EXPERIMENTAL INVESTIGATION ON THE SURFACE DEGRADATION CHARACTERISTICS OF OIL IMPREGNATED PRESSBOARD DUE TO LIGHTNING AND SWITCHING IMPULSES

Similar documents
CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

High-Voltage Test Techniques

The Effect of Practical Voltages on Maximum Amplitude of Partial Discharge with Considering Different Number of Cavities

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Siemens Transformer Technology Seminar Low Partial Discharge Transformers

Testing 320 kv HVDC XLPE Cable System

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

Electric Stresses on Surge Arrester Insulation under Standard and

Lecture 36 Measurements of High Voltages (cont) (Refer Slide Time: 00:14)

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

Generation of Sub-nanosecond Pulses

Analysis of Partial Discharge Patterns for Generator Stator Windings

Simulation Model of Partial Discharge in Power Equipment

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

3.2 Measurement of high voltages

EE 1402 HIGH VOLTAGE ENGINEERING

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

Power Engineering II. High Voltage Testing

HIGH VOLTAGE Insulation Coordination

Visualization of the Ionization Phenomenon in Porous Materials under Lightning Impulse

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY EHV AC AND DC TRANSMISSION

CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS

Field Measurement of Transmission Cable Dissipation Factor

Partial Discharge Inception and Propagation Characteristics of Magnet Wire for Inverter-fed Motor under Surge Voltage Application

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

International Journal of Advance Research in Engineering, Science & Technology

A STUDY ON THE RELATION BETWEEN LEAKAGE CURRENT AND SPECIFIC CREEPAGE DISTANCE

Specialists in HV and MV test and diagnostics. Testing in Substations

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

List of Experiments. Exp. # Experiment Title Page #

Over-voltage Trigger Device for Marx Generators

Software System for Finding the Incipient Faults in Power Transformers

MEDIUM & HIGH VOLTAGE

Lifetime Consumption and Degradation Analysis of the Winding Insulation of Electrical Machines

Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids

Partial Discharge Analysis of a Solid Dielectric Using MATLAB Simulink

KEYWORDS: Impulse generator, Pspice software, spark gap, Power transformer, Hardware.

Characteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements

1. Introduction to Power Quality

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

This is an author-deposited version published in : Eprints ID : 18192

High Votage Module AC/DC/Impulse Test System

DIELECTRIC HEATING IN INSULATING MATERIALS AT HIGH DC AND AC VOLTAGES SUPERIMPOSED BY HIGH FREQUENCY HIGH VOLTAGES

Electric Field Analysis of High Voltage Condenser Bushing

RESONANT TRANSFORMER

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

Coherence and time-frequency analysis of impulse voltage and current measurements

Earthing of Electrical Devices and Safety

High Voltage Engineering

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB

Harmonic Components Analysis of Leakage Current for Standard and Anti-Fog Suspension Insulators under Humidity Conditions

Measurement Of Partial Discharge (PD) In High Voltage Power Equipment

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

Partial Discharge Characteristics of Micro-gaps

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

Life Prediction of Mold Transformer for Urban Rail

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

2013 Applied Power Electronics Conference (APEC) Page 1 of 8

Integrated Electro-optic Sensor based Transient Voltage Measuring System and its Applications

Partial Discharge Patterns in High Voltage Insulation

High Field Electrical Conduction and Breakdown in Solid Dielectrics

CVVOZE Power Laboratories (CVVOZEPowerLab)

Coil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900

Breakdown Voltage of the Transformer Oils under Certain Conditions

Strathprints Institutional Repository

Ferroresonance Experience in UK: Simulations and Measurements

Prepared by Mick Maytum

Frequency Spectrum Analysis of Electromagnetic Waves Radiated by

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

Logic Level Signal Isolation Technology Review. MARK CANTRELL Senior Applications Engineer

HV Module Systems for Testing, Training and Research

EE High Voltage Engineering UNIT IV - MEASUREMENT OF HIGH VOLTAGES AND HIGH CURRENTS PART-A 1. Mention the techniques used in impulse current

