Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit

Similar documents
Sensitivity studies on power transformer ferroresonance of a 400 kv double circuit

Ferroresonance Experience in UK: Simulations and Measurements

A Study on Ferroresonance Mitigation Techniques for Power Transformer

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance

Tab 2 Voltage Stresses Switching Transients

Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

FERRORESONANCE SIMULATION STUDIES OF TRANSMISSION SYSTEMS

Spectral analysis of voltages and currents during different modes of ferroresonance in switchgear

Modeling Ferroresonance Phenomena on Voltage Transformer (VT)

Frequency domain analysis of a power transformer experiencing sustained ferroresonance

FERRORESONANCE SIMULATION STUDIES USING EMTP

Appendix D Fault Levels

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum

STUDY ON THE NON LINEAR CHARACTERISTIC OF POWER TRANSFORMER AND THEIR EFFECT FERRORESONANCE SALIZAWATI BT HJ. SHAMSUDDIN

EDS FAULT LEVELS

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

Parameter Study of Ferro-Resonance with Harmonic Balance Method

FERRORESONANCE - its Occurrence and Control in Electricity Distribution Networks

Improving High Voltage Power System Performance. Using Arc Suppression Coils

IEEE Power Engineering Society 2001 Winter Meeting Columbus, OH. Panel Session. Data for Modeling System Transients

ELECTRICAL POWER TRANSMISSION TRAINER

148 Electric Machines

Modeling and electromagnetic transients study of two 1800MVA phase shifting transformers in the Italian transmission network

Validation of power plant transformers re-energization schemes in case of black-out by comparison between studies and field tests measurements

Comprehensive Study on Magnetization Current Harmonics of Power Transformers due to GICs

Three-Phase/Six-Phase Conversion Autotransformers

Protection of Electrical Networks. Christophe Prévé

ELECTRICAL POWER ENGINEERING

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Solving Customer Power Quality Problems Due to Voltage Magnification

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

Assessment of Saturable Reactor Replacement Options

IVE(TY) Department of Engineering. Electrical Machines 1. Electrical Machines 1. Hour 13. slide 1

Analysis of Switching Transients of an EHV Transmission Line Consisting of Mixed Power Cable and Overhead Line Sections

2. Current interruption transients

SYNCHRONISING AND VOLTAGE SELECTION

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

The Engineering Problem. Calculating GIC Flow through the EHV System

Resonances in Collection Grids of Offshore Wind Farms

Identification of network models parameters for simulating transients

G. KOEPPL Koeppl Power Experts Switzerland

2 Grounding of power supply system neutral

Analysis of a 405 km transmission line with series compensation

Demagnetization of Power Transformers Following a DC Resistance Testing

Energization of a no-load transformer for power restoration purposes: Impact of the sensitivity to parameters.

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

TECHNICAL BULLETIN 004a Ferroresonance

The power transformer

Modeling insulation in high-voltage substations

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

5. Black box arc modelling

86 chapter 2 Transformers

The Advantages and Application of Three Winding Transformers

A SPECIAL CASE OF FERRORESONANCE INVOLVING A SERIES COMPENSATED LINE

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

2 METHODOLOGY. The method of reactive power compensation, proposed in this research is suitable

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

Ferroresonances during Black Starts - Criterion for Feasibility of Scenarios

A Transmission Utility Approach to Electromagnetic Transient Analysis

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

GIS Disconnector Switching Operation VFTO Study

Fast Front Transients in Transformer Connected to Gas Insulated Substations: (White+Black) Box Models and TDSF Monitoring

1% Switchgear and Substations

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

IMPACT OF INRUSH CURRENTS AND GEOMAGNETICALLY INDUCED CURRENTS ON TRANSFORMER BEHAVIOR

General Approach for Accurate Evaluation of Transformer Resonance Effects

Exercises. 6 Exercises

Voltage Sag Index Calculation Using an Electromagnetic Transients Program

FAULT CURRENT LIMITER SURGE PROTECTION DEVICE FOR THE POWER GRID BASED UPON ZERO POWER CONSUMPTION CERAMIC FERRITE PERMANENT MAGNETS

Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies

DEVELOPMENT OF NUMERICAL ALGORITHMS FOR FERRORESONANCE MONITORING

Assessing P28 Guidelines for Renewable Generation Connections

Effects of Harmonic Distortion I

CONTENTS. 1. Introduction Generating Stations 9 40

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

EMT Model of the Sen Transformer for Fault Analysis Studies

ANEW, simple and low cost scheme to reduce transformer

Transformer Fault Categories

EEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Basic Operating Principles of Transformers

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION

Research Article Resistive Ferroresonance Limiter for Potential Transformers

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Simulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault of 10kV Power Grid

Code No: R Set No. 1

Simulation and Analysis of Ferroresonance in Power System

Innovative Science and Technology Publications

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment

SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS

Busbars and lines are important elements

Measurements for validation of high voltage underground cable modelling

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP

Transformer energisation after network blackout

Transcription:

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 4 kv Circuit Charalambos Charalambous 1, Z.D. Wang 1, Jie Li 1, Mark Osborne 2 and Paul Jarman 2 Abstract-- National Grid has performed in the past a number of switching tests on a circuit configuration which was known to exhibit ferroresonance. The aim of the tests was to establish the likelihood of ferroresonance and quantify the effect on switchgear due to the de-energisation of a power transformer attached to a long over head line circuit. This paper, describes and compares the modeling work carried out in ATP (commercially available software) with the field ferroresonance test recordings. The accomplishment of a suitable simulation model will allow sensitivity studies to be carried out to determine the degree of influence of different components and parameters on the ferroresonance phenomenon. Keywords: ATP, Ferroresonance, Power Transformer, Simulation Model, Field Tests. I. INTRODUCTION Certain circuit configuration of the UK transmission network provides an ideal environment for ferroresonance to occur. The possibility of Ferroresonance can be eliminated by the use of additional circuit brakers; however the economic justification needs to be carefully considered. Ferroresonance can be established when a transformer feeder circuit has been isolated, but continues to be energized through capacitive coupling to the energized parallel circuit [1]. A particular example is when one side of a double circuit transmission line connected to a transformer is switched out but remains capacitively energized, normally at a subharmonic frequency, because of coupling from the parallel circuit. Recovering from this condition requires the operation of a disconnector or earth switch on the resonating circuit, potentially resulting in arcing and damage, or switching off the parallel circuit resulting in an unplanned double circuit outage. 1. Charalambos Charalambous Zhongdong Wang and Jie Li are with the School of Electrical and Electronic Engineering, The University of Manchester, Manchester, M6 1QD, U.K (charalambos.charalambous@manchester.ac.uk, zhongdong.wang@manchester.ac.uk). 2. Mark Osborne and Paul Jarman are with National Grid, UK (mark.osborne@uk.ngrid.com, paul.jarman@uk.ngrid.com). Presented at the International Conference on Power Systems Transients (IPST 7) in Lyon, France on June 4-7, 27 Failing to detect or remove a ferroresonant condition can result in overheating of parts of the transformer as it is being repeatedly driven into magnetic saturation by the ferroresonance. Both instrument transformers and power transformers can be subject to ferroresonance. In 1998 National Grid performed a number of switching tests on a circuit configuration which was known to exhibit ferroresonance. This paper describes the modeling work carried out in ATP [2] (commercially available software) to reproduce the field ferroresonance tests performed. Furthermore, the accomplishment of a suitable simulation model will allow the authors to perform sensitivity studies to determine the degree of influence of different components and parameters on the ferroresonance phenomenon [3]. II. THE 4KV DOUBLE CIRCUIT CONFIGURATION A. Physical Circuit Description and Testing The Brinsworth/ Thorpe Marsh circuit was identified as a suitable circuit that could be induced to resonate, and that could be reasonably accessed. The purpose of the tests was to establish the likelihood of ferroresonance to occurring and the impact on the switchgear during quenching of the condition. [4]. Figure 1 illustrates a single line diagram of the Brinsworth/ Thorpe Marsh circuit arrangement. The length of the parallel overhead line circuit is approximately 37km and the feeder has a 1 MVA 4/275/13 kv power transformer. X33 OPEN Thorpe Marsh 4 kv X13 CLOSED X113 CLOSED X42 POW switching Mesh Corner 3 T1 OPEN Fig. 1. Single line diagram of the Brinsworth / Thorpe Marsh circuit arrangement It should be noted this is not a normal running arrangement, however to facilitate the testing this configuration was used on the day. The circuit equipment conditions prior to Ferroresonance testing are as follows: At Thorpe Marsh 4 kv substation side the disconnector X 33 was locked open and mesh corner 3 restored to service. At SGT1 SGT2 Cable 17 m Cable 17 m Brinsworth 275 kv

