Power Quality improvement with Shunt Active Power filter using p-q control technique

Similar documents
Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

NEUTRAL CURRENT COMPENSATION USING FOUR LEG SHUNT ACTIVE POWER FILTER

Control Of Shunt Active Filter Based On Instantaneous Power Theory

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

Power Quality Improvement of Non-Linear Load by Using Instantaneous P-Q Theory

Kanuru; Krishna (Dt); A.P, India. DOI: / Page. 1 G. Aruna Jyothi, 2 DR. P. V. R. L.

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Mitigation of Line Current Harmonics Using Shunt Active Filter With Instantaneous Real and Reactive Power Theory

Modeling of Shunt Active Filter Using P-Q Theory

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

Simulation Results of a Shunt Active Power Filter with Control Based on p-q Theory

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

Performance Analysis of Shunt Active Power Filter Base On Active Reactive Power Theory

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

Comparison of Various Reference Current Generation Techniques for Performance Analysis of Shunt Active Power Filter using MATLAB Simulation

ABSTRACT I. INTRODUCTION

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Power Quality improvement of a three phase four wire system using UPQC

Harmonics Elimination Using Shunt Active Filter

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

Control of Shunt Active Power Filter for Improvement of Power Quality

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

SCIENCE & TECHNOLOGY

International Journal of Advance Research in Engineering, Science & Technology

Analysis of Reference Current Generation for Shunt Active Power Filter Using SRF Algorithm to Compensate Harmonic Current

Simulation Study of PWM Techniques for Voltage Source Converters

Power Quality Improvement using Shunt Passive Filter

Design of Shunt Active Power Filter by using An Advanced Current Control Strategy

Review on Shunt Active Power Filter for Three Phase Four Wire System

Experimental Results of a Single-Phase Shunt Active Filter Prototype with Different Switching Techniques

Design of Shunt Active Filter to Improve Power Quality using Pq Theory

Active Harmonics Filtering of Distributed AC System

Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation

KKR &KSR institute of Technology and sciences,vinjanampadu(v),vatticherukuru(m) Guntur(D) , Andhra Pradesh,India. I.

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

A THREE PHASE SHUNT ACTIVE POWER FILTER FOR HARMONICS REDUCTION

Performance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System

Indirect Current Control of LCL Based Shunt Active Power Filter

Comparative Analysis of Harmonics with and Without Shunt Active Power Filter

Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online):

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

Power Quality enhancement of a distribution line with DSTATCOM

Power Control Scheme of D-Statcom

A Study of Various Filters for Power Quality Improvement

SIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Mitigation of Flicker Sources & Power Quality Improvement by Using Cascaded Multi-Level Converter Based DSTATCOM

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

ENHANCEMENT OF POWER QUALITY USING 9-LEVEL CASCADED H-BRIDGE BASED D-STATCOM WITH IRP THEORY SK. Meeravali* 1, Dr. K.

Comparison of Shunt Active Power Filter Control Strategies for Harmonic Compensation in a Paper Industrial Factory

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

Power Quality Analysis in Power System with Non Linear Load

Literature Review for Shunt Active Power Filters

Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation

Fig. 1 Schematic Diagram Showing Connections to the Active Filter With Non-Linear Load

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Power Factor Improvement Using a Three Phase Shunt Active Power Filter

Application of Tuned Passive Filter for Industrial Six-Pulse Rectifier with R-L Load Viralkumar A. Rana 1 Keyur Rana 2 Atul Talati 3

UNIFIED POWER QUALITY CONDITIONER IN DISTRIBUTION SYSTEM FOR ENHANCING POWER QUALITY

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

A HYBRID ACTIVE FILTER FOR A DIODE RECTIFIER USED AS THE FRONT END OF AN INDUCTION MOTOR DRIVE

CHAPTER 6 THREE-LEVEL INVERTER WITH LC FILTER

ISSN Vol.03,Issue.07, August-2015, Pages:

Harmonics Reduction of 3 Phase Diode Bridge Rectifier by Implementing P-Q Theory with Active Filter

Power Quality Improvement using Active shunt Power filter using PI Controller

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

2020 P a g e. Figure.2: Line diagram of series active power filter.

Shunt Active Power Filter connected to MPPT based photo voltaic Array for PQ enhancement

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF)

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Modified three phase Unified Power Quality Conditioner with capacitor midpoint topology

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

SHUNT ACTIVE POWER FILTER

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 01, 2016 ISSN (online):

