GA A22712 DIII D ICRF HIGH VOLTAGE POWER SUPPLY REGULATOR UPGRADE

Similar documents
A REGULATED POWER SUPPLY FOR THE FILAMENTS OF A HIGH POWER GYROTRON

GA A22577 AN ELM-RESILIENT RF ARC DETECTION SYSTEM FOR DIII D BASED ON ELECTROMAGNETIC AND SOUND EMISSIONS FROM THE ARC

GA A22583 FAST WAVE ANTENNA ARRAY FEED CIRCUITS TOLERANT OF TIME-VARYING LOADING FOR DIII D

GA A23281 EXTENDING DIII D NEUTRAL BEAM MODULATED OPERATIONS WITH A CAMAC BASED TOTAL ON TIME INTERLOCK

GA A SOLID-STATE HIGH VOLTAGE MODULATOR WITH OUTPUT CONTROL UTILIZING SERIES-CONNECTED IGBTs by J.F. TOOKER and P. HUYNH

AN ELM=RESlLlENT RF ARC DETECTION SYSTEM FOR DIII-D BASED ON ELECTROMAGNETIC AND SOUND EMISSIONS FROM THE ARC

GA A25824 A NEW OVERCURRENT PROTECTION SYSTEM FOR THE DIII-D FIELD SHAPING COILS

GA A22574 ADVANTAGES OF TRAVELING WAVE RESONANT ANTENNAS FOR FAST WAVE HEATING SYSTEMS

INFRARED MEASUREMENTS OF THE SYNTHETIC DIAMOND WINDOW OF A 110 GHz HIGH POWER GYROTRON

Accelerator and Fusion Research Division Lawrence Berkeley Laboratory University of California Berkeley, CA 94720

AN IN-LINE POWER MONITOR FOR HE11 LOW LOSS TRANSMISSION LINES

THE MEASURED PERFORMANCE OF A 170 GHz REMOTE STEERING LAUNCHER

INITIAL RESULTS FROM THE MULTI-MEGAWATT 110 GHz ECH SYSTEM FOR THE DIII D TOKAMAK

GA A23983 AN ADVANCED COLLABORATIVE ENVIRONMENT TO ENHANCE MAGNETIC FUSION RESEARCH

GA A22776 THE DESIGN AND PERFORMANCE OF WAVEGUIDE TRANSMISSION LINE COMPONENTS FOR PLASMA ELECTRON CYCLOTRON HEATING (ECH) SYSTEMS

GA A27238 MEASUREMENT OF DEUTERIUM ION TOROIDAL ROTATION AND COMPARISON TO NEOCLASSICAL THEORY IN THE DIII-D TOKAMAK

+o GENEML ATOMfCS. RF POWER DIAGNOSTICS AND CONTROL ON THE DIII-D, 4 MW MHz FAST WAVE CURRENT DRIVE SYSTEM (FWCD)

PERFORMANCE OF THE 110 GHz SYSTEM ON THE DIII D TOKAMAK

FAST WAVE ANTENNA ARRAY FEED CIRCUITS TOLERANT OF TIMElVARYING LOADING FOR DIII-D

($E.. DISCLAIMER. b C

k SLAC-PUB-7583 July 1997 Co/vF PULSE TRANSFORMER R&D FOR NLC KLYSTRON PULSE MODULATOR*

GA A25836 PRE-IONIZATION EXPERIMENTS IN THE DIII-D TOKAMAK USING X-MODE SECOND HARMONIC ELECTRON CYCLOTRON HEATING

by T.E. HARRIS, J.C. ALLEN, W.P. CARY, S.W. FERGUSON,* C.C. PETTY, and R.I. PINSKER

GA A22897 QUASI-OPTIC COMPONENTS IN OVERSIZED CORRUGATED WAVEGUIDE FOR MILLIMETER-WAVE TRANSMISSION SYSTEMS

GA A26816 DESIGNS OF NEW COMPONENTS FOR ITER ECH&CD TRANSMISSION LINES

THE 110 GHz MICROWAVE HEATING SYSTEM ON THE DIII D TOKAMAK

High Explosive Radio Telemetry System. Federal Manufacturing & Technologies. R. Johnson, FM&T; B. Mclaughlin, FM&T;

