MAXTHERMO-GITTA GROUP CORPORATION. Hot Runner Temperature Controller. MC-550 Operation Manual. Version:

Similar documents
APPENDIX APPENDIX A 1

UNICONT. PMG-400 Universal controller and display unit USER'S AND PROGRAMMING MANUAL 1. pmg4111a0600p_01 1 / 24. ST edition

PID500 FULL FEATURED PID TEMPERATURE CONTROLLERS

C C1 C2 AL1 AL2 AL3. Micro-controller X. Model: PXR SEL PXR-4. Operation Manual. ECNO:406a

Analogue temperature controllers

Micro-controller X Model: PXE4. Operation Manual. INP-TN5A1887a-E

Introduction To Temperature Controllers

TA Series. Analog And Non-Indicating Type, PID Control, Set Temperature By Dial. Features. Ordering Information TA S B 4 R P 4 C

Micro-controller X SV C1 C2 AL1 AL2 SEL. Model: PXR3. Operation Manual TN5A2704-E

Operation Instruction Manual KAM-TC1000. Precision Temperature Controller

Series Temperature Controller Instruction Sheet

Fuzzy Temperature Controllers E5AF

Instruction Notes for 108A L Sensor Input

TA Series. Analog And Non-Indicating Type, PID Control, Set Temperature By Dial. Features. Ordering Information TA S B 4 R P 4 C

SYL-2362A2 PID TEMPERATURE CONTROLLER

- SMART TUNE- PID CONTROL - UNIVERSAL, 3 WIRE- TC, RTD AND LINEAR INPUT - AUX- REMOTE SET POINT/ TRIM INPUT - 2x ISOLATED CONTROL AND RETRANSMISSION

Series Valve Temperature Controller. Instruction Sheet

GL102 Intelligent Temperature Controller User s Guide

Digital Temperature Controller

SR25. SHIMADEN DIGITAL CONTROLLER Shimaden, Temperature and Humidity Control Specialists MICROPROCESSOR-BASED AUOT-TUNING PID CONTROLLER

INSTRUCTION MANUAL FOR PROGRAMMABLE CONTROLLER PCD-33A

Humidity Controller TH136 INSTRUCTION MANUAL

Instructions for Tempco Control Enclosure PCM10001 through PCM10004

MICRO-CONTROLLER X (48 48 mm)

XC-E6TCA-P Temperature control module User s manual

PROGRAMMABLE CONTROLLER

Series Temperature Controller Instruction Sheet

A3 Pro INSTRUCTION MANUAL. Oct 25, 2017 Revision IMPORTANT NOTES

TC-408 PID TEMPEARATURE CONTROLLER INSTRUCTION MANUAL

DC1010/DC1020/DC1030/DC1040

Table of Contents Panel Mount Controllers Analog Series C-Series Controller Software Legacy Series Power Controllers Analog Series P-Series

Laboratory Freezer. Model : LLF-402SR / LLF-403SR / LLF-404SR LLF-403SR-H / LLF-404SR-H

Process Controller. PX series INSTRUCTION MANUAL. Thank you for the purchase of HANYOUNG product. Please read this manual carefully.

Instruction Manual (Detailed Version)

GL101B Intelligent Temperature Controller User s Guide

(Relay contact) Digital output. (Relay contact) When the ninth digit in the model code is J (Do1,2 are independent common) Digital output 1

Introduction To Temperature Controllers

SHIMADEN DIGITAL CONTROLLER

8003 1/8 DIN Temperature Controller

1/16 DIN (48 48 mm) temperature controller PXR

- SMART TUNE - PID CONTROL - UNIVERSAL, 3 WIRE - TC, RTD AND LINEAR INPUT - 2 INDEPENDENT SET POINT RAMP UP/ DOWN PROFILES - SERVO VALVE POSITIONER

PROGRAMMABLE CONTROLLER

ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER AI-208. User Manual

High Performance Process & Temperature Controllers

EIO /2009. Zelio Control. Temperature Controller User guide 04/2009 EIO

Delta Temperature Controller DT Series

Temperature Controls

DIN rail mounting temperature controller with current transformer input deltadue series D1 line

TTM-339 TTM-339 PROGRAM CONTROLLER

PROGRAM CONTROLLER OUTLINE

1. Model number 1.1 Explanation of model number A K T 4 1. Phone: Fax: Web:

I/A Series Model 718TC 1/8 DIN Temperature Controller with ma Output

CCE Image may differ from the actual product By Martin Labbé, eng., Jasmin Goupil & Louis Perreault

TA Series. Analog Setting Non-Indicating type, PID Control. Analog and non-indicating type, PID control, set temperature by dial.