A CONTROL TECHNIQUE FOR INSTANT MITIGATION OF VOLTAGE SAG/SWELL BY DYNAMIC VOLTAGE RESTORER

IMPROVING EFFICIENCY OF ACTIVE POWER FILTER FOR RENEWABLE POWER GENERATION SYSTEMS BY USING PREDICTIVE CONTROL METHOD AND FUZZY LOGIC CONTROL METHOD

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

Synchronous Reference Frame Control Algorithm Based Four -Leg Inverter DSTATCOM For Power Quality Improvement

Key-Words: - NARX Neural Network; Nonlinear Loads; Shunt Active Power Filter; Instantaneous Reactive Power Algorithm

Diode Clamped Multilevel Inverter for Induction Motor Drive

Harmonic Immunity And Power Factor Correction By Instantaneous Power Control Of D-STATCOM

International Journal of Scientific & Engineering Research, Volume 6, Issue 8, August ISSN

Transcription:

Power Quality improvement with Shunt Active Power filter using p-q control technique Sumit Kumar 1, Dr.Anju Gupta 2, 1M.Tech Scholar,Power System YMCAUST,Faridabad, 2(Associate Prof.) Electrical Department YMCAUST,Faridabad, Haryana, India ---------------------------------------------------------------------***--------------------------------------------------------------------- Abstract - Improvement of Power quality is major concern in the field of power supply. Various methods have been adapted towards the improvement of power quality. Trend of improving it by using active power filter has been increased in recent years because of its simplicity. In this paper we have used the p-q reference theory as controller to control the output of active power filter to delete the harmonics and to compensate the power factor, PI controller is used to maintain almost constant value under transient and steady state condition. The harmonics occurred due to non linear load which draw current in abrupt manner rather than smooth way leads to create distorted signal on source side on the line which affect the other customers on the same line. By using the vdc as the reference current has been calculated and this reference current is compared with the actual current of active power filter, output from the pq theory is compared with actual current and applied to the gate signal of 3-arm universal bridge used in active filter to delete the harmonics. Hence by using the active power filter IEEE 519 standard which say IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems has been meet. The proposed model has been simulated using MATLAB/SIMULINK and simulation results. Key Words: (SAPF)-shunt active power filter, p-q instantaneous theory, voltage source converter (vsc), matlab/simulink, non-linear load, harmonic elimination 1. INTRODUCTION Decade ago most of the device used are linear and passive in nature have less number of non linear load leads to less impact on the quality of supplied power but In last few years the trend has been changed the electronics equipment has been taken Place a very important role in our day to day life whether it is our household mobile adapter, computer, inverter, refrigerator or commercial fax machine, Xerox machine, printer, PLC s, power electronic convertor device or other various non linear devices, With addition to that various power electronic devices like convertors are used (in adjustable speed drives, switch mode power supplies, etc.) to increase the efficiencies and power factor of wind, solar, and other non-conventional sources to improve the efficiency and ability of system.[1][2] but excessive use of power electronics devices are the origin of harmonics disturbances. Harmonics are actually sinusoidal waveform of periodic waveform with the frequency that is integral multiple of fundamental frequency. When the current with the harmonics flow through transmission line, it increase the resistances of the conductors due to skin effect and cause an abnormal neutral-ground voltage difference. More the non linear load connected to the line higher is the harmonics present in the line which leads to the overheating of transformer, distortion of feeder voltage, excessive neutral current, and it may also leads to damage the circuit breakers, fuses and may leads to wrong measurement low power factor and poor quality of power supply to the customers using that line. Due to the following reason it is must to obligate. Earlier the technique used to compensate the harmonics present in the load current are L-C passive filters but as the problem of undesirable resonance produced in the passive filter and LC passive filter could only absorb harmonic waves of a specific frequency because of these fallbacks it is replaced by active filters. Active filters has the less weights and size,no loading problem and cheaper due to absence of heavy and costly inductors and handling harmonics varies between the specific frequencies. and produce a non-linear voltage drop (Δv) in the line impedance, which distorts the load voltage (vl). and affect the system as discussed above[2] Figure shown below represent the power system with nonlinear load which leads to produce the current with harmonics and the change in the value of current By using the filters we can remove the harmonics, passive filter are generally not used because they will only filter out the frequency for which they are tuned and also resonance can occurred because of interaction take place between passive filter and load connected to line. Therefore the use of active filter is done to compensate the harmonics value unlike over the large frequency range and without any resonance problem. 2016, IRJET Impact Factor value: 4.45 ISO 9001:2008 Certified Journal Page 2937

