A NOVEL APPROACH TOWARDS SIX-STEP OPERATION IN OVERMODULATION REGION IN SVPWM VSI

Similar documents
A Detailed Model of The Space Vector Modulated Control Of A VVVF Controlled Ac Machine Including The Overmodulation Region

An Induction Motor Control by Space Vector PWM Technique

Performance Analysis of Space Vector Modulation

THREE-PHASE voltage-source pulsewidth modulation

Modeling and Simulation of Induction Motor Drive with Space Vector Control

Analysis of Voltage Source Inverters using Space Vector PWM for Induction Motor Drive

Analysis, Simulation and Implementation of Space Vector Pulse Width Modulation For Speed Control Of Induction Motor

Control of Induction Motor Fed with Inverter Using Direct Torque Control - Space Vector Modulation Technique

Simulation of Space Vector Modulation in PSIM

NOVEL SPACE VECTOR BASED GENERALIZED DISCONTINUOUS PWM ALGORITHM FOR INDUCTION MOTOR DRIVES

ANALYSIS OF EFFECTS OF VECTOR CONTROL ON TOTAL CURRENT HARMONIC DISTORTION OF ADJUSTABLE SPEED AC DRIVE

Switching Loss Characteristics of Sequences Involving Active State Division in Space Vector Based PWM

Compensation for Inverter Nonlinearity Using Trapezoidal Voltage

Performance Analysis of SPWM and SVPWM Based Three Phase Voltage source Inverter. K. Latha Shenoy* Dr. C.Gurudas Nayak** Dr. Rajashekar P.

CHAPTER 2 CONTROL TECHNIQUES FOR MULTILEVEL VOLTAGE SOURCE INVERTERS

CHAPTER 4 CONTROL ALGORITHM FOR PROPOSED H-BRIDGE MULTILEVEL INVERTER

Simulation And Comparison Of Space Vector Pulse Width Modulation For Three Phase Voltage Source Inverter

Simulation Analysis of Three Phase & Line to Ground Fault of Induction Motor Using FFT

MULTILEVEL inverters [1], [2] include an array of power

II. PROPOSED CLOSED LOOP SPEED CONTROL OF PMSM BLOCK DIAGRAM

A NEW DESIGN METHOD OF OUTPUT FILTER FOR SPACE VECTOR PWM FED INDUCTION MOTOR

A Fuzzy Controlled PWM Current Source Inverter for Wind Energy Conversion System

Synchronous Current Control of Three phase Induction motor by CEMF compensation

Improved direct torque control of induction motor with dither injection

A Novel Four Switch Three Phase Inverter Controlled by Different Modulation Techniques A Comparison

Performance Analysis of Matrix Converter Fed Induction Motor with Different Switching Algorithms

ON-LINE NONLINEARITY COMPENSATION TECHNIQUE FOR PWM INVERTER DRIVES

Analysis of the Phase Current Measurement Boundary of Three Shunt Sensing PWM Inverters and an Expansion Method

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Low Switching Frequency Pulse Width Modulation For Induction Motor Drives

A Sliding Mode Controller for a Three Phase Induction Motor

Effective Algorithm for Reducing DC Link Neutral Point Voltage and Total Harmonic Distortion for Five Level Inverter

MATLAB/SIMULINK MODEL OF FIELD ORIENTED CONTROL OF PMSM DRIVE USING SPACE VECTORS

Space Vector PWM Voltage Source Inverter Fed to Permanent Magnet Synchronous Motor

PERFORMANCE EVALUATION OF THREE PHASE SCALAR CONTROLLED PWM RECTIFIER USING DIFFERENT CARRIER AND MODULATING SIGNAL

Decoupled Space Vector PWM for Dual inverter fed Open End winding Induction motor drive

Hysteresis Controller and Delta Modulator- Two Viable Schemes for Current Controlled Voltage Source Inverter

Comparative Analysis of Space Vector Pulse-Width Modulation and Third Harmonic Injected Modulation on Industrial Drives.

