C1-207 TRANSMISSION CAPACITY INCREASE BY RETURNING POWER SYSTEM STABILIZERS

Similar documents
LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS

Coordinating Power Oscillation Damping Control using Wide Area Measurements

Subsynchronous oscillations aspects and experiences from Finland

Tor Rolv Time, Øystein Kirkeluten STATNETT Oslo, Norway

VOLTAGE STABILITY OF THE NORDIC TEST SYSTEM

Real-time Monitoring of Power Oscillations and Modal Damping in the European ENTSO-E System

ELEMENTS OF FACTS CONTROLLERS

A PSCAD case study of the main factors influencing the level of subsynchronous torsional interaction caused by HVDC

POWER SYSTEM OSCILLATIONS

Stability Improvement for Central China System

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES

Testing model data usability Excitation Systems PSS Limiters

Power System Reliability and Transfer Capability Improvement by VSC- HVDC (HVDC Light )

Eigenvalue Analysis All Information on Power System Oscillation Behavior Rapidly Analyzed

Facilitating Bulk Wind Power Integration Using LCC HVDC

1400 MW New Zealand HVDC Upgrade: Introducing Power Modulation Controls and Round Power Mode

ANALYTICAL AND SIMULATION RESULTS

Loop Design. Chapter Introduction

Improvement of Rotor Angle Stability and Dynamic Performance of AC/DC Interconnected Transmission System

Dynamic stability of power systems

HVDC MULTI-INFEED PERFORMANCE

Development and Analysis of Nordic32 Power System Model in PowerFactory

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

A Real-Time Platform for Teaching Power System Control Design

Power Quality enhancement of a distribution line with DSTATCOM

DYNAMIC PERFORMANCE OF THE EAGLE PASS BACK-TO-BACK HVDC LIGHT TIE. Å Petersson and A Edris ABB Power Systems AB, Sweden and EPRI,USA

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN

The Baltic Ring Study Transmission System Simulations in the Baltic Sea Region

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Low Frequency Local mode Oscillations in NER Grid, Validation using Model based analysis and Mitigation

Grid Code Review Panel. Information Required to Evaluate Subsynchrononous Resonance on the Transmission System

Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements

Chapter 10: Compensation of Power Transmission Systems

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

Deployment and Initial Experience with Oscillation Detection Application at Bonneville Power Administration

Application Example Document ID: SA Rev. - September 24, 2004

Protection for Sub SSTI Conditions Using an Industrial Sub-harmonic Relay

Testing and Implementation of a Source Locating method at ISO New England

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

ESB National Grid Transmission Planning Criteria

Assessment of Saturable Reactor Replacement Options

A Comprehensive Approach for Sub-Synchronous Resonance Screening Analysis Using Frequency scanning Technique

A new control scheme for an HVDC transmission link with capacitorcommutated converters having the inverter operating with constant alternating voltage

ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS

Unit Auxiliary Transformer (UAT) Relay Loadability Report

EXPERIMENTAL INVESTIGATION OF THE ROLE OF STABILIZERS IN THE ENHANCEMENT OF AUTOMATIC VOLTAGE REGULATORS PERFORMANCE

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

6545(Print), ISSN (Online) Volume 4, Issue 1, January- February (2013), IAEME & TECHNOLOGY (IJEET)

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Partial Power Operation of Multi-level Modular Converters under Subsystem Faults

Power Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)

Transient Stability Improvement Of IEEE 9 Bus System With Shunt FACTS Device STATCOM

Modelling to stability analysis of brushless excitation systems on synchronous generator

EH2741 Communication and Control in Electric Power Systems Lecture 2

A cost effective hybrid HVDC transmission system with high performance in DC line fault handling

Southern Company Interconnection Requirements for Inverter-Based Generation

EXCITATION SYSTEM MODELS OF GENERATORS OF BALTI AND EESTI POWER PLANTS

Power System Stability. Course Notes PART-1

Step-Response Tests of a Unit at Atatürk Hydro Power Plant and Investigation of the Simple Representation of Unit Control System

Experiences of Using Synchrophasors at Duke Energy

Planners Perspective on Series Compensated Transmission Lines

Fundamentals of Servo Motion Control

ABB Automation World 2012, V. Knazkins, 6 June 2012 Countermeasure of PSS4B for Low Frequency Oscillations PSS4B. ABB Group June 4, 2012 Slide 1

each time the Frequency is above 51Hz. Continuous operation is required

Determination of Optimal Account and Location of Series Compensation and SVS for an AC Transmission System