1.2. INSTANTENOUS REACTIVE POWER THEORY There are various methods used to control the value of capacitor so that harmonics of current at source side can mitigate instantaneous reactive power theory is used because of its ease implementation the foremost step is to transform the source voltages into 2 component from three phase value i.e. from (Va, Vb, Vc) to (Vα, Vβ)and similarly the load current from (Ilabc) to (Iα,Iβ) using direct conversion or By using Park transformation converting them in (d-q) component. The principle adjustment of this method is to extract the fundamental component and harmonic removed component using low pass filters ( LPF). [4] Source voltage is given by equation given below Fig1: power system with non-linear load 1.1 Active Filter Vα = Vβ = ]... (i) ]...(ii) Active filter are the equipment which are used to improve both current harmonics and/or voltage harmonicas and compensate power factor, various researchers application shows that series active filter are used for compensate the voltage harmonics and shunt active power filter are used to improve the current harmonics. Figure shown below represent active shunt power filter it uses the voltage source inverter with capacitor at its dc side act as energy storages device. Filter is controlled in a way that it acts as the current source. Three phase Converters used are having six IGBT switches which are given pulses to store the energy in the capacitor and charge and discharge it when required. The supply voltage source gets the required active power and capacitor of shunt active power filter provides the reactive power for the load. The load is a 3-φ diode rectifier supplying a RL load, shown as (Fig. 2)[3]. After applying the shunt active power filter the harmonics which occurs onto the source side due to the non linear load has been removed which in return preserve other customers using same line. Also transformer overheating and misbehaving of measuring equipment has been stopped. Similarly the load current equation is given by Iα = Iβ = ]. (iii) ]...(iv) 3 phase stationary component value is being converted into d-q /a-b rotating coordinate the given figure shows the transformation of three phase stationary (a-b-c) component into rotating two phases. [7] Fig 3: reference frame transformation With the help of above values of current and voltage instantaneous real and reactive power is calculated by the following equation : P = (Vα)(Iα) + (Vβ)(Iβ) (v) q = (-Vβ)(Iα) + (Vα)(Iβ)..(vi) Fig2: 3-φ shunt active power filter As shown in above equations real (P) and imaginary (q) power can be decomposed in Ac and Dc parts. Fundamental current and fundamental voltage is the result of Dc part and harmonics present are resulted due to the presence of Ac part. 2016, IRJET Impact Factor value: 4.45 ISO 9001:2008 Certified Journal Page 2938

After the calculation of P,q reference current has been calculated with the help of these equation as shown below Which give equation of reference current icα,icβ with the help of these value current has been transformed again into three coordinate Ica,Icb,Icc having equation given below Icb = Icc = (vii)..(viii) (ix) The voltage source inverter used in the active power filter makes the harmonic control possible. This inverter uses a d.c. capacitor as the supply and can switch at a high frequency to generate a signal which will cancel the harmonics from the nonlinear load.the capacitor present on DC side of universal bridge/convertor serves to maintain DC voltage in steady state and act as energy storage element while meet real power difference between load and source side at transient periods. In steady state condition the real power supplied by the source is equal to power demand at load plus small power required at active filter to compensate the losses. When load condition changes the power demand changes and hence balance of source and load side effects. This effect has to be compensating by the capacitor present at dc side of universal bridge/convertor. The power is charged or discharged by the capacitor according to its requirement, when real power supplied is equal to the load side power then the capacitor attains the value equal to reference value. Smaller capacitor voltage than reference value indicates that real power supplied from source side is not enough to meet the demand required at load side, and when the dc capacitor voltage attains higher value than the reference than it tries to decrease the value of source current. The dc capacitor voltage is compared reference value which than fed the error signal to pi controller whose output is compared with the instantaneous real power after that it is converted into ica, icb from the equation given above and then this reference current value is being transformed into three component system. Three phase reference current is compared with the actual filter current outcome error signal is send towards the 6 pulse gate signal which leads to operate the switches according to meet the need.[5] 2. MODELING AND SIMULATION RESULT The mat lab model with shunt active filter is as shown below it leads to operate for 0.2 sec,the source voltage, source current, load current, filter current, and dc side capacitor voltage is as shown in the waveforms. The waveform with linear load and non linear load are shown. Fig4: Simulation controller block for p-q theory As in above block by using the equation (i) (ii) and (iii)(iv)[6] we transform three phase voltage source and three phase load current into two component system respectively which is then allow to calculate the value of instantaneous real and imaginary power the output is compared with the error value which came from dc capacitor voltage which is compared with reference dc voltage through pi controller as shown below.[7] Fig5: Vdc compared with Vdc reference and passes through Pi controller Fig6: Simulation model for non linear load with shunt active filter 2016, IRJET Impact Factor value: 4.45 ISO 9001:2008 Certified Journal Page 2939