SPACE VECTOR PULSE WIDTH MODULATION SCHEME FOR INTERFACING POWER TO THE GRID THROUGH RENEWABLE ENERGY SOURCES

Speed Control of Induction Motor using Space Vector Modulation

Simulation with Experimental Measurement of Voltage Total Harmonic Distortion and Harmonic Frequency in Three-Phase Induction Motor fed from Inverter

ABSTRACT I. INTRODUCTION

Z-SOURCE INVERTER WITH A NEW SPACE VECTOR PWM ALGORITHM FOR HIGH VOLTAGE GAIN

Module 5. DC to AC Converters. Version 2 EE IIT, Kharagpur 1

SVPWM Based Two Level VSI for Micro Grids

NPTEL

A Dynamic Modeling Permanent Magnet Synchronous Motor Drive System

MODELING AND SIMULATION OF A THREE PHASE MULTILEVEL INVERTER FOR HARMONIC REDUCTION BASED ON MODIFIED SPACE VECTOR PULSE WIDTH MODULATION (SVPWM)

A DUAL FUZZY LOGIC CONTROL METHOD FOR DIRECT TORQUE CONTROL OF AN INDUCTION MOTOR

Induction Motor Drive using SPWM Fed Five Level NPC Inverter for Electric Vehicle Application

A Switched Boost Inverter Fed Three Phase Induction Motor Drive

Simulation and Analysis of Space Vector PWM Inverter Fed Three Phase Induction Motor Drive

International Journal of Modern Engineering and Research Technology

A Comparative Study of Sinusoidal PWM and Space Vector PWM of a Vector Controlled BLDC Motor

Development of a V/f Control scheme for controlling the Induction motorboth Open Loop and Closed Loop using MATLAB.

Enhanced Performance of Multilevel Inverter Fed Induction Motor Drive

HARDWARE IMPLEMENTATION OF DIGITAL SIGNAL CONTROLLER FOR THREE PHASE VECTOR CONTROLLED INDUCTION MOTOR

DESIGN ANALYSIS AND IMPLEMENTATION OF SPACE VECTOR PULSE WIDTH MODULATING INVERTER USING DSP CONTROLLER FOR VECTOR CONTROLLED DRIVES

Simulation of Speed Control of Induction Motor with DTC Scheme Patel Divyaben Lalitbhai 1 Prof. C. A. Patel 2 Mr. B. R. Nanecha 3

CHAPTER 4 PI CONTROLLER BASED LCL RESONANT CONVERTER

Control of Induction Motor Drive using Space Vector PWM

CURRENT FOLLOWER APPROACH BASED PI AND FUZZY LOGIC CONTROLLERS FOR BLDC MOTOR DRIVE SYSTEM FED FROM CUK CONVERTER

DIRECT TORQUE CONTROL OF THREE PHASE INDUCTION MOTOR BY USING FOUR SWITCH INVERTER

Pulsewidth Modulation for Power Electronic Converters Prof. G. Narayanan Department of Electrical Engineering Indian Institute of Science, Bangalore

Control of grid connected inverter system for sinusoidal current injection with improved performance

CHAPTER 5 CONTROL SYSTEM DESIGN FOR UPFC

Flux-Weakening in IPM Motor Drives: Comparison of State-of-Art Algorithms and a Novel Proposal for Controller Design

DIGITAL SIMULATION OF MULTILEVEL INVERTER BASED STATCOM

International Journal of Scientific & Engineering Research, Volume 5, Issue 6, June-2014 ISSN

CHAPTER 2 CURRENT SOURCE INVERTER FOR IM CONTROL

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

IJCSIET--International Journal of Computer Science information and Engg., Technologies ISSN

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 05 Issue: 12 Dec p-issn:

SIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC

Comparison of Three SVPWM Strategies

Mathematical Analysis of SVPWM for Inverter fed DTC of Induction motor Drive

Design of High-speed Induction Motor Controllers using Space vector Pulse Width Modulation

Australian Journal of Basic and Applied Sciences. Simulation and Analysis of Closed loop Control of Multilevel Inverter fed AC Drives

