Power Quality Enhancement and Mitigation of Voltage Sag using DPFC

Similar documents
Enhancement of Power Quality in Multi Feeders by using MC-DPFC

MITIGATION OF VOLTAGE SAG AND SWELL FOR POWER QUALITY IMPROVEMENT USING DISTRIBUTED POWER FLOW CONTROLLER

Power Quality Improvement And Mitigation Of Voltage Sag And Current Swell Using Distributed Power Flow Controller

Mitigation of Voltage Sag and Swell Using Distributed Power Flow Controller

A Fuzzy based MC-DPFC for Enhancement of Power Quality in Transmission Line

Mitigation of Voltage Sag and Swell by Ant Colony Optimization Technique using DPFC

Performance Of Distributed Power Flow Controller (DPFC) Under Fault Condition

Modeling and Analysis of DPFC to Improve Power Quality

SIMULATION OF DISTRIBUTED POWER FLOW CONTROLLER FACTS DEVICE IN VOLTAGE SAG AND SWELL MITIGATION

Designing Of Distributed Power-Flow Controller

Improvement of Voltage Profile of a Transmission System Using D-Facts

A Modified Control Method For A Dual Unified Power Quality Conditioner

A COMPARATIVE STUDY ON UPFC AND DPFC TOWARDS LOW HARMONIC DISTORTION

Designing and Control of Converters used in DPFC for Mitigation of Voltage Sag and Swell In Transmission Line

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Power Quality Improvement in Distribution System Using D-STATCOM

International Journal of Scientific & Engineering Research, Volume 6, Issue 8, August ISSN

Harmonics Reduction and Power Quality Improvement by using Multilevel DPFC

FUZZY CONTROLLED DSTATCOM FOR HARMONIC COMPENSATION

Improvement of Power Quality Using a Hybrid Interline UPQC

Improvement of System Reliability & Power Transfer Capability using Distributed Power- Flow Controller (DPFC)

FUZZY LOGIC CONTROLLER BASED UPQC FOR POWER QUALITY MITIGATION IN GRID CONNECTED WIND ENERGY CONVERSION SYSTEM

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

DESIGN OF A HYBRID ACTIVE FILTER FOR HARMONICS SUPPRESSION WITH VARIABLE CONDUCTANCE IN INDUSTRIAL POWER SYSTEMS USING FUZZY

Power Quality enhancement of a distribution line with DSTATCOM

Power Control Scheme of D-Statcom

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Application of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System

HARMONIC COMPENSATION USING FUZZY CONTROLLED DSTATCOM

Reduction of Voltage Imbalance in a Two Feeder Distribution System Using Iupqc

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Published by: PIONEER RESEARCH & DEVELOPMENT GROUP ( 1

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Voltage Flicker Compensation using STATCOM to Improve Power Quality

Fuzzy Logic Control of APF for Harmonic Voltage Suppression in Distribution System

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

Power Quality Improvement of Unified Power Quality Conditioner Using Reference Signal Generation Method

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality

Fuzzy Logic Controller Based Three-phase Shunt Active Filter for Line Harmonics Reduction

STATCOM WITH POD CONTROLLER FOR REACTIVE POWER COMPENSATION Vijai Jairaj 1, Vishnu.J 2 and Sreenath.N.R 3

Damping of Sub-synchronous Resonance and Power Swing using TCSC and Series capacitor

Fuzzy Controlled DSTATCOM for Voltage Sag Compensation and DC-Link Voltage Improvement

A RELATIVE STUDY ON UPFC AND DPFC ON THE BASIS OF TOTAL HARMONICS DISTORTION

IJCSIET--International Journal of Computer Science information and Engg., Technologies ISSN

LOW FREQUENCY OSCILLATION DAMPING BY DISTRIBUTED POWER FLOW CONTROLLER WITH A ROBUST FUZZY SUPPLEMENTARY CONTROLLER

Power System Stability Enhancement Using Static Synchronous Series Compensator (SSSC)

Increasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC)

Compensation of Unbalanced Sags/Swells by Single Phase Dynamic Voltage Restorer

Power Flow Control by Using DPFC

Intelligence Controller for STATCOM Using Cascaded Multilevel Inverter

Application of Distribution Static Synchronous Compensator in Electrical Distribution System