Brinsworth 275kV substation the circuit breaker T 1 is open. At Brinsworth 4kV substation all disconnectors and circuit breaker X 42 are in service. Point-on-wave (POW) switching was carried out on the Brinsworth/ Thorpe Marsh circuit using circuit breaker X 42 to induce Ferroresonance. This type of switching prevents switching overvoltage conditions and provides a degree of controllability to the tests. The circuit breaker was tripped via an external POW control device. After each switching operation the POW switching control was advanced by 1ms. At +3ms POW switching, a subharmonic mode ferroresonance was established, while at +11ms POW a fundamental mode ferroresonance was induced. The ferroresonance voltage and current waveforms available from field tests are illustrated in Appendix I.The waveforms presented correspond to the fundamental and subharmonic case. B. Simulation Model Description An ATP model has been developed to simulate the testing carried out on the circuit with the ultimate purpose to match field recordings that were available. Figure 2 illustrates a layout of the simulation model, which includes a description of the components of the model. The main components of the network are: a parallel overhead line circuit (37 km) modeled considering the transmission line characteristics (typical overhead line spacings for a 4kV double circuit) [7], a transformer model utilizing the BCTRAN transformer matrix mode. Saturation effects have been considered by attaching the non- linear characteristics externally in the form of a non-linear inductive element branch. U U AT P Draw Model COWL X33 6.3 m 9.12 m 7.12 m 37km 6.3 m 9.12 m 7.12 m X13 12.8m X113 21.5m X42 POW 3.8m 4.5m Committee type disconnectors HV BUSC Circuit Breaker SGT 2 HV BUSB HV BUSA HV-LV A HV-LV B HV-LV C BCTRAN model Transformer nonlinear characteristics Series and Shunt capacitances of windings Circuit Breaker Cable 17m Fig. 2. Layout of ATPDraw simulation Model, including a description of the components characteristics utilized Non-linear inductances can be modeled as a two slope piecewise linear inductances, with sufficient accuracy [2]. The slope in the saturated region above the knee reflects the air core inductance which is almost linear and low compared with the slope in the unsaturated region. The transformer magnetisation curve has been derived from manufacturer s TV BUS A TV BUSB TV BUSC TV-LV A TV-LV B TV-LV C LV BUSA LV BUSB LV BUSC T 1 data available and is illustrated by Table I. For cylindrical coil construction, it is assumed that the flux in the winding closest to the core will mostly go through the core, since there should be very little leakage. This winding is usually the tertiary winding, and is therefore best to connect the nonlinear inductance across the tertiary terminals. Although attaching the non-linear effect externally is an approximation, it is reasonably accurate for frequencies below 1 khz [5]. TABLE I TRANSFORMER MAGNETIZING CHARACTERISTICS Flux Linkage (Wb-turn) 7.18 48.77 7.85 52.2 8.35 55.27 19.37 58.52 35.4 61.77 78.48 65.2 222.9 65.92 5531.4 66.72 In low frequency transformer models is possible to represent each winding as one element. This does not come at the expense of accuracy. The model also comprises the interwinding and shunt capacitance elements, which have been calculated by employing mathematical methods taking into consideration the transformer equivalent circuit and the winding disc configurations types. C. Transformer Characteristics and Data The transformer characteristics available are tabulated in Table II. TABLE II TRANSFORMER CHARACTERISTICS Rating 1 MVA Type 4/ 275/13 kv (auto) Core Construction Five Limb Core Vector Yy Bolt main: No Bolt Yoke: No % Ratio 4&5 \ Y \ M 6\6\1 The transformer has been modeled in the BCTRAN module of ATP draw which utilizes an admittance matrix representation of the form [ I ] = [ Y ].[ V ] (1) and in transient calculations can be represented as di 1 1 [ ] = [ L] [ v] [ L] [ R][ i] (2) dt The elements of the matrices are derived from open circuit and short circuit tests that are made in the factory. The data used in this simulation model include impedances and losses averaged for the test results of 8 transformers rated at1 MVA (4/275/13 kv). Saturation effects have been modeled externally as previously described. The impedances and load losses can only be measured for

