Canadian Standards Association Mississauga, Ontario To the Part I Committee

Similar documents
NEC 2014 Code Changes

Bulletin Voltage drop in single dwelling units Rule 8-102

Bulletin Voltage drop in single dwelling units Rule 8-102

CHAPTER 2 Wiring and Protection. Article 200 Use and Identification of Grounded Conductors

ECET Fall 2017 Name: _ Lab Assignment #01

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS. Fourth Edition. Extracts from Amendment No.1: June 2011

NOTICE OF RULE MAKING PROCEEDINGS AND PUBLIC HEARING

UNION COUNTY ENGINEER DIVISION OF BUILDING REGULATIONS

Single-Family Dwelling Submittal Requirements

Electrical requirements for plans on all new homes, additions, remodels & Service upgrades

Chapter 1 Electrical Theory and Part C Series Parallel and Code Questions Multiwire Branch Circuits Unit 1 Electrician s Math

DESIGN CHECKLIST INTRODUCTION

Part VIII Electrical GENERAL REQUIREMENTS CHAPTER 33

ANSI-ASC-C63 Interpretation Request Form

***************************************************************************** DRAFT UFGS- 01 XX XX (FEB 2014)

Impact on audit quality. 1 November 2018

PROVINCE.OF BRITISH COLUMBIA. ORDER OF THE LIEUTENANfelOVERNOR IN COUNCIL

GROUP ON INTERNATIONAL AVIATION AND CLIMATE CHANGE (GIACC) FOURTH MEETING SUMMARY OF DISCUSSIONS DAY 3

Statement on variation of 900 MHz and 1800 MHz Wireless Telegraphy Act licences

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

IAASB Main Agenda (March, 2015) Auditing Disclosures Issues and Task Force Recommendations

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

INTRODUCTION...xiii Author s Comments...xiii Exam Preparation...xiii Difficult Concepts...xiv Textbook Errors and Corrections...xv Internet...

Address: South Elgin, IL Phone: ( ) - Fax: ( ) - Cell: ( ) - Contractor Type: Phone: ( ) - Fax: ( ) - Cell: ( ) - Contact Type:

December 8, Ms. Susan Cosper Technical Director Financial Accounting Standards Board 401 Merritt 7 PO Box 5116 Norwalk, CT

Re: Examination Guideline: Patentability of Inventions involving Computer Programs

Suggested Statement/Substantiation for The PoE Task Group PIs

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

CHAPTER 11 PRELIMINARY SITE PLAN APPROVAL PROCESS

Chapter General. Accessible built-in storage facilities shall comply with Section 905. Chapter 9. Built-in Furnishings and Equipment

IAASB Main Agenda (December 2004) Page Materiality

ESA Supporting Ontario s Electrical Safety System

Department of Labor and Industry Electrical Licensing

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Guidance for Industry and FDA Staff Use of Symbols on Labels and in Labeling of In Vitro Diagnostic Devices Intended for Professional Use

Ordinance for Enforcement of the Family Register Act

ARTICLE 11. Notification and recording of frequency assignments 1, 2, 3, 4, 5, 6, 7, 7bis (WRC-12)

Air Monitoring Directive Chapter 9: Reporting

Addendum Sheet Specifications and Tolerances (S&T) Committee Interim Report

City of Lompoc Building & Safety Services Section 100 Civic Center Plaza Lompoc, CA Phone: Fax:

120 / 240 VAC SINGLE SPLIT PHASE & MULTI-WIRE BRANCH CIRCUITS. Excerpt from G4 InverCharge Series Manual BY: VIJAY SHARMA ENGINEER

City of Thousand Oaks

PUBLIC ART PROGRAM Guidelines for Site Plan Projects

Regarding the durability of New Zealand grown European oak timber to be used internally in a new dwelling at 350 Jones Road, Blenheim

April 30, Andreas Bergman Chair International Public Sector Accounting Standards Board 529 Fifth Avenue, 6th Floor New York, NY USA

Ref: S935/gb. 13 th April 2012

Resource Management Act 1991 ( Act ) KAWARAU JET SERVICES HOLDINGS LIMITED. Appellant QUEENSTOWN LAKES DISTRICT COUNCIL.

Article 225: Outside Branch Circuits And Feeders

a) Determine the smallest, standard-sized circuit breaker that should be used to protect this branch circuit.

