ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

Similar documents
SECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

This section applies to the requirements for the performance of power system studies by both the Design Engineer and the Contractor.

SECTION POWER SYSTEMS STUDIES

Electrical Overcurrent Studies

2018 Consultant s Handbook Division 26 Electrical ARC Flash Hazard Analysis

Arc Flash Analysis and Documentation SOP

SECTION PANELBOARDS

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

Arc Flash Analysis Training

ADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

3Ø Short-Circuit Calculations

Short Circuit Current Calculations

Electrical Arc Hazards

2014 NEC Changes Part 1

TABLE OF CONTENT

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

B. Manufacturers: Square-D, G.E. or Westinghosue.

{40C54206-A3BA D8-8D8CF }

First Draft Language

Paul Dobrowsky Innovative Technology Services

2015 NFPA 70E. SESHA 2015 ARIZONA MINI CONFERENCE December 10, 2015 Intel Corporation

SECTION DISTRIBUTION SWITCHBOARDS

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General

Webinar: An Effective Arc Flash Safety Program

DESIGN CHECKLIST INTRODUCTION

Electrical PIP ELEGL03 Guidelines for Power Systems Analysis

BED INTERCONNECTION TECHNICAL REQUIREMENTS

Distribution/Substation Transformer

WATER MAIN ALONG ENTRANCE TO ENCINO PS / HWY 281 TO ENCINO TANK Solicitation Number: CO Job No.:

Arc Flash Calculation Methods

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

JEFFERSON LAB TECHNICAL ENGINEERING & DEVELOPMENT FACILITY (TEDF ONE) Newport News, Virginia

Selective Coordination for Emergency and Legally-Required Standby Power Distribution Systems

NOTICE ER Roland Flood Pumping Station Arc Flash Study

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

Comparison of recloser and breaker standards

Education & Training

Arc Flash Mitigation An Overview. Gus Nasrallah, P.E. Electroswitch May 30, 2013

DESIGN STANDARD DS 29

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

SECTION SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS

.2 Accompany all submissions with a transmittal letter, in duplicate, containing:.4 Specification Section number for each submittal

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section ELECTRICAL IDENTIFICATION

SECTION CLOSEOUT SUBMITTALS SECTION CLOSEOUT SUBMITTALS

SECTION OPERATION AND MAINTENANCE DATA

Anticipated schedule, Page 2. Change the Contract Term from 635 Days to be 1,127 Days.

SECTION 16483D ADJUSTABLE FREQUENCY DRIVE - MICRODRIVE (MVX <10-HP)

THREE PHASE PAD MOUNTED DISTRIBUTION TRANSFORMER ARC FLASH TESTING JUNE 23, 2009 FERRAZ SHAWMUT HIGH POWER LABORATORY NEWBURYPORT, MA

SANITARY SEWER SYSTEM ADMINISTRATIVE STANDARDS A.1 SANITARY SEWER SYSTEM PLAN SUBMITTAL PROCEDURES AND GENERAL REQUIREMENTS

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

MISSISSIPPI STATE UNIVERSITY Office of Planning Design and Construction Administration

ARC FLASH HAZARD ANALYSIS AND MITIGATION

2017 ELECTRICAL SAFETY SERVICES. Arc Flash Electrical Maintenance Lockout/Tagout And More

Power System Study for the Pebble #2 Lift Station Las Vegas, Nevada

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES

Taylor County July 2011 SECTION SHOP DRAWINGS, WORKING DRAWINGS AND SAMPLES

Electrical Measurement Safety. Sponsored By:

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

UNION COUNTY VOCATIONAL-TECHNICAL SCHOOLS West Hall Addition Project Raritan Road, Scotch Plains, NJ

NEVADA DEPARTMENT OF TRANSPORTATION Addendum 3 to RFP July 28, 2017

Technical T TECHNICAL. C o n t e n t s SPEEDFAX TM 2017

SECTION SUBMITTAL PROCEDURES

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --

Short-Circuit Current Calculations

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

NATIONAL ELECTRIC SAFETY CODE 2012 EDITION

A. Action Submittals: Written and graphic information that requires Engineer's responsive action.

SECTION DISTRIBUTION SWITCHBOARDS

1

SECTION SUBMITTALS PART 1 - GENERAL 1.01 RELATED DOCUMENTS

A Guide to Establish an Arc Flash Safety Program for Electric Utilities

NFPA-70E. Electrical Safety in the Workplace. Standard for Edition

SECTION CABLE TRAYS

PROTECTIVE DEVICES CO-ORDINATTION TOOLBOX ENHANCED BY AN EMBEDDED EXPERT SYSTEM - MEDIUM AND LOW VOLTAGE LEVELS

Bruce L. Graves /01/$ IEEE. IEEE Industry Applications Magazine PhotoDisc, Inc.