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

Improved Method for Winding Deformation Detection Sensitivity in Transformer

Insulation Co-ordination For HVDC Station

Comprehensive modeling of Dry type foil winding transformer to analyse inter turn insulation under Lightning Impulse Voltage

FAULT IDENTIFICATION IN TRANSFORMER WINDING

Simulation of characteristics of impulse voltage generator for testing of equipment using MATLAB Simulink

TIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M

PARTIAL DISCHARGE MEASUREMENT AS A DIAGNOSTIC TOOL FOR CURRENT TRANSFORMER

AC CREEPAGE DISCHARGES IN SF 6, CO 2, N 2 AND SF 6 -CO 2 AND SF 6 - N 2 MIXTURES

Capacitive voltage transformers

Correlation between time and frequency domain polarisation measurements for transformer moisture assessment

Dielectric Behavior of Insulating Material Under Transformer Oil

Sessile Water Droplets on Insulating Surfaces Subject to High AC Stress: Effect of Contact Angle.

Basics of electrical transformer

Underground System Design TADP 547

Resistive capacitive voltage divider

9. How is an electric field is measured?

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems

6 - Stage Marx Generator

Study of Insulation Under Varying Field Conditions

Power Quality and Reliablity Centre

Resistive capacitive voltage divider

Transcription:

EXPERIMENTAL INVESTIGATION ON THE SURFACE DEGRADATION CHARACTERISTICS OF OIL IMPREGNATED PRESSBOARD DUE TO LIGHTNING AND SWITCHING IMPULSES S. Mohamed Ghouse, K. Vijayarekha and R. Rajesh School of Electrical and Electronics Engineering, Shanmugha Arts, Science, Technology and Research Academy University, Thirumalaisamudram, Thanjavur, Tamil Nadu, India E-Mail:ghouseee@eee.sastra.edu ABSTRACT In HVDC application the converter transformer plays a major role and its insulation system has to be designed to withstand AC, DC as well as transient overvoltage stresses. In this work the effect of transient over voltages on the oil impregnated pressboard which is one of the main insulating materials used in converter transformer. Lightning and switching over voltages are generated using impulse generator circuit and the stress withstanding capabilities of the samples have been investigated. The changes in the shape of the impulse wave during surface degradation have been observed. The degraded zone of the insulation is subjected to ATR-FTIR spectroscopy. From the characteristic peaks of the spectroscopy the by products formed in the degraded zone of the insulating material due to the effect of lightning and switching impulses have been studied. The surface tracking patterns and the insulation failure due to surface tracking have also been studied. Keywords: converter transformer insulation, oil impregnated pressboard, ATR-FTIR spectroscopy. INTRODUCTION As the power demanding increasing day by day in the global energy market the generation of electricity has to be increased to meet out the required power demand. The power generated using conventional resources as well as non conventional resources have to be transmitted over long distances using EHVAC, UHVAC or HVDC transmission systems. The usage of HVDC transmission system is increasing due to the advantages such as high transmission capacity, reduced loss, reduced cost of the system etc. In HVDC system the converter transformer plays a major role. It has to be designed to withstand carefully as it is subjected to AC as well as DC stresses. Many researchers have studied the effect of power frequency AC stress and DC stresses on the insulation of converter transformer. One of the important solid insulating materials used in the converter transformer is oil impregnated pressboard. The design of insulation to be provided in the converter transformer is critical as it is subjected to AC and DC stresses. Due to switching operation of converter circuit switching surges may also affect the insulation integrity of the converter transformer. The insulation materials used in the transformer especially solid insulation such as oil impregnated pressboard and oil impregnated paper have to withstand such sudden surges. The effect of lightning impulse is also plays a major role in the insulation design of transformer. The main cause of failure of solid dielectrics in transformer insulation is due the application of sudden surges such as Lightning surges, switching surges, surges due to line faults and the higher frequency over voltages caused due to the malfunction of protective devices[1]-[3]. The study of insulation withstanding capability due to such impulse over voltages and exploring the degradation mechanism is very important in order to improvise the design of insulation of converter transformer. In recent years little attention was focused on the study of degradation mechanism of solid transformer insulation such as oil impregnated pressboard. During operation the transformer undergoes multi stress which will affect the physical and chemical properties of the oil impregnated pressboard. The surface discharge activity in the composite oil impregnated pressboard is a long term degradation process which may lead to permanent failure of the solid insulation. The surface discharge activity will enhance due to the effect of sudden surges and may even worsen the insulation strength. Surface tracking will cause carbonization over the surface of the insulation and due to this the conductivity over the surface will enhance which leads to permanent damage. During such degradation gaseous and solid by products will be formed and it will affect the insulation strength of transformer oil. Hence it is important to investigate the effect of lightning and switching over voltages in the degradation mechanism of solid insulation of transformers [2]-[8]. In this work, experimental investigation was carried out to study the performance of oil impregnated pressboard subjected to lightning and switching impulses. Standard lightning impulses of 1.2μs/ 50μs and switching impulses of 250μs/2500μs was generated in the single stage Marx impulse generator circuit. Fresh oil impregnated pressboard samples were prepared and it was subjected to impulse stresses. Surface degradation patterns were observed during the application of impulses. The change in the shape of the impulse waveforms during tracking and the severity of the tracked portion due to impulses were observed. In order to understand the surface characteristic changes of the degraded oil impregnated pressboard the sample was subjected to ATR-FTIR spectroscopy. The 7064