Induction Motor Drives Fed By Four- Leg Inverter

OPTIMAL TORQUE RIPPLE CONTROL OF ASYNCHRONOUS DRIVE USING INTELLIGENT CONTROLLERS

VECTOR CONTROL SCHEME FOR INDUCTION MOTOR WITH DIFFERENT CONTROLLERS FOR NEGLECTING THE END EFFECTS IN HEV APPLICATIONS

MODELLING AND SIMULATION OF DIODE CLAMP MULTILEVEL INVERTER FED THREE PHASE INDUCTION MOTOR FOR CMV ANALYSIS USING FILTER

South Asian Journal of Engineering and Technology Vol.2, No.16 (2016) 21 30

Generation of Voltage Reference Signal in Closed-Loop Control of STATCOM

ISSN: [Shukla* et al., 6(10): October, 2017] Impact Factor: 4.116

International Journal of Emerging Researches in Engineering Science and Technology, Volume 1, Issue 2, December 14

Reduction of Harmonics and Torque Ripples of BLDC Motor by Cascaded H-Bridge Multi Level Inverter Using Current and Speed Control Techniques

ANALYSIS OF POWER QUALITY IMPROVEMENT OF BLDC MOTOR DRIVE USING CUK CONVERTER OPERATING IN DISCONTINUOUS CONDUCTION MODE

A Low Cost SVPWM Controller for Five-Phase VSI Using PIC18F4550

Matlab Simulation Model Design of Fuzzy Controller based V/F Speed Control of Three Phase Induction Motor

COMPARISON STUDY OF THREE PHASE CASCADED H-BRIDGE MULTI LEVEL INVERTER BY USING DTC INDUCTION MOTOR DRIVES

FUZZY LOGIC BASED DIRECT TORQUE CONTROL OF THREE PHASE INDUCTION MOTOR

Simulation and Dynamic Response of Closed Loop Speed Control of PMSM Drive Using Fuzzy Controller

A HIGH RELIABILITY SINGLE-PHASE BOOST RECTIFIER SYSTEM FOR DIFFERENT LOAD VARIATIONS. Prasanna Srikanth Polisetty

Field Programmable Gate Array-Based Pulse-Width Modulation for Single Phase Active Power Filter

Simulation and Dynamic Response of Closed Loop Speed Control of PMSM Drive Using Fuzzy Controller

Simulation & Implementation Of Three Phase Induction Motor On Single Phase By Using PWM Techniques

CHAPTER 4 MODIFIED H- BRIDGE MULTILEVEL INVERTER USING MPD-SPWM TECHNIQUE

Performance Analysis of modulation techniques for Induction motor fed by Diode-Clamped NPC Inverter

CHAPTER 3 H BRIDGE BASED DVR SYSTEM

Transcription:

A NOVEL APPROACH TOWARDS SIX-STEP OPERATION IN OVERMODULATION REGION IN SVPWM VSI Anurag Tripathi 1, Bharti Dwivedi 1 and Dinesh Chandra 2 1 Department of Electrical Engineering, Institute of Engineering and Technology, Sitapur Road, Lucknow, India 2 Department of Electrical Engineering, MNNIT, Allahabad, India E-Mail: shuklakavita@rediffmail.com ABSTRACT Over modulation switching enables the operation of an inverter beyond the normal region, unto the six-step range. As volt-sec compensation is not possible in every sampling period, it is achieved in every sector of operation in overmodulation. The approach presented here segregates the OVM switching into two modes namely, Mode-I and Mode- II. In Mode-I, the required fundamental volt-sec compensation is obtained in every sector by reducing the switching times of the zero voltage vectors and a proportionate increase in the switching times of the active voltage vectors. This process continues until the modulation index of 0.977 beyond which the zero vector switching region is exhausted. In Mode-II, a systematic pattern of switching is proposed, that gets modified with the increasing modulation index. Such switching patterns minimize switching on one hand and give a better harmonic spectrum on the other. The operation of the extended range of mode I and the smooth transition into mode II and six-step is verified using simulation results. Keywords: over modulation, harmonic distortion, volt sec compensation. INTRODUCTION Implementations of various PWM techniques have been a major area of research. Latest of them is space vector modulation technique. The basic advantage of SVPWM is that it increases the linear range of operation till 0.907 unlike the conventional sine PWM method having linear range till 0.785. The concept of operation of linear or non-linear region is based on modulation index that indirectly provides information about the inverter utilization capability.. This feature of SVPWM puts on edge over other PWM techniques. Till MI 0.907 SVPWM inverter operates in the linear region meaning whereby that the modulation index is directly proportional to the fundamental component of the line side voltage. Beyond MI = 0.907 SVPWM inverter stands operating in the non-linear or in other words overmodulation region. This overmodulation region is further divided into two zones. Zone 1 lies between 0.907 < MI 0.9535 and zone II lies between 0.9535 < MI 1.0. The main aim of any PWM technique is to utilize the inverter to its full capacity that is achieved only with six-step operation. In six-step operation, maximum value of the desired voltage vector is obtained. In SVPWM, the operation from under modulation to overmodulation finally leads to the above-mentioned fact i.e. to achieve a six-step operation. Till now the SVPWM and its overmodulation strategy have been studied using voltage vector [1,3] and current dynamics [2] for high performance ac drive system. Fourier series expansion of the waveform of the phase voltage reference is proposed as a new overmodulation strategy in [3]. Over modulation algorithm is proposed for low switching frequency PWM application again taking relationship between controls variable and fundamental voltage based on number of pulses [4]. In addition, Bolognani and Zigliotto have suggested a strategy for smooth transition from overmodulation to six-step operation of SVM inverters in [5]. A classification algorithm developed by A.R. Bakashai et al in [6] also aid in achieving a smooth transition from overmodulation to square wave operation without any approximation. Currently, a few of the researchers [7,8] have developed a new strategy of controlling Induction motor using SVPWM by taking directly stator flux error as the ref. value replacing the voltage vector. Some of the researchers [9,10] have gone to the extent of proposing new strategies in over modulation Zone II with the modification in the formulae of calculating the continuous switching of a single voltage vector. None of the above-mentioned researchers has considered the extension of the range of either of the zones of operation. Contribution and organization of the paper According to Faraday s law of electromagnetic induction (neglecting stator resistance), and in discreet form this can be written as. Hence, it is seen that the requisite change in stator flux vector can be achieved through the application of the voltage vector for a specific duration. The proposed strategy of extending the range of overmodulation zone I and further achieving a smooth transition to overmodulation II and six step, considers the instantaneous value of stator voltage vector. The gating pattern is generated by the sampled error between the reference voltage vector and the estimated or actual voltage vector. Consideration of stator voltage vector error as the commanded value helps to achieve zero flux vector error in a fundamental cycle for all operating angular velocities as in [8]. The achievement of the increased MI for zone I overmodulation, carried out right from the fundamental principle of calculating the switching times and selection 8

