Insulation Level and Test Technology of. 1000kV Power Transformer

Similar documents
How to Analyze and Test the Location of Partial. Discharge of Single-winding Transformer Model

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

How to Conduct the Lightning Impulse Withstand Test of. Three Gorges Right Bank Substation 550kV GIS

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

TECHNOLOGIES FOR TOMORROW

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

HV AC TESTING OF SUPER-LONG CABLES

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

MEDIUM & HIGH VOLTAGE

3. COMBINED TRANSFORMERS Oil-paper insulation

Power Engineering II. High Voltage Testing

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

Electric Stresses on Surge Arrester Insulation under Standard and

TRANSFORMER TECHNOLOGY GPT

GIS Disconnector Switching Operation VFTO Study

Analysis of Variable Frequency Resonant Withstand. Voltage Test for 220kV Long Cable On Site

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

High voltage engineering

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

Field Test and Analysis of Partial Discharge. on GIS Under Impulse Voltage

Transformer Factory Testing

The Application of Partial Discharge Measurement and Location on CGIS

Insulation Co-ordination For HVDC Station

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH

Type 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s

SGM series. AC Resonant Test System. Applications & Advantages

Comparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137

Recent Improvements in K-Factor Models dl

Recent Trends in Ultralarge-capacity Three-phase Transformer Technology

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

VI 3 - i TABLE OF CONTENTS

Modeling insulation in high-voltage substations

Medium voltage circuit breaker technical guide

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

High-Voltage Test Techniques

EE 1402 HIGH VOLTAGE ENGINEERING

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

HIGH VOLTAGE TESTING GENERATION AND MEASUREMENTS

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers

Martin Stoessl R&D Manager Siemens Transformers Austria - Weiz

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

IEC/CIGRE UHV Symposium Beijing Paper 4.2. Challenges on the measuring and testing techniques for UHV AC and DC equipment

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY EHV AC AND DC TRANSMISSION

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

4. CAPACITIVE VOLTAGE TRANSFORMERS AND COUPLING CAPACITORS Oil-paper insulation

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]

The power transformer

Fixed Series Compensation

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location

RESONANT TRANSFORMER

Electrical Design Process

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

AC Voltage Test System with Transformer

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear

Type Test of a 145 kv Termination Type TS 145-II

Diagnostic testing of cast resin transformers

MATEFU Insulation co-ordination and high voltage testing of fusion magnets

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Protection against unacceptable voltages in railway systems

Open Access Application of Partial Discharge Online Monitoring Technology in ± 660kV Converter Transformer

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Transformers. GE Digital Energy. Three Phase up to 1500MVA. with Primary Plus TM

Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Integrated Electro-optic Sensor based Transient Voltage Measuring System and its Applications

TAP CHANGER SELECTING MANUAL TECHNICAL DATA

(2) New Standard IEEE P (3) Core : (4) Windings :

ALLOWABLE LIMITS TO SHORT TIME VOLTAGE DROPS IN HV WITHSTAND TESTS

On-Load Tap Changer Type M

Chapter 1. Overvoltage Surges and their Effects

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

Australian Standard. Instrument transformers. Part 1: Current transformers (IEC Ed.1.2 (2003) MOD) AS AS

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON

Working Group Members

TMS 580. Transformer Loss Measuring System FEATURES BENEFITS APPLICATIONS

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

Shunt Reactor Switching

Proceedings of the 5th WSEAS Int. Conf. on SIMULATION, MODELING AND OPTIMIZATION, Corfu, Greece, August 17-19, 2005 (pp )

Transformer Technology Seminar Winding Selection

Research on Lightning Over-voltage and Lightning Protection of 500kV. HGIS Substation

Method to Determine Wave Resistance of Impulse. Voltage Generator for Lightning Impulse Test

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

CONTENTS. 1. Introduction Generating Stations 9 40

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

Coherence and time-frequency analysis of impulse voltage and current measurements

PES & IAS NY Chapter And NY LMAG June 23 rd, 2015

Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation

Transcription:

Insulation Level and Test Technology of 1000kV Power Transformer Li Guangfan, Wang Xiaoning, Li Peng et al HIMALAYAL - SHANGHAI - CHINA Abstract: The insulation coordination for the first 1000kV UHVAC system in China is studied and determined under the optimization principle. It is not the simple extrapolation of 500kV system and is not in accordance with the standards of GB 311.1-1997 and IEC60071-1-1993. The insulation level of 1000kV power transformer adheres to following items: the lightning impulse voltage is 2250kV; the switching impulse withstand voltage is 1800kV; the power frequency withstand voltage is 1100kV (5min). Due to the differences among the insulation levels and insulation test voltage for different windings of UHV power transformer, the power frequency and impulse test voltage are transmitted among these windings according to transformer ratio. Hence, it is bound to bring about the condition that the insulation design for some conductor terminals cannot be checked by the test voltage specified in the technical specification. Besides, owing to the high voltage class, large capacity and super size of UHV power transformer, the size of its test circuit is correspondingly enlarged, and the influence of stray inductance and capacitance will be more intense. It makes the wave front time of voltage waveform in lightning impulse test extend. However, the design and calculation are generally conducted according to standard waveform. Thus, in the design of UHV power transformer the attention should be paid to the impact of long wave front time test voltage. In this paper, the structural features and insulation level of transformer for 1000kV power transmission project in China as well as special problems during the insulation test are presented in detail. Key words: UHV, power transformer, insulation level, test technology 1. Introduction The success of UHV power transmission lies in the equipment, especially power transformer, reactor and switch. The high voltage and large capacity of UHV power transformer bring higher technical difficulties for design and production. The principle of insulation coordination for UHV power transformer all winding is different. Meanwhile, the dimension is great. Hence, some insulation tests cannot be conducted according to technical codes. info@himalayal.com Page:1 All right reserved.

The rated voltage and maximum voltage of UHVAC power transmission systems being constructed in Japan and China are almost the same, but there is a great discrepancy in the aspect of system composition, line length, main equipment code and insulation technology. Therefore, we should not copy the experience or technology of some nation, but design and produce them based on actual project conditions. The principle of insulation coordination for 1000kV ACUHV power transmission system is different from that of 750kV and below stages. First of all, lightning overvoltage, switching overvoltage and power frequency overvoltage level are further reduced by adopting high-performance arrester, reactors in parallel and advanced system analysis and overvoltage restriction technologies to optimize the insulation coordination. The insulation design of 500kV power transformer cannot be extrapolated to UHV power transformer. The ultra-high voltage, ultra-great capacity and super great dimension impose particular requirements for structure. The paper presents features of power transformer structure used in the 1000kV ACUHV project, insulation level and special problems arising in the insulation test. 2. Features of 1000kV ACUHV Power Transformer Structure 2.1 Structure and type The voltage of UHV transformer is high, and its capacity is large. Extreme and innovative technologies need to be applied in many aspects, including structure, insulation technology, cooling technology, leakage flux, partial overheating, regulating method and transportation. The oil tank structure can be divided into split type and single type. Both Italy and China adopt single type while Japan uses single type. As for iron core structure, three-column structure is generally used, which is shown in Fig.1. The Chinese UHV power transformer adopts single, single-phase and five-column structure. There are three main columns and two side yokes. The capacity of single column is 334MVA. The scheme diagram of structure is shown in Fig.2 and effective drawing is shown in Fig.3 The capacity of single type is 1000MVA, ranking the top in the world. Fig.1 1000MVA/1050kV UHV power transformer of Japan Fig.2 Scheme diagram of single-phase five-column UHV transformer of China A--end of high-voltage coil Am--end of medium-voltage coil info@himalayal.com Page:2 All right reserved.