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

Journeyman's Practice Exam

UPDATES to the. Rules of Procedure. (Edition of 1998) approved by the Radio Regulations Board. Contents

Code Check Electrical is a field guide to common code issues in residential

1 Exam Prep NFPA 70: National Electric Code 2011 Tabs and Highlights

FTTH ENGINEERING AND INSTALLATION INTRODUCTION

Step 1: General Customer information

Standard Development Timeline

2014 NEC Changes Part 1

Home Electrical Wiring. Types of Receptacles and Wiring them for 120v 15Amp/20Amp

Message from the President

B. The designated coverage areas shall include both indoor and outdoor coverage.

TechAmerica Europe comments for DAPIX on Pseudonymous Data and Profiling as per 19/12/2013 paper on Specific Issues of Chapters I-IV

ER 87 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes. (1 mark) ESR 27(2) (2 marks) ESR 74A(1AA)

Proposal for a COUNCIL REGULATION. on denominations and technical specifications of euro coins intended for circulation. (recast)

CITY of ALBUQUERQUE SIXTEENTH COUNCIL

The meaning of planning margins in a post-rrc-06 situation

Technical Requirements for Cellular Radiotelephone Systems Operating in the Bands MHz and MHz

Conformity assessment procedures for hip, knee and shoulder total joint replacements

Solid Surface Countertops

Part 4: Visitability Ordinance. City of Austin Development Services Department

South West Public Engagement Protocol for Wind Energy

Appendix A: Resolution 18 (1994) Review of the ITU s Frequency Coordination and Planning Framework for Satellite Networks

BERKELEY COUNTY ENGINEERING AND

25kV A.C. Electrified Lines - Traction Bonding

ERRATA AND REVISIONS to the CANADIAN PLUMBING CODE

8th Floor, 125 London Wall, London EC2Y 5AS Tel: +44 (0) Fax: +44 (0)

Paul Dobrowsky Innovative Technology Services

AS Australian Standard STEEL WIRE FOR TENDONS IN PRESTRESSED CONCRETE. This is a free 5 page sample. Access the full version online.

Table of Contents. Introduction... 1

FOR UL INTERNAL REFERENCE OR CSDS USE ONLY NOT FOR OUTSIDE DISTRIBUTION

STANDARD COMMENTS 2016 ELECTRICAL PLAN REVIEW CHECK LIST

October 17, Spectrum Management and Telecommunications Policy. International Agreements. Aussi disponible en français

1. Name the horizontal member that rests on the foundation wall to support other wood members.

Ground Fault Location. Turbo Sleuth. Instruction Manual

Absolute Block. Uncontrolled When Printed Document to be part superseded by GKRT0055 Iss 1 and GKRT0077 Iss 1 (published on 07/09/2013)

Company Directive STANDARD TECHNIQUE: SD5F. Relating to connecting multiple small low voltage connections with limited network analysis

St. Philip Parish Richmond, ON

Contractor Advisory Council Minutes October 12, 2017

NEC Code-Making Panel 18. Second Draft Meeting Agenda. November 5-7, San Diego, CA Introduction of Members and Guests

CNSC/Industrial Radiography Working Group Meeting October 16, 2012 CNSC Southern Regional Office, Mississauga, Ontario

Alternating Current Power

CITY OF MERCER ISLAND DEVELOPMENT SERVICES GROUP 9611 SE 36 th Street, Mercer Island, WA (206)

(Circuits Subject to Requirements R1 R5) Generator Owner with load-responsive phase protection systems as described in

8th Floor, 125 London Wall, London EC2Y 5AS Tel: +44 (0) Fax: +44 (0)

FEE Comments on EFRAG Draft Comment Letter on ESMA Consultation Paper Considerations of materiality in financial reporting

Re: JICPA Comments on the PCAOB Rulemaking Docket Matter No. 034

Product Guide Verizon Delaware LLC. Section 11 Delaware LLC Original Sheet 1. Channels

ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

NEC P14 First Draft Ballot (A2016)

Transcription:

Canadian Standards Association Mississauga, Ontario To the Part I Committee Subject No. 3130 Chair: R. Leduc Date: December 24, 2003 Title: Receptacles in Residential Occupancies, Rules 26-710, 26-712, 26-720, 26-722 and 26-726 Submitted by: Ted Olechna of Electrical Safety Authority on July 9, 2003. Proposal: Amend Rules 26-710, 26-712, 26-720, 26-722 and 26-726 as follows: Proposal 1. Receptacles in Residential Occupancies 26-710 General (see Appendices B and G ) This Rule applies to receptacles in all residential occupancies (including dwelling units and single (b) For the purposes of this Rule, all receptacles shall be CSA Configuration 5-15R or except that receptacles having CSA Configuration 5-20RA shall be permitted provided that the ampere rating of the branch circuit wiring supplying such receptacles is not less than 20 A (see Diagram 1 ); and Move the requirement for 20 A wiring for 5-20RA to new clause 26-720(f). This puts the 15 splits at the same level as the 20 T-slot (d) Where split receptacles are installed on a side of a counter work surface in a kitchen designed for use by persons with disabilities, such receptacles shall not be considered as substituting for the receptacles required by Rule 26-712(d) ; and Proposal 2. 26-712 Receptacles in Dwelling Units (see Appendices B and G ) This Rule applies to receptacles in (d) In dwelling units there shall be installed in each kitchen: (i) One receptacle for each refrigerator; and

(ii) Where a gas supply piping or a gas connection outlet has been provided for a free-standing gas range, one receptacle behind the intended gas range location not more than 130 mm from the floor and as near midpoint as is practicable, measured along the floor line of the wall space intended for the gas range; and (iii) Except as permitted by Rule 26-726, a sufficient number of split receptacles or duplex receptacle having a CSA Configuration 5-20RA along the wall behind counter work surfaces (excluding sinks, built-in equipment, and isolated work surfaces less than 300 mm long at the wall line) so that no point along the wall line is more than 900 mm from a receptacle measured horizontally along the wall line; and (iiix) At least one split receptacles or duplex receptacle having a CSA Configuration 5-20RA shall be installed at each island counter space with a long dimension of 600 mm or greater and a short dimension of 300 mm or greater; and (iiixx) At least one split receptacles or duplex receptacle having a CSA Configuration 5-20RA shall be installed at each peninsular counter space with a long dimension of 600 mm or greater and a short dimension of 300 mm or greater. A peninsular countertop is measured from the connecting edge; and (In (iii) the requirement is for 15A splits or 20 T-slot installed in the same clause this will clear up confusion as to the requirements. The addition of islands and peninsulas in kitchen is required as these are being installed. If these are big enough then they shall be required to have a receptacle. The basis of the requirements are from NEC 210.52(C).) (iv) At least one duplex receptacle in a dining area forming part of a kitchen; and (e) The receptacles specified in Paragraph (d) shall not be located: (i) On the area of the wall directly behind the kitchen sink; or (ii) On the area of the counter directly in front of the kitchen sink, where receptacles are installed on a side of a counter work surface as permitted by Rule 26-710(d) ; and with the inclusion of islands and peninsulas this requirement should be applied to these installations as well

Proposal 3. Branch Circuits in Residential Occupancies 26-720 General This Rule applies to branch circuits in all residential occupancies (including dwelling units and single (f) The ampere rating of the branch circuit wiring supplying CSA Configuration 5-20RA receptacles shall be not less than 20 A Proposal 4. see note 26-71(b) 26-722 Branch Circuits in Dwelling Units This Rule applies to branch circuits in (b) Except as may be permitted by Paragraphs (c) and (d) and Rule 26-726 at least two multiwire branch circuits, shall be provided for receptacles installed for along the wall of kitchen counters work surfaces of dwelling units in accordance with Rule 26-712(d)(iii), 26-712(d)(iiix), and 26-712(d)(iiixx) and: With the inclusion of island and penininsula the specific requirements for behind the counter wall space does not apply any more as this you have other locations. As well by stating two branch circuits implies that one can install multi-wire or 20A or a combination. (i) No more than two split receptacles shall be connected to a multi-wire branch circuit; and By eliminating the word split states that you require not more than two receptacles, split or T-slot per branch circuit (ii) No other outlets shall be connected to these circuits; and (iii) Adjacent receptacles shall not be connected to the same multi-wire branch circuit; and The adjacency requirement should be dropped, as it is not based on a safety requirement. If you limit two receptacles per branch circuit and a minimum of two branch circuits, then where the appliances are plugged in is a choice of the consumer. Most consumers are not aware of the adjacency requirement and place the appliances as they see fit in the kitchen.

