POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC

Similar documents
POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:

Southern Company Power Quality Policy

1C.4.1 Harmonic Distortion

Use only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

POWER QUALITY AND SAFETY

Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions

ELECTRICITY ASSOCIATION SERVICES LIMITED 2001

Harmonic Distortion Evaluations

The development of the SA grid code on Power Quality emission. Dr. Gerhard Botha 2017/08/08

Emission Limits for Customer Facilities Connected to the Hydro-Québec Transmission System

Roadmap For Power Quality Standards Development

IEEE sion/1547revision_index.html

Power Quality Requirements for Connection to the Transmission System

Harmonic Requirements

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Table of Contents. Introduction... 1

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

Effective Harmonic Mitigation with Active Filters

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Do You Have a Harmonic Problem?

Power Quality and Harmonic :Causes and Effects with Paper Mill Factory

Harmonic distortion Blackouts Under or over voltage Dips (or sags) and surges, Transients.

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES

Prepared By Pierre Archambault, PEng Power Survey International Inc Trans Canada Hwy. St-Laurent, QC H4S 1S4 CANADA

Harmonic Study in Low Voltage Distribution Network in a Real Time Foundry Industry

16B2011B1 EASY HARMONICS USER MANUAL

Economical Solutions to Meet Harmonic Distortion Limits[4]

Grid Converters for Photovoltaic

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES

CHAPTER 4 MODIFIED H- BRIDGE MULTILEVEL INVERTER USING MPD-SPWM TECHNIQUE

7/15/2002 PP.AFD.08 1 of 28

An Introduction to Power Quality

METHOD TO DETERMINE CONTRIBUTION OF THE CUSTOMER AND THE POWER SYSTEM TO THE HARMONIC DISTURBANCE

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods

Harmonic control devices. ECE 528 Understanding Power Quality

MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN

Power quality report. A Manufacturing Plant

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

Power Quality Summary

Design of SVPWM Based Inverter for Mitigation of Harmonics in Power System

ZENER ELECTRIC PTY LTD

BED INTERCONNECTION TECHNICAL REQUIREMENTS

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

Wind Power Facility Technical Requirements CHANGE HISTORY

Effects of Harmonic Distortion I

Interharmonic Task Force Working Document

Embedded Generation Connection Application Form

Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces. H.A. Khalik, M. A. Aziz, and E. Farouk.

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives

POWER QUALITY REPORT

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

Low Pass Harmonic Filters

CHAPTER 5 SWITCH MODE POWER SUPPLIES

Connection Impact Assessment Application Form

DYNAMIC VOLTAGE RESTORER FOR VOLTAGE SAG MITIGATION IN OIL & GAS INDUSTRY

Contents. All Rights Reserved

IMPLICATIONS OF APPLYING DIFFERENT VAR SUPPORT TECHNOLOGIES IN THE ESKOM TRANSMISSION NETWORK WITH PARTICULAR EMPHASIS ON THE LIFECYCLE COST

IEEE sion/1547revision_index.html

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Power Quality in High Density Residential Distribution Grids

POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER

Impact Assessment Generator Form

Power Quality enhancement of a distribution line with DSTATCOM

RENEWABLE ENERGY SUB-CODE for Distribution Network connected Variable Renewable Energy Power Plants in Ghana

On the Evaluation of Power Quality Indices in Distribution Systems with Dispersed Generation

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

Harmonic Filters for Single Phase Equipment

Embedded Generation Connection Application Form

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY

Technical Interconnection Requirements For Transmission Voltage Customers for Service at 60,000 to 287,000 Volts R XX

Power Quality Report. A Manufacturing Plant

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction. See the Implementation Plan for PRC

Standby Power. Primer

ABB drives. Technical guide No. 6 Guide to harmonics with AC drives

Volume I Issue VI 2012 September-2012 ISSN

Draft Kenya Standard for Balloting Not to be Cited as Kenya Standard

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

II. RESEARCH METHODOLOGY

A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION

A. Harmonics. non-linear loads. are. required)

Performance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System

FAQ for SIMOREG 6RA70 and Control Module

Southern Company Interconnection Requirements for Inverter-Based Generation

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

Transcription:

CITY OF LETHBRIDGE ELECTRIC ENGINEERING STANDARDS POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS The City of Lethbridge acknowledges the use of other utility industry and industry committee developed documents as the framework and sources in producing this technical guideline. Rev. 0 Rev. Date: 2003/02/10 Prepared by: Brent Smith Approved by: Otto Lenz