X0--regulating coil a,x--low-voltage coil X--neutral point compensation winding is set to compensate voltage fluctuation of medium and low winding in the voltage regulating process. The no-load voltage regulating method is adopted in China. In order to simplify the structure of main transformer, voltage regulating winding is installed in the independent container, which is separated from main transformer body and connected with main transformer through bushing. 2.3 Outlet and bushing Fig.3 Effective drawing of UHV power transformer of China The power transformer adopts the method of OFAF. 2.2 The method of regulating the voltage The 500kV power transformer mostly adopts medium-voltage winding terminal to regulate the voltage. The voltage of UHV transformer medium-voltage winding is 500kV. The terminal voltage regulating method requires insulation technologies and voltage-regulating switch. However, it is hard to develop the switch and insulation technologies. Therefore, neutral point regulating method takes place of medium-voltage winding terminal. The neutral point voltage regulating is different from terminal regulating. In the process of regulating, the voltage of medium terminal changes, but also the voltage of low winding fluctuates according to the change of flux. A The Japan adopts GIS as outlet while bushing is adopted as outlet in China. The 1000kV capacitive oil-air bushing with short lower part is a kind of world-class product. The arc distance of bushing is 9m or so; the top is about 17m away from the ground; its weight is about 6t. The power transformer can endure the eighth earthquake. While, the bushing is the weakest part. Because the dimension of UHV bushing is great, the outlets require great mechanical intensity to resist external forces such as wind pressure and conductor swing. For the sake of safety, mechanical support is added between Weidmann structure and the ground, which is shown in Fig.4. info@himalayal.com Page:3 All right reserved.

375t. When transported on the highway, the gradient between its bottom board of power transformer and the ground should be less than 15. The transportation condition in Japan is poorer. Hence, the split type structure is adopted and the weight per single unit should be about 200t. Fig.5 shows the transportation of UHV transformer on the road. Fig.5 The transportation of UHV power transformer in Japan 3. Insulation Level of UHV Power Transformer Fig.4 External mechanical support for UHV transformer The bushing is supposed to pass the 1h PD test under the 1200kV (5min) power frequency withstand voltage and 1.5Um/ 3 power frequency (Um is the maximum switching voltage). After the bushing is installed, it should withstand 1h test under multiple frequency 1100kV (5min) and 1.5Um/ 2.4 Transportation 3 power frequency. The limit on the size of UHV power transformer being transported is as follows: 12m (length) 4.15m (width) 4.9m (height); the weight limit is At present, there is no available international standards for insulation level of 1000kV UHVAC power transmission system. GB311.1-1997 is suitable for 500kV and below system while IEC60071-1993 mainly targets 765kV and below system. The insulation coordination of Chinese first 1000kV UHVAC power transmission system is determined according to the optimization principle. The limit for overvoltage is in the following: switching overvoltage or substation side is 1.6pu (1pu=1100 2 / 3 kv); the maximum value of line side is 1.7pu; power frequency transient overvoltage or busbar side is 1.3pu; line side is 1.4pu. info@himalayal.com Page:4 All right reserved.

The power frequency withstand voltage value of 220kV and below power transformer is obtained through switching overvoltage, namely: U AC,1min =1.1KU Φm /1.35 (1) Where: U AC,1min : the effective value of test voltage, power frequency 1min, kv KUΦm : maximum line-to-neutral voltage K : switching overvoltage calculation multiple, usually 3 1.1: accumulation factor 1.35: switching impulse coefficient or obtained through the lightning impulse overvoltage, namely: UAC,1min=UBIL/ 2 β (2) Where: UBIL : lightning impulse test voltage, kv β: full wave impulse coefficient, usually 1.7 In the above 220kV system, as the protection level improves, insulation level rises while the value of power frequency withstand voltage declines. The purpose of power frequency withstand test is to confirm whether there is partial discharge and verify the insulation intensity. The probability of short-duration and long-time PD can be calculated via Welbull distribution equation: P 1 (U t t t )=1-exp(-kU tm t tm ). The probability is about 1%-2%. Based on the experience, the probability of partial discharge during the test is far lower than 2%. As for important equipment, the probability of partial discharge should be between 0.1% and 0.2%. The test voltage Ut and test time tt are determined. The operation experience shows that most of UHV power transformer breakdowns occur under the power frequency. Therefore, it is reasonable to extend the power frequency withstand voltage time. 4. Insulation Test 4.1 Overview The UHV power transformer has three windings with different voltage stages. These windings are coupled through flux links to transmit and distribute the electric energy in different circuits. Different insulation coordination principles of three voltage stages lead to various multiples between test voltage and rated voltage or highest switching voltage, which will affect the test voltage of each winding. Besides, the voltage of UHV power transformer with large dimension and capacity is high. The stray parameters of test circuit have a significant influence on the wave front time of lightning impulse. Researches indicate that discharge features and routines of transformer insulation are different if affected by switching impulse test voltage, power frequency test voltage and lightning impulse test voltage. Hence, it is necessary to carefully study the insulation test method of UHV power transformer. 4.2 Lightning impulse test info@himalayal.com Page:5 All right reserved.