characteristic peaks were observed and compared with the ATR-FTIR spectrum of fresh oil impregnated pressboard. The characteristic changes clearly indicate the severity of degradation due to lightning and switches impulses. PREPARATION OF TEST SAMPLES The test container was fabricated for conducting the Impulse test on Oil Impregnated pressboard. Transparent Perspex sheets are used as the wall material for Test container. Perspex sheet was preferred due to its transparency, high mechanical, thermal and electrical strength. The test container along with copper pin-plane electrode configuration is shown in Figure-1. in order to simulate extremely non uniform field condition. The electrodes are made up of copper conductors. The oil impregnated pressboard sample was placed between the electrodes. The impulse voltage end of the impulse generated was connected at the point electrode and the plane electrode was grounded. The point plane configuration with the Test sample is shown as Figure-3. Figure-3. Pin plane configuration. EXPERIMENTAL TEST SETUP The pressboard sample was subjected to both Lightning Impulse and Switching Impulse over voltages with the help of Impulse generator circuit. The circuit arrangement for generating LI and SI over voltages is shown in Figure-4. Figure-1. Test container with pin-plane electrode arrangement. Generally high density pressboard are used in power transformers which operates above 132kV and Medium Density Pressboard are for power and distribution Transformers below 132kV and it is made from 100% cellulose based unbleached sulphate softwood pulp. Medium density pressboard was used in this study. The pressboard samples were fabricated by cutting the pressboard with a dimension of 5cm in diameter. Then the pressboard Sample was impregnated in transformer oil for about 10 days in order to improve its electrical properties. The samples were then dried before testing. The prepared oil impregnated pressboard sample is shown in Figure-2. Figure-4. Impulse generator circuit with test sample. The single stage Marx impulse generator circuit used in this study is capable of generating 140kV peak, 1.2μs/ 50μs lightning impulse voltage and 140kV peak, 250μs/ 2500μs switching impulse voltage. The test setup comprises of 10kVA, 100kV AC test transformer and two numbers of 140kV PIV diode unit, 10MΩ current limiting resistor, controllable sphere gap operated by AC servo motor, earth switch, 25000 pf and 1200pF charging capacitor and wave shaping resistors R 1 and R 2. To generate lightning impulse voltage the value of R 1 and R 2 is selected as 245Ω and 2400Ω respectively [9]-[10]. To generate switching impulse wave the value of R 1 and R 2 is selected as 43kΩ and 48kΩ respectively. The laboratory test setup to carry out impulse test on pressboard samples is as shown in Figure-5. Figure-2. Oil impregnated pressboard sample. The influence of electrodes on the surface discharge study of insulating material plays a major role. In this study point-plane electrode configuration is adopted 7065