Putting a damper on resonance

BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A. NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014

FINNISH EXPERIENCES ON GRID EFFECTS OF GIC'S

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Adamantios Marinakis, Scientist, 12 th IEEE SB Power Engineering Symposium, Leuven, Enhancing Power System Operation with WAMS

1

OPERATING PROCEDURE. Table of Contents

Lab 1. Objectives. Single Line Diagram. Methodology. Observations. Jon Jawnsy Yu 26 October 2009

ITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/

Indication of Dynamic Model Validation Process

SSE Offices, Glasgow and Teleconference

New Redundant Automatic Voltage Regulator (AVR) Solution

SRI VIDYA COLLEGE OF ENGG AND TECH

Study on the Improvement of the Special Protection Scheme (SPS) in the Korean power system

How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements

High Voltage DC Transmission 2

MANITOBA HYDRO TRANSMISSION SYSTEM INTERCONNECTION REQUIREMENTS. July 2016 Version 4

ENTSO-E Draft Network Code on High Voltage Direct Current Connections and DCconnected

Constant Terminal Voltage. Working Group Meeting 4 19 th September 2014

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements

Power Control Scheme of D-Statcom

Analysis of Power System Oscillation Damping & Voltage Stability Improvement Using SSSC in A Multimachine System

Oscillatory Stability: Extended Range & Enhanced Source Location

A Review on Power System Stabilizers

Effects and Mitigation of Post-Fault Commutation Failures in Line-Commutated HVDC Transmission System

International Journal of Advance Engineering and Research Development

C2-205 ANALYSIS AND SOLUTION OF TECHNICAL CONSTRAINTS IN THE SPANISH ELECTRICITY MARKET

LFC/AGC Nordic and European perspective. Exchange of balancing services international workshop Jan 2011 Whitley Gjerde

Transcription:

21, rue d'artois, F-75008 Paris http://www.cigre.org C1-207 Session 2004 CIGRÉ TRANSMISSION CAPACITY INCREASE BY RETURNING POWER SYSTEM STABILIZERS STEFAN ELENIUS* JUSSI JYRINSALO SIMO JOKI-KORPELA HELSINKI UNIVERSITY FINGRID OYJ TEOLLISUUDEN OF TECHNOLOGY VOIMA OY (Finland) 1. INTRODUCTION In certain operational situations, poorly damped inter-area oscillations may restrict the transmission capacity from Finland to the other Nordic countries. The frequency of the inter-area oscillation mode is around 0.3 Hz and the generators in southern Finland participate most strongly in these oscillations [1]. Small sustained oscillations of this frequency have occasionally been noticed in the terminal power of the two largest generators in Finland as well as in the power flow of the 400 kv AC transmission lines between Finland and Sweden. Studies revealed that retuning the power system stabilizers (PSS) of the two largest generators in Finland can give as much as 10...20 % of extra transmission capacity towards the Swedish grid. However, both simulations and the first on-site test also revealed that the reactive power controllers (RPC) of the generators in question can strongly interact with the power system stabilizers. After the first on-site test, efforts were made to coordinate the reactive power control loop with the power system stabilizer. However, the second on-site test revealed a new, very low frequency interaction problem. The interaction was also verified by simulations. The RPC loop was again retuned and a third on-site test was performed. The third test included disconnection of one of the interconnecting 400 kv AC lines to Sweden, so as to increase the inter-area reactance and to create large power oscillations. The system tests showed that a solution to the problem had been found and the damping of the inter-area oscillations was much better with the new control system settings than with the original ones. This gives a clear transmission capacity increase. For the simulations we have used the PSS/E-model [2] of the Nordic power system that has been developed by the Nordic transmission system operators during the past twenty years. The model has 1282 generators and 4780 buses. A frequency scanning method was used with the dynamic simulations to optimize the tuning of the control loops. * stefan.elenius@hut.fi

