 4 A current AC15 (inductive) at 230 V 3 A (IEC 60947-5-1) DC12 (resistive) at 24 V 4 A DC13 (inductive) at 24 V 2 A 4

Type CM-SRS.1 Mechanical lifetime 30x10 6 switching cycles Electrical lifetime (AC12, 230 V, 4 A) 0,1x10 6 switching cycles Short-circuit capacity / n/c contact 6 A fast-acting maximum fuse rating n/o contact 10 A fast-acting General data Dimensions (W x H x D) 22.5 x 78 x 100 mm (0.89 x 3.07 x 3.94 in) Mounting DIN rail (EN 50022) Mounting position any Material of enclosure PA 6 Degree of protection enclosure / terminals IP50 / IP20 Electrical connection Wire size fine-strand with wire end ferrule 2x0.75 mm 2 / 2x2.5 mm 2 (2x18 AWG / 2x14 AWG) fine-strand without wire end ferrule 2x0.75 mm 2 / 2x2.5 mm 2 (2x18 AWG / 2x14 AWG) rigid 2x0.5 mm 2 / 2x4 mm 2 (2x20 AWG / 2x12 AWG) Stripping length 8 mm (0.31 in) Tightening torque 0.8 Nm Environmental data Ambient temperature range operation -20...+60 C storage -40...+85 C Damp heat (IEC 60068-2-30) 55 C, 6 cycles Vibration (sinusoidal) (IEC/EN 60255-21-1) class 2 Shock (IEC/EN 60255-21-2) class 2 Isolation data Insulation voltage supply circuit / measuring circuit 600 V (VDE 0110, supply circuit / output circuit IEC 947-1, measuring circuit / output circuit 600 V IEC/EN 60255-5) output circuit 1 / output circuit 2 Pollution degree 2 (VDE 0110, IEC 664, IEC/EN 60255-5) Overvoltage category III (VDE 0110, IEC 664, IEC/EN 60255-5) Test voltage Rated insulation voltage 2.0 kv, 50 Hz between all isolated circuits (type test) Rated insulation voltage 600 V 2.5 kv, 50 Hz Standards Product standard IEC 255-6, EN 60255-6 Low Voltage Directive 2006/95/EC EMC Directive 2004/108/EC Electromagnetic compatibility Interference IEC/EN 61000-6-2 immunity electrostatic discharge (ESD) IEC/EN 61000-4-2 - Level 3 electromagnetic field IEC/EN 61000-4-3 - Level 3 fast transients (Burst) IEC/EN 61000-4-4 - Level 3 powerful impulses (Surge) IEC/EN 61000-4-9 - Level 3 HF line emission IEC/EN 61000-4-6 - Level 3 Interference IEC/EN 61000-6-3 emission electromagnetic field IEC/CISPR 22; EN 55022 - Class B HF line emission IEC/CISPR 22; EN 55022 - Class B 1) Open-circuit principle: output relay energizes if the measured value exceeds b / falls below a the adjusted threshold value 2) In case of measured currents > 10 A, lateral spacing has to be min. 10 mm 5

Technical diagrams Load limit curves U V 300 200 100 80 60 50 40 30 20 2CDC 252 194 F0205 U V 300 200 100 80 60 50 40 30 20 2CDC 252 193 F0205 10 0.1 0.2 0.5 AC load (resistive) 1 2 4 6 10 I A 10 0.1 0.2 0.5 DC load (resistive) 1 2 4 6 10 I A F 1.0 0.9 0.8 0.7 0.6 0.5 2CDC 252 192 F0205 Switching cycles resistive load 2CDC 252 148 F0206 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 cos ϕ Derating factor F for inductive AC load Contact lifetime Switching current [A] Dimensional drawing 2CDC 252 031 F0003 Dimensions in mm Dimensional drawings (Accessories) 4,5.177 62,5 2.46 11,5.453 10.394 22,5.886 2CDC 252 187 F0005 3A11 20.787 8.315 2CDC 252 186 F0005 2.70 68,5 22,5.886 7.275 3,5.138 2CDC 252 185 F0005 60 2.36 ADP.01 - Adapter for screw mounting MAR.01 - Marker label front-to-back size 107 COV.01 - Sealable transparent cover 6

Publication no. 2CDC 112 097 D0201 Printed in the Federal Republik of Germany (07/07) ABB STOTZ-KONTAKT GmbH Eppelheimer Straße 82 69123 Heidelberg, Germany Postfach 10 16 80 69006 Heidelberg, Germany Internet http://www.abb.com/lowvoltage Control Products Electronic Relays and Controls