Figure-5. Laboratory setup of impulse generator circuit. The oil impregnated press board sample is subjected to lightning and switching impulse over voltages using Impulse generator circuit. As per the preferred testing procedure, negative polarity impulse is generated and tested. 5 samples were considered for testing. Impulse test is conducted for 45 minutes per sample and the most degraded sample is taken for surface degradation studies. The sphere gap was adjusted such that the Impulse voltage applied over the test specimen is at the rate of application of impulses over the specimen is 10 impulses per minute. The impulse generator voltage magnitude was increased in steps such that initial surface discharge is observed in the pressboard sample. Initial surface discharge activity was observed at 50kV peak lightning impulse. Figures 6 (a) - 6(d) shows the different impulse patterns observed during the surface discharge activity. depends upon the increase in surface conductivity due to tracking mechanism. It is clear from the experimental investigations that the failure of insulation is mainly depends upon the magnitude of the lightning impulse voltage and the surface resistance to tracking. Similar experimentation is carried out by applying switching impulse by changing the wave shaping components. Initial surface discharge activity was observed at 42kV peak switching impulse. During switching impulse application it was observed that wider tracked regions were formed over the surface of the pressboard which was not observed in case of lightning impulse voltage. Though the switching transients initiate surface discharge activity at lower voltage magnitude compared to lightning impulse more tracked regions were observed at the surface compared to lightning impulses. Figure-7 (a) - (d) shows the different waveforms observed during the surface discharge activity by the application of switching impulses. Figure-7(a) shows the initial switching impulse waveform without discharge. Figure-7(b) shows the change in shape of switching impulse waveform during initial surface discharge activity. Figures 7(c) and 7(d) shows the change in wave shape during severe tracking conditions. Figure-7. Switching impulse wave during surface discharge. Figure-6. Lightning impulse wave during surface discharge. Figures 8(a) - 8(d) shows the surface discharge patterns recorded during experimentations. Initially the surface discharges were observed at the edges of the pressboard instead over the surface. Figure-8(a) shows the initial discharge patterns. As time progresses the discharges were observed at the tip of the pin electrode and the discharges were observed over the surface in an irregular manner. Figure-6 (a) shows the initial lightning impulse waveform without any surface discharge activity. 6. (b) shows the change in shape of the impulse waveform during initial surface discharge. Due to the stress tracked regions were observed at the surface and it leads to further deterioration of the sample. Figures 6(c) and 6(d) shows the waveforms during tracking over the surface of the sample. It was observed that the shape of the waveform didn t collapse immediately, instead the shape changes 7066

