MODELING AND CONTROLLING OF AC VOLTAGE STABILIZER USING SERIES ACTIVE POWER FILTER

Similar documents
Mitigation of Harmonics in Distribution System Using SAPF

Enhancement of Power Quality Using Advanced Series Active Power Filters

Power Quality improvement of a three phase four wire system using UPQC

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

2020 P a g e. Figure.2: Line diagram of series active power filter.

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

Design of Unified Power Quality Conditioner (UPQC) Connected To Three Phase Four Wire System

P.CHAITHANYAKUMAR, T.VARAPRASAD/

Improvement of Power Quality Using a Hybrid Interline UPQC

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation

Unified Power Quality Conditioner (UPQC) in Alleviation of Power Quality Issues

Reduction of Voltage Imbalance in a Two Feeder Distribution System Using Iupqc

Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller

Power Quality Improvement using Shunt Passive Filter

A NOVEL STRUCTURE FOR THREE-PHASE FOUR-WIRE DISTRIBUTION SYSTEM UPQC

Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition

Study & Comparison of Various Topologies of Dynamic Voltage Restorer & Its type: a Review

UNIFIED POWER QUALITY CONDITIONER IN DISTRIBUTION SYSTEM FOR ENHANCING POWER QUALITY

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER

Power Quality Improvement using Active shunt Power filter using PI Controller

Application of Fuzzy Logic Controller in Shunt Active Power Filter

A Power Control Scheme for UPQC for Power Quality Improvement

p. 1 p. 6 p. 22 p. 46 p. 58

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

IMPROVEMENT OF POWER QUALITY USING CUSTOM POWER DEVICES

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Power Quality Improvement of Unified Power Quality Conditioner Using Reference Signal Generation Method

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

A Review on Power Quality Improvement in Distribution System using UPQC

Performance of DVR under various Fault conditions in Electrical Distribution System

Modified three phase Unified Power Quality Conditioner with capacitor midpoint topology

A Modified Control Method For A Dual Unified Power Quality Conditioner

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

COMPENSATION OF POWER QUALITY PROBLEMS USING ACTIVE POWER FILTER

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Mitigating Voltage Sag Using Dynamic Voltage Restorer

ISSN Vol.07,Issue.21, December-2015, Pages:

Exploration in Power Quality Furtherance on Shunt Active Power Filter

Power Quality and the Need for Compensation

Keyword: Distributed System, Filters, Harmonics, Power quality improvement, THD, UPQC and Voltage Harmonics.

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

Simulation and Implementation of DVR for Voltage Sag Compensation

Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller

A Novel Fuzzy Variable-Band Hysteresis Current Controller For Shunt Active Power Filters

Improvement of Power Quality Using a Hybrid UPQC with Distributed Generator

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

Protection from Voltage Sags and Swells by Using FACTS Controller

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

A New Unified Power Quality Conditioner for Grid Integration of PV System and Power Quality Improvement Feature Distribution System

Power Quality Improvement using Hysteresis Voltage Control of DVR

Compare Stability Management in Power System Using 48- Pulse Inverter, D-STATCOM and Space Vector Modulation Based STATCOM

CONTROL OF VOLTAGE SAG/SWELL IN THREE PHASE DISTRIBUTION LINE

IMPROVING EFFICIENCY OF ACTIVE POWER FILTER FOR RENEWABLE POWER GENERATION SYSTEMS BY USING PREDICTIVE CONTROL METHOD AND FUZZY LOGIC CONTROL METHOD

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Design of UPQC with constant frequency controlled scheme for removal of Total Harmonic Distortion

Mitigation of Current Harmonics with Combined p-q and Id-IqControl Strategies for Fuzzy Controller Based 3Phase 4Wire Shunt Active Filter

II. RESEARCH METHODOLOGY

DYNAMIC VOLTAGE RESTORER (DVR) FOR VOLTAGE SAG COMPENSATION WITH FUZZY LOGIC CONTROLLER. Chennai, Tamilnadu, India. Chennai, Tamilnadu, India.