Section Meetings Section Material and Equipment. None Required

Basic Information Required for Photovoltaic Plan Check Submittal *Informational Purposes Only*

East Central College

SECTION SUBMITTAL PROCEDURES

UCCS University Hall Fire Sprinkler System Upgrade March 1, 2011 RTA SECTION SUBMITTAL PROCEDURES PART 1 - GENERAL

(Circuits Subject to Requirements R1 R5) Generator Owner with load-responsive phase protection systems as described in

ENGINEERING STANDARD FOR INSTRUMENTS ELECTRICAL POWER SUPPLY AND DISTRIBUTION SYSTEMS FIRST EDITION MAY 2013

SECTION DEWATERING TANKAGE PART 1 - GENERAL 1.1 RELATED DOCUMENTS

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

Arc Flash and NFPA 70E

A. Action Submittals: Written and graphic information that requires Architect's responsive action.

PROJECT TITLE PROJECT NO: CONTRACT TITLE UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

For crossing under a railroad, contact the specific railroad company's engineering department.

SECTION SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES

Distribution System Development & Preliminary Studies

Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

Standard Development Timeline

Transcription:

ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO. 2018-008-COM.00030 To: Prospective Bidders of Record Date: December 17, 2018 The following changes, additions, revisions, and/or deletions are hereby made a part of the Contract Documents for the aforementioned Project as fully and completely as if the same were fully set forth therein: A. PART 1 BIDDING REQUIREMENTS There are no changes to the Bidding Requirements. B. PART 2 CONTRACT FORMS There are no changes to the Contract Forms in this Addendum. C. PART 3 CONTRACT CONDITIONS 1. Supplementary Conditions 00700 SC-6.08B 2, REPLACE 2. NOT USED with 2. Virginia Department of Environmental Quality Permit. A Certificate to Construct (CTC) has been issued by DEQ for the Project. A copy will be provided to the Contractor by Owner prior to the Notice to Proceed. Contractor shall comply with the terms of the CTC and shall maintain a copy at the Site at all times during the Project. Per the terms of the CTC, Contractor shall coordinate with Owner to apply for and obtain a Certificate to Operate (CTO) before placing the sewer facilities into operation. D. PART 4 SPECIFICATIONS 1. Section 16000 Basic Electrical Requirements, after END OF SECTION (Page 10) and before Section 16111 Conduit, INSERT the attached Section 16000 Appendix: Arc Flash Analysis. 2. Section 17000 CONTROL AND INFORMATION SYSTEMS SCOPE AND GENERAL REQUIREMENTS, 1.04 A after S-L Controls (Sherwood Logan); and before or Micro-Tech Designs, Inc. INSERT Lord & Company, Inc;.

E. PART 5 DRAWINGS There are no changes to the Drawings in this Addendum. END OF ADDENDUM QUESTIONS AND ANSWERS NO. 2 1. Spec 16000, Part 1-General, par. 1.01.C.7 states to Provide an arc flash hazard analysis in accordance with the Owners Requirements as shown in the Appendix. I cannot find these requirements in the Appendix, please clarify. Please see Addendum No. 2. END OF QUESTIONS AND ANSWERS

SECTION 16000 - APPENDIX ARC FLASH HAZARD ANALYSIS PART 1 -- GENERAL 1.01 THE REQUIREMENT A. The Contractor shall provide Short Circuit Studies, Equipment Evaluation Studies, Protective Device Coordination Studies, Load Flow Analyses, and Arc Flash Hazard Studies performed by a professional electrical engineer currently registered in the Commonwealth of Commonwealth of Virginia. B. The scope of work for these studies shall include the Courtland Pump Station only, the existing Courtland Treatment Plant (which is to be demolished) is not included. C. Prior to receiving final approval of the distribution equipment shop drawings for the equipment proposed under this Contract and/or prior to release of that equipment for manufacture, the Preliminary Study Report, as specified herein, shall be submitted and approved. Contractor shall expedite the completion of the Preliminary Study Report so that final approval of proposed equipment is not delayed. 1.02 REFERENCE CODES AND STANDARDS A. Institute of Electrical and Electronic Engineers (IEEE): 1. Standard 141, Recommended Practice for Electrical Power Distribution for Industrial Plants 2. Standard 241, Recommended Practice for Electrical Power Systems in Commercial Buildings 3. Standard 242, Recommended Practice for Protection and Coordination of Industrial and Commercial Systems 4. Standard 399, Recommended Practice for Industrial and Commercial Power System Analysis 5. Standard 519-2014, Recommended Practices and Requirements for Harmonic Control in Electric Power Systems 6. Standard 1584-2002/2004a, IEEE Guide for Performing Arc-Flash Hazard Calculations 32389-022\Arc Flash:012/2018 16000 Appendix -1 COURTLAND PUMP STATION

