GB QUICK GUIDE FOR THE CONFIGURATION OF VARIABLE SPEED DRIVES

Similar documents
The GS1 Digital Keypad LED Display Function Keys Displaying the Status of the GS1 AC Drive Programming the GS1 AC Drive...

TOSVERT TM VF-nC3 Parameter List

CHAPTER AC DRIVE PARAMETERS. In This Chapter...

HPVFP High Performance Full Function Vector Frequency Inverter

1-2 VOLTS PER HERTZ CHARACTERISTICS EXERCISE OBJECTIVE

Variable Frequency Drive / Inverter (0.4 ~ 280kW)

CHAPTER KEYPAD OPERATION AND QUICKSTART. In This Chapter... The GS2 Digital Keypad GS2 Quickstart...3 6

GS1 Parameter Summary Detailed Parameter Listings...4 9

vacon 100 flow ac drives application manual

CHAPTER 8 SUMMARY OF PARAMETER SETTINGS

Invertek Optidrive E3 Frequency Inverter (IP20, 3ph output) Easy Start Guide

BACnet- MS/TP COMMUNICATION V

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection

Before you operate the inverter, the parameters that you must first program are the basic parameters.

NX Series Inverters. HVAC Pocket Programming Guide

vacon 100 ac drives application manual

D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE

P-SERIES VFD 1-40HP (200~230VAC), 1-400HP (380~480VAC),3Ø Dual Rated for Constant & Variable Torque Integrated PID Control

Multi-function, Compact Inverters. 3G3MV Series

Enhanced PID for Air Compressors F7 Drive Software Technical Manual

D SERIES LM16. COMPACT DRIVE V/f and SLV CONTROL. LM16 COMPACT DRIVE V/f and SLV CONTROL

Compact Operating Manual Issue 04/04. sinamics SINAMICS G110

INDEX. i 1. B Braking Resistor Dimensions: A 24 Braking Resistors: A 20 Braking Units: A 20. DURAPULSE AC Drive User Manual

vacon 100 flow ac drives application manual

EFC 3600 Frequency converter for higher energy efficiency and improved process control

VFS11 Parameter List for up to CPU version 105

vacon 100 hvac ac drives application manual

General Purpose AC Drives

Frequency Converter Fv vector control converters for universal applications

Options & Accessories

FUJI Inverter. Standard Specifications

I-7088, I-7088D, M-7088 and M-7088D User Manual

THYFREC-VT110S 200V 1PH System 0.4 to 2.2kW 400V 3PH System 0.75 to 2.2kW QUICK START GUIDE

safety Doc: DPD00714C, Released: vacon 1 ONLY A COMPETENT ELECTRICIAN IS ALLOWED TO CARRY OUT THE ELECTRICAL INSTALLATION! 1.

MA7200 PLUS INVERTER SERIES PID Quick Start Manual For Fan and Pump Applications

Options & Accessories

SJ100 Series Inverter Quick Reference Guide. Single-phase Input 200V Class Three-phase Input 200V Class Three-phase Input 400V Class

CHAPTER 8 PARAMETER SUMMARY

VFD Reference Guide. In-The-Field Tool

Compact & Powerful Inverter STARVERT ig5a 0.4~1.5kW 1phase 200~230Volts 0.4~22kW 3Phase 200~230Volts 0.4~22kW 3Phase 380~480Volts

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13

Jaguar Motor Controller (Stellaris Brushed DC Motor Control Module with CAN)

ADJUSTABLE SPEED DRIVES. AS1 Drive

The MFT B-Series Flow Controller.

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht

ig5a 0.4~1.5kW (0.5~2HP) 1phase 200~230Volts 0.4~22kW (0.5~30HP) 3Phase 200~230Volts 0.4~22kW (0.5~30HP) 3Phase 380~480Volts Compact & Powerful Drive