HITACHI. L100-M Series Inverter Quick Reference Guide. Hitachi Industrial Equipment Systems Co., Ltd. Single-phase Input 100V Class

INSTRUCTION SHEET. Eaton Logic Controller ELCM TC Temperature Modules. [Applicable Temperature modules] ELCM-TC04ANNN MTN1

MODEL: W2TS. Mini-MW Series

Continental Hydraulics Installation Manual CEM-PA-A

SYL-2352P Ramp and Soak PID Temperature Controller Version 1.2 (May 2016)

HIL Simulation Lab Work

1 Digital input (24Vac or dry contact) Inputs

SHIMADEN PROGRAMMABLE CONTROLLER

SR90 Series. (SR91, SR92, SR93, SR94) Digital Controller. Instruction Manual

PID-CONTROL FUNCTION AND APPLICATION

STR-LCF. Security Advice Caution. Notes on Disposal. Electronic Fan Coil Thermostat (Flush mounting) Datasheet. Application

Series 7 Power Controllers

SJ100 Series Inverter Quick Reference Guide. Single-phase Input 200V Class Three-phase Input 200V Class Three-phase Input 400V Class

AK48 SPECIFICATIONS APPLICATIONS GENERALS FEATURES. 1/16 DIN Process controller

FC-33, DC SELECTABLE SIGNAL CONDITIONER

Controller Algorithms and Tuning

Infinite Thermal Solutions Inc.

Temperature Controller

Excellent low-cost Process & Temperature Controllers

MICRO-CONTROLLER X (96 96 mm)

Digital Controller TTM i4n User s Manual Contents

MICRO-CONTROLLER X (48 96 mm)

Single Phase Full-Wave Motor Driver for Fan Motor AM7228

DC1010/DC1020/DC1030/DC1040/Compact type DIGITAL CONTROLLERS Specification

Bulletin E-90-OCN Series CN7200, CN7600, CN7800, CN7500 Microprocessor Based Temperature Process Control

Enhanced PID for Air Compressors F7 Drive Software Technical Manual

Documentation. Content. Measurement and Control. Type: ELT-GP1. 1. Installation instructions 2. Data sheets 3. Declarations of conformity

E2T0 DVP

MODEL: M1EXT. with Display M1E Series

PID Controller-Single Loop (1/16 DIN - Microcontroller Based) (Product Code 10.10)

Jacket heater, etc Mounting bracket for Pipe wrapping. (Optional) Temperature sensor. Output (To heater) (Optional)

DIN rail mounting dual loop controller/ analogue acquisition module

REX-F400 REX-F700 REX-F900

(4,7mm).187 DIA (4) CONTROLLER SUPPLY VOLTAGE : 115 volts _+ 10%, 50/60 Hz., 4 V.A. maximum 230 volts + 100, 50/60 Hz., also available.

R7426A. MicroniK 200 TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK

Instruction Manual. Program Controller X. Type : PVX. INP TN1PVXa-E

VI. SET-UP PARAMETER. Input filter

Cat.No. W240-E1-1 SYSMAC C200H-TV. Heat/Cool Temperature Control Unit OPERATION MANUAL

Temperature/Process Controller with Isolated Analog Output Board

Instruction manual SMART 96-2 / WG-2 ph

TLK 96 S MICROPROCESSOR-BASED DIGITAL ELECTRONIC CONTROLLER. OPERATING INSTRUCTIONS Vr. 00 (ENG) - cod.: ISTR INSTRUMENT DESCRIPTION

MC-2 Series Micro Processor Temperature Controller

To agents or distributors Make sure to pass this instruction manual to final customers. CONTENTS

PLUG-IN DIGITAL TEMPERATURE CONTROLLER

General Information SANUP ELECTRIC CO. PRODUCTS. Since 1963 APPROVAL

Series 942 User's Manual

Transcription:

Hot Runner Temperature Controller MC-550 Operation Manual Version:1011040001 http://www.maxthermo.com

To avoid injury or damage caused by improper operation, please follow The instruction and keep the instrument in a ventilated place to ensure its stability. CONTENT MC-550 Hot Runner Temperature Controller Module 1 Features 2 Specification 3 Faceplate 3-1 Faceplate Description 3-2 Faceplate Appearance & Dimension 4 Operating Description 4-1 Parameter flow chart 4-2 Level Parameter Description 4-3 Control Modes 4-4 Self Tuning Function 4-5 Auto Tuning Function 4-6 Soft Start Function 4-7 Manual Function 4-8 Standby Function 4-9 Error Indication 4-10 Wiring Diagram 5 Order Information