Figure-8. Surface discharge patterns during testing. During the application of lightning impulses the discharges initially spread over the surface in an irregular pattern. After sometime the discharges were found to follow only a specific region in the surface. The other portion of the pressboard was not affected by the discharges. But in case of switching impulses the discharges spread over the surface in an irregular way and it creates tracking patterns in a wider region compared to lightning impulses. Figures 8(b) and 8(c) shows the surface discharge during switching impulse. It is clear from figure that the pattern covers wider region. Figure 8.(d) shows the surface discharge pattern during lightning impulse. The discharge region confined to a particular portion of the pressboard. A continuous arc through the surface of the specimen was observed. Though the other part of the insulation was not affected the degradation caused by lightning impulse was severe. Figures 9(a) - 9(d) shows the degraded regions over the surface of the pressboard due to lightning and switching impulses. Figure-9(a) shows the oil impregnated subjected to lightning impulses. It is clear from the photograph that the tracking over the surface of the specimen was observed over a narrow region. But the physical damage caused by the lightning impulse is severe. Figure-9(b) shows the peel off region in the surface of the oil impregnated pressboard. Figure-9(c) shows the oil impregnated pressboard sample subjected to switching impulse. It is clear from the photograph that the tracking over the surface of the specimen was observed over a wider region compared to the sample subjected to lightning impulse. Almost 40 percent of the surface was degraded during testing. But the severity of the physical damage at the surface was less compared to lightning impulse samples. No peel off region was observed at the surface of the specimen subjected to switching impulses. The surface degradation phenomenon not only depends upon the magnitude of the impulse. It also depends upon the front and tail time of the impulse. More analysis is required with different switching transient over voltages with different front and tail time [11]-[12]. ATR-FTIR SPECTROSCOPY ANALYSIS ATR-FTIR spectroscopy provides a wavelength spectrum of a functional group that is formed at the surface of the degraded portion of the samples. Figure- 10(a)- 10(c) shows the ATR-FTIR spectra obtained at the degraded region of the oil impregnated pressboard samples. The spectra clearly indicate the functional group formed due to characteristic changes that occur due to ageing. In general, the characteristic peaks for Alkanes and carboxylic acids formation appear in the range 2850 and 3000 cm- 1, alcohols, carboxylic acids, esters, ethers are detected in the range 1320 and 1000 cm- 1, alkenes are present in range 1000 and 650 cm- 1, aromatic compounds, primary and secondary aminesare detected in the range 900-675 cm- 1 and alkyl halides are detected in the range 850-550 cm- 1 and 700-610 cm- 1. Figure-10. (a) ATR-FTIR analysis of fresh pressboard. Figure-9. Degraded region over the surface of the pressboard. ATR-FTIR spectroscopy was carried out on fresh sample, surface degraded sample due to lightning impulses and switching impulses. Figure-10 (a) shows the ATR- FTIR spectra of fresh sample. It is clear that the characteristic peaks appears in the range 3000-2800 cm-1 corresponds to presence of alkenes due to C-H stretch. 7067

