AEA300R22S / AEA400R22S-1 Power Supply Product Specification

Similar documents
AED500H22S Power Supply Product Specification. An APM Electronics USA, Inc. Power Supply Specification For ERP1U Power Supply

SSD3000 MODULE 280 WATT 12V FRONT END 8.66 x 1.99 x x 50.5 x 40mm

IX-500R8PD8. Redundant Power Supply ( PS2 MINI - 500W+500W ) SPECIFICATION. Revision: 1.0

IS -500RSH1UP. Redundant Power Supply ( 1U- 500W ) SPECIFICATION. Revision: 1.0

SPECIFICATION. SilverStone Zeus ST75ZF. Switching Power Supply. With Active PFC PS/2 750W

Switching Power Supply SPECIFICATION

DA850. The all around power DECATHLON

OP650 -P. Single rail stepping up to a higher gear OP SERIES

PET NA FEATURES DESCRIPTION DATA SHEET

SPECIFICATION SilverStone ST30NF for Standard Switching Power Supply With Active PFC PS/2 Fanless 300W

NIGHTJAR SERIES SST-ST45NF. Optimum fan-less power supply with stability and silence

SFX Form Factor SST-SX650-G SST-SX500-G. The standard SFX power supply benchmark

SPECIFICATION ARP

Product Specification

TC-600PD2. Switching Power Supply ( 600W PS2 ATX12V ) SPECIFICATION. Revision: 1.0

Matrix Power Company MH xxx-va series Specification Document

DSA150 Series. xxx Series. 150 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125.

ST-250MAK-05E. Switching Power Supply SPECIFICATION

SPECIFICATION REDUNDANT POWER SUPPLY HOT-SWAPPABLE 370W+370W

TC-750PD8. Switching Power Supply ( PS2 ATX750W 8 0 PLU S ) SPECIFICATION. Revision: 1.0

DSR120 Series. xxx Series. 120 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details

SPECIFICATION. SilverStone OLYMPIA OP1000 Switching Power Supply Active PFC

SPECIFICATION SWITCHING POWER SUPPLY BPS-300SP/2U 6-OUTPUT WITH ACTIVE PFC FUNCTION SINGLE POWER 300W BEST POWER SOLUTIONS, INC.

This convection-cooled series is designed for use in commercial and industrial environments in temperatures up to 50 C.

SPECIFICATION SWITCHING POWER SUPPLY SINGLE POWER 250W BEST POWER SOLUTIONS, INC. 9F, NO.196-7, SEC.3, TA-TUNG RD SHI CHIH, TAIPEI, TAIWAN, R.O.C.

The MDU150 Series provides the same benefits as the MPU150 Series, with nominal 48 volt DC input.

SFD550-12BG Front-End Preliminary Data Sheet DC Input, 12V Output, 550 Watts

Asia-Pacific North America Europe, Middle East Bel Power Solutions, Inc. BCD.

SPECIFICATION REDUNDANT POWER SUPPLY HOT-SWAPPABLE BPS-460RDX 6-OUTPUT 460W+460W BEST POWER SOLUTIONS, INC.

The MPB150 product line is approved to the latest international regulatory standards, and displays the CE Mark.

TB65 65W Single Output Test and Measurement/Industrial Series

Electrical Specifications Input

LCL Series. SIngle Output Industrial Supplies. High Efficiency. Low Cost. 150 W Convection Cooled. 300 W & 500 W with Internal Fans

ENHANCE SWITCHING POWER SUPPLY SPECIFICATION 250 WATT MODEL NO:V525

VISION HISTORY Rev Level Rev Date Change Made Reason for Change Effective Approved By A 11/11/13 Specification Release S. Sadot A1 14/01/14 Update ope

CLP0205 Open Frame Power Supply Vac input; 5Vdc output; 200W Output Power; 0.25A stdby