1. Vacon Startup Startup Wizard PID Mini-Wizard Multi-pump mini-wizard... 5

Modbus communication module for TCX2: AEX-MOD

PowerFlex 400 AC Drive Guide Specification

General Purpose Drives

1. INTRODUCTION Fire Mode PID Application Parameter lists DESCRIPTION OF PARAMETERS... 8

NXL HVAC APPLICATION MANUAL Programming manual for NXL HVAC drives

Emotron VSA Variable Speed Drive

Rexroth Frequency Converter Fe 0.75 kw to 7.5 kw / 400 VAC

6.9 Jump frequency - Avoiding frequency resonance

FREQUENCY INVERTER VFR-013 QUICK START GUIDE

VF-nC1 Adjustable Speed Drive Engineering Specification

3. Be aware of the ambient temperature. Use the unit within the specified ambient temperature only.

ig5a Compact AC Drive 0.4~1.5kW(0.5~2HP) 1-phase 200~230Volts 0.4~22kW(0.5~30HP) 3-Phase 200~230Volts 0.4~22kW(0.5~30HP) 3-Phase 380~480Volts

PARAMETER LIST MICROFUSION

Revision 1. March 21, ADC Operation Manual N 11 th St San Jose CA

ADJUSTABLE SPEED DRIVES FS1

SRC-110 Series Zone Controllers with Modbus RTU

INTERNATIONAL SERVICE BULLETIN - I #2-319 Liberty - Delta M+ VFD parameter list. A VFD parameter list is required when replacing a DELTA M+ VFD.

M-Max series drives. The next generation of OEM drives

MICROMASTER kw - 11 kw. Operating Instructions (Compact) Issue 10/06. www. ElectricalPartManuals. com. User Documentation

MICROMASTER kw - 11 kw

E3 Adjustable Speed Drive Engineering Specification

ADJUSTABLE SPEED DRIVES. W7 Series. 18 Pulse

Jaguar speed controllers

S11 Adjustable Speed Drive Engineering Specification

Frequency Converter Fe Economical converters for universal applications

AV-300i Specifications. GE Industrial Systems. Product Specifications. A New Concept in Automation. AV-300i

NX series Constant and variable torque Variable Speed Drives for induction motors

DCmind Soft + CANopen

Dual-inverter Wire Drawing Machine CHV130 series Frequency inverter Operation manual

user's manual nx frequency converters beam pump application asfiff13

AV-300i Specifications. Saftronics Inc. PC10 Product Specifications PC10. Mini Vector AC Drive

Operating Instructions

Automate. Hardware: Software: 1. Somove Lite V (or latest version available) for drive configuration optional

Programming Guide. VLT HVAC Drive FC 100

µservo drive user s guide

AV-300i Specifications. Saftronics Inc. VG10 Product Specifications VG10. Dynamic Vector Drive

Optidrive Applications Support Library

Version number A=standard P=Cold Plate (Frame A only) T=Brake chopper (Frame A only) Input voltage 11=115VAC 21=230VAC 1φ 23=230VAC 3φ 43=400VAC

The new Yaskawa Varispeed G7 Inverter

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

FREQUENCY INVERTER VFR-091 QUICK START GUIDE

Advanced user guide. Commander SX. IP66/Nema 4X AC Variable Speed Drive en / a. Part Number :

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

Brushed DC Motor Control. Module with CAN (MDL-BDC24)

vacon nx all in one application manual ac drives Phone: Fax: Web: -

Vector Frequency Inverter PRODUCT ORIENTATION

maxon document number:

THYFREC-VT210S 400V System 37 to 315kW (C/T) 400V System 45 to 370kW (V/T) QUICK START GUIDE

Hitachi P1 Closed Loop Hoist Basic Instruc on Manual

Tarocco Closed Loop Motor Controller

VFS9 Parameter List for Version110 or later

Multifunction Keypad OP-KP-LCD. Multi-function Keypad with LCD & LED display for programming IMO Jaguar Inverters.

HITACHI. L100-M Series Inverter Quick Reference Guide. Hitachi Industrial Equipment Systems Co., Ltd. Single-phase Input 100V Class

Transcription:

GB QUICK GUIDE FOR THE CONFIGURATION OF VARIABLE SPEED DRIVES LOVATO ELECTRIC S.P.A. 24020 GORLE (BERGAMO) ITALIA VIA DON E. MAZZA, 12 TEL. 035 4282111 FAX (Nazionale): 035 4282200 FAX (International): +39 035 4282400 E-mail info@lovatoelectric.com Web www.lovatoelectric.com VLB3 Steps to follow for the configuration of the variable speed drive: LEARN HOW TO NAVIGATE THE MENU See chapter 1 HOW DO YOU WANT TO MAND THE RUN AND STOP OF THE MOTOR? See chapter 2 HOW DO YOU WANT TO ADJUST THE FREQUEY OF THE MOTOR? See chapter 3 DO YOU USE THE REMOTE DISPLAY UNIT LOVATO EXCRDU1? YES See chapter 4 SET THE MOTOR PARAMETERS See chapter 5 SUMMARY PAGE 1. Navigation in the menu and loading default settings... 2 2. Command the run/stop of the motor... 3 2.1 2-wires control from the flexible I/O terminal block... 3 2.2 From keypad... 3 2.3 3-wires control from flexible I/O terminal block... 3 3. Frequency adjustment... 4 3.1 From keypad... 4 3.2 From external potentiometer... 4 3.3 From analog input signal type 0-... 4 3.4 From analog input signal type 4-20mA... 5 3.5 With preset frequency setpoints... 5 3.6 From motor potentiometer (MOP)... 5 3.7 With Modbus communication protocol... 6 3.8 PID Control - Setpoint adjusted with keypad and feedback signal type 0-... 6 3.9 PID Control - Setpoint adjusted with keypad and feedback signal type 4-20mA... 6 4. Control with remote display unit LOVATO MODEL EXCRDU1... 7 4.1 Connection of the RS485 bus... 7 4.2 Configuration for Run/Stop control and frequency adjustment... 8 4.3 Configuration for PID control... 8 5. Motor parameters... 9 1

1. NAVIGATION IN THE MENU AND LOADING DEFAULT SETTINGS Function of the keypad keys Navigate: select group/parameter. Change parameter setting. Pressed shortly: enter in the sub parameter level. Keep pressed for more than 3 sec to save parameter settings in the memory. Exit from the menu/parameter Stop motor Run motor Activate full keypad control (available from firmware version 4.1) Reversal of rotation direction (available from firmware version 4.1) Example of navigation in the menu of the VSD and modification of a parameter. Back to the previous level Enter in parametrisation mode Select the group Back to the previous level Enter in the group Select the parameter Back to the previous level Confirm the parameter to modify Select the sub-parameter Back to the previous level without saving Confirm the sub-parameter Modify the value of the parameter Confirm the modify Keep pressed for 3 seconds to save all the parameters modified. Load default settings TO LOAD THE DEFAULT PARAMETERS, SET P700.01=1 2

2. MAND THE RUN/STOP OF THE MOTOR 2.1 2-wires control from the flexible I/O terminal block Run/Stop P400.01 VSD enable 1 VSD always enabled (default setting) P400.02 Run/stop command 11 Run/stop command from digital input (connected between terminals -) 2.2 From keypad Start Stop P400.01 VSD enable 1 VSD always enabled (default setting) P400.12 Keypad control 1 Activate keypad as control source P400.02 Run/stop command 1 Constant true (run/stop command is managed by keypad) 2.3 3-wires control from flexible I/O terminal block Stop Start forward P400.01 VSD enable 1 VSD always enabled (default setting) P400.02 Run/stop command 11 Run/stop command is given by ( contact). It serves as start enable for the function Start forward (P400.06). P400.06 Start forward command 12 Start forward command from ( contact) 3

3. FREQUEY ADJUSTMENT 3.1 From keypad Increase the frequency Decrease the frequency P201.01 Frequency setpoint source 1 Frequency adjusted from keypad 3.2 From external potentiometer Potentiometer P201.01 Frequency setpoint source 2 Frequency adjusted with analog input 1 () P430.01 Analog input 1 () configuration 0 Analog signal type 0- P430.02 Value of frequency when is at minimum 0Hz Frequency when is at minimum ( = 0V) P430.03 Value of frequency when is at maximum 50Hz Frequency when is at maximum ( = ) 3.3 From analog input signal type 0- Analog signal 0...DC + P201.01 Frequency setpoint source 2 Frequency adjusted with analog input 1 () P430.01 Analog input 1 () configuration 0 Analog signal type 0- P430.02 Value of frequency when is at minimum 0Hz Frequency when is at 0V P430.03 Value of frequency when is at maximum 50Hz Frequency when is at 4