B. American National Standards Institute (ANSI): 1. Standard C37.90, IEEE Standard for Relays and Relay Systems Associated with Electric Power Apparatus 2. Standard C37.91, Guide for Protective Relay Applications to Power Transformers 3. Standard C37.95, Guide for Protective Relaying of Utility-Consumer Interconnections. 4. Standard C37.96, Guide for AC Motor Protection 5. Standard C57.12.59, Guide Dry-Type Transformer Through-Fault Current Duration 6. Standard C.57.13, Standard Requirements for Instrumentation Transformers 7. Standard C57.109, Guide for Liquid-Immersed Transformer Through Fault-Current Duration C. National Electrical Code (NEC) D. National Fire Protection Agency (NFPA): 1. NFPA 70E, Standard for Electrical Safety in the Workplace (2018 edition) 1.03 SUBMITTALS A. The Contractor shall submit for review and approval, four (4) paper copies of the Preliminary Power System Studies Report, four (4) paper copies of the Pre-final Power System Studies Report, and six (6) paper copies of the Final Power System Studies Report. One (1) electronic copy of each report shall be also submitted on a CD. The electronic version of each report shall be in the PDF file format. Each section of the report shall be placed in a separate PDF file to allow fast and easy navigation between sections. Additional details regarding the report requirements are specified elsewhere herein. B. All Reports shall bear the signature and seal of the professional electrical engineer that performed the study. C. The Contractor shall also submit one (1) electronic copy of the system model and all required database files generated by the software analysis package used. Files shall be placed on a CD and submitted with the Preliminary, Pre-final, and Final Power System Studies Reports. 1.04 QUALIFICATIONS A. The Power System Studies shall be performed by a professional electrical engineer registered in the Commonwealth of Virginia. The registered professional electrical engineer shall have a minimum of five (5) years of experience in performing power systems studies. 32389-022\Arc Flash:012/2018 16000 Appendix -2 COURTLAND PUMP STATION

B. The resume of the registered professional electrical engineer shall be submitted for approval prior to the start of work. An experience table shall also be provided detailing the power systems studies of similar scope to this Contract that have been performed by the proposed engineer over the last two (2) years. The table shall, at a minimum, list the facility owner s name, facility contact person with phone number and email address, and overall scope of work that was provided. PART 2 -- PRODUCTS 2.01 POWER SYSTEM STUDIES A. General 1. The Contractor shall provide Short Circuit Studies, Equipment Evaluation Studies, Protective Device Coordination Studies, Load Flow Analyses, and Arc Flash Hazard Studies for the entire electrical system. The studies shall be performed in accordance with IEEE 399, Recommended Practice for Industrial and Commercial System Power Analysis (IEEE Brown Book). 2. The studies shall include all portions of the electrical distribution system from the serving electric utility company protective devices, the normal and standby power sources down to and including the 208-volt equipment. The studies shall include all motor controllers, transfer switches, and panelboards as shown on the Drawings. System connections and those which result in maximum fault conditions shall be adequately covered in the study. 3. The studies shall be performed with the aid of SKM Systems Analysis Power Tools for Windows (PTW) software, Version 8.0 or newer. No other software analysis packages are acceptable. B. Data Collection for the Studies 1. The Contractor shall collect all required utility transformer and service information for use in these studies. The serving electric utility representative contact information can be found in Section 16000, Basic Electrical Requirements. 2. All other information required for the studies shall be obtained from approved shop drawing submittals for the equipment included under this Contract. C. Short Circuit Studies 1. The short circuit study shall be performed in accordance with the latest editions of IEEE Std. 399 and IEEE Std. 141. 2. The study input data shall include the serving electric utility company's short circuit contribution, resistance and reactance components of the branch impedances, the X/R ratios, base quantities selected, and other source impedances. 3. Short circuit close and latch duty values and interrupting duty values shall be calculated on the basis of assumed three-phase bolted short circuits at each bus, 32389-022\Arc Flash:012/2018 16000 Appendix -3 COURTLAND PUMP STATION