of switching states is discussed in this paper. The mathematical equations developed are simulated through MATLAB / SIMULINK. SPACE VECTOR MODULATION TECHNIQUE Figure-1 shows the three modes of operation of SVPWM. The operation within the inscribed circle of the regular hexagon is the linear region while operation outside the inscribed circle until the circumscribed circle around the hexagon depicts overmodulation region. 010 1 0 2 δ overmodulation 3 4 5 001 101 110 V* 100 Locus of Undermodulation (Linear Region) Overmodulation (Zone I & II) Desired Ref Voltage Figure-1. Three modes of operation of SVPWM. At the end of the liner modulation i.e. at a MI of 0.907, the reference voltage vector tip traces a circle whose radius becomes greater than that of the inscribed circle of the hexagon representing the voltage vectors that can be applied in the six sectors. OVERMODULATION (ZONE I) Figure-2 As can be seen from the Figure-2, OB = Vs (k) max (maximum available voltage vector in a sector), OD = Vs * (k) (desired voltage vector also called the reference voltage) and OC = 0.866 Vs(k) max (maximum voltage vector available in the linear region of modulation). The whole situation in the OVM I stage can be divided into two regions A & B. The value of the reference voltage vector i.e. Vs * (k) = OD is more than that available i.e. OC, in region A. In region B, the reference voltage vector Vs * (k) is less than the available voltage vector (whose maximum value is Vs(k) max ). In region A, maximum loss of voltage occurs when the desired reference vector is at 30 degrees and the available voltage vector is only OC= 0.866 Vs (k) max so Max loss at this angle = Vs*(k)-0.866 Vs(k)max (1) For the switching times τau_a, τau_b, and τau_0, τau_0 becomes negative in region A, which otherwise is not possible practically, so τau_0 is taken to be equal to zero and the switching is obtained by applying active states for τau_a and τau_b period only. The voltage vector in this region thus moves along the hexagon till the boundary of the region B starts. In the region B, there is an ample reference vector magnitude to accommodate the τau_0 so all three switching times are applied albeit in a modified manner. The loss of angular velocity in the region A is compensated in the region B. This compensation results in the modification of the switching times. The rationale of the proposed method lies in the fact that since negative values of τau_0 are not possible to achieve in the region A, the value of τau_0 is kept zero in this region and only the two active voltage vectors are switched. The accompanying loss in the volt-seconds has to be compensated. This is done in the region B where the values of τau_a & τau_b have to be increased by applying the factor Kc, which is decided by equating the maximum loss (of volt-sec) in the region A with the maximum possible value of compensation that can be provided in the region B. Thus the average angular velocity can be made equal to the desired (reference) value in a sector rather than that in a complete cycle. It has been found that the modulation index at which negative values of τau_0 start occurring (during simulation) is the value at and beyond which compensation for the loss of volt-sec in the region A cannot be done. The modified switching times are τau_a1 = τau_a + 0.5 K C τau_0 τau_b1 = τau_b + 0.5K C τau_0 τau_01 = τau_s τau_a1 τau_b1 (2) Where K C is a compensation factor which decides what percentage of the maximum voltage vector ought to be required to compensate for the loss of angular velocity in the region A. In the literature reported thus far [9], the end of over modulation region I happens at a modulation index of 0.9535 after which over modulation II sets in which comprises of a continuous application of a particular voltage vector to achieve a particular value of angular velocity of the voltage vector. The simulated results with the above switching times in equations (2) show that the overmodulation I region persists beyond the above reported modulation index and it gets stretched till 0.977. This is an extension of around 2.35 % which is a significant improvement. 9

OVERMODULATION (ZONE II) In the overmodulation Zone II region, the time till which a continuous application of a particular voltage vector is done, is the duration till when due to absence of switching, the control feature is lost. This keeps on increasing with the increased velocity demand. During this period, any one vector is held for a certain time. Zone II uses the concept of continuous application of a particular voltage vector in order to achieve the desired average voltage vector and hence angular velocity. The operation in Zone II finally leads to the achievement of six-step output voltage. At six-step stage, the control on the angular velocity is lost but maximum value of the voltage is available giving a fixed but maximum angular velocity. (or the frequency which is that of the fundamental component of the inverter output voltage waveform) is 50 Hz. Thus the normalized value of the voltage vector will be given by: Vs (normalized) = [(2*pi*50)/20000] = 0.0157. So long as the value of the reference voltage vector locus does not cross the 0.0157 mark (as is shown in figs 3(b) for MI = 0.9535 and 4(b) for MI = 0.97), the compensation is possible and the overmodulation region I is said to exist. RESULTS AND DISCUSSIONS The simulated results using MATLAB/SIMULINK are given in Figures 3, 4 and 5 where typical values of MI = 0.9535, 0.97 and 0.99 are considered respectively, for showing the difference in the various waveforms from the usual limit of over modulation Zone I i.e. MI = 0.9535. Figure-3(c) Figure-3(a) The plots of various parameters are shown in Figures 3(a, b and c) for MI = 0.9535, which is the existing reported value of MI where overmodulation region I terminates and thus this MI value demarcates over modulation zone I and zone II. Figure 3(a) proves that the actual value of voltage vector strictly tries to follow the reference voltage vector and through the compensation the areas can become equal. The same is depicted for MI = 0.97 in Figure-4(a) where the maximum loss in actual voltage vector is successfully compensated by the maximum available voltage vector at the vertices of the hexagon. The same control and compensation is not possible for MI = 0.99 as is clear from Figure-5(a). Here, clearly overmodulation Zone II exists and a continuous switching of a single voltage vector control technique is adopted to finally reach to six-step voltage level. Figure-3(b) In the above simulations the switching frequency has been taken as 20 KHz and the modulating frequency Figure-4(a) 10