VOLTAGE SAG COMPENSATION USING UNIFIED POWER FLOWER CONTROLLER IN MV POWER SYSTEM USING FUZZY CONTROLLER

Investigation of D-Statcom Operation in Electric Distribution System

A NOVEL APPROACH ON INSTANTANEOUS POWER CONTROL OF D-STATCOM WITH CONSIDERATION OF POWER FACTOR CORRECTION

Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition

B.Tech Academic Projects EEE (Simulation)

Design and Development of DVR model Using Fuzzy Logic Controller for Voltage Sag Mitigation

SIMULATION OF D-Q CONTROL SYSTEM FOR A UNIFIED POWER FLOW CONTROLLER

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Voltage Sags in Distribution Systems with Induction Motor Loads Fed by Power Converters and Voltage Mitigation using DVR and D-STATCOM

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

Voltage Improvement Using SHUNT FACTs Devices: STATCOM

UNIFIED POWER QUALITY CONDITIONER IN DISTRIBUTION SYSTEM FOR ENHANCING POWER QUALITY

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Grid-Voltage Regulation Controller: IUPQC

Mitigation of Fault in the Distribution System by using Flexible Distributed Static Compensator (FD-STATCOM)

Improvement of Power Quality Using a Hybrid UPQC with Distributed Generator

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

Volume I Issue VI 2012 September-2012 ISSN

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

Mitigation of Voltage Sag/Swell Using UPQC

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Single Phase Shunt Active Filter Simulation Based On P-Q Technique Using PID and Fuzzy Logic Controllers for THD Reduction

ANALYSIS OF UNIFIED POWER QUALITY CONDITIONER DURING VOLTAGE SAG AND SWELL CONDITIONS

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1

IMPROVEMENT OF POWER QUALITY USING CUSTOM POWER DEVICES

Improving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC)

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side

Power Quality and the Need for Compensation

Neural Network Based Distributed Powerflow Controller For Mitigating Voltage Sag And Swell In A Transmission System

Investigation of negative sequence injection capability in H-bridge Multilevel STATCOM

Multi-Pulse Voltage Source Converter Statcom For Voltage Flicker Mitigation

Performance of DVR under various Fault conditions in Electrical Distribution System

Fuzzy Controllers for Boost DC-DC Converters

Direct and Indirect Control Strategies of DSTATCOM Power Factor Controller

ISSN Vol.07,Issue.21, December-2015, Pages:

IJESR/Nov 2012/ Volume-2/Issue-11/Article No-21/ ISSN International Journal of Engineering & Science Research

FUZZY BASED SMART LOAD PRIMARY FREQUENCY CONTROL CONTRIBUTION USING REACTIVE COMPENSATION

ISSN Vol.04,Issue.16, October-2016, Pages:

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Performance of Indirectly Controlled STATCOM with IEEE 30-bus System

Improved Active Power Filter Performance for Renewable Power Generation Systems

SIMULATION OF DSTATCOM FOR POWER FACTOR IMPROVEMENT

Transcription:

Power Quality Enhancement and Mitigation of Voltage Sag using DPFC M. Bindu Sahithi 1, Y. Vishnu Murthulu 2 1 (EEE Department, Prasad V Potluri Siddhartha Institute of Technology, A.p, India) 2 (Assistant Professor, EEE Department, Prasad V Potluri Siddhartha Institute of Technology, A.P, India) ABSTRACT: The Distributed power flow controller is mainly used to control the power flow and also used to mitigate voltage and current waveform deviations and improves the quality of power in the matter of few seconds. The structure of DPFC is identical to the UPFC. In DPFC the dc capacitor link between series and shunt converter is terminated. DPFC consists of a single shunt converter and several small independent single phase series converters are employed. The operating function of shunt converter is like a STATCOM and series converter employs a Distributed- FACTS concept. The exchange of active power between the series and shunt converter is through the transmission line. The DPFC has the ability to control the transmission line parameters such as line impedance Z, transmission angle Ө, and bus voltage magnitude. The problems obtained with power quality issues such as voltage sag and swell can be mitigated by using DPFC. The DPFC is installed in between transmission lines and connected to a single machine infinite bus power system which is simulated in MATLAB/SIMULINK in order to determine the performance of DPFC in the power system. Key words: Power quality improvement, Mitigation of voltage and Current waveform deviations, Distributed power flow controller. I INTRODUCTION magnetizing currents are obtained with the starting of large machines. Power electronic based system is used to control the ac transmission system parameters and to increase power transfer capability and also to improve the power quality. The most serious threats for sensitive electrical equipment in grids are voltage sag and swell. These voltage sag and swell are mitigated and improves the power quality by using DPFC. In this paper DPFC is represented as a new FACTS device which is determined from UPFC and has the same controlling capability but with less cost and higher reliability. DPFC is used to compensate the unbalanced voltage and currents in transmission system. It can also be used to compensate zero and negative sequence unbalanced currents in transmission line. The structure of DPFC is derived from the UPFC and has the same control capability. The DPFC consists of single shunt converter and multiple small independent series converter. The operating performance of shunt converter is like a STATCOM.The main function of shunt converter is to inject a constant third harmonic component current into a transmission line. The series converter consists of PWM controlling technique and it is a single phase converter. The main function of series converter is to maintain capacitor dc voltage by the use of third harmonic frequency components. Within the DPFC each converter consists of own DC capacitor in order to maintain the required dc voltage. DPFC also contains a high pass filter and shunt connected to the line in order to extract the harmonics. The power system mainly incorporates with generation, transmission, distribution, and consumption. The power system mainly deals with the problem i.e. increase in power demand and also with the power quality related problems such as voltage, current & frequency distortions. Electrical apparatus will be affected due to power quality related problems. The power quality problems are obtained due to appearance of short circuits in the grid, to faster switching operations, high inrush ISSN: 2231-5381 http://www.ijettjournal.org Page 265

required amount of voltage is generated by series converter at the third harmonic frequency, and the active power is absorbed from harmonic components. The active power exchange between the shunt and series converter is shown in the fig. By assuming a lossless converter, the active power generated at fundamental frequency is equal to the active power absorbed at third harmonic frequency. Fig.1: Single line diagram of DPFC II. DPFC OPERATING PRINCIPLE The main advantage of DPFC is elimination of DClink between shunt and series converter and using third harmonic current to exchange the active power Active power exchanged in lines with eliminated DC link: In DPFC the dc & ac terminal of shunt converter and series converter are connected to the transmission line. The exchange of active power between two converters can be done through transmission line, as the dc link is eliminated. The power exchange in the DPFC is done based on theory which is nothing but power theory of non sinusoidal components. According to Fourier series analysis, the sum of nonsinusoidal voltage or current can be represented as sum of the sinusoidal components at different frequencies with different amplitude. The obtained active power from non-sinusoidal voltage and current can be defined as the product of voltage and current mean value. All the cross product with different frequencies and their integrals are zero; the active power can be represented by the equation: Fig.2: Active power exchange between DPFC converters By the selection of third harmonic component: The current flowing in a transmission line at higher frequencies provides high impedances which results raise in voltage level of series converters. The third harmonic current is the smallest harmonic order frequency with less impedance so the obtained voltage level of converters is also less. The third harmonic current component is similar to the zerosequence current and the zero-sequence current in three phase system can be naturally blocked in Y Δ transformers. Eq (1) Where and are the i th harmonic voltage and current and is the angle between the voltage and current at same frequency. The above equation expresses the active power at different frequency components. The active power generated from the grid at fundamental frequency is absorbed by the shunt converter and injects current back into the grid at a third harmonic frequency. The obtained third harmonic current will flows through the transmission line. Due to the amount of active power required from shunt converter at fundamental frequency, the Fig.3 : transformer In power system the voltage levels can be changed by the use of Y Δ transformers. Extra filter is not required in order to prevent harmonic leakage current. Therefore highpass filter is eliminated. The main advantage of using third harmonic component is active power can be exchanged, grounding the Y Δ transformers in order to route harmonic current into a network. The 3 rd, 6th, 9th harmonic frequencies these are all zero sequence harmonic frequencies. These ISSN: 2231-5381 http://www.ijettjournal.org Page 266