motor controller, distribution panelboard, pertinent branch circuit panel and other significant locations through the system. The short circuit tabulations shall include symmetrical fault currents, and X/R ratios. For each fault location, the total duty on the bus, as well as the individual contribution from each connected branch, shall be listed with its respective X/R ratio. 4. The short circuit study report shall include recommendations for equipment selection based on calculated short circuit values and all input and output data from the software model. D. Equipment Evaluation Studies 1. An equipment evaluation study shall be performed to determine the adequacy of proposed circuit breakers, panelboards, motor controllers, automatic transfer switches, busses, etc. located at the plant by tabulating and comparing the short circuit ratings of these devices with the calculated fault currents. Appropriate multiplying factors based on system X/R ratios and protective device rating standards shall be applied. A table shall be provided in the report showing the calculated fault currents and the corresponding short circuit ratings of the equipment. E. Protective Device Coordination Studies 1. A protective device coordination study shall be performed to provide the necessary calculations and logic decisions required to select or to check the selection of power fuse ratings, protective relay characteristics and settings, ratios and characteristics of associated current transformers, and low voltage circuit breaker trip characteristics and settings. 2. The coordination study shall include all low voltage classes of equipment from the serving electric utility company service protective devices down to and including all adjustable circuit protective devices. The phase and ground overcurrent protection shall be included as well as settings of all other adjustable protective devices. 3. The time-current characteristics of the proposed protective devices shall be printed on a log-log scale. The plots shall include complete titles, representative one-line diagram and legends, significant motor starting characteristics, complete parameters of transformers, complete operating bands of low voltage circuit breaker trip curves and fuses. The coordination plots shall indicate the types of protective devices selected, proposed relay taps, time dial and instantaneous trip settings, transformer magnetizing inrush and ANSI transformer withstand parameters, cable thermal overcurrent withstand limits and significant symmetrical and asymmetrical fault currents. All restrictions of the National Electrical Code shall be adhered to and proper coordination intervals and separation of characteristic curves shall be maintained. The coordination plots for phase and ground protective devices shall be provided on a system basis. A sufficient number of separate curves shall be used to clearly indicate the coordination achieved. 4. The selection and settings of the protective devices shall be provided separately in a tabulated form listing circuit identification, IEEE device number, current 32389-022\Arc Flash:012/2018 16000 Appendix -4 COURTLAND PUMP STATION

transformer ratios and connections, manufacturer and type, range of adjustment and recommended settings. F. Load Flow Analyses 1. A load-flow analysis shall be performed to determine the steady-state loading profile of the pump station. The analysis shall be based on both the serving electric utility as a source and the standby generator as a source. From the results of the load flow analysis, the report shall indicate areas of overloaded conductors or equipment in the power distribution system design. 2. The report shall also include a total source load summary table, as well as single line diagrams showing only the load flow data. 3. Load flow analysis results shall also be presented in a tabular format in the report. G. Arc Flash Hazard Studies 1. An Arc Flash Hazard Study shall be performed in accordance with IEEE Std. 1584, NFPA 70E, and OSHA 29-CFR, Part 1910 Subpart S. 2. The Arc Flash Hazard Study Report shall include but not be limited to the following: a. An executive summary outlining the electrical distribution system b. A brief overview of what arc flash hazards are and how to avoid them. c. Serving electric utility information received. Copies of the information received shall be included in an appendix. d. All assumptions made to complete the report e. Definitions of key terms used in the report f. Any recommendations to reduce the arc flash incident energies where they are found to exceed 12 cal/cm^2. Any/All possible protective device settings changes that can be made to reduce the incident energy below this level, but that also do not affect the coordination of the electrical system, shall be discussed. g. Arc flash hazard warning labels as specified herein. h. An NFPA 70E energized work permit for each location where a warning label is provided. i. Arc flash evaluation summary sheets as specified herein 32389-022\Arc Flash:012/2018 16000 Appendix -5 COURTLAND PUMP STATION