winding pairs, but the designed load capability for the tertiary winding of this 1 MVA design is only 6 MVA compared with the 1 MVA throughput for the HV and LV terminals. Thus the H-T and L-T losses and impedances would be measured at 6 MVA. For this simulation model data a common base load is chosen to be 1 MVA. In service, the tertiary load would never be above 6 MVA if it was loaded, so the total losses for three-winding loading would be not much greater than the H-L load loss at 1 MVA. The impedances and losses averaged for the test results of 8 transformers are tabulated in Table III. TABLE III TRANSFORMER SHORT CIRCUIT FACTORY DATA Impedance (%) Power (MVA) Loss (kw) HV-LV 15.8 1 1764 HV-TV 117.2 1 (6) 28677 (172.62) LV-TV 91.5 1 (6) 29875 (1792.5) Furthermore, the average no-load loss at rated voltage and frequency (measured on the tertiary) was 74.4 kw, whilst the average magnetizing current was.12% at 1 MVA base. Zero sequence data was not available and therefore zero sequence data that had been employed in this simulation model has been set equal to the positive sequence data. This is a reasonable assumption to make for a 5-limb core transformer with a tertiary winding. Provision of a tertiary winding on 5- limb cores drastically alters the zero sequence impedance, since zero sequence currents are able to circulate around the delta tertiary winding and thus balance those flowing into the primary winding [6]. Without a tertiary winding, the 5 limb core would have a higher zero sequence impedance (than the case where a tertiary winding is present) due to the 4 th and 5 th return limbs shunting the high reluctance zero sequence path (air path). The 4 th and 5 th return limbs of a 5 limb core are of much reduced section compared with the three main limbs. A zero sequence test at full load current would cause the 4 th and 5 th limbs to saturate and the core would turn into a 3-limb equivalent. In such a case the assumption of setting the zero sequence equal to the positive sequence data would not be valid. III. ATP MODEL VERIFICATION The circui t conditions described in section A of II, in terms of the disconnectors and circuit breakers status, were considered in the simulation model. Circuit breaker X 42, was utilized to carry out POW switching to initiate ferroresonance. It should be noted that the circuit breaker X 42 was tripped at a point in time (simultaneously for the three phases) that would ensure minimum voltages and energy transfer. This point has been marked as a reference point to start POW switching. Fundamental and subharmonic ferroresonance waveforms have been produced by simulation at a specific time. Table IV illustrates a comparison between the POW switching time corresponding to the field tests and to the simulation model. The ferroresonance voltage and current waveforms produced by simulation are also illustrated in Appendix I. POW switching control (time) POW switching control (time) TABLE IV P.O.W SWITCHING TIME COMPARISON Field Waveform Simulation Tests Description +3 ms +3.2 ms Subharmonic Mode +11 ms +12.6 ms Fundamental Mode The following set of figures illustrates a comparison of a sector of the final steady state ferroresonance mode waveforms produced by ATP and those available from field recordings, for the fundamental and subharmonic case, for each one of the 3 phases (R, Y, and B). Figures 4-9 compare the simulation results with the field results obtained for voltage and current corresponding to Phase R, Y and B respectively, for the fundamental mode ferroresonance. Voltage Magnitude (kv) 3 25 2 15 1 5-5 -1-15 -2-25 2 2.5 2.1 2.15 2.2 _Phase R _Phase R Fig. 4. Comparison of Fundamental Mode Ferroresonance- Section of Voltage waveform R phase 25 2 15 1 5-5 -1-15 -2-25 2 2.5 2.1 2.15 2.2 Fig. 5. Comparison of Fundamental Mode Ferroresonance- Section of Current waveform R phase