Product Specification sheet

REDUNDANT AC 300W POWER SUPPLY. Technical Specifications TD-AC-300W-MAX

INPUT VOLTAGE STARTING MINIMUM NORMAL MAXIMUM MAXIMUM INPUT RANGE VOLTAFE VOLTAGE VOLTAGE VOLTAGE CURRENT

Medical Safety Approvals (-M versions) Industrial Heavy Duty Terminals. Output Power up to 1500 W. High Power Density - 18W/in 3

PDAM500 Series 500W Power Supply

Doc. EA Model Number:

LB115S 115W Single Output

PEAK OUTPUT CURRENT 1. MAP V 4.7V to 5.8V 8A 11A 0.2% ±1% 1% 4.9V to 5.1V PEAK OUTPUT CURRENT 4 LINE REGULATION

TE60 60W Single Output External Power Test & Measurement/Industrial Series

AC/DC Power Supply Single-Output

TE90 90W Single Output External Power Test & Measurement/Industrial Series

TE60 60W Single Output External Power Test & Measurement/Industrial Series

DA45C USB-PD. Product Descriptions. 45 Watts

TE40 40W Single Output External Power Test & Measurement/Industrial Series

LPS. TE20 15W-20W Single Output External Power Test & Measurement/Industrial Series. Features

REDUNDANT DC 200W POWER SUPPLY. Technical Specifications TD-DC-200W-12V

POWER DS1100PED Watts Distributed Power System. Electrical Specifications. Data Sheet

70 Watt Switching Medical Grade Switching Power Supply with Active PFC CONTENTS 1. GENERAL CIRCUIT TOPOLOGY...2

18093-PS PHIHONG TECHNOLOGY CO., LTD. General Specification PSM (DC)

MB120S 120W Single Output Medical Series

TE W Single Output External Power Test & Measurement/Industrial Series

Single-output models feature wide-range output adjustability to meet a wide variety of standard and user-specific output voltage requirements.

Output Power Output Voltage (3) Output Current Total Regulation (2) Efficiency (5) Model Number (1,6) 8 W 3.3 VDC 2.50 A 7% 68% AEL15US03 (4) 12 W

Output Voltage* (nom.)(adjustable)

The SPAFCBK-14G meets international safety standards and displays the CE-Mark for the European Low Voltage Directive (LVD).

POWER DS750PED. 750 Watts Distributed Power System. Electrical Specifications. Data Sheet

All specifications valid at normal input voltage, full load and +25 C after warm-up time unless otherwise stated.

420 W High Line Output Power. Rugged Industrial Construction. -40 C to +70 C Operation. 5 V Standby. Screw Terminals. SEMI F47 Compliant

POWER DS250SPE. 250 Watts Distributed Power System. Electrical Specifications. Data Sheet

HEC-150RTN-48QSCA. A. Features. B. Description. C. Models. D. Electronic Specifications - Input Specifications

TECHNICAL DATASHEET MDS Medical AC-DC Open Frame 065APS18 B Highlights & Features Safety Standards Model Number: Unit Weight Dimensions (W x L x H):

POWER DS1100PED Watts Distributed Power System. Electrical Specifications. Data Sheet

Electrical Specifications. Input voltage range Vac: 1000 W/1200 W Vac: 1200 W. Max input current. ITHD 10% Leakage current

IMA 400 Watts Power Supply Series. for medical and industrial applications. Product data sheet

11SP 4247 LCD TV Power specification Rev 1.3 Specification

SPECIFICATION ESD FSP600-80PSA(SK) Released Date:2017/02/08-10:47:01

IMA 600 Watts Power Supply Series. for medical and industrial applications. Product datasheet

Electrical Specifications

STRIDER ESSENTIAL SERIES SST-ST50F-ES230 Power for everything you need

IMA 1000 Watts Power Supply Series. for medical and industrial applications. Product data sheet

Compliance. Safety Approvals USA Canada Europe. Isolation: General. Dimensions. AC Input CN1 Output CN2 Optional CN3. Weight

FEATURES AND BENEFITS. Compact size: 6.5 x 2.8 x 1.5

HEC-100RTA-48QSCA Rev A1.0

TC-2U70PD8. Switching Power Supply ( 2U 700W 80PLUS) SPECIFICATION. Revision: 2.0