The standard waveform of lightning impulse test voltage is (1.2±30%)/(50±20%) μs. It is found that wave front time of actual test for UHV transformer in some countries is 5μs, which exceeds a limit. The wave front time conforms to the standard if applied to Chinese 500kV transformer; however, if applied to 750kV power transformer, the rising time of lightning impulse voltage wave front far exceeds (1.2±30%)μs, and even reaches 4μs. That means that wave front time of UHV transformer will be longer on the UHV power transformer. The influence of 5μs wave front on main insulation and minor insulation is different. Generally speaking, the design and calculation is conducted according to standard waveform. Therefore, electric field distribution of test voltage with longer wave front time is different from design calculation value. The steeper the wave front is, the stricter the minor insulation impulse gradient distribution becomes. According to calculation program, the value of oil field intensity in the impulse test voltage with longer wave front declines. On the one hand, longer wave front cannot completely verify the design of short wave front; on the other hand, the decline of oil field intensity will aggravate the pressure of paper or solid insulation. Please keep that in mind in the design of power transformer. 4.3 Switching impulse test In the 220kV and below power transformer test, the 1min power frequency withstand test (or induced test) is often used to replace the switching impulse test. As 500kV and above power transformer is being put into use, protective equipment such as high-performance arrester is widely used, resulting in the decline of insulation level of electric system. When insulation level of the system falls, we cannot use power frequency withstand test to guarantee the level of switching impulse test, but conduct the switching impulse withstand test for power transformer. Generally speaking, the voltage of switching wave test is transferred according to turn ratio in the three windings. The principle of insulation coordination of UHV transformer three windings is different. If the switching impulse test voltage of UHV end is up to the standard, the test voltage of 500kV side would be relatively low; if test voltage of 500kV side is achieved, UHV end would exceed the limit. Hence, 1min short-duration power frequency withstand test (630kV) is used to replace the switching impulse withstand test. In addition, the wave front of switching overvoltage may reach 3000μs while standard test waveform is 250/2500μs, which needs to be taken into account in the design of the power transformer. 4.4 Induced withstand voltage test The 500kV side of induced withstand voltage test also cannot reach the specified test voltage. The terminal potential of 500kV side can be improved through potential of auxiliary transformer neutral point. For this purpose, the insulation level info@himalayal.com Page:6 All right reserved.