(c) Notwithstanding Paragraph (b), where the provisions of 26-712(d)(iii) require only one receptacle, only one multi-wire branch circuit need be provided; and If the kitchen counter is that small then the appliances that are used will be minimum as well. Either a split circuit or 20 A should be acceptable. (d) Notwithstanding Paragraph (b), connection to a multi-wire branch circuit of receptacles identified in Rule 26-710(d) shall be permitted, even though the circuit already supplies two split receptacles; and By deleting the multi-wire makes the clause general which will permits split or 20 A T- slot. Proposal 5. 26-726 Alternative to Split Receptacles and Multi-Wire Branch Circuits in Kitchens (see Appendix B) (1) Notwithstanding Rules 26-712(d)(iii) and 26-722(b), it shall be permitted to provide a duplex receptacle having a CSA Configuration 5-20RA in lieu of each split receptacle required along the wall of a kitchen counter work surface, provided that: (a) Not less than two branch circuits are provided; and (b) The ampacity of the branch circuit conductors is not less than 20 A; and (c) The rating of the overcurrent device protecting each branch circuit is 20 A. (2) Not more than two of the duplex receptacles described in Subrule (1) shall be connected to one 20 A branch circuit. (3) Adjacent receptacles shall not be connected to the same branch circuit. (4) The 20 A branch circuits described in Subrule (1) shall not supply any other outlet. This rule can be deleted as the requirements are incorporated in the general section.

Supporting Information: Background info from NEC 210-52 C (3) Kitchen Receptacle Requirements. Receptacles installed in a kitchen to serve countertop surfaces shall be supplied by not fewer than two small-appliance branch circuits, either or both of which shall also be permitted to supply receptacle outlets in the same kitchen and in other rooms specified in 210.52(B)(1). Additional small-appliance branch circuits shall be permitted to supply receptacle outlets in the kitchen and other rooms specified in 210.52(B)(1). No small-appliance branch circuit shall serve more than one kitchen. (C) Countertops. In kitchens and dining rooms of dwelling units, receptacle outlets for counter spaces shall be installed in accordance with 210.52(C)(1) through (5). (1) Wall Counter Spaces. A receptacle outlet shall be installed at each wall counter space that is 300 mm (12 in.) or wider. Receptacle outlets shall be installed so that no point along the wall line is more than 600 mm (24 in.) measured horizontally from a receptacle outlet in that space. (2) Island Counter Spaces. At least one receptacle outlet shall be installed at each island counter space with a long dimension of 600 mm (24 in.) or greater and a short dimension of 300 mm (12 in.) or greater. (3) Peninsular Counter Spaces. At least one receptacle outlet shall be installed at each peninsular counter space with a long dimension of 600 mm (24 in.) or greater and a short dimension of 300 mm (12 in.) or greater. A peninsular countertop is measured from the connecting edge. (4) Separate Spaces. Countertop spaces separated by range tops, refrigerators, or sinks shall be considered as separate countertop spaces in applying the requirements of 210.52(C)(1), (2), and (3). (5) Receptacle Outlet Location. Receptacle outlets shall be located above, but not more than 500 mm (20 in.) above, the countertop. Receptacle outlets rendered not readily accessible by appliances fastened in place, appliance garages, or appliances occupying dedicated space shall not be considered as these required outlets.