Electrical Specifications

POWER DS1600SPE Watts Distributed Power System. Electrical Specifications. Ordering Information. Data Sheet

POWER DS1100SLPE Watts Distributed Power System. Electrical Specifications. Data Sheet

POWER DS Watts Distributed Power System. Data Sheet

Electrical Specifications. > 0.9 beginning at 20% load. ITHD 10% Leakage current. Ordering Information

E E E E E E E E E E E

Model Selection Model Output Current Total OVP Number Class Volts (Convection Cooled) Efficiency 1 Ripple &Noise 2 Regulation Threshold

All specifications valid at normal input voltage, full load and +25 C after warm-up time unless otherwise stated.

Features. Regulated Converters. RAC05-K 5 Watt 1 x 1 Single Output RAC05- SK. AC/DC Converter

AC/DC Power Supply Series APPLICATION NOTE

Metal Case Power Supplies

Electrical Specifications VAC/390 VDC, Universal (Derate from 100% at 115VAC to 78% at 90VAC)

Line Reg Load Reg Ripple Efficiency *Model Number Output V Output I (nom/max) (nom/max) & Noise (min/nom)

Watts HCP Series

General. Environmental. EMC & Safety

Notes: Note1: Efficiency is tested at nominal input and full load at +25 C ambient. Output Voltage 400VAC 320VAC 360VAC 400VAC 400VAC

General. Environmental. EMC & Safety

CLP0224 Open Frame Power Supply Vac input; 24Vdc output; 200W Output Power

LFWLP W 12V 15.00A 25.00A 92%

These medical power supplies are ideal for monitoring, home health equipment as well as surgical devices.

Transcription:

Power Supply An 400W/300W Power Supply Specification For Standard 2U Redundant PSU

SPECIFICATION Model Name: Rev: Description Author / Editor Date 1.0 Initial Engineering Specification Gilbert Lin 2015-02-05 1.1 1. Improve the efficiency from Bronze Level to Sliver Level 2. Add 3C 5000 Meter Standard 1.2 1. 5VSB Ripple Noise Modify to 60Mv 2. Modify Inrush Current Spec. Gilbert Lin 2015-06-10 Gilbert Lin 2015-07-01 1.3 Modify Tvout & Tpwok holdup time Gilbert Lin 2015-07-06 1.4 Modify 5v & 3.3v Output Rating Gilbert Lin 2015-08-28 1.5 Update safety requirements Gilbert Lin 2015-09-08 1.6 Update CCC Certificate to 5000M Hannah Lai 2015-12-01 Design Product Verification Mechanical Electrical Approval Safety Approval Page : 1

1. Purpose This specification defines the performance characteristics and functions of a 400 watts 2U form factor of power supply with Active PFC (Power Factor Correction) and PMBus (Power Management Bus). 2. Input Requirements 2.1 Input Rating The power supply must operate within all specified limits under the rated input voltage range, shown in below table. The AC line inrush current shall not damage any component nor cause the AC line fuse to blow under any DC conditions and with any specified AC line input voltage and frequency. Inrush current is tested at 25 ambient and cold start within 1/4 AC cycle. Repetitive On/Off cycling of the AC input voltage shall not damage the power supply. Parameter Minimum (Vac) Table 1: Input Rating Rated (Vac) Maximum (Vac) Max. Current (A) 400W 300W Input Voltage 90 V 100-240V 264 V 5.0~2.5 4.0~2.0 Input Frequency 47 Hz 50 / 60 63 Hz - - Note: 1. The charging current for X capacitors is not considered as in-rush current 2.2 AC Line Transient Specification AC line transient conditions are characterized as sag and surge conditions. Sag conditions (also referred to as brownout conditions) will be defined as the AC line voltage dropping below nominal voltage. Surge conditions will be defined as the AC line voltage rising above nominal voltage. The power supply shall meet the regulation requirements under the following AC line sage and surge conditions. Table 2: AC Line Sag Transient Performance Duration Sag Operating AC Voltage Line Frequency Load Performance Criteria Continuous 10% 230/115VAC 50/60 Hz 100% No loss of function or performance 0-1/2 AC cycle 30% 230/115VAC 50/60 Hz 70% No loss of function or performance > 1/2 AC cycle > 30% 230/115VAC 50/60 Hz 70% Loss of function Acceptable Self-recoverable Page : 2