DEVELOPMENT OF THE PULSE TRANSFORMER FOR NLC KLYSTRON PULSE MODULATOR* Abstract

RF HIGH VOLTAGE PERFORMANCE OF RF TRANSMISSION LINE COMPONENTS ON THE DIII-D FAST WAVE CURRENT DRIVE (FWCD) SYSTEM

Measurements of MeV Photon Flashes in Petawatt Laser Experiments

1997 Particle Accelerator Conference, Vancouver, B.C., Canada, May 12-16, 1997 BNL

GA A24030 ECE RADIOMETER UPGRADE ON THE DIII D TOKAMAK

GA A24463 CONTROL SYSTEM FOR THE LITHIUM BEAM EDGE PLASMA CURRENT DENSITY DIAGNOSTIC ON THE DIII D TOKAMAK

National Accelerator LaboratoryFERMILAB-TM-1966

GA A23741 DATA MANAGEMENT, CODE DEPLOYMENT, AND SCIENTIFIC VISUALIZATION TO ENHANCE SCIENTIFIC DISCOVERY THROUGH ADVANCED COMPUTING

MAPPING INDUCED POLARIZATION WITH NATURAL ELECTROMAGNETIC FIELDS FOR EXPLORATION AND RESOURCES CHARACTERIZATION BY THE MINING INDUSTRY

National Accelerator Laboratory

P2110B 915 MHz RF Powerharvester Receiver

GA A FABRICATION OF A 35 GHz WAVEGUIDE TWT CIRCUIT USING RAPID PROTOTYPE TECHNIQUES by J.P. ANDERSON, R. OUEDRAOGO, and D.

Nanosecond, pulsed, frequency-modulated optical parametric oscillator

Los A LA-UR Los Alamos National Laboratory Los Alamos, New Mexico 87545

User s Manual for Integrator Long Pulse ILP8 22AUG2016

PEP-I11Magnet Power Conversion Systems:.

Hardware-in-the-Loop Testing of Wireless Systems in Realistic Environments

ENLARGEMENT OF GLASS AND PLASTIC SHELLS TO 2 mm IN DIAMETER BY REDROPPING THROUGH A SHORT HEATED TOWER

Multi-Output Power-Supply Controller

Y f OAK RIDGE Y4 2 PLANT. Lionel Levinson General Electric Company. November 24, Approved for Public Release; distribution is unlimited.

The Development of an Enhanced Strain Measurement Device to Support Testing of Radioactive Material Packages*

Up-conversion Time Microscope Demonstrates 103x Magnification of an Ultrafast Waveforms with 300 fs Resolution. C. V. Bennett B. H.

GYROTRON-BASED MILLIMETER-WAVE: BEAMS FOR MATERIAL PROCESSING. Thomas Hardek Wayne Cooke. William P e r r y D a n i e l Rees

National Accelerator Laboratory

High-]FrequencyElectric Field Measurement Using a Toroidal Antenna

Implementation of an Acoustic Emission Proximity Detector for Use in Generating Glass Optics. M. A. Piscotty, J. S. Taylor, K. L.

Advanced Regulating Pulse Width Modulators

The ACT External HEPA Push-Through Filter Assembly. A. A. Frigo, S. G. Wiedmeyer, D. E. Preuss, E. F. Bielick, and R. F. Malecha

MAPPING INDUCED POLARIZATION WITH NATURAL ELECTROMAGNETIC FIELDS FOR EXPLORATION AND RESOURCES CHARACTERIZATION BY THE MINING INDUSTRY

Advanced Regulating Pulse Width Modulators

Isolated High Side FET Driver

Quarterly Technical Progress Report. For the period starting July, , ending September 30, Xiaodi Huang and Richard Gertsch