2. POWER OSCILLATIONS IN THE FINNISH GRID The Finnish power transmission grid is a part of the synchronous Nordic grid. The national grid operator, Fingrid Oyj has the responsibility of maintaining the operational reliability of the Finnish power system. The most important interconnections to Scandinavia are two 400 kv AC lines between the northern parts of Finland and Sweden and a 400 kv DC connection between the southern parts of the two countries (Figure 1). Hydro power plant Thermal power plant Substation Olkiluoto power plant Russia Estonia Latvia Lithuania Germany Poland Figure 1. Map of the Nordic power system. The transmission capacity of the 400 kv AC interconnections is in most situations determined by stability issues. Voltage stability becomes a limiting factor after certain contingencies when importing power from the northern parts of Sweden. However, in export situations when the power is transmitted all the way to southern Scandinavia, the limiting factor is poorly damped inter-area oscillations. The frequency of these system-wide oscillations is around 0.3 Hz. The power system stabilizer settings for the largest generators in Finland had previously been assessed in the beginning of 1980 s. In the end of 1998 some prolonged low-frequency oscillations were observed during a low load situation. There were no line outages in the grid at that time and the power exchange between Sweden and Finland was relatively low. This incident suggested that the damping issue should be reassessed in 2

the present situation where both the grid and its loading patterns had considerably changed from the 1980's. In the first phase, the studies were concentrated on the power system stabilizers at the two largest generators in Finland, i.e. Olkiluoto power plant. It was soon also found out that the power system stabilizers may in some situations interact with reactive power controllers thus giving rise to sustained power oscillations. 3. OLKILUOTO POWER PLANT CONTROLS On the west coast of Finland, in Eurajoki, Teollisuuden Voima Oy (TVO) operates two 840 MW boiling water reactors (by ASEA ATOM AB). TVO was founded in 1969 by a number of Finnish industrial companies with the purpose of building and operating large power plants. The company supplies electricity to its shareholders at cost. The first Olkiluoto unit was connected to the national grid in September 1978 and the second unit in February 1980. The units have been uprated twice since the commissioning. The thermal power of each reactor was increased from 2000 MW to 2160 MW in 1984 and to 2500 MW in 1998. The corresponding nominal values of the net electrical output were 660 MW, 710 MW and 840 MW, respectively. Normally, both units are used in reactive power control mode and voltage control is only prioritized in case the terminal voltage differs more than 2,5% from its setpoint value. The principle is that no reactive power is supplied to the grid during normal operational conditions. By using this kind of mode the maximum amount of reactive power is kept as disturbance reserve and furthermore, the generators can be operated at a stable temperature condition. The generators have brushless excitation systems with rotating AC pilot- and main-exciters. The generators can also be operated in constant field current mode, where the pilot exciter, voltage controller and thyristor rectifier are replaced with an excitation transformer, current controller and a separate thyristor rectifier. The selection between the two modes is done by means of switches on the DC side of the thyristor bridges. (Figure 2). Figure 2. Functional block diagram for the excitation systems at Olkiluoto. 3

4. DYNAMIC SIMULATIONS AND ON-SITE TESTING 4.1 Frequency response of the excitation system The power system stabilizers at Olkiluoto use the active power at the generator terminals as input signal and the stabilizer output is connected in parallel with the voltage reference of the voltage regulator. The original stabilizers were tuned primarily for damping local machine oscillations. In order to determine what transfer function would be required to damp the inter-area oscillations, a frequency scanning technique for the PSS/E power system simulator was developed, implemented and used together with the normal PSS/E-simulations by the main author. The frequency response of the transfer function from the voltage reference to the terminal power of the Olkiluoto generators has been obtained by simulations with the large Nordic power system model (Figure 3.a). The Olkiluoto power system stabilizers were switched off during the frequency scanning. The frequency response with the highest magnitude is obtained in the 4...8 rad/s range. These oscillations occur between generators or groups of generators in Finland. Another resonance is at 2.0 rad/s (0.32 Hz). This is the inter-area mode, where the generators in Finland oscillate against the generators in the southern parts of Sweden and Norway. The phase shift is about 45 degrees lead at the 2.0 rad/s resonance, and changes sharply in the 5...7 rad/s range from lead to lag. The resonance at 50 rad/s is generator/exciter shaft torsional oscillations. Figure 3. a) Frequency response of the excitation systems of the Olkiluoto generators. b) Frequency response of the power system stabilizers at Olkiluoto. 4.2 Frequency response of the power system stabilizer The design criteria that is used for stabilizers with negative feedback is to obtain an open loop phase shift of about zero degrees and a relatively high loop gain at the frequencies that need damping. The power system stabilizers at Olkiluoto were originally designed to have a good damping of local machine oscillations. The stabilizers were retuned in 2003 to give a good damping in the inter-area frequency range while still having an acceptable damping of the local machine modes. (Figure 3.b). 4