Duration Surge Operating AC Voltage Table 3: AC Line Surge Transient Performance Line Frequency Load Performance Criteria Continuous 10% 230/115VAC 50/60 Hz 100% No loss of function or performance 0 - ½ AC cycle > 1/2 AC cycle 30% 230/115VAC 50/60 Hz 100% No loss of function or performance > 30% 230/115VAC 50/60 Hz 100% Loss of function Acceptable Self-recoverable 3. DC Output Specification 3.1 Output Power / Currents Table 4: Load Range (400W) Voltage Minimum Load Maximum Continuous Load +3.3V 0.5A 20A +5V 0.5A 20A +12V 1A 32A -12V 0A 0.5A +5VSB 0.1A 2.5A Note1. : Total output of 3.3V and 5V shall not exceed 140W Note2. : Total output shall not exceed 400W Note3: Operating Ambient, normal mode: 0 C ~ 40 C Table 4-1: Load Range(300W) Voltage Minimum Load Maximum Continuous Load +3.3V 0.5A 20A +5V 0.5A 20A +12V 1.0A 24A -12V 0A 0.5A +5VSB 0.1A 2.5A Note1. : Total output of 3.3V and 5V shall not exceed 140W Note2. : Total output shall not exceed 300W Note3: Operating Ambient, normal mode : 0 C ~ 50 C Page : 3

3.2 Voltage Regulation, Ripple and Noise Table 5: Regulation, ripple and noise Output Voltage +3.3V +5V +12V -12V 5VSB Load Reg. ±5% ±5% ±5% ±10% ±5% Line Reg. ±1% ±1% ±1% ±1% ±1% Ripple & Noise 50mV 50mV 120mV 120mV 60mV Ripple and noise shall be measured using the following methods: a) Measurements made differentially to eliminate common-mode noise b) Ground lead length of oscilloscope probe shall be 0.25 inch. c) Measurements made where the cable connectors attach to the load. d) Outputs bypassed at the point of measurement with a parallel combination of 10uF tantalum capacitor in parallel with 0.1uF ceramic capacitors. e) Oscilloscope bandwidth of 0 Hz to 20MHz. f) Measurements measured at locations where remote sense wires are connected. g) Regulation tolerance shall include temperature change, warm up drift and dynamic load 3.3 Capacitive Loading The power supply shall be stable and meet all requirements in the following table, except dynamic loading requirements. Table 6: Capacitive Loading Conditions Output MIN MAX Units +3.3V, +5V, +12V 1000 11,000 uf 5VSB 1 500 uf 3.4 Dynamic Loading The output voltages shall remain within the limits specified in Table-Regulation, ripple and noise for the step loading and within the limits specified in Table-Transient Load Requirement for the capacitive loading. The load transient repetition rate shall be tested between 50Hz and 5kHz at duty cycle ranging from 10%-90%. The load transient repetition rate is only a test specification. The step load may occur anywhere within the MIN load to the MAX load shown in Table-Load Range. Table 7: Transient Load Requirements Output Step Load Size Load Slew Rate Capacitive Load +12v 50% of Max. Load 0.5 A/uS 2200 uf +3.3V, +5V 30% of Max. Load 0.5 A/uS 2200 uf 5VSB 0.5A 0.5 A/uS 20 uf 3.5 Closed Loop Stability The power supply shall be stable under all load conditions. A minimum of 40degrees phase margin and 4dB gain margin is required. 3.6 Overshoot at Turn-on/Turn-off Any output overshoot at turn on shall be less than 10% of the nominal output value. Any overshoot shall recover to be within regulation requirements in less than 10ms. Page : 4