Chair s Comments: This proposal deals with several issues: a) Combining 15 A split and 20 A T-slot requirements. There s a perception that the Code implies the split receptacle installation in kitchens as a preferred method of installation over the use of the 20 A circuit and the 5-20RA receptacles. Both methods are acceptable and should be given equal considerations. b) Requiring receptacles at islands and peninsulas. The Code is silent on this and as a result there is inconsistency on the availability of receptacles in these situations. c) Eliminating the adjacency requirement. Currently the Code requires that adjacent receptacles for kitchen counters be on different branch circuits whether it s the 15 A split or the 20 A T-slot. To assist the Subcommittee, the Chair proposes dealing with one item at a time and resolving that item before moving on to the next. A 3-column document for item a) is intended to make it easier for the Subcommittee members to compare the proposal to existing requirements. The Chair has also introduced some editorial changes in an effort to clarify or simplify specific requirements. The 1 st column shows the existing requirements, the 2 nd column is the submitter s proposal and the 3 rd column gives the submitter s rationale. The Chair s comments and editorial suggestions are shown in the 2 nd and 3 rd columns using the track changes (strikeout/underline) feature. Item a) Combining 15 A split and 20 A T-slot Requirements. Existing Requirements Proposal with Chair s suggestions Rationale / Chair s additional comments 26-710 General (see Appendices B and G) This Rule applies to receptacles in all residential occupancies (including dwelling units and single dwellings) as follows: For the purposes of this Rule, all receptacles shall be CSA Configuration 5-15R except that receptacles having CSA Configuration 5-20RA shall be permitted provided that the ampere rating of the branch circuit wiring supplying such receptacles is not less than 20 A (see Diagram 1); and Where split receptacles are installed on a side of a counter work surface in a kitchen designed for use by persons with disabilities, such receptacles shall not be considered as substituting for the receptacles required by Rule 26-712(d); and (b) For the purposes of this Rule, all receptacles shall be CSA Configuration 5-15R or CSA Configuration 5-20RA (T-slot (/see Diagram 1); and (c) (d) Where receptacles (15 A split or 20 A T-slot) are installed on a side of a counter work surface in a kitchen designed for use by persons with disabilities, such receptacles shall not be considered as substituting for the receptacles required by Rule 26-712(d); and Move the requirement for 20 A wiring for 5-20RA to new clause 26-720(f). This puts the 15 splits at the same level as the 20 T-slot. The term T-slot is added because reference to the term is made in subsequent Rules. The term is well understood by industry. By removing the word split, and adding the bracketed (15 A split or 20 A T-slot), the reference to receptacles applies to either method.

Existing Requirements Proposal with Chair s suggestions Rationale / Chair s additional comments 26-712 Receptacles in Dwelling Units (see Appendices B and G) This Rule applies to receptacles in (d) In dwelling units there shall be installed in each kitchen: Except as permitted by Rule 26-726, a sufficient number of split receptacles along the wall behind counter work surfaces (excluding sinks, built-in equipment, and isolated work surfaces less than 300 mm long at the wall line) so that no point along the wall line is more than 900 mm from a receptacle measured horizontally along the wall line; and 26-722 Branch Circuits in Dwelling Units This Rule applies to branch circuits in (a) ; and (b) Except as may be permitted by Paragraphs (c) and (d) and Rule 26-726 at least two multi-wire branch circuits shall be provided for receptacles installed along the wall of kitchen counter work surfaces of dwelling units in accordance with Rule 26-712(d)(iii) and: (i) No more than two split receptacles shall be connected to a multi-wire branch circuit; and (ii) No other outlets shall be (d) In dwelling units there shall be installed in each kitchen: (i) (ii) (iii) A sufficient number of split receptacles or duplex receptacles having a CSA Configuration 5-20RA(15 A split or 20 A T-slot) along the wall behind counter work surfaces (excluding sinks, built-in equipment, and isolated work surfaces less than 300 mm long at the wall line) so that no point along the wall line is more than 900 mm from a receptacle measured horizontally along the wall line; and 26-720 General This Rule applies to branch circuits in all residential occupancies (including dwelling units and single dwellings) as follows: (e) ; and (f) The ampere rating of the branch circuit wiring supplying CSA Configuration 5-20RA shall be not less than 20 A. 26-722 Branch Circuits in Dwelling Units This Rule applies to branch circuits in (a) ; and (b) Except as may be permitted by Paragraphs (c) and (d), at least two branch circuits shall be provided for receptacles (15 A split or 20 A T-slot) installed for kitchen counters of dwelling units in accordance with Rule 26-712(d)(iii) and: (i) No more than two receptacles shall be connected to a branch circuit; and (ii) No other outlets shall be connected to these circuits; In (iii) the requirement is for 15 A splits or 20 T-slot installed in the same clause this will clear up confusion as to the requirements. Alluding to receptacles with the bracketed (15 A split, and 20 A T- slot) is editorially equivalent to the proposal. I see it as easier reading for the code user. See Note 26-710(b) This requirement moved from 26-710(b) is more appropriately located here. By stating two branch circuits implies that one can be multi-wire or 20A or a combination. Adding the bracketed (15 A split or 20 A T-slot) after receptacles reinforces the equality of the two wiring methods and emphasizes that 15 A receptacles would need to be split thus requiring a multi wire branch circuit. By eliminating the word split states that you require not more than two receptacles, split or T-slot per branch circuit. We will deal with the adjacency requirement in a future round of deliberations.