4.3 Generator reactive power controller In addition to a normal voltage control, the generators at Olkiluoto are provided with reactive power controllers. The operators can choose whether to have the reactive power controller in service or not. The reactive power controller originally changed the voltage control reference with a speed of 0.005 pu/second, when the reactive power was outside a small dead-band. Later the dead-band was replaced with a linear range (sections 4.5 4.7). If a disturbance leads to a voltage deviation of more than 2.5 % from the voltage setpoint for a duration longer than 2 seconds, the reactive power controller returns the voltage to within 2 % of the setpoint, after which it is deactivated. 4.4 Controller interaction A stabilizer with an improved phase-shift at the inter-area oscillation mode was studied together with the reactive power control model. The simulations showed a sustained oscillation of 0.3 Hz after a disturbance was applied to the system. The sustained power variation was 2.2 MW for each generator at Olkiluoto. This phenomenon was discovered immediately before a scheduled on-site test of the new stabilizer. (Figure 4.a). The damping ratios are calculated according to equation 4.1 1 A1 damping ratio ζ = p p n ln (4.1) 2 π A2p p where A1 p-p and A2 p-p represent the magnitudes of the oscillations at the beginning and at the end of the chosen observation interval for calculation of damping, and n represents the number of cycles in this interval. The equation has been derived during this work. The damping ratio ζ in (4.1) relates directly to the damping ratio used in linear control theory [4] [5]. During the on-site testing of the new stabilizer, special attention was paid to the interaction with the reactive power controller. Variations similar to the simulations were obtained in the output signal of the reactive power controller. Therefore, it was decided not to take the new stabilizer into service at this time. Figure 4. a) Simulation with original reactive power controller showing sustained oscillations after disturbance. b) Simulations with a reactive power controller with linear range. 5

4.5 Reactive power controller with linear range Because of the interaction problem encountered during the on-site testing, further simulations were done with the reactive power controller. It was found that by coordinating the action of the reactive power controller with the action of the power system stabilizer, a better damping performance could be obtained than when operating with the power system stabilizer alone. By simulations, it was found that after applying a disturbance to the system, the highest damping ratio was obtained at a reactive power variation of 13 Mvar at the generator terminals (Figure 4.a). Therefore, a linear range was introduced to the reactive power controller, which linearly decreased the output magnitude of the reactive power controller with the reactive power variation at the generator terminals at the inter-area oscillation frequency (Figure 4.b). A linear range of ±10.0 Mvar was introduced with the reactive power controllers at the plant. The modified reactive power controllers were used together with the old power system stabilizers for six months. After this trial period, a new power system stabilizer was tested on-line. During this testing another low frequency variation of 0.8 rad/s (0.125 Hz) in the reactive power at the generator terminals was encountered. The variations were not noticed immediately, because the magnitude of the variation varied by time. The internal supervisory functions of the reactive power controller eventually switched off the controller. Because the old power system stabilizer had encountered no problems with the modified reactive power controller, the old stabilizer was put back in service. 4.6 Reactive power controller with enlarged linear range A simulation study was again initiated to find the cause for the 0.8 rad/s (0.125 Hz) interaction between the new power system stabilizer and the modified reactive power controller. The frequency response of the transfer function from the voltage reference to the reactive power output of one of the generators was plotted, while the other generator was operating in parallel with its reactive power controller active (Figure 5). By means of the Bode plot and the transfer function for the reactive power controller, it could be calculated that the gain of the reactive power control loop was about 1 p.u. at the 0.8 rad/s (0.125 Hz) resonance frequency with a phase margin of about 30 degrees. Note that the reactive power controller, which is of integrator type, has a phase shift of -90 degrees over the whole frequency range. 0.125 Hz resonance gain phase shift ω [rad/s] Figure 5. Frequency response of transfer function from the voltage reference to the reactive power at the generator terminals. The power system stabilizers are active at both generators and the reactive power controller is active only at the parallel generator. 6