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

Development and Simulation of Dynamic Voltage Restorer for Voltage SAG Mitigation using Matrix Converter

A CONTROL TECHNIQUE FOR INSTANT MITIGATION OF VOLTAGE SAG/SWELL BY DYNAMIC VOLTAGE RESTORER

International Journal of Research (IJR) e-issn: , p- ISSN: X Volume 2, Issue 09, September 2015

ISSN: [Bhat * et al., 7(8): August, 2018] Impact Factor: 5.164

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

Mitigation of Voltage Sag/Swell Using UPQC

Simulation of a Dynamic Voltage Restorer to Compensate Voltage Sag for Improving Power Quality

Design of Dynamic Voltage Restorer for three phase network as steady state device in the Distribution System

Key-Words: - NARX Neural Network; Nonlinear Loads; Shunt Active Power Filter; Instantaneous Reactive Power Algorithm

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Design of Shunt Active Filter to Improve Power Quality using Pq Theory

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

Grid Interconnection of Wind Energy System at Distribution Level Using Intelligence Controller

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy

DYNAMIC VOLTAGE RESTORER FOR EFFICIENT DETECTION AND COMPENSATION OF VOLTAGE SAG USING ANN BASED LMS AS A NEW CONTROL STRATEGY

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

Reduction In Total Harmonic Distortion Using Active Power Filters

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Voltage Correction Methods in Distribution System Using DVR

Power Factor Improvement Using a Three Phase Shunt Active Power Filter

Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based Dstatcom

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Improvement in Power Quality of Distribution System Using STATCOM

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 03, 2015 ISSN (online):

Literature Review for Shunt Active Power Filters

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

POWER QUALITY ASSESSMENT AND ENHANCEMENT IN A GRID CONNECTED RENEWABLE ENERGY SYSTEM USING DYNAMIC VOLTAGE RESTORER

Transcription:

MODELING AND CONTROLLING OF AC VOLTAGE STABILIZER USING SERIES ACTIVE POWER FILTER Pratyenja Ganorkar 1, D.A.Shahakar 2 1 PG Scholar, Electrical Engineering Department, P.R.Pote (Patil) College of Engineering & Management, Amravati, Maharashtra, India 2 Head of Department, Electrical Engineering Department, P.R.Pote (Patil) College of Engineering & Management, Amravati, Maharashtra, India ABSTRACT These hundreds area unit sensitive for any input variations in voltage. The performance of the electrical instrumentality gets worsened if they're furnished with contaminated or distorted voltage. variety of solutions area unit offered within the gift day apply like power issue correction system with detuned filter, capacitance banks and series reactors to mitigate harmonics, improve power issue, avoid electrical resonance. Much passive filters area unit still used those they need mounted compensation and therefore the threat of resonance. Solutions to those issues are often of 2 ways- one is to vary the look of the systems so the matter gets reduced and therefore the alternative is to seek out a remedy for the prevailing system. The various hundreds area unit classified in line with the issues raised by them and to focus on the assorted sensible solutions that may solve them to a good extent. This paper focuses on modeling and analysis of Custom Power Device (SAPF). MATLAB/Simulink based mostly models for Voltage stabilizer using series active power filter (SAPF) is given. Among varied PWM techniques, physical phenomenon band voltage management PWM is popularly used as a result of its simplicity of implementation. This renowned technique doesn't would like any info regarding system parameters. The SAPF is simulated for various voltage variations at input generated by the 3 part programmable supply and therefore the results area unit given. Keyword: - Voltage stabilizer using series active power filter, Power quality 1. INTRODUCTION Power quality phenomena embrace all doable things during which the wave form of the provision voltage (voltage quality) or load current (current quality) deviate from the curving wave form at rated frequency with amplitude equivalent to the rated rms price for all 3 phases of a three-phase system [1]. The wide selection of power quality disturbances covers fast, short length variations, e.g. impulsive and oscillating transients, voltage sags, short interruptions, yet as steady state deviations, like harmonics and flicker. One can even distinguish, supported the cause, between disturbances associated with the standard of the provision voltage and people associated with the standard of the present taken by the load [2]. To the primary category covers voltage dips and interruptions, principally caused by faults within the grid. These disturbances could cause tripping of sensitive instrumentality with fatal consequences in industrial plants wherever tripping of vital equipment will bear the stoppage of the entire production with high prices associated. One will say that during this case it's the supply that disturbs the load. To avoid consistent cash losses, industrial customers typically conceive to install mitigation instrumentation to shield their plants from such disturbances. The second category covers phenomena thanks to caliber of this drawn by the load. During this case, it's the load that disturbs the supply. A typical example is current harmonics drawn by worrisome masses like diode rectifiers, or unbalanced currents drawn by unbalanced masses. Customers don't expertise any direct production loss associated with the incidence of those power quality phenomena. However poor quality of this taken by many purchasers along 9319 www.ijariie.com 411