MC-550 Hot Runner Temperature Controller Module 1 Features Auto Error Display Function Auto / Manual / Standby Control Mode Auto Tuning / Self Tuning Thermocouple J or K Type Options Deviation High & Low Alarm Temperature Range:100~400 / 212~752 Soft Start Function DPID Control 2 Specification Power Supply:AC 85V~250V, 50/60Hz Load Current Rating (A):15A, 1650W (110V), 3300W (220V) Output:Pulse Width Modulation (PWM) Main Input:Thermocouple K, J type Temperature Range:100~400 / 212~752 Control Mode:DPID Accuracy: ±0.5%F.S. ±1dig. Work Temperature:-10 ~50 Work Humidity:10%~80%RH (non-condensing) Size:177 x 50 x 193 mm (L x W x H) Weight:about 470g 1

3 Panel 3-1 Panel Description 1 2 3 4 5 6 1. SOFT 2. OUT Soft Start Indicator (SOFT): Continual ON is for performing soft function. Blinking per second is for performing DPID function. Blinking per 0.5 second is for performing auto tuning function. Output Indicator: ON is for performing output. 7 8 9 11 12 10 3. Present Value 4. Set Value 5. UP Increase Key 6. SET Set Key & Enter Key 14 13 15 7. DOWN Decrease Key 8. MODE Select Parameters 9. AUTO Auto Indicator 10. SEL SEL Key= Select Auto mode, Standby mode & Manual mode 11. STANDBY Standby Indicator 12. MANUAL Manual Indicator 13. Module Handle 14. Module Power Switch 15. Module Screw 2

3-2 Panel Appearance & Dimension Unit:mm 16 75 177 60 10 50 4 170 19 3

4 Operating Description 4-1 Parameter flow chart Level1 (User level) Level2 (PID level) Level3 (Input level) Operating display Operating display Operating display 3 sec. Press the MODE and DOWN key 3 sec. and UP key 3 sec. AL-H 50 -St- -off- key:on/off -In- IC-J key:ca-k AL-L 50 At -on- key:on/off C--F CdSP key:fdsp Stby t 10 -Pb- 0 Unlt --1.0 key:--0.1 Stby P. 75 KP 30 SOFt -on- key:on/off LOCK -on- key:on/off t1 240 key:on/off HC-H C16.0 Id 0 -rh- 400 -Hz- 50HZ key:50/60 HZ Return to Return to Return to 4

4-2 Level Parameter Description A. Level1 (User level) Name Range Description Ex-factory AL-H Deviation high alarm 0~50 When +(AL-H), display AL-H 50 AL-L Deviation low alarm -50~0 When -(AL-L), display AL-L -50 Stby Standby mode time 1~999 min Standby time setting 10 Stby Standby mode rate 0.00~0.99 The rate on the basis of can be set from 0.00~0.99 0.75 Ex. =200, Stby=0.75, Stby =150 LOCK Function LOCK ON / OFF On : can t setting ; Off : can setting Off Id ID Number CH00~CH16 Communication address CH00 B. Level2 (PID level) Name Range Description Ex-factory ST Self tuning ON / OFF Performing DPID tuning when power is ON ( Under the status of Soft function OFF ) Off At Auto tuning ON / OFF On : Auto tuning function On Pb offset -100~100 When is not correct with, you can adjust this parameter with (+) or (-) 0 KP Proportional band 0~400-30 ti Integral time 0~9999-240 td Derivative time 0~9999-60 Ar Anti-reset windup 0~100 Setting range from 0~100 to limit integral 100 ranp Ramp 0~50 C / min. for soft start 20 FILt Digital filter 0~255-200 op.ou Output percentage 0~100 When the sensor is broken or a short circuit happens,this shows the manual output 50 percentage rl Low range setting 0~400-0 rh High range setting 0~400-400 C. Level3 (Input level) Name Range Description Ex-factory In Input selection K / J Select the input range J C--F Unit selection C / F Range of setting : C / F C Unlt Decimal point 1.0 / 0.1 Decimal setting 1.0 SOFT Soft start ON / OFF On : Soft start (ST function : off) On HC-H HC-n Load current high limit setting Load current low limit setting 0.0~16.0 0.0~16.0 When Load Current HC-H, Display=Ht.St and output off When Load Current HC-n, Display=Ht.oP and output off HZ Output Hz selection 50Hz / 60Hz Power frequency selection 50Hz 16 0.0 5