Figure-4(b) Figure-5(b) Figure-4(c) Figures 4(a, b and c) show the plots of same parameters considered in Figure-3 but for MI = 0.97. Figure-3(b) and Figure-4(b) reflect the difference in value of magnitude of reference voltage vector. The increased value of the normalized voltage vector in Figure-4(b) is still within the range (0.0157) where compensation is possible, whereas in Figure-5(b) for MI = 0.99 the magnitude of voltage vector crosses the boundary of the desired value and thus loses control through compensation process. Figure-5(c) The waveforms of various parameters for MI = 0.99 are given in Figures 5(a, b and c). As seen from Figure-5(c) which is the plot between τau_0 and Vs(k), the value of τau_0 becomes negative, unlike in Figure-3(c) and Figure-4(c) where the values of τau_0 are positive. The negative values of τau_0 directly reflect the zone of operation in over modulation II region in SVPWM inverter. Since τau_0 cannot be negative so is kept zero and the control is achieved through a continuous application of the active state vectors. Thus, the overmodulation zone II operation starts. The simulated results in Figures 3(c), 4(c) and 5(c) define and conclude the extended range of operation of Zone I in overmodulation region. A smoother control of torque and speed of threephase induction motor is easily possible now with extended range of overmodulation Zone I. This gives greater flexibility in obtaining the required input voltage of the motor from the SVPWM inverter by generating the gating signals accordingly. It also helps in a better and smooth transition from overmodulation to six step operation. Figure-5(a) 11

CONCLUSIONS The novel approach towards the achievement of extended range of Zone I overmodulation presented in this paper when realized through simulations show the improved transient response of the induction motor with less effect of non linearity faced during overmodulation operation in SVPWM inverter. Since the Zone I range is stretched beyond the existing value of MI = 0.9535, this in turn, automatically reduces the range of operation in Zone II i.e. now Zone II region starts at a much later value of MI i.e. 0.977. Hence, the control and transition to six-step operation of the required voltage vector is easier and even. Thus the proposed approach removes the problem arising out of the extreme non-linearity starting with the advent of overmodulation zone II by increasing the range of operation of zone I. REFERENCES [1] Jul Ki Seok, Sheok Kim and Ki Sul. 1998. Overmodulation strategy for High Performance Torque Control. IEEE Trans. on PE. July [2] J. Ki Seok and S.K. Sul. 1995. A New Overmodulation Strategy for IM Drive Using SVPWM. IEEE. [3] D.C. Lee and G.M. Lee. 1998. A Novel Modulation Technique for SVPWM Inverters. IEEE Trans. on PE. November. [4] G. Narayanan and V.T. Rang. 2001. Nathan Overmodulation Algorithm for space vector modulated and its application to low switching frequency PWM technique. IEE Proc. EPA. Vol. 148, No. 6. [5] S. Bolognani and M. Zigliotto. 1997. Novel Digital Continuous Control of SVM Inverter in the Overmodulation Range. IEEE Trans on Industry Applications. 33(2): 525-530. [6] A.R. Bakashai, P.K. Jain, Hua Jain. 2002. Incorporating the Overmodulation Range in Space Vector Pattern Generation using a Classification Algorithm. IEEE Trans on PE. 15(1): 83-91. [7] X. Xu and D. W. Novotny. 1992. Selection of the flux reference for induction machines in the Field Weakening Region. IEEE Trans. Ind. Appl. 28(6): 1353-1358. [8] A. Tripathi, A.M. KhambadKone and S.K. Panda. 2001. Space Vector based constant frequency, direct torque control and dead beat stator flux control of ac machines. IEEE International Conference on Industrial Electronics, Control, Instrumentation and Automation, IECON. Vol. 2, November. [9] S. Venugopal. 2006. Study on over modulation methods for PWM Inverter Fed AC drives. MS Thesis. Department of Electrical Engg. IISc, Bangalore. [10] Shun Jin, Yan-ru Zhong and Wei-bing Cheng. 2006. Novel SVPWM Overmodulation Scheme and Its Application in Three-Level Inverter. 37 th IEEE PESC. June. 12