Voltage Magnitude (kv) 4 3 2 1-1 Figures 1-15 compare the simulation results with the field results obtained for voltage and current corresponding to phase R, Y and B respectively, for the subharmonic mode ferroresonance. 12 1 8-2 -3-4 2 2.5 2.1 2.15 2.2 _Phase Y _Phase Y Fig. 6. Comparison of Fundamental Mode Ferroresonance- Section of Voltage waveform Y phase 3 Voltage R-Phase (kv) 6 4 2-2 -4-6 -8-1 2 1 Fig. 1. Comparison of subharmonic Mode Ferroresonance- Section of Voltage waveform R phase 5 4-1 3-2 -3 2 2.5 2.1 2.15 2.2 Fig. 7. Comparison of Fundamental Mode Ferroresonance- Section of Current waveform Y phase 25 2 15 1 Current R phase (A) 2 1-1 -2-3 -4-5 Fig. 11. Comparison of subharmonic Mode Ferroresonance- Section of Current waveform R phase 15 Voltage Magnitude (kv) 5-5 -1-15 -2 Voltage Y phase (kv) 1 5-5 -25 2 2.5 2.1 2.15 2.2-1 Fig. 8. Comparison of Fundamental Mode Ferroresonance- Section of Voltage waveform B phase 25 2 15-15 Fig. 12. Comparison of subharmonic Mode Ferroresonance- Section of Voltage waveform Y phase 8 1 6 5-5 -1-15 -2-25 2 2.5 2.1 2.15 2.2 Fig. 9. Comparison of Fundamental Mode Ferroresonance- Section of Current waveform B phase Current (A) 4 2-2 -4-6 -8 Fig. 13. Comparison of subharmonic Mode Ferroresonance- Section of Current waveform Y phase

1 Voltage B phase (kv) 8 6 4 2-2 -4-6 -8-1 Field Tests Fig. 14. Comparison of subharmonic Mode Ferroresonance- Section of Voltage waveform B phase TABLE VI COMPARISON OF FIELD AND SIMULATION RESULTS (SUBHARMONIC) Peak 9 1 5 Peak 45 42 38 48.29 6 37.6 9.28 8.997 8.72 Peak 75 95 45 Peak 35 5 35 5.64 69.41 41.5 5.6 9.3 5.5 5 Current B phase (A) 4 3 2 1-1 -2-3 -4 The minor differences on the voltage and current waveforms that appear on the illustrated Figures can also be seen on the frequency analysis waveforms illustrated by Figures 16 and 17, for the fundamental and subharmonic case respectively. Figures 16 and 17 compare the frequency content of voltage waveforms of the field recording results and the produced simulation results for one phase. -5 Fig. 15. Comparison of subharmonic Mode Ferroresonance- Section of Current waveform B phase The figures presented clearly illustrate that the ATP model can replicate the field recordings with a significant degree of accuracy, both in the fundamental and subharmonic case. For the subharmonic case the ferroresonance condition had a frequency content of 16 2/3 Hz. Table VI tabulates the peak and rms voltage and current values corresponding to field recordings and to simulation results. Fig. 16. Comparison of Frequency content of voltage waveforms (Fundamental Y phase ) TABLE V COMPARISON OF FIELD AND SIMULATION RESULTS (FUNDAMENTAL) Peak (B) Peak 21 191 33 315 18 173 Peak 19 151 325 33 19 167 Peak 2 22 19 62.56 7 58.93 145 22 14 46.45 7.52 45.79 Fig. 17. Comparison of Frequency content of voltage waveforms (subharmonic Y phase) For the fundamental case the ferroresonance condition had a frequency content of 5 Hz. Table V tabulates the peak and rms voltage and current values corresponding to field recordings and to simulation results. IV. CONCLUSIONS Ferroresonance is a low frequency phenomenon that can occur when a transmission line connected to a transformer is switched out with the parallel circuit still energised. The complex UK network is such that a few power transformers are exposed to ferroresonance on mesh corner and circuit tee connections, mainly because of historical design precedents.