SOLID-STATE MODULATORS FOR RF AND FAST KICKERS

Detector And Front-End Electronics Of A Fissile Mass Flow Monitoring System

GA A23307 THE 8.4 MW MODULATOR/REGULATOR POWER SYSTEMS FOR THE ELECTRON CYCLOTRON HEATING FACILITY UPGRADE AT DIII D

High Voltage CMOS Boost White LED Driver

HIGH-POWER CORRUGATED WAVEGUIDE COMPONENTS FOR mm-wave FUSION HEATING SYSTEMS

Five-beam Fabry-Perot velocimeter

Measurements of edge density profile modifications during IBW on TFTR

An experimental system was constructed in which

Argonne National Laboratory P.O. Box 2528 Idaho Falls, ID

GA A22869 BOUNCE COATING INDUCED DOMES ON GLOW DISCHARGE POLYMER COATED SHELLS

Introduction to Radar Systems. Clutter Rejection. MTI and Pulse Doppler Processing. MIT Lincoln Laboratory. Radar Course_1.ppt ODonnell

GA A24691 STATUS OF THE ELECTRON CYCLOTRON HEATING SYSTEM ON DIII D

INTEGRATED CIRCUITS. AN120 An overview of switched-mode power supplies Dec

Recent advances in ALAMO

STP-NU ROADMAP TO DEVELOP ASME CODE RULES FOR THE CONSTRUCTION OF HIGH TEMPERATURE GAS COOLED REACTORS (HTGRS)

Product Datasheet P MHz RF Powerharvester Receiver

Test Results of the HTADC12 12 Bit Analog to Digital Converter at 250 O C

cycle to cycle, so errors can be used to update the reference waveforms for future cycles. At A P S, updates are

AT V Synchronous Buck Converter

UCRL-ID Broad-Band Characterization of the Complex Permittivity and Permeability of Materials. Carlos A. Avalle

Detection of Targets in Noise and Pulse Compression Techniques

Programmable, Off-Line, PWM Controller

DISCLAIMER. Portions of this document may be illegible in electronic image products. Images are produced from the best available original document.

Design of Kickerhiurnper Magnet and PF'N for PAR

Specification of APS Corrector Magnet Power Supplies from Closed Orbit Feedback Considerations.

MAKING TRANSIENT ANTENNA MEASUREMENTS

AN_0454. RC Snubber for Class-D Audio Amplifiers INTRODUCTION. Rev 1 MAR 18

GA A22963 RECENT DEVELOPMENTS ON THE HIGH POWER ECH INSTALLATION AT THE DIII D TOKAMAK

STP-PT-032 BUCKLING OF CYLINDRICAL, THIN WALL, TRAILER TRUCK TANKS AND ASME SECTION XII

HF Power Amplifier (Reference Design Guide) RFID Systems / ASP

C0da-r I&9 Commissioning Experience with the PEP-XI Low-Level RF System*

A7221A DC-DC CONVERTER/BUCK (STEP-DOWN) 600KHz, 16V, 2A SYNCHRONOUS STEP-DOWN CONVERTER

Radio Frequency Current Drive for Small Aspect Ratio Tori

Pin # Pin Name Pin Type Description

A7632A. AiT Semiconductor Inc. APPLICATION ORDERING INFORMATION TYPICAL APPLICATION

High-Voltage, Non-Isolated Buck-Boost Converter for ISDN Digital Phones

2352 Walsh Ave. Santa Clara, CA U. S. A. Tel.: (408) , Fax: (408)

Pin # Pin Name Pin Type Description. 4 GND Signal ground Signal ground pin. Connect ADC and DAC grounds to here.

Reducing space charge tune shift with a barrier cavity

FAN1851A Ground Fault Interrupter

Analog Technologies. Dual Mode Laser Driver LDA1-CP1-D

Transcription:

GA A22712 DIII D ICRF HIGH VOLTAGE POWER SUPPLY REGULATOR UPGRADE by W.P. CARY, B.L. BURLEY, and W.H. GROSNICKLE NOVEMBER 1997

DISCLAIMER This report was prepared as an account of work sponsored by an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, produce, or process disclosed, or represents that its use would not infringe privately owned rights. Reference herein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise, does not necessarily constitute or imply its endorsement, recommendation, or favoring by the United States Government or any agency thereof. The views and opinions of authors expressed herein do not necessarily state or reflect those of the United States Government or any agency thereof.