GENERAL OVERVIEW 1 1.1 WHAT DOES THIS SPECIFICATION MEAN Due to the increase in harmonic loads, utilities across Canada are implementing power quality limits to protect customer and utility equipment. The purpose of this document is to explain the harmonic limits and voltage flicker limits the customer must meet, the commissioning process for the specification, and the procedure that takes place to mitigate customer complaints. The limits that are described in this document reflect industry standards. 1.2 ADHERING TO THE GUIDELINES To maintain a high quality of electrical utility service, all new customers and all existing customers connected to the City of Lethbridge power system are required to adhere to the specifications and guidelines in this document. If a customer exceeds these limits it is probable that the customer will have to be disconnected from the City Of Lethbridge power system. The conditions that determine whether a customer will be connected are listed below. The criterion for stage 1 and stage 2 are outlined in Section 3. The City of Lethbridge will be able to connect the customer if the customer has: completed all steps in stage one. completed all steps in stage two. does not produce harmonics and does not have to be evaluated under any of the stages of acceptance. The customer cannot be connected to the power system if the customer has been: rejected under any of the stages. 1 A customer may be disconnected from the power system if: the customer exceeds the limits described in the specifications; and other customers and/or utility equipment is being adversely affected. 1.3 WHAT IS THE CONNECTION PROCESS? Found below is a brief description of the stages of the process that harmonic producing customers must follow in order to be connected to the City of Lethbridge power system. A detailed description of this process is found in Section 3. Step 1: Step 2: Step 3: Step 4: Step 5: Step 6: Step 7: A new customer, consultant, or Energy Service Provider contacts a designer at the City of Lethbridge for connection of a new service or an upgrade. The designer gives the customer, consultant, or Energy Service Provider the power quality specifications and informs the engineer that a customer has been given the document. The engineer contacts the customer and the two parties discuss the customer s operation and the specifications. If required, the engineer administers the specifications. The customer submits a report, which demonstrates that it will adhere to the specifications. The engineer reviews the report and confirms all electrical utility standards are met. The customer is connected to the power system.

POWER QUALITY LIMITS 2 2.1 HARMONIC CURRENT DISTORTION LIMITS All City of Lethbridge customers that are connected to the City of Lethbridge Power distribution system are responsible for complying with the harmonic current limits, at the point of common coupling, that have been stipulated by the City of Lethbridge. The current harmonics created by the customer cannot exceed the limits that are outlined in Tables 2.1 and 2.2, at the point of common connection (PCC). These limits are applied to each phase current individually and are expressed as a percentage of the customer s maximum demand load current. Table 2.1 Harmonic Distortion Limits 69kV and Below I SC /I L h<11 11 h<17 17 h<23 23 h<35 35 h THD <20 See Note 4 4.0 2.0 1.5 0.6 0.3 5.0 20 50 7.0 3.5 2.5 8.0 50 100 1 4.5 4.0 1.5 0.7 12.0 100 1000 12.0 5.5 5.0 2.0 15.0 > 1000 15.0 7.0 6.0 2.5 1.4 2 1 See Section 4 for explanations of the symbols. 2 The symbol h is for odd harmonics only. 3 Triplen harmonics are limited to 1/3 of the limits for odd-order harmonics. 4 All power generation equipment applications are limited to these values of current distortion regardless of the actual short circuit ratio I SC/I L. Tab Distortion Limits Table 2.2 Harmonic Distortion Limits 138kV I SC /I L h<11 11 h<17 17 h<23 23 h<35 35 h THD <20 See Note 4 2.0 0.75 0.3 0.15 2.5 20 50 3.5 1.75 1.25 0.25 4.0 50 100 5.0 2.25 2.0 1.25 0.35 6.0 100 1000 6.0 2.75 2.5 7.5 > 1000 7.5 3.5 3.0 1.25 0.7 1 All of the information found in the notes below Table 2.1 also pertain to Table 2.2