can ultimately lead to caliber of the facility delivered to alternative customers [3]. Each harmonics and unbalanced currents ultimately cause distortion and severally, unbalance within the voltage moreover. Therefore, correct standards area unit issued to limit the number of harmonic currents, unbalance and/or flicker that a load could introduce. To fits limits set by standards, customers typically need to install mitigation instrumentation. In recent years, each industrial and business customer of utilities has reported a flood tide of misadventures associated with power quality. the difficulty stems from the multiplied refinement of today s automatic instrumentation, whether or not variable speed drives or robots, automatic production lines or machine tools, programmable logic controllers or power provides in computers. They and therefore their like area unit way at risk of disturbances on the utility system than were the previous generation of mechanical device instrumentation and the previous less automatic production and knowledge systems. A growing range of masses is sensitive to customers vital processes that have pricey consequences if disturbed by either poor power quality or power interruption. For the explanations represented higher than, there's a growing interest in instrumentation for mitigation of power quality disturbances, particularly in newer devices supported power physics referred to as custom power devices ready to deliver bespoke solutions to power quality issues. 2. MATLAB SIMULATION MODEL The Voltage stabilizer using series active power filter is employed to compensate the supply facet disturbances like voltage sags, swells and conjointly harmonic distortions. during this configuration, the filter is connected nonparallel with the road being stipendiary. Therefore the configurations square measure usually brought up as a series active filter. The approach relies on the principle of injecting voltage nonparallel with the road through the injection electrical device to cancel the supply facet voltage disturbances and so it makes the load facet voltage curving. Fig. 1 shows the MATLAB/ Simulink model of designed system. The main components of the below system are as follows. Mains supply Nonlinear load Active Power Filter Voltage source inverter Interface reactor Reference voltage generator Hysteresis voltage controller Fig -1: MATLAB simulation model of proposed Voltage stabilizer using series active power filter 9319 www.ijariie.com 412

3. MATLAB SIMULATION RESULT 3.1. Case 1 model Fig. 2 shows the source voltage in which rated 1 p.u voltage is created from 0 to 0.1 seconds, 0.8 p.u sag from 0.1 to 0.15 seconds,1 p.u voltage from 0.15 to 0.2 seconds, 1.2 p.u swell from 0.2 to 0.25 seconds, 0.4 p.u sag from 0.25 to 0.3 seconds, 0.9 sag from 0.3 to 0.4 seconds and 1p.u voltage from 0.4 to 0.5 seconds. Table -1: Source Voltage parameters 3-phase (line-ground) Time (Second) Voltage (pu) Load 0 to 0.1 1 R = 50Ω; 0.1 to 0.15 1.8 L = 1 mh 0.15 to 0.2 1 0.2 to 0.25 1.2 0.25 to 0.3 0.4 0.3 to 0.4 0.9 0.4 to 0.5 1 Fig -2: 3-Phase Source voltage (Line-Ground) 9319 www.ijariie.com 413

Fig-3: Source Voltage in each Phase Fig. 4 shows the compensated voltage injected by each phases to cancel the source side disturbances present in the system. Fig-4: Compensated voltages injected for each phases Due to the injection of the above voltages through the injection transformer in series with the line the load voltage is sinusoidal as shown in Fig. 5. 9319 www.ijariie.com 414

Fig-5: 3-Phase Load voltage (Line-Ground) The Total harmonic distortion of source voltage is 1.64% and load voltage is 0.04 % as shown in Fig. 4.6 & Fig. 4.7 respectively. Fig-6: Source voltage harmonic spectrum Fig-7: Load voltage harmonic spectrum The SAPF is simulated with only interruptions in the form of Sag, Swell in the input side & the performance of SAPF is analyzed by taking the FFT analysis of the Source and load Voltages. 9319 www.ijariie.com 415