of neutral point should be 66kV and above, and the voltage of 1min power frequency withstand test is 140kV. The terminal test voltage of 500kV side can reach 630kV via improving neutral point potential when the short-duration power frequency withstand test of 500kV is being conducted. The wiring diagram of 500kV short-duration power frequency withstand test is shown in Fig.6. In the Fig.6: G -- medium-frequency generator; T1-- middle power transformer; T2-- auxiliary power transformer. Fig.6 The wiring diagram of 500kV short-duration power frequency withstand test The regulating voltage transformer is placed at the limit positive tap during the test; the induced multiple is 1.633; support voltage of neutral point is Uo=110.2kV; UA=1050/ 3 1.633+110.2=1100kV; UAm=525/ 3 1.05 1.633+110.2=630 kv. If the induced multiple is reduced, test voltage of UHV winding can also be reduced. 3.5 Fast transient overvoltage The oscillating frequency of overvoltage is very high and the wave-front is steep. It is also called steep wave-front overvoltage. The initial forward position is ranging from 3ns to 200ns. Generally speaking, the FTO is less than 2.0pu. Some can reach 2.5pu but rarely 3.0pu. The average value of FTO is lower than lightning impulse withstand level. The FTO has a direct impact on the internal insulation of power transformer. In the direct connection circuit between power transformer and GIS or non-direct circuit, many transformers are subject to FTO, leading to insulation damage. The FTO has a significant effect on the front windings of power transformer. The high-performance arrester, high-voltage reactors in parallel and lower reactance of neutral point cannot limit the FTO. Based on the experience, the most effective measure is to place the open and close switch in the isolation switch of GIS. It is necessary to study the influence of FTO on the UHV transformer insulation. 5. Long-duration Induced Withstand Voltage Test with PD Measurement on Site It is not difficult to perform the routine performance test on site. The long-duration induced withstand voltage test with PD measurement is recommended after installation in order to check the insulation condition after long-distance transportation and on-site installation. info@himalayal.com Page:7 All right reserved.

The test voltage and time can be properly reduced, such as 1.5Um/ 3 to 1.3Um/ 3 and 5min to 1min. It is very difficult to conduct the PD test on site: 1The no-load loss of UHV transformer is expected to reach 200kW. There are also active loss of other parts of test circuit. Hence, power transformer needs to have large capacity. 2The voltage of low-voltage winding is 110kV. It is required that high-voltage low PD middle transformer, compensation reactor and leads with great diameter should be used to avoid the corona; 3 It is very difficult to deal with voltage sharing of high -medium voltage terminal and voltage sharing cover with great diameter. Hence, it is suggested that experts be gathered to study the on-site PD test method of UHV power transformer and the development of test power source. 6. Conclusions (1) The insulation level of UHV power transformer is determined through the principle of insulation coordination optimization. Because the principle of three windings of UHV transformers is different, the test voltage of all winding will be affected. Therefore, some tests for medium-low voltage winding cannot be conducted according to specified mode. Moreover, the great size of UHV power transformer also affect waveform factor of lightning full wave. In summary, as for UHV power transformer, short-duration power frequency withstand test is suggested to replace the switching wave impulse test for 500kV winding. (2) As for the induced withstand voltage test, test voltage of 500kV winding side cannot reach the required value. The short-duration power frequency withstand test is recommended to check the main insulation of 500kV side. The minor insulation fails to pass the test. (3) The wave front time of switching overvoltage of UHV power transmission system is far more than 250μs. The research on features of oil paper insulation under 3000μs wave front is needed. (4) The rising time of wave front of lightning impulse test voltage is likely to far exceed the (1.2±30%) μs. It is necessary to carefully study the influence of different wave front time on the insulation. (5) It is suggested that experts conduct research into the equipment and method of on-site PD test for UHV power transformer. REFERENCES [1] Kovalev V, Panibratets A, Volkova O, et al. The equipment for the AC 1150kV transmission line [C]. International Workshop on UHVAC Transmission on Technology, Beijing: China, 2005. info@himalayal.com Page:8 All right reserved.

[2] Ardito A, de Nigris M, Giorgi A, et al. The Italian 1000kV project [C[. International Workshop on UHVAC Transmission on Technology, Beijing: China, 2005. [3] Yamagata Y, Tamaki E, Ikeda M, et al. Development and field test of 1000kV 3000MVA transformer [C]. CIGRE Paris session 1998. [4] Toshiba. 1000kV transformer [C]. International Workshop on UHVAC Transmission on Technology, Beijing: China, 2005. [5] Kawamura T, Kobayashi T, Ebisawa Y, et al. Development and long term field tests for UHV 3000MVA transformer in Japan [C]. IEC/CIGRE UHV Symposium, Beijing, 2007. [6] GB 311.1-1997 Insulation Coordination of High Voltage Power Transmission Equipment [S]. [7] IEC60071-1-1993. Insulation for coordination high voltage transmission and distribution equipment [S]. info@himalayal.com Page:9 All right reserved.