Table 1: Parameter used SOURCE VOLTAGE SYSTEM FREQUENCY DC LINK REFERENCE VOLTAGE 415 V 50HZ 950 V DC SIDE CAPACITANCE 2500x10-6 LOAD SIDE RESISTANCE 15ohm Fig10: Source current with shunt active filter LOAD SIDE INDUCTANCE 10x10-3 AC SIDE RESISTANCE 0.01ohm AC SIDE INDUCTANCE 1e-6 Fig11: Waveform show 3-phase active filter current Fig7: Source current with linear load The source current with linear current shown above indicate pure sinusoidal waveform i.e. There is no harmonics present in the line. But when the load side is equipped with equipments with power electronics devices it leads to produce the harmonics pollution in the source current as shown below Fig12: Dc side capacitor voltage Fig13: FFT Analysis show harmonic Fig8: load current with non linear load Fig9:single phase load current FIG14: FFT Analysis with shunt active filter 2016, IRJET Impact Factor value: 4.45 ISO 9001:2008 Certified Journal Page 2940

CONCLUSIONS: Increase of the use of power electronics device as the load leads to create the need of research in the field to mitigate the harmonics pollution. In order to protect the various equipment connected to the line flow with harmonics. It does not only effect the transformer or generator like equipment but also the quality of power at household consumers effected by it and suffer the poor quality, hence in the world of privatization of electrical utility it is necessary for various company to overcome the situation of harmonic,so the customer can get the good quality of power. In this paper we are using the shunt active power filter to compensate the harmonics with the help of p-q control scheme. The harmonics has been decreased from 23 percent to 4 percent which are under the IEEE standardization. REFERENCES [1] Mr. Kalpesh L. Deshmukh, Mr. Suhas M. Shembeka Performance of Shunt Active Power Filter based SRF Algorithm under Non Linear Load International Journal of Engineering and Technical Research (IJETR) ISSN: 2321-0869, Volume-3, Issue-5, pp. 388-391, May 2015 [2] João L. Afonso, Member IEEE, H. J. Ribeiro da Silva and Júlio. S. Martins, Member IEEE Active Filters for Power Quality Improvement 10-13 Set.Porto, Portugal, ISBN: 0 7803 7139 9, 2001 [3] P. Salmerón and S. P. Litrán Improvement of the Electric Power Quality Using Series Active and Shunt Passive Filters IEEE TRANSACTIONS ON POWER DELIVERY, pp.1-10, January 12, 2010 [4] Musa Yusup Lada, Ismadi Bugis and Md Hairul Nizam Talib Simulation a Shunt Active Power Filter using MATLAB/Simulink The 4th International Power Engineering and Optimization Conf. (PEOCO2010)IEEE, Shah Alam, Selangor, pp. 371-375,MALAYSIA: 23-24 June 2010 [5] Keyur V. Patel, Priyank R Bhavsa Simulation & Analysis of Shunt Active Filter for Power Quality Improvement International Journal Of Current Engineering And Scientific Research (Ijcesr) ISSN (Print): 2393-8374, (Online): 2394-0697, Volume-2, Issue-8,pp. no-84-90, 2015 [6] Zahzouh Zoubir, Khochmane Lakhdar, Haddouche Ali A New Multilevel Active Power Filter Using Switches Meticulously Controlled International Journal of Power Electronics and Drive System (IJPEDS) Vol. 6, No. 1, pp. 168~177 ISSN: 2088-8694, March 2015 [7] Mr. Dipak Suresh Badgujar,Mr. Kiran. P. Varade.,C. Veeresh, Shunt Active Filter for Power Quality Improvement International Journal of Engineering Research and General Science Volume 3, Issue 4, pp no. 137-148, ISSN 2091-2730, July-August, 2015 2016, IRJET Impact Factor value: 4.45 ISO 9001:2008 Certified Journal Page 2941