3.4 From analog input signal type 4-20mA Analog signal 4-20mA + P201.01 Frequency setpoint source 2 Frequency adjusted with analog input 1 () P430.01 Analog input 1 () configuration 4 Analog signal type 4-20mA P430.02 Value of frequency when is at minimum 0Hz Frequency when is at 4mA P430.03 Value of frequency when is at maximum 50Hz Frequency when is at 20mA 3.5 With preset frequency setpoints Preset frequency selection Bit 1 Preset frequency selection Bit 0 (bit 0) (bit 1) Preset frequency activated Open Open No preset frequency activated. The frequency is adjusted by the source set in P201.01 Open Closed Preset frequency 1 Closed Open Preset frequency 2 Closed Closed Preset frequency 3 Selection table of preset frequencies. P400.18 Preset frequency selection bit 0 14 is the bit 0 of preset frequency selection P400.19 Preset frequency selection bit 1 15 is the bit 1 of preset frequency selection P450.01 Preset frequency 1 20Hz Value of preset frequency 1 ( closed) P450.02 Preset frequency 2 45Hz Value of preset frequency 2 ( closed) P450.03 Preset frequency 3 50Hz Value of preset frequency 3 ( and closed) 3.6 From motor potentiometer (MOP) MOP DOWN MOP UP If the motor potentiometer is active as setpoint source, the frequency setpoint can be changed via the triggers assigned to two input contacts configured with the functions "MOP UP" (increase frequency) and "MOP DOWN" (decrease frequency). P400.04 Reset fault function (default: ) 0 Disable the reset fault function P400.13 Reverse rotation function (default: ) 0 Disable the reverse rotation function P400.23 Motor potentiometr UP function 12 = MOP UP function P400.24 Motor potentiometr DOWN function 13 = MOP DOWN function P400.25 Enable motor potentiometer as setpoint 1 MOP is used as frequency setpoint P413.00 Motor potentiometr starting mode 0 The last MOP value is used as initial value 5

3.7 With Modbus communication protocol P400.37 Activate network control 1 Network control activated P510.01 Modbus node ID 1 Insert the node ID P510.02 Baud rate 4 Select the baudrate (e.g. 4 means a baudrate of 19200 bps) P510.03 Data format 1 Definition of the data format (e.g: 1 means 8/E/1 : 8 data bits, Even parity, 1 stop bit) P515.01 Response to time-out 0 No action in case of Modbus time-out 3.8 PID Control - Setpoint adjusted with keypad and feedback signal type 0- P201.02 PID setpoint source 1 PID setpoint adjusted from keypad P210.00 Minimum frequency 30Hz Insert the value of the minimum frequency P430.01 Analog input 1 () configuration 0 Analog signal type 0- P600.01 PID enable 1 PID function enabled P600.02 PID feedback source 1 PID feedback connected to analog input P610.01 PID sleep mode activation 1 PID sleep mode enabled. Sleep mode is activated when the frequency is less than P610.03 for a time longer than P610.05 P610.03 PID sleep mode: frequency treshold 35Hz See above P610.05 PID sleep mode: delay time 5sec See above 3.9 PID Control - Setpoint adjusted with keypad and feedback signal type 4-20mA P201.02 PID setpoint source 1 PID setpoint adjusted from keypad P210.00 Minimum frequency 30Hz Insert the value of the minimum frequency P430.01 Analog input 1 () configuration 4 Analog signal type 4-20mA P600.01 PID enable 1 PID function enabled P600.02 PID feedback source 1 PID feedback connected to analog input P610.01 PID sleep mode activation 1 PID sleep mode enabled. Sleep mode is activated when the frequency is less than P610.03 for a time longer than P610.05 P610.03 PID sleep mode: frequency treshold 35Hz See above P610.05 PID sleep mode: delay time 5sec See above 6

4. CONTROL WITH REMOTE DISPLAY UNIT LOVATO MODEL EXCRDU1 EXCRDU1 4.1 Connection of the RS485 bus EXCRDU1 remote display unit can control up to 32 starters in contemporary at choice between variable speed drives VLB3 series and soft starters ADXL series, connected in RS485. TE. The terminals TA and TB of the RS485 port of the VLB3 have the polarity reversed compared to the terminals A and B of the remote display unit EXCRDU1. If the VLB3 is the last node of the RS485 network, is necessary to insert the bus terminating resistor (integrated into VLB) by setting in position ON the dip-switch R. Otherwise, you must leave the dip-switch R in position OFF. VLB Dip-switch R = terminating resistor 7