GA A22712 DIII D ICRF HIGH VOLTAGE POWER SUPPLY REGULATOR UPGRADE by W.P. CARY, B.L. BURLEY, and W.H. GROSNICKLE This is a preprint of a paper to be presented at the 17th IEEE/NPSS Symposium on Fusion Engineering, October 6 11, 1997, San Diego, California and to be published in the Proceedings. Work supported by the U.S. Department of Energy under Contract No. DE-AC03-89ER5111 GA PROJECT 366 NOVEMBER 1997

DIII D ICRF High Voltage Power Supply Regulator Upgrade* W.P. Cary, B.L. Burley, and W.H. Grosnickle General Atomics P.O. Box 85608, San Diego, California 92186-978 Abstract For reliable operation and component protection, of the 2 MW 30 120 MHz ICRF Amplifier System on DIII D, it is desirable for the amplifier to respond to high VSWR conditions as rapidly as possible. This requires a rapid change in power which also means a rapid change in the high voltage power supply current demands. An analysis of the power supply s regulator dynamics was needed to verify its expected operation during such conditions. Based on this information it was found that a new regulator with a larger dynamic range and some anticipation capability would be required. This paper will discuss the system requirements, the asdelivered regulator performance, and the improved performance after installation of the new regulator system. It will also be shown how this improvement has made the amplifier perform at higher power levels more reliably. INTRODUCTION After early operation it was determined that the response time of the high voltage power supply regulator needed to be improved for optimal operation of the amplifier system at full rated power [1]. Since building a new power supply would have been cost prohibitive, it was decided to take a closer look at the existing hardware and determine what if anything could be done to improve it s transient performance. SYSTEM REQUIREMENTS The original specification for the power supply written by ABB called for less than 10% variation in anode voltage for all power levels of operation [1]. This means that for a nominal anode voltage of 22 kv that the voltage may not droop by more that 2.2 kv. Furthermore the supply needed to respond to load changes in the order of 1 ms from full load to no load and vice versa. These relatively modest requirements are necessary since we are operating the final amplifier tube at its upper limit with regards to anode current and particularly its Screen Grid current. At the upper power limit of these tubes one needs to carefully adjust the operating point as not to exceed either the anode dissipation or the screen current. Too large of a change in the anode voltage causes a change in the operating point of the tube which usually causes a fault and termination of the rf pulse. INVESTIGATION Fig. 1 shows the voltage response for the FPA anode voltage. As can be seen from the plots the supply was not able to regulate with the required voltage output during the initial application of rf. The large droop in anode voltage caused excessive screen grid current which in turn caused the protective circuits of the transmitter to be activated. In this case the protective circuits limited the output power as can be seen in trace #2 of Fig. 1. Upon further investigation it became obvious why the supply was not able to handle the required impulse. The power supply design is based around an SCR controller operating at a nominal 80 vac. 12.7 kv is fed to a step-down transformer who s output is fed to the SCR regulator and then to a step-up transformer rectifier which in turn has an LC filtering network between it and the amplifier (Fig. 2). Since the design of the controller requires a zero crossing before conduction can start there is an inherent 16 ms response delay in the system. This is an addition to other delays associated with the various feedback circuits and other passive circuit elements. There were two modes of unsatisfactory operation found. The first was the large droop in voltage early in the pulse. This was caused by the fact that the SCR unit just cannot respond faster than the first zero crossing or about 16 ms for the 3 phase input. As can be seen from Fig. 1, after this 1 2 3 Ch1 Ch3 Ch2 Ch 1.00 V Anode Voltage 3 kv/ div. Anode I 100 A/ div. Output Power 1 MW/ div Screen I 2A/ div. M20.0 ms Aux 1.50 V Fig. 1. Pre upgrade PFA waveforms. 1 anode current, 2-output power, 3-screen current, and -anode voltage. * Work supported by U.S. Department of Energy under Contract No. DE-AC03-89ER5111. GENERAL ATOMICS REPORT GA-A22712 1

