Transformer Factory Testing

Similar documents
KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Electrical Design Process

Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

PES & IAS NY Chapter And NY LMAG June 23 rd, 2015

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

Power Measurements and Basic Electrical Diagnostic Tests

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

Hands-On Transformer Testing and Maintenance

(2) New Standard IEEE P (3) Core : (4) Windings :

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

Substation Preventive Maintenance

Regional Technical Seminar TAP CHANGERS

Comparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

SECTION TRANSFORMERS

Power Transformers Basics

FIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC.

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

Effects of Harmonic Distortion I

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

TRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K

TRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

EEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Basic Operating Principles of Transformers

TEST REPORT. Table Of Contents

Error vs. Uncertainty Historical Perspective

PROBLEMS on Transformers

UNIVERSITY OF TECHNOLOGY By: Fadhil A. Hasan ELECTRICAL MACHINES

148 Electric Machines

7. INSPECTION AND TEST PROCEDURES

Monitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis

86 chapter 2 Transformers

State of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company

CASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION. - S K Mishra & S K Das NHPC Ltd O&M Division

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

MEDIUM & HIGH VOLTAGE

Prolific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2

Chapter 7 Conclusion 7.1 General

Transformer Design: Economics & Reliability

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)

Pomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers

Transformer Technology Seminar What to consider at Design Reviews

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

Testing and Diagnostic of Power Transformers & Distribution Transformers

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

Transformers handling and transport

PUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT

TMS 580. Transformer Loss Measuring System FEATURES BENEFITS APPLICATIONS

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

Generator Advanced Concepts

Transformer Tests BEST BALIKESİR ELEKTROMEKANİK SANAYİ TESİSLERİ A.Ş. Facility 1 : Ağır Sanayi Bölgesi No Balıkesir / Türkiye

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER

500 kva Dry-type Isolation Transformer V-Delta to 208Y/120V 3PH - NEMA 1/Indoor

~=E.i!=h. Pre-certification Transformers

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

The Reflective Wave Phenomena

APPENDIX B: Generation Interconnection Application Form

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL

Impact Assessment Generator Form

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

About us. Vision. To lead our field in innovation, quality and customer service.

Evaluating Transformer Heating due to Geomagnetic Disturbances

CHAPTER 4. Distribution Transformers

IVE(TY) Department of Engineering. Electrical Machines 1. Electrical Machines 1. Hour 13. slide 1

Type 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s

Code No: R Set No. 1

Reactor and inductor are names used interchangeably for this circuit device.

Transformers. 6.1 Principles of operation. Professor D.J. Allan Merlindesign. Chapter 6

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet

Liquid-Filled Transformers

Power Transformer Testing

Siemens Transformer Technology Seminar Insulation & Thermal Design

Transformer Engineering

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

RESONANT TRANSFORMER

Embedded Generation Connection Application Form

WDG 12 - Technical Data Sheet

Power transformers for Network, Rectifiers, Furnace

WDG 71 - Technical Data Sheet

ISSN: [IDSTM-18] Impact Factor: 5.164

WDG 61 - Technical Data Sheet

Mechanical Design. Brian Brinson Mechanical Design Manager.

Transcription:

Transformer Factory Testing John J. Foschia Test Engineer John.Foschia@spx.com September 2018

Reasons for Testing Compliance with user specifications Assessment of quality and reliability Verification of design calculations Compliance with applicable industry standards September 27, 2017 2

IEEE C57.12.00-2015 Table 17 Routine Tests Routine tests shall be made on every transformer to verify that the product meets the design specifications Design Tests Design tests shall be made to determine the adequacy of the design of a particular type, style, or model of transformer or its component parts. Test data from previous similar designs may be used for current designs, where appropriate. Once made, the tests need not be repeated unless the design is changed to modify performance. Other Tests Other tests are identified in product specifications and may be specified by the purchaser in addition to routine tests September 27, 2017 3

Class I and Class II Power Transformers New Definition: C57.12.00-2015 Sec 5.10 Class I Class II Nominal System Voltage (kv) < 69 kv = 69 kv 115 kv 69 kv < 115kV Top Nameplate Rating (KVA) Any <10,000 1ϕ <15,000 3ϕ Any 10,000 1ϕ 15,000 3ϕ September 27, 2017 4

List of Tests September 27, 2017 5

List of Tests (Cont d) September 27, 2017 6

Preliminary Testing Tests Class I Class II Voltage Ratio Routine Routine Insulation Power factor Routine Routine Insulation Resistance Routine Routine 1Φ Excitation test SPX Routine SPX Routine CT Ratio & Polarity SPX Routine SPX Routine Control Wiring Checks & Hi-pot Routine Routine Auxiliary Losses Routine Routine September 27, 2017 7