Existing Requirements Proposal with Chair s suggestions Rationale / Chair s additional comments connected to these circuits; and (iii) Adjacent receptacles shall not be connected to the same multi-wire branch circuit; and (c) Notwithstanding Paragraph (b), where the provisions of Rule 26-712(d)(iii) require only one receptacle, only one multi-wire branch circuit need be provided; and (d) Notwithstanding Paragraph (b), connection to a multi-wire branch circuit of receptacles identified in Rule 26-710(d) shall be permitted, even though the circuit already supplies two split receptacles; and and (iii) Adjacent receptacles shall not be connected to the same branch circuit; and (c) Notwithstanding Paragraph (b), where the provisions of Rule 26-712(d)(iii) require only one receptacle (15 A split or 20 A T- slot), only one branch circuit need be provided; and (d) Notwithstanding Paragraph (b)(i), connection to a branch circuit of receptacles identified in Rule 26-710(d) shall be permitted to be connected to those receptacles required by Rule 26-712(d)(iii), even though the circuit already supplies two receptacles; and If the kitchen counter is that small then the appliances that are used will be minimum as well. Either a split circuit or a 20 A should be acceptable. By deleting multi-wire makes the clause general which will permit split or 20 A T-slot. Paragraph (d) is further edited to more precisely describe the intent. 26-726 Alternative to Split Receptacles and Multi-Wire Branch Circuits in Kitchens (see Appendix B) (1) Notwithstanding Rules 26-712(d)(iii) and 26-722(b), it shall be permitted to provide a duplex receptacle having a CSA Configuration 5-20RA in lieu of each split receptacle required along the wall of a kitchen counter work surface, provided that: (a) Not less than two branch circuits are provided; and (b) The ampacity of the branch circuit conductors is not less than 20 A; and (c) The rating of the overcurrent device protecting each branch circuit is 20 A. (2) Not more than two of the duplex receptacles described in Subrule (1) shall be connected to one 20 A branch circuit. (3) Adjacent receptacles shall not be connected to the same branch circuit. Deleted This Rule can be deleted as the requirements are incorporated in the general section.

Existing Requirements Proposal with Chair s suggestions Rationale / Chair s additional comments (4) The 20 A branch circuits described in Subrule (1) shall not supply any other outlet. Subcommittee Deliberations (1 st Round) 9 of 14 members responded all in favour of the proposal as laid out by the Chair. One member commented on his concern for requiring receptacles for moveable islands. The S/C will deal with that item in the next Round. Another member suggested that we should consider requiring a minimum number of circuits rather than a minimum number of outlets. Thus for a certain counter length we would require say three circuits. We would still require receptacles with a minimum distance apart but would not limit two receptacles per circuit. The Chair rules these comments to be non-germane since it goes beyond the original proposal. I suggest that this may be dealt with under a new subject. The Chair declares consensus for this part of the proposal dealing with a) Combining 15 A split and 20 A T-slot requirements to make them equal in terms of their applicability. Chair s Comments (for the 2nd Round) Members will recall the proposal to deal with this subject in 3 parts. We have completed and reached consensus on the first part. Now the S/C will deal with the 2 nd and 3 rd part in 2 separate tables below: Item b) Requiring receptacles at islands and peninsulas. Existing Requirements Proposal with Chair s suggestions Rationale / Chair s additional comments 26-712 Receptacles in Dwelling Units (see Appendices B and G) This Rule applies to receptacles in 26-712 Receptacles in Dwelling Units (see Appendices B and G) This Rule applies to receptacles in