4.2 Configuration for Run/Stop control and frequency adjustment VLB setting Parameter Description Set Meaning P201.01 Frequency setpoint source 5 Setpoint specified via network P201.02 PID setpoint source 5 PID setpoint specified via network P400.37 Network enable 1 Network enabled P510.01 Serial node address 1-255 Modbus serial node P510.02 Baud rate 5 38400bps P510.03 Data format 1 8 data bits, even parity, 1 stop bit P515.01 Response to timeout 0 No response P530.01 Modbus parameter 1 P123.00 Motor temperature P530.02 Modbus parameter 2 P108.01 Output power P530.03 Modbus parameter 3 P121.01 PID setpoint P530.04 Modbus parameter 4 P121.02 PID feedback P530.05 Modbus parameter 5 P121.03 PID status P530.06 Modbus parameter 6 P151.01 Operating time P530.07 Modbus parameter 7 P107.00 Actual Torque P530.08 Modbus parameter 8 P210.00 Min frequency P530.09 Modbus parameter 9 P211.00 Max frequency P530.10 Modbus parameter 10 P605.01 PID, min value P530.11 Modbus parameter 11 P605.02 PID, max value P530.12 Modbus parameter 12 P400.37 Trigger PID P530.13 Modbus parameter 13 P190.01 Product code TE. To communicate with the EXCRDU1 remote display unit, all the above parameters (except for the serial node address, which can be modified as you prefer) must be set to the value indicated in the table. 4.3 Configuration for PID control VLB setting Parameter Description Set Meaning P201.01 Frequency setpoint source 5 Setpoint specified via network P201.02 PID setpoint source 5 PID setpoint specified via network P400.37 Network enable 1 Network enabled P510.01 Serial node address 1-255 Modbus serial node P510.02 Baud rate 5 38400bps P510.03 Data format 1 8 data bits, even parity, 1 stop bit P515.01 Response to timeout 0 No response P530.01 Modbus parameter 1 P123.00 Motor temperature P530.02 Modbus parameter 2 P108.01 Output power P530.03 Modbus parameter 3 P121.01 PID setpoint P530.04 Modbus parameter 4 P121.02 PID feedback P530.05 Modbus parameter 5 P121.03 PID status P530.06 Modbus parameter 6 P151.01 Operating time P530.07 Modbus parameter 7 P107.00 Actual Torque P530.08 Modbus parameter 8 P210.00 Min frequency P530.09 Modbus parameter 9 P211.00 Max frequency P530.10 Modbus parameter 10 P605.01 PID, min value P530.11 Modbus parameter 11 P605.02 PID, max value P530.12 Modbus parameter 12 P400.37 Trigger PID P530.13 Modbus parameter 13 P190.01 Product code P600.01 PID enable 1 PID function enabled TE. To communicate with the EXCRDU1 remote display unit, all the above parameters (except for the serial node address, which can be modified as you prefer) must be set to the value indicated in the table. TE. In the case of use of PID control, if you follow the above configuration, the feedback signal must be connected to the first analog input of the VLB3. 8

5. MOTOR PARAMETERS P208.01 AC input voltage 400V Insert the value of the supply voltage P300.00 Motor control mode 6 V/f characteristic control, open loop P302.00 V/f shape 0 Linear V/f (Applications: conveyor belts, ) 1 Quadratic V/f (Applications: pumps, fans, ) P303.01 V/f Base voltage 400V Set the same value of the rated voltage of the motor (P320.07) P303.02 V/f Base frequency 50Hz Set the same value of the rated frequency of the motor (P320.05) P315.01 Slip compensation 5% Set the suggested value P320.04 Rated speed of the motor _rpm Insert the rated speed of the motor P320.05 Rated frequency of the motor Hz Set the rated frequency of the motor P320.06 Rated power of the motor KW Set the rated power of the motor P320.07 Rated voltage of the motor V Set the rated voltage of the motor P320.08 Rated cosphi of the motor Set the rated cosphi of the motor P323.00 Rated current of the motor _A Insert the rated current of the motor. Setting this parameter, the motor thermic protection will be enabled. TE. If you need to enable the sensorless vector control set P300.00=4. All the other parameters must be left to default settings 9