4-3 Control Modes Press the SEL key for 3 seconds, the controller can be switched to the AUTO / STANBY / MANUAL modes. AUTO Mode STANDBY Mode Perform DPID function key to select value / Output percentage / Ampere. Press MODE + SET key for 3 sec to start Auto Tuning function. When the STANDBY mode is working, the standby value of is required to set with corresponding STANDBY time ( stby-t ) and STANDBY % ( stby-p ). After the given STANDBY time, STANDBY Mode will return to AUTO Mode automatically. MANUAL Mode When MANUAL Mode is selected, it is able to change to MANUAL Mode automatically or by manual ( When detecting a broken circuit of sensor ). Change the Output percentage by pressing or key. 4-4 Self Tuning Function For example: When one user starts operating a new MC-550 Hot Runner Temp. Controller, and does not know how to set up Kp, tl, Td parameters, meanwhile, the mold temperature is < 70%. The ST function will be activated to process the auto tuning on Kp, ti, Td parameters and to implement DPID controlling. Step 1: Press + key for 3 sec to enter Level 2. (=ST) Step 2: Press Key for setting ST=ON Step 3: Press + key for 3 sec to enter Level 3. (=In) Step 4: Press Key to find and set the parameter SOFT = OFF Step 5: Press key for 3 sec to retune. Step 6: After the above 5 steps are done, please turn off the controllers and re-start the power. The controllers will automatically start ST function in auto mode. Step 7: When ST is processing, the SOFT light will flash per sec. When the SOFT light is off, the ST process is done. 6

4-5 Auto Tuning Function For Example: If one MC-550 is out of control while the injection machine is working, the user can replace a new MC-550 on the machine. If after the replacement the control status is not as good as the previous MC-550, it is recommended to activate the AT function. The controller will then practice auto tuning to set up Kp, tl, Td parameters and to implement DPID control. Step 1: To make sure that in Auto Mode, there is no other function under working status. Step 2: Press + key for 3 sec to enter Level 2 (=ST) Step 3: Press Step 4: Press key to set the parameter AT=ON key for 3 sec to return Step 5: Press + key for 3 sec till the SOFT light flash per 0.5 sec. When the SOFT light is off, the AT process is done. 4-6 Soft Start Function For example: The Soft Start function is for setting the Ramp value to prevent the temperature from overshooting. Step 1: Press + key for 3 sec to enter Level 3. (=In) Step 2: Press key to select Soft mode and set it to on Step 3: Press + key for 3 sec to enter Level 2. (=ST) Step 4: Press key for setting ST=Off Step 5: Press Key to set the parameter ranp Step 6: After the above steps are done, please turn off the controllers and re-start the power. The controllers will automatically start the soft start function in auto mode. Step 7: When the soft start function is activated, the Soft light will be on continuously until the soft start process is done. Remarks: To stop soft start function, please press or key for 3 sec. 7

4-7 Manual Function For example: While a Thermocouple is broken on the machine, the controller will be switched to the Manual mode automatically. Before replacing a new thermocouple, please set up an output percentage value at discretion (according to the user s experience) to stabilize the output voltage for heaters. It can keep the mold in a stable temperature condition until the replacement process is completed. (a) Manual Switch: Step 1: Check whether the Auto Mode is off (judged by SOFT or AUTO light) Step 2: Press key for 3 sec to switch to the Manual mode. (=op.ou) Step 3: Please adjust the demanded output percentage value by pressing or key (b) Auto Switch: Step 1: Set up your demanded output percentage. (op.ou= 50 is pre-set ex-factory value.) Step 2: When an input error happens, the controller will automatically be switched to the Manual model, and will control the output percentage according to the pre-set value. 4-8 Standby Function Standby Temp. (150 C) Standby Time 1 hours For example: When the user is replacing a new mode on the machine, the STANDBY mode can be activated to prevent products from a deformed condition caused by a rapidly rising temperature. Step 1: Press key for 3 sec to enter Level 1. (= AL-H) Step 2: Press Step 3: Press key to set the parameter Stby-t. key again to set the parameter Stby-P Step 4: After the above steps, please press Step 5: Press key for 3 sec to switch to STANDBY mode. key for 3 sec to finalize the setting procedure. 8

4-9 Error Indication No. Parameter Display Code Description Solvent 1 tc. op Sensor open Check wiring, change sensor 2 tc. re Sensor wiring opposite Check wiring 3 AL-H High alarm Check sensor and heater, external wiring 4 AL-L Low alarm Check sensor and heater, external wiring 5 Ht. op Heater open Check wiring, change heater 6 Ht. St Heater short Check wiring, change heater 7 FU-1 Fuse 1 broken Change fuse 1 (250V 15A) 8 FU-2 Fuse 2 broken Change fuse 2 (250V 15A) 9 Tr. St Output short Check wiring, change TRIAC 4-10 Wiring Diagram TRIAC Main Input : K, J type + - Fuse 2 Output : Heater Power Supply : 85~250VAC ~ Handle Ground Fuse 1 Screw 5 Order Information Model No.:MC-550 9