(d) In dwelling units there shall be installed in each kitchen: (i) (ii) (iii) (iv) At least one duplex receptacle in a dining area forming part of a kitchen; and (e) The receptacles specified in Paragraph (d) shall not be located: (i) On the area of the wall directly behind the kitchen sink; or (ii) On the area of the counter directly in front of the kitchen sink, where receptacles are installed on a side of a counter work surface as permitted by Rule 26-710(d); and (f) (d) In dwelling units there shall be installed in each kitchen: (i) (ii) (iii) (iv) At least one split receptacles or duplex receptacle having a CSA Configuration 5-20RA (15 A split or 20 A T-slot) shall be installed at each permanently fixed island counter space with a long dimension of 600 mm or greater and a short dimension of 300 mm or greater; and (v) At least one split receptacles or duplex receptacle having a CSA Configuration 5-20RA (15 A split or 20 A T-slot) shall be installed at each peninsular counter space with a long dimension of 600 mm or greater and a short dimension of 300 mm or greater. A peninsular countertop is measured from the connecting edge; and (vi) At least one duplex receptacle in a dining area forming part of a kitchen; and (e) The receptacles specified in Paragraph (d) shall not be located: (i) On the area of the wall directly behind the kitchen sink; or (ii) On the area of the counter directly in front of the kitchen sink; and (f) The addition of islands and peninsulas in kitchen is required as these are being installed. If these are big enough then they shall be required to have a receptacle. The basis of the requirements are from NEC 210.52(C). Minor editorial changes are proposed to remain consistent with the approach taken in the 1 st round deliberations Clause 12.3 of Appendix B requires that explanatory notes be located in an Appendix and Clause 12.22 only allows one sentence per Rule, Subrule Paragraph or Clause. Therefore, the second sentence in Paragraph (v) is deleted and the following Appendix B note is added: A peninsular countertop is measured from the connecting edge. with the inclusion of islands and peninsulas this requirement should be applied to these installations as well The submitters proposed removal of where receptacles are installed on a side of a counter work surface as permitted by Rule 26-710(d) seema appropriate, and makes the paragraph less wordy.

26-722 Branch Circuits in Dwelling Units This Rule applies to branch circuits in (a) (b) Except as may be permitted by Paragraphs (c) and (d) and Rule 26-726 at least two multi-wire branch circuits shall be provided for receptacles installed along the wall of kitchen counter work surfaces of dwelling units in accordance with Rule 26-712(d)(iii) and: 26-722 Branch Circuits in Dwelling Units This Rule applies to branch circuits in (a) (b) Except as may be permitted by Paragraphs (c) and (d), at least two branch circuits shall be provided for receptacles (15 A split or 20 A T-slot) installed for kitchen counters of dwelling units in accordance with Clauses (iii), (iv) and (v) of Paragraph (d), Rule 26-712(d)(iii) and: With the inclusion of island and peninsula the specific requirements for behind the counter wall space does not apply any more as this you have other locations. As well by stating two branch circuits implies that one can install multi-wire or 20A or a combination. Item c) Eliminating Adjacency Requirement Existing Requirements Proposal with Chair s suggestions Rationale / Chair s additional comments 26-722 Branch Circuits in Dwelling Units (a) (b) (i) (ii) (iii) Adjacent receptacles shall not be connected to the same multi-wire branch circuit; and 26-722 Branch Circuits in Dwelling Units (a) (b) (i) (ii) (iii)deleted The adjacency requirement should be dropped, as it is not based on a safety requirement. If you limit two receptacles per branch circuit and a minimum of two branch circuits, then where the appliances are plugged in is a choice of the consumer. Most consumers are not aware of the adjacency requirement and place the appliances as they see fit in the kitchen. Subcommittee members are requested to respond by indication whether the agree with the submission (including chair s comments) as it pertains to: b) Requiring receptacles at islands and peninsulas, and c) Eliminating the adjacency Rule Subcommittee Deliberations (2 nd Round) 1. With regards to the survey question pertaining to requiring receptacles at islands and peninsulas, 10 members responded all in favour of the proposal including comments by the Chair. There were a couple of comments concerning installation methods where there is no back wall for the receptacle that could perhaps be addressed in an Appendix B note. 2. With regards to the survey question pertaining to the elimination of the adjacency rule, 9 members responded, 6 in favour and 3 opposed. The main reason for those opposing the elimination of the adjacency requirement was a concern of overloading circuits and the resulting nuisance tripping. One member suggested that the potential overloading is a safety concern.