harmonic frequencies can also be used to exchange active power. The transmission line capacity can be determined by line impedance; the impedance of transmission line is inductive and is proportional to the frequency. Therefore higher frequency of transmission line will cause high impedance. The lower frequencies are offered by the zero sequence harmonic components, Therefore third harmonic component is selected. Advantages of DPFC: The DPFC has some advantages when compared to UPFC, the following advantages are: two frequency voltage sources. The multiple number of series converters is represented by single large converter with the voltage, which is equal to the sum of the voltages for all series converter.. Control strategies of DPFC: There are three control strategies they are as follows: Central control Series control Shunt control 1) Low cost: In DPFC there is no phase to phase voltage isolation required by series converter. Each converter power rating can be easily produced in series production line. 2) Higher control capability: The DPFC can control impedance of line Z, transmission angle Ө and bus voltage magnitude these are all the parameters of power system. DPFC consists of higher control capability. Therefore DPFC can be used to improve system stability and can also be used to improve the power quality related problems such as voltage sag and swell, low frequency power oscillation damping, balancing asymmetry etc. 3) Higher reliability: Due to the redundancy of the series converter gives an improved reliability of the converter. Since both the shunt and series converter are independent. If the failure has been occurred at one converter another converter will not influenced. III. STEADY STATE ANALYSIS OF DPFC In this following section, the steady-state analysis and also the behavior of the DPFC are analyzed, and the DPFC controlling capability is specified in parameters of the network and the DPFC. To simplify the performance of DPFC, the converters of DPFC are placed in series with controllable voltage sources. Each converter in DPFC generates the voltage at two different frequencies at the fundamental and third harmonic frequency; here in this paper we are assuming that the converters and the transmission line are lossless, the total generated active power will be zero at the Fig.4: DPFC control block diagram a) Central control: The main function of central controller it controls both series and shunt controller and sends the reference signals to both controllers. b) Series control: In DPFC each single phase series converter has its own control through the line. The inputs of series controller are capacitor voltages, line current and series voltage reference in rotating dq-frame. Series controller consists of low pass filter and 3 rd pass or high band pass filter is required inorder to create fundamental and third harmonic current. Series controller also consists of two single-phase phase lock loop (PLL) which is used to maintain the frequency and phase information from network. The series controller maintains the capacitor dc voltage of its own converter by utilizing third harmonic frequency components and to generate voltage at fundamental frequency that is obtained by the central control. ISSN: 2231-5381 http://www.ijettjournal.org Page 267

IV. POWERQUALITY ENHANCEMENT Fig.5: Block diagram of series converter control c) Shunt control: Shunt converter is operated like STATCOM. The shunt converter consists of one three phase converter which is connected back to back to a single phase converter that is to a series converter. The active power from the grid is absorbed by three phase converter at fundamental frequency and controls the dc capacitor voltage of three phase and single phase converter. The main objective of shunt control is to inject a third harmonic current which is constant is injected into the transmission line inorder to provide active power for the series converter. The system model consists of a source which is of three phase is connected to the non linear three phase RLC load which is connected through a parallel transmission lines (i.e, line1 and line2) which are of same line length. The DPFC is incorporated in between the transmission lines, the shunt converter is connected in parallel to the transmission line through a Y Δ transformer and series converter is connected in series to the transmission line. The system parameters are listed in TABLE. In order to simulate the dynamic performance of DPFC a fault is created near the load. The time duration of fault is 0.5sec (500-1000milli seconds). In this system the fault occur between the time 500ms to 1500ms. During this fault time the voltage is goes to sag position as shown in figure. The voltage magnitude is reduced by 0.65 percent of its nominal value during this fault time. Three Phase Source Rated Voltage 230 KV Rated Power/Frequency 100MW/60 HZ X/R 3 Short circuit capacity 11000 MW Transmission line Resistance 0.012 pu/km Inductance/Capacitance Reactance 0.12/0.12 pu/km Length of Transmission line 100 km Shunt converter 3-phase Nominal power 60 MVAR DC Link capacitor 600 µf Coupling Transformer(Shunt) Nominal power 100 MVA Rated Voltage 230/15 KV Series Converter Rated Voltage 6 KV Nominal power 6MVAR Three phase fault Type ABC-G Ground resistance 0.01 ohm Table: Simulation system parameters V. FLC Implementation in DPFC Fig.6: Block diagram of shunt converter control Fuzzy logic controllers are formed by simple rules such as If A and B then C. These rules are defined by persons experience and also by the Knowledge of systems behaviour. The system performance is improved by these rules. Each rule defines one membership function which is the function of FLC. More control mechanism of FLC can be provided by the number of membership functions. In this work, the input of the fuzzy system consisting of 7 membership functions, so the fuzzy system rules is ISSN: 2231-5381 http://www.ijettjournal.org Page 268