Preliminary Tests Voltage Ratio Test Performed with ratio-meter (TTR) based on voltage comparison principle to check that windings are wound with correct turns including tapped turns Low voltage is applied to HV winding and voltage measured across LV/other winding is fed back to ratiometer which displays the applied/measured voltage ratio (= turns ratio) Turns ratio is compared with voltage ratio requirement to meet tolerance of +/- 0.5% CT Ratio and Polarity Test Verify Polarity ( & also Ratio ) and wiring to control box Leak Test 10 PSI for 10 hours minimum Typically Tested during Manufacturing before release to Test September 27, 2017 8

Preliminary Tests (cont.) Insulation Power Factor C57.12.90 Sec. 10.10 Between Windings To Ground Test voltage is typically 10kV Power Factor is affected by temperature; Recommended 10 0 to 40 0 C No IEEE Limit for PF, Max 0.5% good for most units September 27, 2017 9

Preliminary Tests (cont.) Single Phase Excitation Test Test typically performed on HV terminal and tested at 10kV Test is performed one phase at a time and currents are compared For three phase transformers, two phases are expected to have similar and higher current compared to third; current measured on phase wound on center limb on three legged core will have lower current due to lower magnetic reluctance Winding Insulation Resistance C57.12.90 Sec. 10.11 Typically tested at 1/2.5/5 kv and held for 1 minute before taking reading Test performed high voltage to low voltage and ground and low voltage to high voltage and ground Acceptable values varies with design, voltage class and cooling medium - typically is greater than 500MOhms September 27, 2017 10

Performance Characteristic Tests Tests Class I Class II No Load Losses Routine Routine % Excitation Tests Routine Routine Load Losses Routine Routine Positive Sequence Impedance Zero Sequence Impedance Routine Special Routine Routine Winding Resistances Routine Routine Sound Test Other Other September 27, 2017 11

No-Load Test Connection C57.12.90 Section: 8 No Load Loss and Excitation Current Core Loss ~ Hysteresis Loss, Eddy Current Loss Hysteresis Loss ~ Flux Density & Grade of Steel Eddy Current Loss ~ Frequency, Temperature Test Circuit Transformer is excited from either TV/LV or HV side at 60 Hz with a variable voltage sinusoidal source All other terminals are left open Applied voltage is slowly increased to test voltage 90%, 100%, 110% Measurement Require high precision loss measurement system Losses corrected to 20 o C September 27, 2017 12

No-Load Test Connection 60 Hz SOURCE September 27, 2017 13

Load Losses and % Impedance Load Loss C57.12.90 Sec. 9 Load Losses are the losses of TRANSFORMER DUE TO LOAD CURRENT Load Loss = I 2 R loss + Eddy loss + Stray loss Eddy losses depend on conductor thickness and width and leakage flux distribution Stray loss depends on % impedance, winding dimensions and clearance to tank and clamps Impedance % Impedance = VOLTAGE FOR RATED CURRENT X 100 RATED VOLTAGE September 27, 2017 14

Winding Resistance Test C57.12.90 Section: 5 Performed with standard resistance bridge, DC current is fed to the winding and voltage developed across is measured Resistance = Voltage/Current is displayed and compared with design value Required for Load Loss calculation Reference for heat run winding temp rise calculation: R 1 234.5 + T 1 for Copper = R 2 234.5 + T 2 1-2 = 0.6667 2-3 = 0.6667 3-1 = 0.6667 Sum = 2.0001 x 1.5 = 3 1-2 = 2 2-3 = 2 3-1 = 2 Sum = 6 x 0.5 = 3 September 27, 2017 15

Load Loss Test Connection Test Circuit Transformer is excited, preferably from HV side at 60 Hz with a variable voltage sinusoidal source. LV terminals are shorted. Applied voltage is slowly increased to feed the rated test current in the windings. Measurement With the help of a precision loss measurement system load current, voltage and losses are measured: Measured loss = I² R Loss at ambient + stray loss I² R Loss at 85ºC = I² R Loss at ambient*(234.5+85)/(234.5 + ambient) Stray Loss at 85ºC = Stray Loss at ambient*(234.5+ambient)/(234.5 + 85) September 27, 2017 16

Load Loss Test Connection (cont.) September 27, 2017 17

Load Loss Test Connection (cont.) September 27, 2017 18

Dielectric Tests Tests Class I Class II Impulse (Line) SPX Routine Routine Impulse (Neutral) SPX Routine Routine Switching Surge Impulse Other Routine > 345 KV Applied Voltage Routine Routine 7200 cyl. Induce test Routine SPX Routine with PD NA 1- Hr. Induce test with PD Other Routine September 27, 2017 19