Chair s Comments (2 nd Round) In response to the advice for an Appendix B note, the chair agrees that it may have some value but suggests this could be a new subject if deemed necessary. Rule 26-710(c) sets the requirement for not permitting receptacles to be mounted facing up on counter work surfaces leaving the installer to find existing products that would be acceptable mounted on a counter or mounting the receptacle on sides of the counter (which the proposal does not prevent). In response to those members opposing the adjacency rule, the Chair refers to the submitter s original rationale (found on page 3): The adjacency requirement should be dropped, as it is not based on a safety requirement. If you limit two receptacles per branch circuit and a minimum of two branch circuits, then where the appliances are plugged in is a choice of the consumer. Most consumers are not aware of the adjacency requirement and place the appliances as they see fit in the kitchen. The Chair also refers to the submitter s comments made in the last round of deliberations: We should concentrate on the Safety aspect, consumers do not know of the adjacency requirements, and therefore place appliances as they see fit. The safety aspect is that there is proper branch circuit provisions no matter which configuration you have. The NEC has no adjacency provision and I have heard no one trying to change. Because the user is generally unaware that adjacent receptacles are on different circuits, there is no assurance that the user will not overload the circuit regardless of whether the receptacles are adjacent or not. In any case, safety is mitigated by the overcurrent protection. The Chair therefore concludes the negative votes to be non-persuasive and declares consensus on this subject. Subcommittee Recommendation: 1. Amend Rule 26-710 to read as follows: 26-710 General (see Appendices B and G) This Rule applies to receptacles in all residential occupancies (including dwelling units and single (a) ; and (b) For the purposes of this Rule, all receptacles shall be CSA Configuration 5-15R except that receptacles having CSA Configuration 5-20RA shall be permitted provided that the ampere rating of the branch circuit wiring supplying such receptacles is not less than 20 Aor CSA Configuration 5-20RA (T-slot) [see Diagram 1]; and (c) ; and (d) Where split receptacles (15 A split or 20 A T-slot) are installed on a side of a counter work surface in a kitchen designed for use by persons with disabilities, such receptacles shall not be considered as substituting for the receptacles required by Rule 26-712(d); and (e) 2. Amend Rule 26-712 to read as follows: 26-712 Receptacles in Dwelling Units (see Appendices B and G) This Rule applies to receptacles in (a) ; and (b) ; and (c) ; and (d) In dwelling units there shall be installed in each kitchen: (i) ; and (ii) ; and

(iii) Except as permitted by Rule 26-726, aa sufficient number of split receptacles (15 A split or 20 A T-slot) along the wall behind counter work surfaces (excluding sinks, built-in equipment, and isolated work surfaces less than 300 mm long at the wall line) so that no point along the wall line is more than 900 mm from a receptacle measured horizontally along the wall line; and (iv) At least one receptacle (15 A split or 20 A T-slot) installed at each permanently fixed island counter space with a long dimension of 600 mm or greater and a short dimension of 300 mm or greater; and (v) At least one receptacle (15 A split or 20 A T-slot) installed at each peninsular counter space with a long dimension of 600 mm or greater and a short dimension of 300 mm or greater; and (iii)(vi) At least one duplex receptacle in a dining (e) The receptacles specified in Paragraph (d) shall not be located (i) ; and (ii) On the area of the counter directly in front of the kitchen sink, where receptacles are installed on a side of a counter work surface as permitted by Rule 26-710(d); and (f) 3. Amend Rule 26-720 to read as follows: 26-720 General This Rule applies to branch circuits in all residential occupancies (including dwelling units and single (a) ; and (b) ; and (c) ; and (d) ; and (e) ; and (f) The ampere rating of the branch circuit wiring supplying receptacles with CSA Configuration 5-20RA shall be not less than 20 A. 4. Amend Rule 26-722 to read as follows: 26-722 Branch Circuits in Dwelling Units This Rule applies to branch circuits in (a) ; and (b) Except as may be permitted by Paragraphs (c) and (d), and Rule 26-726 at least two multi-wire branch circuits shall be provided for receptacles (15 A split or 20 A T-slot) installed along the wall offor kitchen counters work surfaces of dwelling units in accordance with Rule 26-712(d)(iii) Subparagraphs (iii), (iv), and (v) of Rule 26-712(d), and: (i) No more than two split receptacles shall be connected to a multi-wire branch circuit; and (ii) No other outlets shall be connected to these circuits; and. (iii)adjacent receptacles shall not be connected to the same multi-wire branch circuit; and (c) Notwithstanding Paragraph (b), where the provisions of Rule 26-712(d)(iii) require only one receptacle, only one multi-wire branch circuit need be provided; and (d) Notwithstanding Paragraph (b)(i), connection to a multi-wire branch circuit of receptacles identified in Rule 26-710(d) shall be permitted to be connected to those receptacles required by Rule 26-712(d)(iii), even though the circuit already supplies two split receptacles; and (e) 5. Delete Rule 26-726 entirely. 6. Add the following Appendix B note: 26-712(d)(v) A peninsular countertop is measured from the connecting edge.