formed in 49 rules. Based upon these rules the controller performs its functions. The basic rule such as if-then rule are defined as If (error is small and rate of change of error is small) then output. The signals error and change of error or error rate is described as crisp variables in the FLC such as large negative (LN), Large positive (LP), medium negative (MN), Medium positive (MP), Small negative (SN), Very small (VS), Small positive (SP). 3. Construct the rule base (initialization) 4. Convert crisp input data to fuzzy values using the membership functions (fuzzification) 5. Evaluate the rules in the rule base (inference) 6. Combine the results of each rule (inference) 7. Convert the output data to non-fuzzy values (defuzzification). Results These are shown in Fig.7. The input values of the fuzzy controller are connected to the output vales of fuzzy controller i.e. crisp values by the ifthen rules. The relationship between the input and the output values can be obtained easily by using Center of gravity type of inference method. The output values or fuzzy values are characterized by memberships and named as crisp variables such as Zero(Z), negative big (NB), negative medium (NM), negative small (NS), positive medium (PM), positive small (PS) and positive big (PB). The membership functions of output variables and the FLC rules are shown in Table I e/ e LP MP SP VS SN MN LN LP PB PB PB PM PM PS Z MP PB PB PM PM PS Z NS SP PB PM PM PS Z NS NM VS PM PM PS Z NS NM NM SN PM PS Z NS NM NM NB MN PS Z NS NM NM NB NM LN Z NS NS NM NB NB NB Fig.5.1: Output Voltage during fault condition Figure 5.1 shows the simulation result for output voltage during fault. In this fault period a sag condition occurs in the output voltage. Fig.5.2: Output Current during Fault Condition During this fault time the load current raises its magnitude around 1.2% per unit as shown in figure Fuzzy logic algorithm: 1. Defines the terms and also linguistic variables (initialization) 2. Construct the membership functions (initialization) ISSN: 2231-5381 http://www.ijettjournal.org Page 269

Fig.5.3: Output voltage compensated by DPFC controller Fig.5.6: THD of load voltage with DPFC (pi controller) Now the PI controller is replaced with fuzzy controller the THD value is reduced to 3.65% Fig.5.4: Compensated Output Current by DPFC controller THD value for a system is 12.36% and it is reduced by using DPFC controller Fig.5.7: THD of load voltage with DPFC (Fuzzy controller) S.NO Name THD value 1 Load voltage without DPFC 12.36% Fig.5.5: THD of load voltage without DPFC (PI controller) A PI controller based DPFC controller is used for that system and now the THD value is reduced to 3.88% 2 Load voltage with DPFC(PI) 3 Load voltage with DPFC(Fuzzy) 3.88% 3.65% TABLE 1: Comparison of THD values THD values for load voltage without DPFC, load voltage with DPFC using PI controller and load with DPFC using fuzzy controller are compared and listed in above table. ISSN: 2231-5381 http://www.ijettjournal.org Page 270