SWITCHGEAR OIL FILLED TANK CONTROLLER OIL FILLED TANK OIL FILLED TANK CAP ENCL INPUT 12.7 KV, 30 80V.1H V.D DISC CON H3 SUPPLIED BY ABB H2 FIRING CIRCUIT MOTORIZED TAP SWITCH OIL FILLED TANK 0M OHM 500 UFD 0KV H1 FIRING CIRCUIT LEM 10-28KVDC 50.6A CONTINUOUS 160A PULSE, 10% DUTY >10% REGULATION VOLTAGE REGULATOR REFERENCE SIGNAL Fig. 2. H.V.P.S. diagram. MOTORIZED TAP SWITCH 120VAC IFB VFB RECEIVER FIBER/ IFB OPTIC FEEDBACK VFB XMITTER initial dip in voltage the output would rise to the desired voltage and regulate rather well for the remainder of the pulse. The second mode of improper operation was caused by the regulators over current protection circuitry. When operating at very high power levels into DIII D, the system would occasionally block rf production due to fast changes in antenna loading associated with changing plasma conditions. These blocks would cause the transmitter to go from full output power to no output and back to full power on the order of 10 s of ms. This would cause the regulator circuit to shut off the SCRs at the termination of the rf. However, the slow turn off of the SCR s would lead (~ 16 ms) to a slight overshoot in voltage which then caused the regulator to phase the SCRs to a full off condition. When the regulator tried to catch up with the current demand associated with the re-application rf, the SCRs would be suddenly phased for full conduction. This would result in an over current condition and cause the SCRs to shut down. The capacitor bank would quickly be discharged and the rf power would decline until a screen over current condition in one of the amplifier stages would terminate the rf completely. The two problems required two different answers. First was the SCR over current shutdown. It was decided to modify the way in which we required the rf to come back on after a transmission line or antenna fault. We first 2 GENERAL ATOMICS REPORT GA-A22712 shortened the off time thus not allowing the SCRs to completely phase back, secondly we request the power to be reapplied in a step fashion thereby spreading the I over a slightly longer time period. This seems to have alleviated most of the over current type faults. The second problem required a much more sophisticated approach. What was needed was a circuit that could foretell when the current demand would be coming and what that demand would be. Since the amplitude and shape of the rf could be remotely controlled in real time, a circuit that knew what that demand would be has not yet been designed what was know was when the pulse was about to happen. The droop could be avoided by just adding a delay to the rf request and using the original request to start a preboost. Fig. 3 shows a simplified circuit for the FPA power supply regulator. What was done was to tell the regulator to increase the output voltage an adjustable amount and for an adjustable length of time before the actual beginning of the rf pulse. It was found that this set up can only be optimized for a given power and voltage condition, but experimentation has shown that by setting it for a nominal power output of 2 MW, satisfactory results are achieved for pulses of less power as long as the requested anode voltage is held constant. Fig. shows the voltage improvement for a high power pulse. Note that not only is the anode voltage held

The integrator is reset when the SCR enable off is sent Integrator reset -15 clamp +.v +15 ERROR Reset Sw The boost level is adjusted by the gain of the amplitier, the pulse width of the boost, the time constant of the input resistor times the integrator capacitor and the magnitude of the voltage boost. P-ERROR Fast Loop SW on when RF on Fast Loop Fast loop on when RF on and SCR enable on Boost Boost is on just prior to RF and after tude with restart of power supply and again just prior to RF Dynamic Reg Output During a boost the charging of the integrator capacitors is subtracted to keep the boost at a fixed level yet charge the capacitors to hold the boost value after the boost is over Fig. 3. Upgraded regulator diagram. Ch Zoom: 1.0 Vert 0.5 Horz Anode Voltage 3 kv/ div. constant but that the screen grid current is also constant and much lower in amplitude. SUMMARY 1 2 3 Ch1 Ch3 10.0 V Ch2 Ch.00 V 1.00 V M0.0 ms Aux Anode I 100 A/ div. Output Power 1 MW/ div Screen I 2A/ div. 1.50 V Fig.. Post upgrade FP waveforms. 1-anode current, 2-output power, 3-screen current, -anode voltage. As can be seen from the comparison between Figs. 1 and, there has been a significant improvement in the initial voltage droop which is most evident in the screen grid current. This has allowed the amplifier to operate much nearer specified maximum output power without over dissipation or excessive screen current. This has also led to improved reliability or quality of the rf pulse during plasma operations where the load variations can cause large swings in plate loading. REFERENCE [1] W. Schminke et al., Upgrade of ICRH generators for ASDEX/W VII, 12th Symposium on Engineering Problems of Fusion Research, Monterey, 1987. GENERAL ATOMICS REPORT GA-A22712 3