2.2 HARMONIC VOLTAGE DISTORTION LIMITS The City of Lethbridge has the responsibility to supply voltage at the PCC that does not exceed the distortion limits listed in the table below. Table 2.3 Harmonic Voltage Distortion Limits Bus Voltage at PCC (V n ) Voltage IHD (%) Voltage THD (%) V n 69kV 3.0 5.0 V n = 138kV 1.5 2.5 The above information, as with all information found in this document, should be verified with the City of Lethbridge. Table 2.2 Harmonic Distortion Limits 2.3 SHORT DURATION HARMONIC LIMITS The harmonic limits listed in the tables in Sections 2.1 and 2.2 refer to steady state conditions. However, due to the time-varying nature of harmonics and certain facility operations, such as start-up, harmonics may exceed the limits given in the previously mentioned tables. The table below shows the acceptable limits for harmonic bursts. Table 2.4 Short Duration Voltage and Harmonic Levels Acceptable Harmonic Distortion Levels (THD and IHD) Maximum Duration of a Single Harmonic Burst in a 24 Hour Period (T maximum ) Total Duration of All Harmonic Bursts in a 24 Hour Period (T total ) 3.0 X Steady State Limit 1 sec < T maximum < 5 sec 15 sec < T total < 60 sec 2.0 X Steady State Limit 5 sec < T maximum < 10 min 60 sec < T total < 40 min 1.5 X Steady State Limit 10 min < T maximum < 30 min 40 min < T total < 120 min X Steady State Limit 30 min < T maximum 120 min < T total The limits mentioned in the table above are allowed only if the other customers are not adversely affected by the harmonic bursts. 2.4 EVALUATING CONCERNS FOR HARMONIC FILTERS AND POWER FACTOR CORRECTION Power factor correction capacitors and harmonic filters at customer facilities may absorb harmonic currents from the system or magnify harmonic currents created by the customer load equipment. These installations should be coordinated with the City of Lethbridge. 2 It is not the purpose of these guidelines to penalize customers for harmonic currents that are absorbed from the power system. More detailed evaluation is necessary to assess the impact of a customer that is applying either harmonic filters or power factor correction capacitors. Please note that the harmonic filters or power factor correction capacitors applied in customer facilities should be designed assuming background voltage distortion levels as specified in Table 2.3

2.5 FLICKER LIMITS FOR MOTOR STARTING AND CYCLICAL LOADS The voltage flicker limits for customers connected to the City of Lethbridge power system are shown in the figure below. In the case where there is a single customer on a transformer, the voltage fluctuations may not exceed the limits in Figure 2.1 on the utility side of the transformer. If there is more than one customer connected to a transformer, the voltage fluctuations may not exceed the limits found in Figure 2.1 on the customer side of the transformer. 2.6 GENERAL FLICKER LIMITS Customers that have loads with random fluctuation characteristics will be evaluated according to the procedures in IEC 1000-4-15. The weighting curves for 60Hz, 120 volt systems will be used. A customer with fluctuating loads should not result in Pst value exceeding at the 99% probability level recorded during an interval of at least one week. 2

COMMISSIONING PROCESS & GUIDELINES 3 3.0 CRITERIA FOR STAGED ACCEPTANCE OF NEW INSTALLATION Only harmonic-producing customers are required to be evaluated under staged acceptance. The commissioning process for applying the Power Quality Specifications is a cooperative effort between the customer and the utility. Each party will provide the relevant information necessary to determine the impact on the power system. Refer to Figure 3.2 for the commissioning process and Figure 3.3 for the staged acceptance process. 3.1 STAGE 1 - AUTOMATIC ACCEPTANCE Customers that have a small amount of harmonic load may be allowed to connect to the system without detailed evaluation. In order to be automatically accepted the customer must satisfy the following two criteria. Criterion 1: The first requirement is that the customer shall satisfy S Dw / S SC < 0.1% S Dw is the amount of weighted disturbing load within the customer s facility and is calculated by using the following: S Dw = (SDi Wi ) i Where: S Di = power rating for an individual disturbing load (kva) W i = weighting factor for the disturbing load (pu) S SC = actual three phase short capacity at the PCC The weighting factors for various types of loads are given in Figure 3.1. If the type of load is unknown, a weighting factor of should be used. Criterion 2: The second requirement is the customer s capacitors cannot cause a harmonic resonance. The parallel resonant frequency, hr, only needs to be checked out for the two harmonic orders that are adjacent to hr. The following equation may be used to calculate hr, if all capacitors are connected to the same busbar. h r = (MVA SC )/(MVAR cap ) Since MVAsc and MVARcap may change with loading, this criterion must satisfy all system conditions. 3.2 STAGE 2 - EVALUATION OF HARMONIC EMISSIONS In order to be accepted at Stage 2, the customer must adhere to the City of Lethbridge Harmonic Specification by performing a detailed harmonic analysis and submitting a report to the City of Lethbridge. If the harmonic distortion exceeds the limits in the specification, then the customer must install harmonic control equipment to remedy the situation.