3.7 Timing Requirements Figure 1: Output Voltage Timing AC Input AC off AC On Vout Tvout_holdup Tac_on-delay Tpwok_low Tsb_on-delay Tpwok_off Tpwok_off PWOK Tpwok_on Tpwok_holdup Tsb_on-delay Tpwok_on Tpson_pwok 5VSB Tsb_vout Tsb_holdup PSON# Tpson_on_delay AC turn 0n/off cycle PSON turn on/off cycle Table 8: Timing Requirements Item Description MIN MAX Units Tvout_rise Output voltage rise time from each main output 1 20 ms Tvout_on Output voltage rise time for the 5VSB out put 1 25 ms All main output must be within regulation of each other within this time. 50 ms Tvout_off All main output must leave regulation within this time 400 ms Tsb_on-delay Tac_on-delay Tvout_holdup Delay from AC being applied to 5VSB being within regulation. Delay from AC being applied to all output voltages being within regulation. Time all output voltage stay within regulation after loss of AC tested at 70% of maximum load. Tpwok_holdup Delay from loss of AC to deassertion of PWOK tested at 70% of maximum load. Tpson_on_delay Delay from PSON# active to output voltage within regulation limits. 1500 ms 2500 ms 12 ms 11 ms 5 400 ms Tpson_pwok Delay from PSON# deactive to PWOK being deasserted. 50 ms Tpwok_on Delay from output voltage within regulation limits to PWOK asserted at turn on. 100 500 ms Page : 5

Tpwok_off Tpwok_low Tsb_vout Delay from PWOK deasserted to output voltage dropping out of regulation limits measured at 70% of maximum load. Duration of PWOK being in the deasserted state during an off/on cycle using AC or the PSON# signal. Delay from 5VSB being in regulation to O/Ps being in regulation at AC turn on. 1 ms 100 ms 10 1000 ms 3.8 Hot Swap Requirements Hot swapping a power supply is the process of inserting and extracting a power supply from an operating power system. During this process the output voltages shall remain within the limits with the capacitive load specified. The hot swap test must be conducted when the system is operating under static, dynamic, and zero loading conditions. The power supply can be hot swapped by the following method: Extraction: The AC power will be disconnected from the power supply before the power supply is being extracted from the system. This could occur in standby mode or powered on mode. Insertion: The AC power will be connected to the power supply after the supply is inserted into the system and the supply will power on into standby mode or powered on mode. In general, a failed (off by internal latch or external control) supply may be removed, then replaced with a good power supply, however, hot swap needs to work with operational as well as failed power supplies. The newly inserted power supply will get turned on in standby or Power On mode once inserted. 3.9 Efficiency 1. The power module efficiency shall at least come up to the 80plus sliver standard specified as 85%, 89%, and 85% minimum respectively measured at 20%, 50%, and 100% loads with 230VAC/60Hz input, 25C ambient temperature, and cooling fan power consumption excluded. 2. The overall power efficiency shall be in excess of 80% measured under the simultaneous conditions of 115V input and full load. 4. Protection Circuits Protection circuits inside the power supply shall cause only the power supply s main outputs to shutdown. If the power supply latches off due to a protection circuit tripping, an AC cycle OFF for 15 sec and a PSON # cycle HIGH for 3 sec must be able to restart the power supply. 4.1 Over Current Protection (OCP) The power supply shall have current limit to prevent main outputs from exceeding the values shown in Table-Over Current Protection. The power supply shall latch off if the current exceeds the limit. Table 9: Over Current Protection Voltage Minimum of rated load Maximum of rated load Shutdown Mode +3.3V, +5V, +12V 110% 150% Latch Off Page : 6