Future Scope: The DPFC is a new FACT device and has lower cost and more reliable when compared to the UPFC. Moreover, the DPFC also require modification in future research orientation, which are classified as Series converter weight reduction: The series converters on transmission line are huge which results in extra pressure to the towers. So a light weight series converter unit is desirable. Third harmonic current management: The third harmonic component within the DPFC leads to extra losses in transformers and in transmission lines. In this project third harmonic current within the DPFC is set at a constant value. The magnitude of third harmonic current can be managed by the amount of active power required. So the losses of the DPFC can be reduced. Communications: Since the series converters operate outdoors, wireless or PLC is required for communication purpose between the central control and series control. The communication should be reliable to continue the operation if any disturbances have been occurred such as lightening or storm. CONCLUSION A concept to controlling the power quality issues i.e. DPFC is implemented in this paper. The proposed theory of this device is mathematical formulation and analysis of voltage dips and their mitigations for a three phase source with linear load. In this paper we also proposed a concept of fuzzy logic controller for better controlling action. As compared to all other facts devices the DPFC based Fuzzy has effectively control all power quality problems and with this technique we get the THD as 3.65% and finally the simulation results are shown above. REFERENCES [1]. Ahmad Jamshidi, S. Masoud Barakati, and M. Moradi Ghahderijani, Impact of Distributed Power Flow Controller to Improve Power Quality Based on Synchronous Reference Frame Method, IACSIT International Journal of Engineering and Technology, Vol. 4, No. 5, October 2012. [2]. Ahmad Jamshidi, S. Masoud Barakati, and Mohammad Moradi Ghahderijani, Power Quality Improvement and Mitigation Case Study Using Distributed Power Flow Controller IEEE confrence 2012. [3]. L. Thakre Factor Affecting Characteristics of Voltage s Serbian Journal of Electrical Eng. Vol. 5, No.1, pp. 171-182, May2008. [4]. J. R. Enslin, Power mitigation problems, IEEE Int. Symp. Industrial Electronics (ISIE 98), Vol. 1, pp. 8 20. 1998. [5]. A. Chandra, A review of active filters for power quality improvement, IEEE Trans. Ind. Electron. pp. 8 20.Vol. 46, No. 5, pp. 960 971, 1999. [6]. M. A. Hannan, member IEEE, presents PSCAD/EMTDC Simulation of Unified Series-Shunt Compensator for Power Quality Improvement, IEEE Transactions on Power Delivery, Vol. 20, No. 2, April 2005. [7]. A. L. Olimpo Modeling and analysis of custom power systems by PSCAD/EMTDC, IEEE Trans. Power Delivery, Vol. 17, No.1, pp. 266 272, Jan. 2002. [8]. P. Pohjanheimo published a paper on Steady state modeling of custom power components in power distribution networks, IEEE Power Engineering Society Winter Meeting, Vol. 4, pp. 2949 2954,Jan. 2000, [9]. Dalibor Cevoric published a topic of A FACTS Device: Distributed Power Flow Controller IEEE Transaction on Power Electronics, Vol.25, No.10, October 2010 [10]. Braham Frreira posted a paper on DPFC control during shunt converter failure in IEEE Transaction on Power Electronics, 2009. [11]. Yuan, Zhihui, Sjoerd W. H. de Haan, JanBraham Ferreira, and Dalibor Cvoric. "A FACTS Device: DistributedPower-Flow Controller(DPFC)",IEEE Transactions on Power Electronics, 2010 [12]. A. Bhattacharya and C. Chakraborty, A shunt active power filter with enhanced performance using ANN-based predictive and adaptive controllers, IEEE Trans. Ind. Electron., Vol. 58, No. 2, pp. 421 428, Feb. 2011. [13]. Alok Agarwal,Rajul Misra and Vipul Agarwal, Fuzzy Logic based power oscillation damping through Unified power flow controller in Power System, IT IJEIE, Vol.1, No.1,pp.11-15,Jan 2011 [14]. Comparison between Conventional PID and Fuzzy Logic Controller for Liquid Flow Control: Performance Evaluation of Fuzzy Logic and PID Controller by Using MATLAB/Simulink by Gaurav, Amrit Kaur, International Journal of Innovative Technology and Exploring Engineering (IJITEE) ISSN: 2278-3075, Vol-1, Issue-1, June 2012 Mandava Bindu Sahithi received the B.Tech degree in Electrical and Electronics Engineering from Vijaya institute of technology for women in 2014 and pursuing M.Tech in Power system control and Automation at Prasad V Potluri Siddhartha Institute of Technology. Research includes Power Quality improvement using FACTS device. Y.Vishnu Murthulu received the AMIE (ELECTRICAL) and M.Tech degree in Electrical and Electronics Engineering from the University of JNTU college of Engineering Hyderabad, Telengana respectively. ISSN: 2231-5381 http://www.ijettjournal.org Page 271