3.3 INFORMATION REQUIREMENTS Tab 3.1 Table 3.1 Responsibilities to Supply Information Customer will supply the following information The City of Lethbridge will supply information pertaining to A single line diagram, a list of linear load and nonlinear loads, a list of transformers, and a list of capacitors and filters. PCC location, fault current at PCC, and supply system impedance.

3.4 WEIGHTING FACTORS FOR DIFFERENT TYPES OF HARMONIC PRODUCING LOADS The following figure shows various weighting factors. Type of Load Typical Waveform Distortion Weighting Factor (W i ) Single Phase Power Supply 80% (high 3rd) 2.5 Semiconverter high 2nd,3rd, 4th at partial loads 2.5 6 Pulse Converter, capacitive smoothing, no series inductance 80% 2.0 6 Pulse Converter, capacitive smoothing with series inductance > 3%, or dc drive 40% 6 Pulse Converter with large inductor for current smoothing 28% 0.8 12 Pulse Converter 15% ac Voltage Regulator varies with firing angle 0.7 Fluorescent Lighting 17% Figure 3.1 Weighting Factors

3.5 THE COMMISSIONING PROCESS New customer/consultant/ ESP contacts designer at the City of Lethbridge. Designer gives customer the harmonic specification and informs engineer about new customer. Designer proceeds with normal planning process. Customer and engineer exchange information for harmonic specs. Does the customer s facility produce harmonics? No Yes Engineer administers spec and executes criteria for staged acceptance. Was customer accepted under staged acceptance? Yes Connect the customer No Do not connect the customer. Figure 3.2 Commissioning Process

3.6 STAGED ACCEPTANCE Stage 1 Is a detailed evaluation required? Customer produces reports demonstrating Stage 1 requirements. Yes Stage 2 Customer performs harmonic analysis and submits report to the City of Lethbridge. Stage 2 Do the customer s calculations comply with harmonic limits? Yes No Customer must install harmonic control equipment. City of Lethbridge verifies the customer s calculation. Do actual harmonic measurements satisfy the harmonic spec? Yes Customer accepted. No Customer not accepted. Figure 3.2 Commissioning Process Figure 3.3 Staged Acceptance

SYMBOLS AND DEFINITIONS 4 4.1 SYMBOLS h Harmonic order (2, 3, 4, 5,...) h r Parallel resonant frequency as a multiple of the fundamental frequency. I h Magnitude of individual harmonic components (rms amps). I L Maximum demand load current (fundamental frequency component) at PCC (rms amps). (Calculated as the average of the maximum monthly demand currents for the previous 12 months or estimated based on predicted load profiles.) I sc Actual system short circuit current at PCC under normal circumstances. MVA sc System short circuit MVA at the capacitor bus. MVAR cap MVAR rating of capacitor bank. P st Short-term flicker assessed in a 10 minute interval. V h Magnitude of individual harmonic components (rms volts). Nominal system rms voltage (rms volts). V n 4.2 DEFINITIONS Harmonic: IHD: PCC: THD: A harmonic is a sinusoidal component of a periodic wave form having a frequency that is an integral multiple of the 60 Hz fundamental frequency. For example, the second, third, and fourth order harmonics have frequencies of 120, 180, and 240 Hz respectively. Individual harmonic distortion (IHD) is the magnitude of distortion at each individual harmonic. The IHD can be expressed in both voltage and current as a percentage of the fundamental component. Point of common coupling (PCC) is the location on the CITY OF LETHBRIDGE power system that is electrically closest to the specified customer and is common to other City of Lethbridge customers. Total harmonic distortion (THD) 2 Vh Voltage: h= 2 THD = Vn X(100%) 50 50 2 h I : h= 2 THD = IL X(100%)

REFERENCES 5 1. Allard, G. et al, New Hydro-Quebec Guide for Limiting Harmonic Emissions at the Distribution Level: Principles and Applications. CEA Distribution Planning Conference #16, 1996. 2. Guide and Requirements for Harmonic Control for Customers Supplied at a Voltage Level from 69kV to 287 kv. British Columbia Hydro, June 1994. 3. Guide for Applying Harmonic Limits on Power Systems, IEEE Std 519a/D5, May 1996. 4. Nesbitt, R., City of Calgary Electric System Standard for Voltage Flicker, ENMAX Power Corporation, October 1989. 5. Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, IEEE Std 519-1992, April 1996.