A reliable ATP based simulation model can be achieved when the parameters of the system and transformer are known or can be derived with reasonable accuracy. The graphical results presented in this paper clearly demonstrate the capability of the simulation model to reproduce the field recordings with a significant degree of accuracy, both in the fundamental and subharmonic case. The development and validation of this simulation model with the field recordings available allowed the authors to perform a number of sensitivity studies that deal with the effect on ferroresonance of point on wave (P.O.W) switching, transmission line and core losses and the interaction between these variables. The sensitivity studies investigate the effect the above described interactions have on energy transfer in the transformer, on the magnitude of ferroresonant voltages and currents and the duration of overvoltages, etc. The findings are the topic of a scientific paper submitted [3]. Lastly this simulation model will form the benchmark and will produce the input data of a detailed (topologically and geometrically accurate) transformer model that would enable the understanding of magnetic field analysis (heating and fluxing) within a transformer under ferroresonance and its degrading mechanisms. V. ACKNOWLEDGEMENT The authors gratefully acknowledge the EPSRC RAIS funding scheme and National Grid for the financial support. The authors also acknowledge the technical support provided by National Grid. 3 2 1-1 -2-3 Fundamental mode ferroresonance R phase Fundamental mode ferroresonance Y phase Fundamental mode ferroresonance B phase 15 155 16 165 17 175 18 185 19 195 2 Fig. 19. Fundamental Mode Ferroresonance Current (Field Recordings) 2 15 1 5-5 -1-15 -2 Sub-harmonic mode ferroresonance R phase Sub-harmonic mode ferroresonance Y phase Sub-harmonic mode ferroresonance B phase 12 13 14 15 16 17 18 19 Fig. 2. Subharmonic Mode Ferroresonance Voltage (Field Recordings) 1 8 6 4 2-2 -4-6 -8-1 Sub-harmonic mode ferroresonance R phase Sub-harmonic mode ferroresonance Y phase Sub-harmonic mode ferroresonance B phase 12 13 14 15 16 17 18 19 Fig. 21. Subharmonic Mode Ferroresonance Current (Field Recordings) 6 4 2-2 -4-6 R_Phase Voltage Y_Phase Voltage B_Phase Voltage 2.5 2.55 2.6 2.65 2.7 2.75 2.8 2.85 2.9 2.95 3 Fig. 22. Fundamental Mode Ferroresonance Voltage () VI. REFERENCES 3 R_Phase Current Y_Phase Current B_Phase Current [1] National Grid Seven Year statement Control of Ferroresonance Technical Guidance Note, December 24, National Grid, UK, www.nationalgrid.com/sys [2] ATP Rule Book and Theory Book, Can/Am EMTP User Group, Portland, OR, USA, 1997. [3] C. Charalambous, ZD Wang, Mark Osborne, Paul Jarman, Sensitivity studies on a power transformer model for ferroresonance on a 4 kv Circuit. IET Proceedings in Generation, Transmission and Distribution (Under Review) [4] Ferroresonance Tests on Brinsworth-Thorpe Marsh 4 kv circuit, Technical Report TR (E) 389, Issue 1, July 21, National Grid, UK.. [5] Juan A. Martine-Velasco, Bruce A. Mork, Transformer Modeling for Low Frequency Transients The state of the Art, IPST 23 New Orleans, USA. [6] A.C Franklin, D.P Franklin, The J&P Transformer Book, 12th Revised edition, Elsevier Science & Technology [7] British Electricity International, Modern Power Station Practice, EHV Transmission, Volume K, Pergamon Press 2 1-1 -2-3 2.5 2.55 2.6 2.65 2.7 2.75 2.8 2.85 2.9 2.95 3 Fig. 23. Fundamental Mode Ferroresonance Current () R_Phase Voltage Y_Phase Voltage B_Phase Voltage 2 15 1 5-5 -1-15 -2 2.5 2.6 2.7 2.8 2.9 3 3.1 3.2 3.3 3.4 3.5 Fig. 24. Subharmonic Mode Ferroresonance Voltage () 5 4 3 2 1-1 -2-3 -4-5 VII. APPENDIX Fundamental mode ferroresonance R phase Fundamental mode ferroresonance Y phase Fundamental mode ferroresonance B phase 15 155 16 165 17 175 18 185 19 195 2 Fig. 18. Fundamental Mode Ferroresonance Voltage (Field Recordings) R_Phase Current Y_Phase Current B_Phase Current 1 8 6 4 2-2 -4-6 -8-1 2.5 2.6 2.7 2.8 2.9 3 3.1 3.2 3.3 3.4 3.5 Fig. 25. Subharmonic Mode Ferroresonance Current ()