Impulse Testing C57.12.90 Section: 10.3 Lightning Impulse Class II Routine, Class I Other Reduced Wave RFW (50 70% of Full Wave) Full Wave * Two (2) Chopped Waves Full Wave Full Wave * Transformer Neutrals 1 RFW 2 FW 1 FW* *Added in 2015 Standard September 27, 2017 20

Impulse Test Lighting Impulse Front Time 1.2 microseconds + - 30% Tolerance (1.67 Times the time between 30% and 90% voltage) Tail Time 50 microseconds + - 20% (Time to 50% peak voltage) Chop Time > = 3 microseconds for > = 150 KV > = 2 microseconds for < 150 KV Chopped Wave September 27, 2017 21

Waveform Comparisons RFW & FW Overlay Voltage Waveform Current Waveform September 27, 2017 22

Impulse Generator (cont.) September 27, 2017 23

Impulse Generator (cont.) Multiplier Circuit RC circuit with circuit Inductance Multiplier circuit introduced by Prof. Marx Impulse capacitor Cs are charged in parallel and discharged in series after firing the switching gaps F Front Time T1 is determined by Rd whereas time to half value is determined by Re September 27, 2017 24

Impulse Generator (cont.) Series Parallel Stages Stages in series for higher voltage Stages in parallel for higher energy September 27, 2017 25

Voltage and Current Wave Shape Comparison (Reduce and Full Wave) Chop wave failure Failure between LTC Leads Cable to cable failure Turn to turn failure within winding September 27, 2017 26

Impulse Failure Waveforms September 27, 2017 27

Switching Impulse Test Switching Impulse Test C57.12.90 Sec. 10.2 Time to peak value > 100 microseconds Time for 90 % of peak Value > 200 microseconds Time to first zero on tail of the wave >1000 microseconds Test Circuit Test for each HV Line terminal Ground Neutral terminal for all Wye connection Ground other end of all Delta windings All Line terminals to be kept open except test terminal September 27, 2017 28

Switching Impulse September 27, 2017 29

Low Frequency Dielectric Test Applied Voltage Test Transformer Connections Test Levels Induced Voltage Test Transformer Connections Test Levels Class I & Class II Partial Discharge September 27, 2017 30

Applied Voltage Test C57.12.90 Section: 10.6 All terminals of winding under test are shorted together and connected to the 60 Hz supply through a high voltage test transformer. All other winding terminals are shorted together and connected to ground. Tank is also connected to ground During this test, as both ends of winding are connected, all parts of the winding and leads attain the same voltage level with respect to ground and all other windings Test voltage is raised slowly to the required voltage and held for 1 minute. The test is considered to be passed if there is no collapse of voltage or no audible internal sound After testing one winding, connection is changed for another windings and are tested in a similar way September 27, 2017 31

Induced Voltage Test vs. Applied Voltage Test September 27, 2017 32

Applied Voltage Test (cont.) Test Voltage For Delta connected windings, applied test voltage level corresponds to NSV For example: Equivalent applied test voltage for 230kV ( 750,825,900 BIL) is 345kV For Wye connected windings, the applied test voltage is limited to the BIL of Neutral For example: If line end BIL is 550kV and neutral end BIL is 150kV, then equivalent applied test voltage is limited to 50kV (equivalent for 150 BIL) September 27, 2017 33

Induced Voltage Test C57.12.90 Section: 10.7 to 10.9 Test Connection Three phase voltage is applied to LV terminals at frequency 2 times rated frequency; all other line terminals are left open, Neutral and Tank is grounded Test Voltage & Duration Class I Transformers Test voltage is equivalent to twice the volts/turn and line end is raised to achieve equivalent power frequency test voltage across phases Test duration is 7200 Hz; if test frequency is 180 Hz then test duration = 7200/180 = 40 seconds Test is considered to be passed if no collapse of voltage occurs or no audible internal sound is present September 27, 2017 34

Induced Voltage Test (cont.) Test Voltage & Duration Class II Transformers Enhancement level 173% maximum tap voltage for 7200 Hz One hour test voltage 150% for 1 hour Partial discharge limits < = 500 pc September 27, 2017 35

C57.12.00 Table 4 September 27, 2017 36

Location Temperature Distribution Model Top Winding Hot Spot R V Hot Spot Gradient Ambient Oil Winding T V W D G COM SER Avg. Avg. Winding Gradient L T C Bot. Oil Rise 65C 65C Avg. Winding Rise Hot Spot Winding Rise 80C 24 Hour Max Avg. Ambient = 30C (Max Ambient = 40C) Temperature September 27, 2017 37