3. The following parameters shall be used in the Arc Flash Hazard Study: a. Working distance for all equipment: 18 b. Maximum arc duration for all equipment: 2 seconds c. Incident energies, arc flash hazard boundaries, and hazard risk categories shall be calculated over a ±15% of calculated arcing fault current. The worst case incident energies that result shall be used in the study report. d. The equipment that connects to both the electric utility service and the standby power is in an open-transition configuration. The power sources will be incapable of paralleling with each other. e. The arc flash analysis shall be performed as if the facility is being supplied by either of the electric utilities and as if the facility is being supplied by the standby generators. The worst case values from each calculation shall be used in the study report. 4. Arc Flash Warning Labels shall be produced for each location that allows access to energized parts. Labels shall be printed in color on adhesive backed labels. Labels shall be an ANSI Z535.4 compliant (minimum size 4 in. x 6 in.) thermal transfer type label. For incident energy values of less than 40 cal/cm^2, the labels shall have an orange colored header with the word WARNING. For incident energy values equal to and above 40 cal/cm^2, the labels shall have a red colored header with the word DANGER. Each label shall include the following information: a. Bus name b. System operating voltage c. Date of issue d. Flash hazard protection boundary e. Incident energy level 5. Arc Flash Evaluation Summary Sheets shall be produced. Summary sheets shall list the following: a. Bus name b. Upstream protective device name and protective device settings c. Bus line-to-line voltage d. Bus bolted fault e. Protective device bolted fault current 32389-022\Arc Flash:012/2018 16000 Appendix -6 COURTLAND PUMP STATION

f. Arcing fault current g. Protective device trip / delay time h. Breaker opening time i. Solidly grounded column j. Equipment type k. Gap 2.02 Study Reports l. Arc flash boundary m. Working distance n. Incident energy A. The results of the Power Systems Studies shall be summarized in a series of reports. A total of three (3) separate reports shall be provided as follows: 1. Preliminary Report The Preliminary Report shall consist of all power systems studies as specified herein, with the following exceptions: a. NFPA 70E energized work permits shall not be included b Arc flash hazard warning labels shall be printed on plain paper for format review purposes only. Actual labels with calculated values shall not be included. 2. Pre-final Report The Pre-final Report shall incorporate all comments received from the previous report review and shall include specific equipment data from the approved shop drawings of the proposed electrical equipment. The Pre-final Report shall consist of all power systems studies as specified herein, with the following exceptions: a. NFPA 70E energized work permits shall not be included b. Sample arc flash hazard warning labels shall be printed on plain paper for calculated value review purposes. Actual adhesive labels shall not be included. 3. Final Report The Final Report shall consist of all power systems studies as specified herein, including final adhesive arc flash hazard warning labels. Final report shall incorporate all installed electrical equipment, including any field changes made during construction, and all comments received from the previous report review. All as-left protective device settings shall be included in the report. B. Reports shall be furnished in the quantities specified herein, neatly organized into properly 32389-022\Arc Flash:012/2018 16000 Appendix -7 COURTLAND PUMP STATION

identified 3 (minimum) 3-ring binders. Tabs shall clearly separate each section of the report. Each report shall begin with a table of contents. The following sections shall be included in the report as a minimum: 1. Executive Summary 2. Short Circuit Study 3. Equipment Evaluations 4. Protective Device Coordination Study 5 Load Flow Analysis 6. Arc Flash Study C. All data used in the reports such as conductor sizes and lengths, motor sizes, utility contribution information, and the like shall be included in the appendices of the report. D. All single line diagrams and time current curves shall be provided in the reports on 11x17 paper, properly folded to fit into the report binder. Use of standard 8.5x11 paper for these purposes is not permitted. Single line diagrams shall be appropriately split up between several sheets (if required) to allow the drawing scale to be adjusted in order to make text and symbols legible. PART 3 EXECUTION 3.01 FIELD ADJUSTMENT A. Contractor shall adjust all relay and protective device settings according to the recommended settings table provided in the approved Pre-Final Report. B. Contractor shall make minor modifications to equipment as required to accomplish conformance with short circuit and protective device coordination studies. 3.02 ARC FLASH LABELS A Contractor shall place approved adhesive arc flash labels on equipment after the Final Report is reviewed and approved. 32389-022\Arc Flash:012/2018 16000 Appendix -8 COURTLAND PUMP STATION

3.03 TRAINING A. The Contractor shall train the Owner s electrical personnel of the potential arc flash hazards associated with working on energized equipment. The training shall meet the following requirements: 1. Contractor shall submit all training material including agenda, handout, presentation, and objectives 30 days in advance of the proposed training date. The training shall be designed to last approximately 4-hours. 2. Owner may provide a training room if required by Contractor. The training room will be located at Loudoun Water s Main Office in Ashburn, Virginia. 3. The Contractor shall provide an Instructor with a current Professional Engineering License issued by NCEES and minimum of 5-years professional experience in arc flash hazards associated with working on energized equipment as approved by the Owner. 4. Contractor shall provide training material for 15 trainees. 5. Contractor shall provide Certificates of Attendance to all attendees upon completion of the training session. - END OF 16000 APPENDIX - 32389-022\Arc Flash:012/2018 16000 Appendix -9 COURTLAND PUMP STATION

THIS PAGE INTENTIONALLY LEFT BLANK