4.2 Over Voltage Protection (OVP) The power supply is protected against over voltage due to an internal regulator failure. When an over voltage condition is detected, all DC outputs are disabled (except the 5VSB). The fault must be removed to restore the DC outputs. The limits are given in Table 11. Table 10: Over Voltage Protection Voltage Minimum Maximum Shutdown Mode +3.3V +3.9V +4.5V Latch Off +5V +5.7V +6.5V Latch Off +12V +13.3V +14.5V Latch Off 4.3 Short Circuit Protection The power supply shall shut down in latch off mode when the output voltage is short circuit (impedance less than 0.1ohm). 1) The power supply shall be no physical damage when +12V, +3.3Vand +5V, is shorted to its DC return. 2) 5VSB shall be Auto Restart when short condition is removed. 4.4 No Load Operation No damage or hazardous condition should occur with all the DC output connectors disconnected from the load. The power supply may latch into the shutdown state. 4.5 Over Temperature Protection In BP (OTP) The power supply will shut down when an over temperature condition occurs. No damage shall be caused. Ambient Temperature(Inlet Air) Power Status > 55 C Warning > 60 C Power Shut off, but no damages <55 C Power Recovery 5. Environmental Requirements 5.1 Temperature Operating Ambient, normal mode (Inlet air): 0 C ~ 50 C Operating Ambient, normal mode (Inlet air): 0 C ~ 40 C Non-operating Ambient:: -40 C ~ 70 C (-40 F~ 158 F) For 300W For 400W 5.2 Humidity Operating: 20% ~ 90%RH non-condensing Non-Operating: 5% ~ 95%RH non-condensing 5.3 Altitude Operating: Sea level to 16,404 ft (5000 m) Non Operating: Sea level to 40,000 ft (12192m) Page : 7

5.4 Mechanical Shock Non-Operating: 50 G Trapezoidal Wave, 11mS half sin wave. The shock is to be applied in each of the orthogonal axes. 5.5 Vibration (Non-Operating) The power supply shall be subjected to a vibration test consisting of a 10 to 300 Hz sweep at a constant acceleration of 2.0g for duration of one (1) hour for each of the perpendicular axes X, Y and Z (0.1 octave/minute). The output voltages shall remain within specification. 5.6 Electromagnetic Compatibility Electromagnet ic Interference Harmonics Flicker ESD Susceptibility Radiated Susceptibility FCC CFR Title 47 Part 15 Sub Part B EN55022/EN55024 IEC61000-3-2 Class A IEC61000-3-3 EN-61000-4-2 EN61000-4-3 Table 11: EMC Requirements Conducted A Class -6dB Radiated A Class -6dB ±8KV by Air, ±4KV by Contact, Performance Criteria B 80MHz~1000MHz (3V/m(mns) Amplitude 80% AM 1KHz, Criteria A EFT/Burst EN61000-4-4 5KHz, AC: 1KV, DC: 0.5 KV, Performance Criteria B Surge Voltage Conducted Susceptibility EN61000-4-5 EN61000-4-6 Line-to-Line: 1KV Line-to-Ground: 2KV, Performance Criteria B 0.15MHz~80MHz 3V/m Amplitude 80% AM 1KHz, Performance Criteria A RF Conducted EN61000-4-8 50 Hz/3A(ms)/m Performance Criteria A Voltage Dips and Interruptions Leakage Current Insulation Resistance Dielectric Withstand Voltage EN61000-4-11 EN60950-1 30%(Voltage Dips) 60%(Voltage Dips) >95%(Voltage Dips) 1.75mA@240VAC 10 ms at 70% load 100ms 500ms Primary to secondary : 20 meg. ohm min. 500VDC Primary to FG : 20 meg. ohm min. 500VDC Primary to secondary : 4242VDC for 1 min. Primary to FG : 2121VDC for 1 min. Criteria B Criteria C Criteria C Page : 8

5.7 Safety Agency Requirements This power supply is designed to meet the following safety : Table 12: Product Safety Product Safety: UL: UL60950-1, 2nd Edition, 2014-10-14 6 Reliability 6.1 Mean Time Between Failures (MTBF) The MTBF of the power module in PSU () shall be calculated utilizing the Part-Stress Analysis method of MIL217F. The calculated MTBF of the power supply shall be greater than 100,000 hours under the following conditions: Full rated load; 120V AC input; Ground Benign; 25 C 7. Mechanical Overview Dimension: 85mm(W) x 84mm(H) x 217mm(D) Weight: 3.4kg 7.1 Input AC Connector The AC inlet is a IEC320 C14 type 3pin connector Page : 9