Temperature Rise Test C57.12.90 Section: 11 Measurements during temperature rise test Top oil temperature Ambient temperatures Top and bottom radiator temperature Hot winding resistance at shut down Top Oil Rise = Top oil temperature Average ambient Mean oil rise = Top oil temperature Average of top & bottom header temp Average winding rise = { (Hot Resistance/Cold Resistance) X (234.5+ambient temp) } Ambient Gradient = Average winding rise Mean oil rise Hot spot Rise = Top oil rise + Hot spot gradient Hot spot gradient = Gradient (1 + k); k = hot-spot factoralculate September 27, 2017 38

Average Winding Rise September 27, 2017 39

DGA DGA Sequence Before Test, After Dielectric, Before/After Temp Rise test, After all Tests Gassing rate depend on many factors - Winding temperature rise, Ambient Temperature, Duration of test, Design characteristics like current and flux density Expect significant difference lab to lab Limits per C57.130 Gas Generation During Temp Rise Test PPM/ Hour Hydrogen H2 < 1 Carbon Monoxide CO < 2 Carbon dioxide CO2 < 18 Methane CH4 Ethane C2H6 Ethylene C2H4 < 0.4 Acetylene C2H2 0 September 27, 2017 40

Sound Test C57.12.90 Section: 13 Core audible sound: This sound component originates in the transformer core Load audible sound: This sound component is primarily produced by vibrations of the windings and tank walls when the transformer is loaded. When a transformer is highly loaded, load sound can be a significant contributor to the total sound of the transformer,especially for low no-load noise medium and large power transformers. Cooling system audible sound: typically consists of broadband fan noise, plus discrete tones (of low levels) at the fan blade passage frequency and its harmonics. The sum of core and cooling system sound components is typically referred to as the no-load noise of a transformer. The total audible sound of the transformer, however, is the sum of all three components, 2015 standard outlines measurement methods for Load sound and calculation to arrive Total sound. Sound levels are specified in NEMA-TR1 and that is only No-Load Sound Level Load Sound is not significant for smaller transformers ( < 100 MVA ) unless No load sound required is below NEMA September 27, 2017 41

Sound Test Procedure Measurements are generally taken on a weighted scale as per NEMA standard Location of measurements start at drain plug and around the transformer at approximate 3 foot intervals, 12 inches away from transformer tank/radiators as applicable at 1/3 and 2/3 heights for transformers over 9 feet With fans running readings are taken 6 feet distance September 27, 2017 42

Other Tests Bushing Cap & PF C1/C2 Core excitation test typically 110% for 24 Hours Leakage Reactance test Front of Wave Impulse testing Frequency response analysis (FRA) Fast Front Switching Impulse ( FFSI ) Special Termination Lightning Impulse ( STLI ) LTC Tests - Operate LTC at No Load Voltage - Operate LTC under Load - Dynamic Resistances - DGA from LTC September 27, 2017 43

Questions? Thank you!

Certified Test Report

Certified Test Report (CTR ) September 27, 2017 46

CTR September 27, 2017 47

CTR September 27, 2017 48

CTR September 27, 2017 49

CTR September 27, 2017 50

CTR September 27, 2017 51

Zero Sequence Testing

Zero Sequence Test Transformers with one neutral externally available (D-Y / Y-D) C57.12.90 Sec. 9.5.1 %Z 0 = 300 (V MEASURED /V RATED ) (I RATED /I MEASURED ) V MEASURED V RATED I MEASURED I RATED ---------- Measured Excitation Voltage -------------- Rated Phase-to-Neutral Voltage of Excited Winding ----------- Measured Total Input Current Flowing in the Three Parallel-Connected Phases ----------------Rated Current per Phase of the Excited Windings September 27, 2017 53

Zero Sequence Test Transformers with two neutrals externally available (Auto, YY, YYD, etc.) C57.12.90 Sec. 9.5.3 September 27, 2017 54

Zero Sequence Test Transformers with two neutrals externally available (Auto, YY, YYD, etc.) Z 1NO : Apply a single-phase voltage to winding 1 between the shorted line terminals of winding 1 and its neutral. All other windings are open-circuited. Z 1NS : Apply a single-phase voltage to winding 1 between the shorted line terminals of winding 1 and its neutral. Short the line terminals and neutral of winding 2. Z 2NO : Apply a single-phase voltage to winding 2 between the shorted line terminals of winding 2 and its neutral. All other windings are opencircuited.. September 27, 2017 55