4 5 8. 1 5 c m - 1 VOL. 12, NO. 24, DECEMBER 2017 ISSN 1819-6608 Alkanes are also detected from the characteristic peaks which occur in the range 146cm-1 to 1370 cm-1. %T 0 4000 3500 3000 2500 2000 1500 1000 500450 cm-1 Name Description Figure-10. (b)atr-ftir Analysis of LI degraded pressboard. Figure-10 (a) shows the ATR-FTIR spectra of sample subjected to lightning impulse voltage. When the degraded zone of the subjected to ATR-FTIR spectroscopy, alkanes and aldehydes formations are detected in the range 2900-2800 cm-1 due to C-H stretch. Alcohols and carboxylic acid formation are detected in the range 1320-1000cm-1. Alcohols, carboxylic acids, esters, ethers are detected in the range 1320-1000 cm-1 due to C- O stretch. The formation of alkyl halides are detected in the range 690-515cm-1. %T 100 90 80 70 60 50 40 30 20 10 100 90 80 70 60 50 40 30 20 10 SU-LI-5cm- SU-SI-5Cm- 3338.80cm-1 3366.92cm-1 2855.05cm-1 2922.40cm-1 2855.10cm-1 2923.37cm-1 Figure-10. (c)atr-ftir Analysis of SI degraded pressboard. When the degraded zone of the lightning impulse tested specimen subjected to ATR-FTIR spectroscopy alkanes and aldehydes formations are detected in the range 2900-2800 cm-1 due to C-H stretch. Alcohols and carboxylic acid formation are detected in the range 1320-1000cm-1. But the change in %T was minimum compared to lightning impulse samples. CONCLUSIONS This work deals with the effect of lightning and switching impulse in the surface degradation of oil impregnated pressboard. It is clear from the experimental investigations that the effect of lightning and switching impulses in degrading the surface of the insulation is distinctly different. The wave shapes during tracking was recorded. It is inferred from the wave shapes that during 1640.59cm-1 1375.65cm-1 1459.50cm-1 1376.33cm-1 1459.49cm-1 1156.58cm-1 1103.89cm-1 1031.15cm-1 1097.31cm-1 600.67cm-1 666.21cm-1 719.41cm-1 555.34cm-1 0 4000 3500 3000 2500 2000 1500 1000 500450 cm-1 Name Description 607.94cm-1 465.54cm-1 1627.93cm-1 5 5 1. 9 5 c m - 1 721.30cm-1 initial surface discharge the pattern of the impulse was not significantly changing. But during the severe discharge condition due to the failure of the surface resistance the change in shape of impulse waveforms have been observed. ATR-FTIR spectroscopy studies have been carried out to investigate the by product formed due to the surface degradation. It is clear from the studies that the degraded oil impregnated pressboard releases alcohols and carboxylic acids which will react with transformer oil and reduces the life of the insulation. ACKNOWLEDGEMENT The authors thank the Management of SASTRA University and DST-FIST (Sanction order ref: SR/FST/ETI-338/2013(C) dated 10/09/2014) for their motivation and financial support for creating the facilities at HV lab of SASTRA, with which the Experimental works were carried out. REFERENCES [1] 2004. Pressboard and Presspaper for electrical purposes-part 2:Methods of tests, IEC Standred 60641-2. [2] Fabian Schober, Stephan Harrer and Andreas Küchler, Frank Berger, Wolfgang Exner and Christoph Kraus. 2016. Transient and steady- State DC behavior of oilimpregnated pressboard. IEEE Electrical Insulation Magazine. 32(4): 8-14. [3] Orlando Girlanda, Kun Wei, Lars E. Schmidt. 2016. Static and quasi-static behavior of dry and oil impregnated pressboard. 2016 Electrical Insulation Conference (EIC), Montréal, Qc, Canada, 19-22. [4] F. Schober, A. Kuchler W. Exner, Ch. Krause. 2015. Influence of Board Density on the Conductivity of Oil-impregnated Pressboard for HVDC Insulation Systems. 2015 Electrical Insulation Conference (EIC), Seattle, Washington, USA, 7-10. [5] T. Umemoto, S. Kainaga, H. Muto and T. Tsurimoto, S. Yoshida, M. Kozako and M. Hikita. 2014. Characteristics of Partial Discharge in the Oil Gap Separated by Pressboard Barrier in Oil/Pressboard Composite Insulation System. 2014 IEEE International Conference on Liquid Dielectrics, Bled, Slovenia, June 30 - July 3. [6] D. Fabiani and G.C. Montanari. 2011. The effect of voltage distortion on ageing acceleration of insulation systems under partial discharge activity. IEEE Electr. Insul. Mag. 17(3): 24-33. 7068

[7] V. Sokolov, Z. Berler and V. Rashkes. 1999. Effective Methods of Assessment of Insulation System Conditions in Power Transformers: a View Based on Practical Experience. IEEE Electr. Insul. Conf. Electr. Manufacturing & Coil Winding. pp. 659-667. [8] J. Li, W. Si, X.Yao and Y. Li. 2009. Measurement and simulation of partial discharge in oil impregnated pressboard with an electrical aging process. Measurement Sci. Techn. 20(10): 17. [9] J. Li, W. Si, X. Yao and Y. Li. 2009. Partial Discharge Characteristics over Differently Aged Oil/pressboard Interfaces. IEEE Trans. Dielectr. Electr. Insul., Vol. 16, No. 6, pp. 1640-1647. [10] B. Sonerud, T. Bengtsson, J. Blennow and S. M. Gubanski. 2009. Dielectric heating in insulating materials subjected to voltage waveforms with high harmonic content. IEEE Trans. Dielectr. Electr. Insul. 16(4): 926-933. [11] P. Caramia, G. Carpinelli, P. Verde, G. Mazzanti, A. Cavillini and G.C. Montanari. 2000. An approach to life estimation of electric plant components in the presence of harmonic distortion. 9 th Int l. Conf. Harmonics and Quality of Power. 3: 887-892. [12] B. Florkowska, M. Florkowski and P. Zydron. 2007. The Role of Harmonic Components on Partial Discharge Mechanism and Degradation Processes in Epoxy Resin Insulation. IEEE Int l. Conf. Solid Dielectr, Winchester, UK. pp. 560-563. 7069