8. PMBUS COMMAND CODE SUMMARY (For PDB ): Table 13: Support Command Code Table Command Code Command Name SMBus Transaction Type Number of Data Bytes Data Format 03h CLEAR_FAULTS Send Byte 0-19h CAPABILITY (1) Read Byte 1 Byte 20h VOUT_MODE (1) Read Byte 1 Byte 1Ah QUERY (1) Read Byte 1 Byte 79h STATUS_WORD Read Word 2 Word 7Ah STATUS_12V_VOUT Read Byte 1 Byte 7Bh STATUS_12V_IOUT Read Byte 1 Byte 7Dh STATUS_TEMPERATURE Read Byte 1 Byte 80h STATUS_MFR_SPECIFIC Read Byte 1 Byte 8Bh READ_12V_VOUT Read Word 2 Linear Vout 8Ch READ_12V_IOUT Read Word 2 Linear 8Dh READ_TEMPERATURE_1 (2) Read Word 2 Linear 96h READ_12V_POUT Read Word 2 Linear 99h MFR_ID Block Read 6 ASCII 9Ah MFR_MODEL Block Read 9 ASCII 9Bh MFR_REVSION Block Read 2 ASCII 9Eh MFR_SERIAL Block Read 12 ASCII A7h MFR_POUT_MAX Read Word 2 Linear A8h MFR_TAMBIENT_MAX Read Word 2 Linear B0h STATUS_PDB Read Byte 1 Byte E0h READ_3V3_VOUT Read Word 2 Linear Vout E1h READ_3V3_IOUT Read Word 2 Linear E2h READ_3V3_POUT Read Word 2 Linear E3h READ_5V_VOUT Read Word 2 Linear Vout E4h READ_5V_IOUT Read Word 2 Linear E5h READ_5V_POUT Read Word 2 Linear Note : READ_TEMPERATURE_1, should provide the PDB inlet temperature Page : 10

Table 14: Contents in 79h (STATUS_WORD)Command Code Byte Bit Number Status Bit Name Meaning Low 7 Reserved Return=0 6 OFF The Unit Main Power OFF = 1 ;Power ON = 0; 5 +12V_OV_FAULT An output overvoltage fault has occurred = 1 ; Normal = 0 4 +12V_OC_FAULT An output overcurrent fault has occurred = 1 ; Normal = 0 3 Reserved Return=0 2 Temperature A Temperature fault or warning has occurred = 1 ; Normal = 0 [1:0] Reserved Return=0 High 7 +12V_VOUT An output voltage fault or warning has occurred = 1 ; Normal = 0 6 +12V_IOUT An output current fault or warning has occurred = 1 ; Normal = 0 5 Reserved Return=0 4 MFR_SPECIFIC Any Bits of Byte Action (See Table 18) 3 POWER_ GOOD# The POWER_GOOD signal is OK = 0; ;FAIL = 1 [2:0] Reserved Return=0 Table 15 : Contents in 7Ah (STATUS_VOUT)Command Code Bit Number Status Bit Name Meaning 7 +12V_OV_FAULT VOUT > 14.5V = 1 ; Normal = 0 6 +12V_OV_WARNING VOUT > 13.2V = 1 ; Normal = 0 5 +12V_UV_WARNING VOUT < 10.8V = 1 ; Normal = 0 4 +12V_UV_FAULT VOUT < 8.4V = 1 ; Normal = 0 [3:0] Reserved Return=0 Table 16: Contents in 7Bh (STATUS_IOUT)Command Code Bit Number Status Bit Name Meaning 7 +12V_OC_FAULT 12V_IOUT > Max Current of 130% = 1 ; Normal = 0 6 Reserved Return=0 5 +12V_OC_WARNING 12V_IOUT > Max Current of 110%@10ms = 1 ; Normal = 0 [4:0] Reserved Return=0 Table 17: Contents in 7Dh (STATUS_TEMPERATURE)Command Code Bit Number Status Bit Name Meaning [7:4] Reserved Return=0 3 Ambient_OT_FAULT Ambient temperature >60 C = 1 ; Normal = 0 2 Ambient_OT_WARNING Ambient temperature >55 C = 1 ; Normal = 0 [1:0] Reserved Return=0 Page : 11