3.2. Case 2 model Fig. 8 shows the source voltage in which rated 1 p.u voltage is created from 0 to 0.1 seconds, 0.8 p.u sag from 0.1 to 0.15 seconds,1 p.u voltage from 0.15 to 0.2 seconds, 1.2 p.u swell from 0.2 to 0.25 seconds, 5th order harmonics of 0.4 p.u and 7th order harmonics of 0.2 p.u from 0.25 to 0.4 seconds, 0.9 sag from 0.4 to 0.5 seconds. the load is R=50Ω and L=10 mh. Fig-8: 3-Phase Source voltage (Line-Ground) Fig-9: Source Voltages per phase Fig. 10 shows the compensated voltage injected by each phases to cancel the source side disturbances present in the system. 9319 www.ijariie.com 416

Fig-10: Compensated voltages injected for each phases Due to the injection of the above voltages through the injection transformer in series with the line the load voltage is sinusoidal. The Total harmonic distortion of source voltage is 64.37% and load voltage is 0.72 % as shown in Fig. 11 & Fig. 12 respectively. Fig-11: Source voltage harmonic spectrum Fig-12: Load voltage harmonic spectrum 4. CONCLUSION A Voltage stabilizer using series active power filter has been investigated for power quality improvement. Numerous simulations area unit administrated to research the performance of the system. Physical phenomenon controller primarily based Voltage stabilizer using series active power filter is enforced for harmonic and voltage distortion compensation of the non-linear load. The Simulation is even extended for abnormal faults occurring on the ability system like L-G & L-L faults. 9319 www.ijariie.com 417

This section presents an summary of series active filter, its principle of operation and its management theme to come up with reference load voltage and physical phenomenon voltage controller to administer pulses to the series filter to inject the voltage through electrical device asynchronous with the road and also the simulation waveforms for supply voltage, salaried voltage and cargo voltage area unit planned. The doctor's degree of the load voltage with the inclusion of the active filter is well below five-hitter that is that the harmonic limit obligatory by the IEEE 519 standards. 5. REFERENCES [1] Bhim Singh and venkateswarlu.p, A Simplified Control Algorithm for Three- Phase, Four-Wire Unified Power Quality Conditioner Journal of Power Electronics, Vol. 10, No. 1, January 2010 pp.91-96. [2] B.Singh,K.Al-Haddad,and A.Chandra, A review of active power filters for power quality improvement, IEEE Trans.Ind.Electron.,vol.45,no.5,pp.960-971,Oct 1999. [3] V.Khadkikar,A.Chandra,A.O.Barry,and T.D.Nguyen, Application of UPQC to protect a sensitive load on a polluted distribution network, in Proc. IEEE PES General Meeting,Montreal,QC,Canada,2006,6pp. [4] V.Khadkikar,A.Chandra,A.O.Barry,and T.D.Nguyen, Conceptual analysis of unified power quality conditioner(upqc), in proc. IEEE ISIE,2006,pp.1088-1093. [5] Vinod Khadkikar and Ambrish Chandra, A Novel Structure for Three-Phase Four-Wire Distribution System Utilizing Unified Power Quality Conditioner (UPQC) IEEE Transactions on Industry Appl., Vol. 45, No. 5, September/October 2009. [6] Yash Pal, A. Swarup, and Bhim Singh, A Comparison of Three Topologies of Three-Phase Four-Wire UPQC for Power Quality Improvement 16 th National Power systems conference, 15th-17th December, 2010 pp.227-232. [7] S. Chakraborty and F. A. Farret, A Single Phase High Frequency AC Microgrid with an Unified Power Quality Conditioner, Proceedings on IEEE 2003, pp.952-967. [8] Active power filter with automatic control circuit for neutral current harmonic minimization technique by mohd izhar bin a bakar [9] Handbook of Power Quality by Angelo Baggini. [10] S.K. Jain, P. Agrawal and H.O. Gupta, Fuzzy logic controlled shunt active power filter for power quality improvement IEEE Proceedings on Elect.Power.Appl.Vol 149.No.5,September 2002. 9319 www.ijariie.com 418