The resonance can be seen in the same Bode plot because the other generator has its reactive power control loop closed. A higher phase margin is normally required for feedback controllers [4]. The stimulus to the oscillation was believed to have originated from an aliasing problem [5] with the new digital power system stabilizer. From the Bode plot it was determined that the gain of the reactive power controller would need to be lowered with a factor of ten. This was accomplished at the plant by increasing the linear range of the reactive power controller from ±10 Mvar to ±140 Mvar, which lowered the gain by a factor of fourteen. 4.7 System tests On-site tests were done with new stabilizer settings (Figure 3.b) and the reactive power controller with a linear range of ±140 Mvar and the generators at full power. The 0.8 rad/s (0.125 Hz) oscillation problem had now disappeared making it possible to verify the system damping with different stabilizer settings and system configurations. By utilizing the Fennoskan HVDC transmission link between southern parts of Finland and Sweden, the power on the AC lines was increased towards Sweden and maintained at the same level for each test. With the old stabilizer settings, one of the interconnecting 400 kv AC lines between Finland and Sweden was switched out and a few minutes later switched back in. This created quite large power oscillations and their damping was monitored both at the generating station and in the AC lines to Sweden. The same tests were repeated with the new stabilizer settings. The power transfer to Sweden on the AC lines was about 1000 MW for all tests. With one of the interconnecting lines switched out, there was only one 400 kv AC line carrying this power. The damping ratios from the system tests have been calculated from the generator power recordings using the recursive least-square method for modal analysis with the PSS/E [3] (Table I). Table I Damping ratios for OLG1 power when switching one of the 400 kv AC lines between Finland and Sweden ζ f Old stabilizer Opening line 3.58E-2 0.252 Hz settings Closing line 4.17E-2 0.277 Hz New stabilizer Opening line 4.47E-2 0.246 Hz settings Closing line 5.13E-2 0.279 Hz The results from the system tests show that the new stabilizer settings at the Olkiluoto generators have improved the damping of the lowest inter-area oscillation mode in the Nordic power system. The decrease in stability caused by the line outage has been fully compensated for with the use of new stabilizer settings at Olkiluoto. The system test showed a smaller damping improvement than obtained by simulations. One of the reasons for this is differences in the response between the excitation system model used in the simulations and the response of the excitation system at the plant. This indicates that further work is needed on excitation system modeling. 7

5 CONCLUSIONS A combination of simulation techniques and on-site measurements has been used to find the cause for occasional sustained low-frequency oscillations in the Finnish transmission grid. The work was done in cooperation with a transmission system operator, a power plant owner and a university, thus giving a wide view on the problem. The most detailed dynamic simulation model available of the Nordic power system has been used together with a frequency scanning technique and time domain simulations. The simulated frequency responses of the transfer functions from the voltage reference to the active power and reactive power at the generator terminals with different controller configurations have been proven beneficial in this work. The same frequency scanning technique has been used to find settings that make the power system stabilizers effective on damping inter-area oscillations. Modifications of the power system stabilizers originally caused interaction problems with the generator reactive power controllers. A set of on-site tests and simulations were done to find the cause of the interactions. When the solutions to these problems had been found system tests were done which included activation of the lowest inter-area oscillation mode in the Nordic power system. The system tests showed that a solution to the problem had been found and that the damping of the lowest inter-area oscillation mode was much better with the new control system settings than with the original ones. The new control system settings were left in service after these tests which made it possible to increase the power transfer limit from Finland to Sweden. The system tests also showed that further work is needed on excitation system modeling. 6 REFERENCES [1] Uhlen, K; Elenius, S; Norheim, I; Jyrinsalo, J; Elovaara, J; Lakervi E; Application of linear analysis for stability improvements in the Nordic power transmission system, (IEEE/PES general meeting, July 2003, Toronto Canada, pp. 1-7). [2] PSS/E-29, Operational manual and Application guide, (Power Technologies, Inc., 2002). [3] PSS/E-29, PSSPLT program manual, (Power Technologies, Inc., 2000, pp. 4.33-4.44). [4] Skogestad, S; Postlethwaite, I; Multivariable feedback control: Analysis and design, (John Wiley & Sons Ltd, 1996, pp. 35-36). [5] Åström, K.J; Wittenmark, B; Computer controlled systems: Theory and design, (Prentice Hall, 1997. pp. 17, 128). The authors kindly acknowledge the research funding from the Development Fund of Electric Power Technology (SVK-pooli) in Finland. 8