Table 18 : Contents in 80h (STATUS_MFR_SPECIFIC)Command Code Bit Number Status Bit Name Meaning 7 3V3_UV_FAULT VOUT < 2.8V = 1 ; Normal = 0 6 3V3_OV_FAULT VOUT > 4.5V = 1 ; Normal = 0 5 5V_UV_FAULT VOUT < 3.5V = 1 ; Normal = 0 4 5V_OV_FAULT VOUT > 6.5V = 1 ; Normal = 0 3 3V3_IOUT_OC_ FAULT 3V3_IOUT > Max Current of 130% = 1 ; Normal = 0 2 3V3_IOUT_OC_ WARNING 3V3_IOUT > Max Current of 110% = 1 ; Normal = 0 1 5V_IOUT_OC_ FAULT 5V_IOUT > Max Current of 130% = 1 ; Normal = 0 0 5V_IOUT_OC_ WARNING 5V_IOUT > Max Current of 110% = 1 ; Normal = 0 Table 19 : Contents in B0h (STATUS_PDB)Command Code Bit Number Status Bit Name Meaning 7 PSU1_FAULT PSU1 FAULT = 1 ; Normal = 0 6 PSU2_FAULT PSU2 FAULT= 1 ; Normal = 0 5 PSU1 PLUG_STATUS PSU1 PLUG-OUT= 1 ; PLUG-IN = 0 4 PSU2 PLUG_STATUS PSU2 PLUG-OUT= 1 ; PLUG-IN = 0 3 POWER_GOOD# POWER_GOOD signal is FAIL= 1; OK = 0 2 PSON# PSON#_H = 1 ; PSON#_L = 0; [1:0] Reserved Return=0 Table 20: MFR Meaning (For 400w PDB) Command Code Command Name Meaning 99h MFR_ID 9Ah MFR_MODEL 9Bh MFR_REVSION 9Eh MFR_SERIAL Code = 12 (ex. T201XXG00001) A7h MFR_POUT_MAX 400 (W) A8h MFR_TAMBIENT_MAX 40 ( C) Table 20-1: MFR Meaning (For 300w PDB) Command Code Command Name Meaning 99h MFR_ID 9Ah MFR_MODEL 9Bh MFR_REVSION 9Eh MFR_SERIAL Code = 12 (ex. T201XXG00001) A7h MFR_POUT_MAX 300 (W) A8h MFR_TAMBIENT_MAX 50 ( C) MCU Device Table 21: Pmbus Address Set PDB address BE Page : 12

9. LED behaviors: Power Supply Condition Normal No AC power to all power supplies Power Fail Table 22 :LED Behaviors LED State GREEN OFF RED 10. Signals from Wire Harness Table 23: Signals from Wire Harness (PFD Cable) Power Supply Status Signal Type Works Normally High Power Module Not Inserted or Pulled Out Low Power Fail Low Fan Fail Low Note: 1) Alarm reset is used to clear power fail status by shorting circuit activities. 2) Buzzer shall alarm if signal goes low. Appendix I. Data Format Description The Linear Data Format is typically used for commanding and reporting the parameters such as (but not only) the following: Output Current (A) Output Power(W) Temperature( ) Any Warning Limit The Linear Data Format is a two byte value with: An 11 bit, two s complement mantissa and a 5 bit, two s complement exponent (scaling factor). The format of the two data bytes is illustrated in Figure The relation between Y, N and the real world value is: X = Y 2 N Where, as described above: X is the real world value; Y is an 11 bit, two s complement integer; and N is a 5 bit, two s complement integer. Devices that use the Linear format must accept and be able to process any value of N. Page : 13